Combined Footing For Two

This document provides design calculations for a square combined footing to support two columns. It includes calculations for the footing size, reinforcement requirements, bending moment, shear force, and development length. The footing size is determined to be 3.4m x 3.4m based on the total load. The maximum bending moment is calculated as -145.6346 kNm. The required area of longitudinal reinforcement is determined to be 1004.096 mm2 using a reinforcement depth of 450mm. Shear and development length checks are also provided.

Uploaded by

er.praveenraj30
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
373 views

Combined Footing For Two

This document provides design calculations for a square combined footing to support two columns. It includes calculations for the footing size, reinforcement requirements, bending moment, shear force, and development length. The footing size is determined to be 3.4m x 3.4m based on the total load. The maximum bending moment is calculated as -145.6346 kNm. The required area of longitudinal reinforcement is determined to be 1004.096 mm2 using a reinforcement depth of 450mm. Shear and development length checks are also provided.

Uploaded by

er.praveenraj30
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 15

FONDATION DESIGN FOR SQUARE FOOTING :

Given : FOR footing of column B3 Joinf ID 14


Size of the column = 400*400 mm
= 0.40 m
Material Properties :
Grade of concrete (fck) = M 20 N/mm2
For steel (fy) = 500 N/mm2
Bearing Capacity of soil qu = 150 KN/m2

Load Calculation :
Load on Column wc = 238 KN
Self Wt of footing wf = 24 KN
Total Load wc + wf = 262 KN

Area of Footing :
A = wc + wf
qu
A = 1.75 m2
Side of square footing = 1.3 m
say 2.40 m
Factored soil pressure due to column load only
Pu = 61.98 KN/m2

bending moment at critical section (Mu) 74.375 KNm

effective depth reqired is Mu=0.138*Fck*b*(d^2)


we get d=
so we adopt effective depth D= 600 mm

check for shear one way


shear force(Vu)= 59.5 KN
nominal shear stress Ʈv= 0.0413194 N/mm2
assuming 0.2% steel Ʈc = 0.32 N/mm2
if Ʈv< Ʈc then results is ok OK

check for shear two way


shear force(Vu)= 61.070139 KN
Normal shear stress Ʈv= 0.0254459 N/mm2

shear strength Ʈc = 1.118034 N/mm2


if Ʈv< Ʈc then results is ok OK
Area of Steel Reinforcement :
Mu = 0.87*fy*Ast*d*(1-(Ast/bd)*(fy/fck)) eq 1
Mu= 74.375 KNm
fy= 500 N/mm2
fck= 20 N/mm2
b= 2.40 m
d= 600 mm
solving eq 1 we get
Area of Steel Reinforcement :
Ast= 1239.19 mm2

Using Diameter of the bars = 12 mm

ast = 113.04 mm2

Required Spacing = 218.9301

we provide 12mm @ 150mm c/c spacing


provide Ast = 1808.64 > 1239.19 OK

Check for Development Length :

Ld = ɸ(0.87*fy)
4*Ʈbd

= 679.6875

actual embedment length provided from face of the column is

= 0.95 m
950 mm
CHECK:(if greater than LD,OK)
RESULT: OK
Material Properties :
Grade of concrete (fck) M 20 N/mm2
For steel (fy) 500 N/mm2 696 KN
Bearing Capacity of soil qu = 150 KN/m2 773 KN
JOINT ID 7,15

P1= 464 P2 515.3333 KN 464


515.3333

0.35 0.35

0.6 2.1 0.6

3.3

1 length and width of footing


CG of load from property line
X= 1.705037 m

LENGTH OF FOOTING=3.4100749
6.24

USING
length of
footing 3.42 m
there will be slight ecentricity of 0.12
it will cause a moment of with respect to centroid of footing 117.52 KNm
this effect is neglected

assume wt of footing & earth above it as 5% of total wt


total wt on earth 1028.3 KN
Footing width 2.004483

adopt width of footing, B 1.53 m

2 longitudinal bending moment and shear


Factored load on Column 1 696 KN
Factored load on Column 2 773 KN
Net Upward soil Pressure 280.74 KN/m2

Net Upward Soil Pressure per unit length 429.5322 KN/m

Maximum Shear Force at Centre line of Column A


V1 -257.7193
V2 438.2807

Maximum Shear Force at Centre line of Column B


V1 257.7193
V2 -515.2807

Point Of Zero Shear Force From Centre OF Column A


438.2807 515.280701754386
=
X 2.1 - X
manually calculating
X 0.965213 m 0.965213

Maximum B.M computed From Left side -145.6346 KNm

fck
Maximum B.M computed From Right side -230.8549 KNm fy
Mu
b
Take Maximum BM -145.6346 KNm d

For Overall depth Ast


effective depth reqired is Mu=0.133*Fck*b*(d^2)
d 186 mm

adopt Overall Depth due to Shear Consideration 400 mm

3 Main Negative Longitudinal Reinforcement


Area of Steel Reinforcement :
Mu = 0.87*fy*Ast*d*(1-(Ast/bd)*(fy/fck)) Eq 1
Mu 145.6346 KNm
fy 500 N/mm2
fck 20 N/mm2
b 1530 mm
d 450 mm
Solving Eq 1

Ast 1004.096 mm2

Using Diameter of the bars 12 mm

ast 113.04 mm2

Required Spacing 172.245705997639 mm

Provide 12mm @ 150mm c/c spacing


Provide Ast = 1153.008 > 1004.096 OK

Development Length :
for 16mm dia=(40*ɸ) 640 mm

check for shear one way (Column B)


shear force(Vu) 81.6111111111112 KN
nominal shear stress Ʈv 0.133351488743646 N/mm2
assuming 0.2% steel Ʈc 0.32 N/mm2
if Ʈv< Ʈc then results is ok OK

check for shear two way (Column B)


shear force(Vu) 1325.82261208577 KN
Normal shear stress Ʈv 1.10485217673814 N/mm2

shear strength Ʈc 1.1180339887499 N/mm2


if Ʈv< Ʈc then results is ok OK
12.73028
= 20
= 500
= 145634589
= 1530
= 350

= 1004.096
Combined Footing Design Excel Sheet
Sample Design

Material Properties
Grade of concrete (fck) = 20 N/mm2
For steel (fy) = 500 N/mm2
Bearing Capacity of soil = 120 N/mm2
Unfactored Load on Column 1 = 464 KN
Unfactored Load on Column 2 = 515.33333 KN
Size of Column 1
Width = 350 mm
Depth = 350 mm
Size of Column 2
Width = 350 mm
Depth = 350 mm
C/C spacing betwing C1 and C2 = 2.1 m
Projection along C1, a = 0.6
Projection along C2, a1 = 0.6

1 length and width of footing

CG of load from property line


X= = 1.7050374 m
LENGTH OF FOOTING= = 3.4100749 m
USING length of footing = 3.42 m
there will be slight ecentricity of = 0.12 m
it will cause a moment of with respect to centroid
of footing = 117.52 KN-m
this effect is neglected

assume wt of footing & earth above it as 5% of total wt


total wt on earth = 1028.3 KN
Footing width = 2.0044834 m
adopt width of footing, B = 1.53 m

2 longitudinal bending moment and shear

Factored load on Column 1 = 696 KN


Factored load on Column 2 = 773 KN

Net Upward soil Pressure = 280.73998 KN/m2


Net Upward Soil Pressure per unit length = 429.53216 KN/m
Maximum Shear Force at Centre line of Column A
V1 = -257.7193 KN
V2 = 438.2807 KN

Maximum Shear Force at Centre line of Column B


V1 = 257.7193 KN
V2 = -515.2807 KN

Point Of Zero Shear Force From Centre OF Column A


X = 0.9652126 m

Maximum B.M computed From Left side = -145.6346 KN-m


Maximum B.M computed From Right side = -230.8549 KN-m

Take Maximum BM = -145.6346 KN-m


For Overall depth
effective depth reqired is
Mu=0.133*Fck*b*(d^2)
d = 186 mm
adopt Overall Depth due to Shear Consideration 400 mm

3 Main Negative Longitudinal Reinforcement

Area of Steel Reinforcement :


Mu = 0.87*fy*Ast*d*(1-(Ast/bd)*(fy/fck)) Eq -- 1
Mu = 145.63459 KN-m
fy = 500 N/mm2
fck = 20 N/mm2
b = 1530 mm
d = 450 mm
Solving Eq 1

Ast = 1004.0959 mm2


Using Diameter of the bars = 12 mm
ast = 113.04 mm2
Required Spacing = 172.24571 mm
Provide 12mm @ 150mm c/c spacing = 1153.008 > 1004 OK

4 check for shear one way (Column B)

shear force(Vu) = 81.611111 KN


nominal shear stress Ʈv = 0.1333515 N/mm2
assuming 0.2% steel
Ʈc = 0.32 N/mm2
if Ʈv< Ʈc then results is ok OK

check for shear two way (Column B)

shear force(Vu) = 1325.8226 KN


Normal shear stress
Ʈv = 1.1048522 N/mm2
shear strength
Ʈc = 1.118034 N/mm2
if Ʈv< Ʈc then results is ok OK
12.7959
Grade of concrete (fck) M 20 N/mm2
For steel (fy) 500 N/mm2
Bearing Capacity of soil qu = 120 KN/m2

P1= 323.33333 KN P2= 367.3333 KN

0.3 0.3

0.15 4.16 0.15

4.46

1 length and width of footing


CG of load from property line
X= 2.3625097 m

LENGTH OF FOOTING= 4.725019

USING
length of
footing 4.46 m
there will be slight ecentricity of -8.88E-16
it will cause a moment of with respect to centroid of foot -6.13E-13 KNm
this effect is neglected

assume wt of footing & earth above it as 5% of total wt


total wt on earth 725.2 KN
Footing width 1.355007

adopt width of footing, B 1.53 m

2 longitudinal bending moment and shear


Factored load on Column 1 450 KN
Factored load on Column 3 718 KN
Factored load on Column 2 447 KN
Net Upward soil Pressure 236.6716 KN/m2

Net Upward Soil Pressure per unit length 362.1076 KN/m

Maximum Shear Force at Centre line of Column A


V1 -54.31614
V2 395.6839

Maximum Shear Force at Centre line of Column B


V1 54.31614
V2 -663.6839

Point Of Zero Shear Force From Centre OF Column A


395.6839 663.683856502242
=
X 4.16 -

manually calculating
X 2.8836 m 1.553799

Maximum B.M computed From Left side 368.5692 KNm

Maximum B.M computed From Right side -548.08 KNm

Take Maximum BM 368.5692 KNm

For Overall depth


effective depth reqired is Mu=0.133*Fck*b*(d^2)
d #NUM! mm

adopt Overall Depth due to Shear Consideration 500 mm

3 Main Negative Longitudinal Reinforcement


Area of Steel Reinforcement :
Mu = 0.87*fy*Ast*d*(1-(Ast/bd)*(fy/fck)) Eq 1
Mu -368.5692 KNm
fy 500 N/mm2
fck 20 N/mm2
b 1530 mm
d 500 mm
Solving Eq 1

Ast 1975.01 mm2


Using Diameter of the bars 16 mm

ast 200.96 mm2

Required Spacing 155.679616812067 mm

Provide 16mm @ 110mm c/c spacing


Provide Ast = 2795.17090909091 > 1975.01 OK

Development Length :
for 12mm dia=(40*ɸ) 640 mm

check for shear one way (Column B)


shear force(Vu) 41.6423766816144 KN
nominal shear stress Ʈv 0.054434479322372 N/mm2
assuming 0.2% steel Ʈc 0.32 N/mm2
if Ʈv< Ʈc then results is ok OK

check for shear two way (Column B)


shear force(Vu) 1484.83059292476 KN
Normal shear stress Ʈv 0.928019120577977 N/mm2

shear strength Ʈc 1.1180339887499 N/mm2


if Ʈv< Ʈc then results is ok OK
485

551

323.3333

367.3333

6.24
.683856502242