Calculation tool. in excel tables form. Created to easily calculate and determine the size of cooling units (compressors) in BTU and KW for Cold Rooms.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
100%(1)100% found this document useful (1 vote)
1K views
Cold Room Calculator
Calculation tool. in excel tables form. Created to easily calculate and determine the size of cooling units (compressors) in BTU and KW for Cold Rooms.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 3
Transmission Load Q= U*A*( Temp out - Temp in )*24/1000 Lighting Load Q=La
U = Value of insulation w/m2K 0.25 Lamps = qtty of lamps
2 A= Total area of walls, ground and roof m 222 Time = Length of work time Temp out = Ambient tempert. Outside the room ˚C 50 Wattage = Power of lamps Temp in = Temperature inside the room ˚C 12 Q = Lighting Load Q = Transmission load Kwh/day 50.616
Product Exchange Q=m*cp*(Temp out - Temp in)/3600 Fan Motors Load Q
m = Mass of Product Kg 600 Fans = Qtty of fans CP = Specific heat energy Kj/Kg 3.7 Time = Length of work time Temp out = Temp. of product entering ˚C 15 Wattage = Power of motor's fan Temp in = Temp in the Room ˚C 12 Q = Fan motors Load Q = Product Exchange load Kw 1.85 Electrical Defrost Loa Power = Rating of heating element Product resp Q=m*resp/3600 Time = Defrost run Time m = mass of new product per day kg 0 Cycles = Qtty of run cycle per day resp = Respiration of heat KJ/Kg 0 Effi = Percentage of heat dissip in th Q = Internal Load Kwh 0 Q = Electrical Defrost Load Lighting Load Q=Lamps*Time*Wattage/1000 Air Infiltration load Q =Cycle*vol*energy*(Temp out-Tem tty of lamps lamp 4 Cycle = Air change cycles per day ngth of work time Hr/day 3 Volume = Volume of cold room = Power of lamps W 200 Energy = Energy per cubic meter ng Load Kwh/day 2.4 Temp out = Air temperature outside Temp in = Air temperature Inside Q = Air infiltration Load
Fan Motors Load Q=Fans*Time*wattage/1000 Internal People Load Q=People*time*heat /10
tty of fans Fan 2 People = Qtty of people per day ngth of work time Hr/day 20 Time = Length of work time = Power of motor's fan W 200 Heat = heat dissipated per person motors Load Kwh/day 8 Q = Internal Load
Electrical Defrost Load Q=Power*Time*cycle*effi
Rating of heating element Kw 1 Cold Room Cooling Load/day frost run Time Hr 0.3 75.856 KW/day Qtty of run cycle per day Cycle 3 entage of heat dissip in the room % 0.3 ical Defrost Load Kwh/day 0.27 Required Cooling Compressor 5.6892 ycle*vol*energy*(Temp out-Temp in)/3600 ay cyc/day 3 3 m 180 3 r Kj/˚C/m 2 tside ˚C 50 de ˚C 12 Kw 11.4