Power Factor Correction

Calculation tool in excel form. To calculate the size of capacitors bank capacity in Kvar to correct the power factor and increase power consumption efficiency in your house or facility.

Uploaded by

Samer Chahrouk
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
30 views

Power Factor Correction

Calculation tool in excel form. To calculate the size of capacitors bank capacity in Kvar to correct the power factor and increase power consumption efficiency in your house or facility.

Uploaded by

Samer Chahrouk
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

Power Factor P = True Power (KW)/Apparent Power (KVA) Capacitor Size Q =

Reactive Power Q = Apparent power x Cosfi KVAR

Apparent Power S = SQRT (True power^2 + Reactive power^2) KVA

Corretion - Capacitor Size

Power consumption KW 100 Real COSfi 0.86 Target Cosfi

Real Apparent Power 116.279069767442 KVA Target Apparent Power

Real Reactive Power 59.3365154519678 KVAR Target Reactive Power

Capacitor Size:
pacitor Size Q = Real Reactive power - Target reactive power KVAR

Target Cosfi 0.96

104.1667 KVA

29.16667 KVAR

30.1698487853011 KVAR