EPS Startup Test Procedure - SEC
EPS Startup Test Procedure - SEC
INDEX
SECTION-1 INTRODUCTION ........................................................................................................................ 3
SECTION-2 SAFETY....................................................................................................................................... 5
SECTION-3 MECHANICAL CHECKS AND VISUAL INSPECTION................................................................ 6
SECTION-4 INSULATION RESISTANCE TEST ................................................................................................. 7
SECTION-5 HIGH VOLTAGE TEST ................................................................................................................ 9
SECTION-6 CURRENT TRANSFORMER TEST .............................................................................................. 13
SECTION-7 VOLTAGE TRANSFORMER TEST.............................................................................................. 18
SECTION-8 POWER TRANSFORMER TEST ................................................................................................. 21
SECTION-9 METAL CLAD SWITCHGEAR .................................................................................................. 25
SECTION-10 CIRCUIT BREAKER / CONTACTOR ...................................................................................... 27
SECTION-11 DISCONNECTOR / GROUND SWITCH ................................................................................ 29
SECTION-11 DISCONNECTOR / GROUND SWITCH ................................................................................ 29
SECTION-12 PROTECTIVE RELAY .............................................................................................................. 30
SECTION-12 PROTECTIVE RELAY .............................................................................................................. 30
SECTION-13 MEASURING INSTRUMENTS .................................................................................................. 31
SECTION-14 PROTECTION FUNCTION TEST.............................................................................................. 32
SECTION-15 POWER CABLE TEST.............................................................................................................. 36
SECTION-16 STATION DC SYSYTEM .......................................................................................................... 37
SECTION-17 TRANSFORMER OIL TEST....................................................................................................... 39
SECTION-18 SCHEME VERIFICATION TEST: .............................................................................................. 40
SECTION-19 COMMISSIONING TEST ........................................................................................................ 41
SECTION-1 INTRODUCTION
The purpose of these specifications is to assure that all tested electrical
equipment and systems supplied by either contractor or owner are
operational and within applicable standards and manufacturer’s tolerances
and that equipment and systems are installed in accordance with design
specifications.
The need for acceptance testing of electrical power systems is very clear to
those with extensive start-up and/or operating experience. Shipping and
installation damage, field and factory wiring errors, manufacturing defects,
and systems and components not in accordance with drawings and
specifications are some of the many problems that can be detected by
appropriate testing. When these defects are found before start-up they can
be corrected under warranty and without the safety hazards and possible
equipment and consequential damages of loss of use/production that can
occur if discovered after startup or energizing. In addition, test results obtained
during acceptance testing are invaluable as base reference data for the
periodic testing that is an essential element of an effective maintenance
program.
This document lists a majority of the field test available for assessing the
suitability for service and reliability of the power distribution system. Certain
tests have been assigned an “optional” classification. The following
considerations were used in determining the use of the “optional”
classification:
1. Did another test listed provide similar information?
2. How did the cost of the test compare to the cost of other tests providing
similar information?
3. How commonplace was the test procedure? Is it new technology?
While acknowledging the above, it is still necessary to make an informed
judgment for each particular system regarding how extensive the testing
should be. The approach taken in these specifications is to present a
comprehensive series of tests that is applicable to most industrial and larger
commercial systems. The guidance of an experienced testing professional
should be sought when making decisions such as how extensive testing should
be. In smaller systems some of the tests can be deleted. In other cases, a
number of the tests indicated as optional should be performed.
As a further note, it is important to follow the recommendations contained in
the manufacturer’s instruction manuals. Many of the details of a complete
and effective acceptance testing procedure can only be obtained from that
source.
SECTION-2 SAFETY
Proper safety procedures shall be reviewed and followed before each activity
listed in this procedure. Job Safety Analysis followed by a toolbox/pre-job
meeting shall be conducted prior to any activity listed in this procedure.
Proper safety procedures as detailed in the Square D/Schneider Electric “Field
Services Safety, Health and Environmental Handbook”, employee training,
and customers requirements shall be implemented as dictated by each sites
requirements.
Services Employees are NOT authorized to work on live equipment. There may
be occasions in which you are taking measurements or checking voltages
within an energized enclosure, but you are NOT authorized to “do Hands on
Live” repairs!
Company representative does not typically perform shutdown and/or
switching operations, because these operations may result in damage to
property or persons downstream of the equipment as a result of conduct,
errors, or omissions made by others. If a customer requests Company
representative to perform such services, technicians must contact their
Manager for approval and proper procedures.
3.2. PROCEDURE:
The following points to be checked in mechanical checks and visual
inspection.
Visual inspection:
- Nameplate details
- Physical condition (damage/ defect)
- Installation checks
- Equipment verification against rating and matching with requirement.
Mechanical checks:
- Power circuit connection tightness by torque method.
- Control wiring tightness.
- Interlock checks between equipment.
- Mechanical operations like rack in/ rack out.
The mechanical checks and visual inspection for equipments has been listed
in detail under respective section.
TABLE 4.1
TEST VOLTAGE LIMITS
10min/1min Ratio
Insulation condition
(Polarisation Index)
Dangerous <1
Poor >1 to <1.5
Questionable >1.5 to <2
Good >2 to <4
Excellent >4
TABLE 4.2
POLARISATION INDEX
5.3.1. SWITCHGEAR:
It includes panel enclosure, bus bar, CT & breaker / contactor. The following
precautions should be taken care, before starting the test:
- A visual inspection will be made to ensure the surface dust and moisture
has been removed from the component under test.
- Ensure the component is isolated from other connected system, which
may feed back to other components or circuits not under test.
- A check shall be made to verify the ground for the component under test
and test equipment being connected to system ground.
- CT’s secondary terminals shall be shorted.
- VT’s & Surge arresters shall be isolated from the equipment under test.
- Mark out test area and assure nobody can enter during test.
- Circuit breakers/contactors should be inserted and closed.
- Busbars should be fully mounted tightened and shields between phases &
between phases and earth should be in place. Moreover, busbar covers
should be in place.
- All earthing switches related to equipment under test should be open.
- Busbar conductivity test shall be performed.
- Insulation resistance test should be performed before and after
commencing the test.
- Instructions of test equipment being used should be followed.
- After each test subject under test should be discharged to ground.
- The test connection shall be made as shown in the fig. 5.1.
Required test voltage shall be raised slowly and maintained for one minute
between one phase and other phases connected to ground and than
reduced slowly to zero, testing shall be repeated for other phases as
mentioned above. During each test leakage current shall be recorded.
After the above test, another test shall be repeated after opening all circuit
breakers / contactors and applying test voltage across opening distance
between poles with three poles shorted on both sides and grounded on one
side only as shown in the fig.5.2. Test voltage limits are mentioned in table 5.1.
Fig 5.1
HV test for switchgear
Fig 5.2
HV test for opening distance
5.3.2. POWER CABLES:
DC Voltage Test:
a) Test for 5min with phase-to-phase voltage of the system applied between
the conductor and the metallic screen
b) Test for 24 hours with the normal operating voltage Uo of the system.
Note: Normally cables have three voltages specified: i.e. Uo\U\Um
Where Uo=rated Phase to earth/screen voltage
U= rated Phase to phase voltage
Um=rated maximum Phase to phase voltage
-For cables used for solidly earthed system screen current for the earth fault will
be high but cable Uo rating is low i.e. Uo=U/1.732
-For cables used for resistance earthed system screen current will be low for
earth fault but cable Uo rating is high i.e. Uo=U
Note:
A VLF (Very Low Frequency) high voltage of 3xUo shall be applied between
conductor and screen. Some utility customers are accepting this.
For Switchgear:
No flashover or disruptive discharge should occur during test. Corona
discharge noise may be heard during this test.
Rated I min.
Rated voltage power frequency Test voltage at
(KV) withstand voltage field =80%KV
(KV)
7.2 20 16
17.5 38 30.4
36 70 56
Note: For old switchgear the test voltage shall be reduced according to the
age.
TABLE 5.1
SWGR TEST VOLTAGE
Fig 6.1
Polarity test
Limits:
The value must be with in specified on nameplate after the effect of
temperature taken in to account. If not factory test results shall be taken as
reference.
Ohmmeter
Note2 Ohmmeter
Note1
Burden
Fig 6.2
CT resistance / loop resistance test
Limits:
The calculated burden should be less than rates CT burden.
Note:
Ammeter selector switch should be at respective phase during test.
High impedance relays shall be shorted during the test.
Demagnetisation:
Before start the test demagnetise the core by Inject voltage on secondary
terminals and increase up to where considerable increment in current with
small voltage increment. Now start decreasing the voltage to zero, the rate at
which increased.
Magnetisation test:
Now increase the voltage and monitor the excitation current up to the CT
reaching near to saturation point. Record the reading of voltage and current
at several points. Plot the curve and evaluate the Vk and Img from the graph.
Limits:
Class X CT:
The obtained Vk should be greater than specified one; mag current should be
less than specified one.
Protection class CT:
The secondary limiting voltage can be calculated as follow
Vslv = Is * ALF (Rct + (VA/Is*Is))
Is – rated secondary current
Rct- CT secondary resistance
VA- rated CT burden
ALF – Accuracy limit factor
The mag current (Img) drawn at Vslv can be obtained from graph. The
following criteria should be satisfied.
Img < accuracy class * ALF * Is
Metering Class CT:
Accuracy can be ensured as follow,
Fig 6.3
Magnetisation test
Core identification:
When one CT is having several cores used for different purposes. The cores
can be identified during primary injection test by shorting the one of the core
at CT terminal itself and check there is no current only at relevant load. The
same can be verified for other cores.
Inject 25% of rated primary current between phase to phase with all
connected burden. Measure secondary current at all points of CT circuits. It
shall be done for other phases.
Limits:
- Secondary current should only be observed at respective phase and
neutral leads during Phase to earth injection.
- Secondary current should only be observed at respective phases and no
current on neutral during Phase to phase injection.
Fig 6.4
Primary injection /Ratio test
Fig 7.1
Polarity test
Limits:
The calculated burden should be less than rates VT burden.
Note:
Voltmeter selector switch should be at respective phase during test.
Fig 7.2
Ratio test
7.3.9. VT CIRCUIT CHECK:
This test is to confirm all the loads of VT are connected properly and no mix-up
between phases.
Inject three-phase voltage with different magnitude at each phase, on the
secondary circuit (VT side isolated), and measure voltage at all points. Verify
that there is no mix-up between phases.
connected RY, YB, BR or RB, YR, BY) and voltage shall be measure at
respective secondary winding. This test shall be done phase-by-phase for all
taps.
Limits:
Compare the trend of voltage ratio with reference to nameplate or previous
factory test results.
r
R
A
y V1
Y
V2 220V
b AC
B
Fig 8.1
Ratio / Excitation test
Limits:
The result should match with nameplate specification.
r
R
y
Y
3ph
b 220V
B
AC
Fig 8.2
Vector Group test
Fig 8.3
Winding resistance test
Limits:
Test results should match with nameplate specification or factory test results
shall be taken as reference.
Buchholz relay:
Operation verification shall be done gas injection as per supplier’s instruction
manual.
Alarm and trip contacts wiring shall be checked for proper operation.
Oil / Winding temperature indicator:
- OTI and WTI shall be calibrated with standard thermometer as per
supplier’s instruction manual.
- For WTI shall be tested for thermal image by injecting current at current
terminals as per supplier’s instruction manual.
- Check alarm / trip contacts for proper function.
Cooler fans:
- Insulation resistance of fan motor to be checked.
- Fan starting current and running current shall be noted and direction of
rotation to be checked.
- The overload relays should be properly adjusted.
OLTC mechanism:
- Operation test shall be carried out for OLTC.
- Check Operation interlock.
This test is to confirm the busbar joints are connected properly and verify the
tightness.
The test connection diagram is as shown in Fig.
The test shall be done with CBs inserted and closed. Measure the contact dc
resistance between panels by injecting 100ADC. This will include busbar joint,
CB contact resistance, CB cluster resistance, and CT primary resistance (if
applicable).
Limits:
The obtained results should be similar for all phases for each set of
measurement.
Other influencing factors to be considered, like length of the measured path,
rating of the busbar, rating of CB, rating of CT and temperature.
Fig 9.1
Contact resistance test
IEC60298: – AC metal enclosed switchgear and control gear for rated voltage
above 1KV to 52KV.
Limits:
Operation shall be observed without fail.
This test is to confirm the above tested relay is properly connected / interfaced
with system, that required. This will verify all inputs to relay and outputs from the
relay are properly connected, as it required. An injection (current/ voltage)
shall be made and checked the functions outputs (trip, alarm, indication,
control). Inputs shall be initiated from the source and monitored the proper
outputs from the relay.
Limits:
The observed accuracy of meter at various points shall be compared with
meter accuracy class.
Note:
Meter accuracy is influenced by ambient temperature at which the test is
conducted. The temperature shall be noted during test and manufacturer
instruction shall be followed for temperature effects on accuracy.
Stability Test:
The test connection shall be made as shown in Fig 14.2. Inject primary current
of minimum 50 % primary operating current. The CTs secondary current and
differential current at relay shall be measured. A zero differential current
measurement shall be satisfactory results.
Fig 14.1
Busbar protection sensitivity test
Fig 14.2
Busbar protection stability test
3 Phase
shorting
3 Phase at LV
test
supply
Fig 14.3
Transformer diff. Protection stability test
1 Phase
grounding
3 Phase at LV
test
supply
Fig 14.4
Transformer REF protection stability test
The test voltage shall be applied between conductor and shield or screen
connected to ground. The reading shall be taken for each phase as below.
- Phase to ground + other phases.
The test voltage shall be applied for 1 min and the test voltage limits has been
listed in table 4.1.
This is very important test for cable. Continuity check shall be done with both
ends isolated and individually for each phase. The phase marking shall be
done at both the ends. If there are many runs of cable, phasing check shall be
done for each run.
IEC 60502-2: Power cables with extruded insulation and their accessaries from
1 KV to 30KV.
- Multimeter.
- Battery loading unit (Torkel-720 (Programma Make) or equivalent. The
Torkel-720 is capable of providing a constant current load to the battery
under test.
This test establishes the correct operation of the battery charger within the
specified voltage and current levels in various operational modes.
• Mandatory Condition: The battery set should have been properly charged
as per the commissioning instructions of the battery manufacturer for the
duration specified.
• Visual Inspection: Cleanliness of battery is checked and the electrolyte
level checked as specified on the individual cells. The tightness of cell
connections on individual terminals should be ensured.
• The load current, minimum voltage of battery system, ampere-hour,
duration etc., is preset in the test equipment using the keypad. For (e.g.) a
58 AH battery set, 5 Hr. duration specification 11.6 A and 5 Hr. duration are
set. Minimum voltage setting is = No. of cells x end cell voltage of cells as
per manufacturer specification.
• It is to be ensured that the set value of the current and duration is within
the discharge capacity of the type of cell used. Also the total power to be
dissipated in the load unit should be within the power rating of the battery
load kit.
• Individual cell voltages to be recorded before the start of the test.
• Battery charger to be switched off/load MCB in charger to be switched
off.
• Loading of the battery to be started at the specified current value.
Individual cell voltages of the battery set are to be recorded every half an
hour.
• It is to be ensured that all the cell voltages are above the end-cell voltage
specified by the manufacturer. If any of the cell voltages falls below the
threshold level specified by the manufacturer, this cell number is to be
noted and the cell needs to be replaced.
• Test set automatically stops loading after set duration (or) when minimum
voltage reached for the battery set.
• Test to be continued until the battery delivers the total AH capacity it is
designed for. Value of AH and individual cell voltages to be recorded
every half an hour.
Acceptance Limits:
This test establishes the AH capacity of battery set at required voltage. The
acceptance limit for the test is to ensure the battery set is capable of
supplying the required current at specified DC voltage without breakdown for
the required duration.
• A clean, dry GLASS container is to be used. The size of the container should
be at least three times the size of the test cell. (A container of
approximately 1 litre is sufficient)
• During sampling, rinse the glass container with little quantity of oil and
drain.
• Fill the container with oil until the container over flows.
• Do not allow free air space inside the container.
• Do not allow air bubbles inside the container.
• Sampled Container should be closed airtight with cork or any other non-
reactive material.
• (Optional). In case the oil is to be transported to a larger distances, ensure
that oil is stored in a clean and dry place and transported with utmost
care.
• Before filling the oil in the test cell, gently agitate the container without
creating air bubbles.
• Rinse the walls of the test cells with little of oil and drain it.
• Ensure that the electrodes of the test cell are clean.
• Fill the oil sample until overflow, into the test cell without formation of air
bubbles.
• Do not start the test for at least for 5 min. after filling the test sample (oil).
• The oil sampling to be carried out as per the procedure explained in the
sampling instructions.
• The BDV test to be started after at least 5 minutes from the filling of the
sample oil in the test cell.
• Ensure that the gap between the electrodes is maintained at 2.5mm.
• Ensure that the electrodes are clean.
• The rate of rise of the test voltage to be adjusted at 2kV per second.
• Conduct the BDV test for 5 to 6 times for the same sample with a time
interval of at least 3 - 4 minutes between tests.
• Ensure that between tests, stirring of the test sample is carried out.
• Record the test results and obtain the average of the test results to obtain
the Breakdown voltage of the test sample. (Ignore the odd values)
- Multimeter
- Others (if required any).
18.3. PROCEDURE:
- Multimeter
- Phase angle meter
- Phase sequence meter
- Communication software (if required)
The following items shall be check without fail prior to energise the system.
Phasing checks:
Before making two live feeders parallel, the phasing must be checked though
the source is same. This could be done in two methods. One method is hot
phasings, most reliable method, since the check is done on the primary. The
voltage difference between feeders shall be monitored by connecting hot
stick (Voltage detector equipment, rated for system voltage, that will indicate
presence of voltage) between Rph-Rph, Yph-Yph, Bph-Bph of two feeders
respectively. Another method is phasing between VT secondaries, and a
caution be taken for this method, that there is no mistake on secondary wiring.
To ensure correct connection of primary and secondary, energise both the VTs
by any one supply and do phasing between secondaries. For correct
connection no voltage difference shall be observed during phasing. Now the
VTs could be energised with respective feeder’s supply and repeat the
phasing between VT secondaries. If there is no considerable voltage
difference between the feeders voltage, they are ready to parallel.
Synchronising Check:
Before making to different source of same voltage level, in addition to phasing
check, synchronisation must be done. The following steps shall be followed.
• Adopt proper setting for synchro-check relay.
• Check the secondary grounding for all VTs are at same point (star point or
Y phase).
• Energise both the VTs with same source.
• Do phasing between VT secondaries, check synchro-check relay picks up
continuously and synchroscope is staying at 12’o clock position. This
ensures that the primary and secondary connections of VTs are correct.
• Now energise the VTs with respective sources.
• Check the synchroscope the pointer continues to rotate. This rotation
(incoming voltage vector is rotating with respect to running voltage) is due
to slip frequency between the sources, i.e., phase angle between the
voltages varying time to time due to frequency difference of supplies.
• If the observed rotation is fast, try to make it slow by increasing or
decreasing speed of the machines.
• Once the rotation is slow, when the incoming voltage phase angle
difference falling with in the setting value the synchronising relay will pick
up and it will drop off as soon as the phase angle difference exceeds.
• It is allowed to parallel the sources with in this period.
This test to verify the directional protection / distance relay is looking in desired
direction (trip direction). This could be confirmed by on load test. The principle
of the test is that the load current and voltage shall be simulated in trip
direction and observe the relay operation. The VT or CT input to the relay shall
be reversed and observe the relay is reset.
The procedural method could be difference with different type of relays. The
relay manufacturer’s procedure shall be followed for directional check. The
following precautions shall be taken during directional test.
- Protection shall be put out of service, i.e. all out put contacts are isolated.
- Never open circuit CT circuit.
- At the end of the test all the connections shall be restored back.
This is the test to confirm the stability of a differential protection for through
fault with load current. The following precautions shall be taken during test.
- Protection shall be put out of service, i.e. all out put contacts are isolated.
- Never open circuit CT circuit.
- At the end of the test all the connections shall be restored back.
The entire feeder’s current shall be measured with phase angle. The
differential current at main relay and voltage across CT bus shall be measured.
At normal load condition there should be no differential current and voltage.
Power flow
Pilot wire
Fig 19.1
Pilot wire protection on load test
All the meters show the primary quantity with secondary input quantities.
Sometime it is impart to check the meter reading with actual inputs for correct
polarity, particularly in power, energy measurement.
For power meter the input current and voltage shall be measured with angle.
The meter reading could be validated as shown in fig 19.2.
(MW = ZERO)
-90
- MW + MW
(MW = MAX.) -180 0 (360) (MW = MAX.)
- MW + MW
-270
(MW = ZERO)
(MVAR = MAX.)
90
+ MVAR + MVAR
(MVAR = ZERO) 180 0 (360) (MVAR = ZERO)
- MVAR - MVAR
270
(MVAR = MAX.)
Fig 19.2
Nature of load