VAV Types
VAV Types
M
Performance Data ...............................................................................................................................................................M28
EDV/EDC - Dual Duct with Attenuator ................................................................................................................................M30
Performance Data ...............................................................................................................................................................M31
MDV/MDC - Dual Duct High Performance Blending ..........................................................................................................M33
Performance Data ...............................................................................................................................................................M34
Suggested Specifications....................................................................................................................................................M36
Model Number Specification ..............................................................................................................................................M37
AHRI Certification ...............................................................................................................................................................M38
SINGLE/DUAL DUCT TERMINALS
M2
www.ruskintitus.com | www.titus-hvac.com | www.titus-energysolutions.com
Single/Dual Duct Terminal Products Single/Dual Duct Terminals
SINGLE DUCT TERMINALS
pages: M4-M24
ESV
AVAILABLE CONFIGURATIONS CONTROL OPTIONS UNIT ACCESSORIES
• With integral attenuator. • Pneumatic. • Fibre Free lining.
• With water coils. • Electric. • Steri-Loc™ lining.
• With integral electric coil section. • TA1 electronic. • UltraLoc lining.
• OEM controls program. • Multi-outlet section.
M
• Factory mounting of controls by others. • Round outlet adapter.
• OEM controls (Titus Alpha BACnet). • EcoShield.
• Removable flow sensor.
For detailed controls information, please refer to the Terminal Unit Accessories section. M3
www.ruskintitus.com | www.titus-hvac.com | www.titus-energysolutions.com
M
ESV Casing Leakage, cfm Damper Leakage, cfm
INLET ∆PS, IN WG INLET ∆PS, IN WG
SIZE 0.5 1.0 2.0 3.0 SIZE 1.0 2.0 4.0 6.0
4, 5, 6 2 3 4 5 4, 5, 6 3 4 6 7
7, 8 4 5 7 9 7, 8 3 4 6 7
9, 10 4 6 8 10 9, 10 3 4 6 7
12 5 7 10 12 12 3 4 6 7
14 6 9 13 16 14 3 5 7 8
16 7 10 14 17 16 4 5 7 9
Titus continues to offer the most innovative and popular EcoShield is a sustainable liner comprised of recycled denim
lining alternatives for special applications including Fibre- making it environmentally friendly and contains no harmful
Free; the industry benchmark Steri-Loc; and the premium irritants or chemicals.
DESIGN FEATURES
Fibre-Free eliminates the requirement for foil linings and With a detailed understanding developed through years of
solid inner liners since there is no fiberglass in the airstream. selling and supporting the powerful TD1 digital controller,
Additionally, Fibre-Free minimizes mold growth since it holds and now the Titus BACnet OEM controls, Titus has industry
no moisture, is acoustically preferable to foil or solid metal leading experience in the application of Direct Digital Control
linings and maintains acceptable thermal protection. All (DDC) to terminals. This same expertise is made available
of these benefits are available at a competitive price and when your project requires quality engineering, coordination
significantly less than solid metal liners. and manufacturing for factory mounting when controls are
supplied by others.
Steri–Loc provides a smooth, nonporous skin to guard
M4 against mold and bacteria growth. Erosion is eliminated, Count on Titus - the industry leader in VAV!
as there is no glass fiber exposure to the airstream. It has
www.ruskintitus.com | www.titus-hvac.com | www.titus-energysolutions.com
Design Features (continued) Single/Dual Duct Terminals
DESIGN FEATURES
M5
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
For detailed information on specific control types, refer to the following pages in
cfm Increase
Min.
Section S:
Pneumatic: See pg. O18 Analog: See pg. O11 Digital: See pg. O5
Room Temperature Increase
Ho
toward the closed position. On a further increase in room temperature, the unit
tW
modulates the cold airflow from the minimum (which must be greater than zero) to
at
er
the maximum setting.
cfm Increase
Fl
ow
Min.
Pneumatic: See pg. O18 Analog: See pg. O11 Digital: See pg. O5
Room Temperature Increase
Ho
Max.
tW
modulates the cold airflow from the lower minimum to the maximum setting.
at
er
Fl
In the heating mode, the unit references the alternate (higher) minimum airflow. As
ow
Alt. Min.
the room temperature decreases, the unit modulates the airflow from the maximum cfm Increase
to the higher minimum, then modulates the hot water coil valve toward the open
position. The valve operates only in the heating mode. Min.
A further increase in room temperature changes the operation to the cooling mode,
ate
rF
and the unit modulates the cold airflow from minimum to maximum, which is the
low
mode, and the unit modulates the cold airflow from minimum to maximum, which
is different from the heating maximum (usually higher). Both the heating and the
cooling maximum airflows are adjustable.
Room Temperature Increase
Pneumatic: See pg. O18 Analog: See pg. O11 Digital: See pg. O5
M6
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
Control Strategies (continued) Single/Dual Duct Terminals
Constant Volume, Hot Water Reheat
The cold airflow remains constant regardless of changes in duct pressure or room
temperature. As the room temperature increases, the unit modulates the hot water
Ho
coil valve toward the closed position.
tW
a te
cfm Increase
rF
Pneumatic: See pg. O18 Analog: See pg. O11 Digital: See pg. O5
low
Room Temperature Increase
one step at a time. On a further increase in room temperature, the unit modulates
the cold airflow from the minimum (which must be greater than zero) to the
Step 1
maximum setting.
cfm Increase
Min.
Pneumatic: See pg. O18 Analog: See pg. O11 Digital: See pg. O5
Room Temperature Increase
Pneumatic: See pg. O18 Analog: See pg. O11 Digital: See pg. O5
Room Temperature Increase
When the signal is removed, the unit resumes normal control of airflow. With the Min.
central system now supplying cold air, as room temperature increases, the unit
modulates the cold airflow from minimum to the maximum setting. CONTROL STRATEGIES
Pneumatic: See pg. O18 Analog: See pg. O11 Digital: See pg. O5 Room Temperature Increase
M7
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
ESV
Electronic
DESV • Digital • Controls supplied by Titus are
Electronic factory calibrated for a quicker
start-up.
• Standard AeroCrossTM multi-point
center averaging velocity sensor
(except EESV).
PESV Pneumatic
W Actuator M L
H D
M Multi-Point
Center Averaging F 4½”
Control
Cover
(optional)
Thermostat &
20 psi Main Air
Connections for
Slip and Drive
Cleat Connection
Velocity Sensor
¼” Dia. Tubing
DESV M
L
W
AESV F G
EESV
H 12¼”
D
F
INLET CFM AESV
D G H L M W
SIZE RANGE PESV DESV
EESV
4 0-225 3⅞ 1⅞ 2⅛ 7⅜ 8 15½ 5⅜ 12
5 0-350 4⅞ 1⅞ 2⅛ 7⅜ 8 15½ 5⅜ 12
6 0-500 5⅞ 1⅞ 2⅛ 7⅜ 8 15½ 3⅜ 12
7 0-650 6⅞ ⅞ 1⅛ 7⅜ 10 15½ 3⅜ 12
8 0-900 7⅞ ⅞ 1⅛ 7⅜ 10 15½ 3⅜ 12
ESV
12¼ H
INTEGRAL ELECTRIC COIL
With a rigid one piece assembly,
Titus locates the heating elements for
optimal heat transfer and insets them
for protection during shipment
and installation.
39½ 6¼ W
STANDARD FEATURES:
• Primary automatic reset thermal
cutout (one per coil).
12 H
• Secondary manual reset
thermal cutout.
• Airflow switch
(differential pressure). 365/8
• Derated nickel chrome
M
heating elements.
• Magnetic or safety contactors
(as required).
L W
• Line terminal block.
• Control terminal block.
• ETL listed.
• 80/20 nickel chrome element wire. H
OPTIONAL FEATURES:
• Class ll, 24 volt control transformer. Side View End View
• Mercury contactors.
• Door interlock disconnect switch.
• Main supply fuses.
• Dust tight construction. M 39½ L
• Removable flow sensor. W
6 8 3⅜ 12 5 7¼
7, 8 10 3⅜ 12 5 7¼
9, 10 12½ 3⅜ 14 5 7¼
12 15 3⅜ 16 5 7¼
14 17½ 3⅜ 20 7½ 9¾
16 18 3⅜ 24 7½ 9¾
24X16 18 3⅜ 38 5 7¼
Note: The total length of the ESV basic unit and
accessories (attenuators and coils) is the summation of
basic unit length and the accessories length.
All dimensions are in inches.
M9
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
2 Outlets 3 Outlets
36” 33/8” TYP. 36”
33/8” TYP.
G G
D TYP.
D TYP. H D TYP. H
4 Outlets 5 Outlets
36” 33/8” TYP. 36”
33/8” TYP.
M G M G
D TYP.
M D TYP. H D TYP. H
ROUND OUTLETS
Unit Size D H W
33/8“ 4“ W
4 3⅞ 8 12
5 4⅞ 8 12
6 5⅞ 8 12
ACCESSORIES
7 6⅞ 10 12
8 7⅞ 10 12
D D H 9 8⅞ 12½ 14
10 9⅞ 12½ 14
12 11⅞ 15 16
14 13⅞ 17½ 20
16 15⅞ 18 24
Removable Sensor
#8 Sheet metal screw Installed
6 places
Sensor
Removed
Removable flow
sensor assembly
9.00 9.00
Control Types:
PESV / Pneumatic
AESV / Analog Electronic
DESV / Digital Electronic
M
cfm Ranges of Minimum and Maximum Settings
Total cfm PESV - Pneumatic PESV - Pneumatic AESV - Analog Electronic DESV - Digital
Inlet Size
Range Titus II Controller Titus I Controller TA1 Controller Typical Controller
Minimum Maximum Minimum Maximum MINIMUM MAXIMUM MINIMUM MAXIMUM
4 0-225 45*-170 80-225 55*-170 80-225 45*-225 45-225 30*-225 30-225
5 0-350 65*-270 120-350 85*-270 120-350 65*-350 65-350 40*-350 40-350
6 0-500 80*-330 150-500 105*-330 150-500 80*-500 80-500 45*-500 45-500
7 0-650 105*-425 190-650 135*-425 190-650 105*-650 105-650 70*-650 70-650
8 0-900 145*-590 265-900 190*-590 265-900 145*-900 145-900 90*-900 90-900
9 0-1050 175*-700 315-1050 225*-700 315-1050 175*-1050 175-1050 120*-1050 120-1050
10 0-1400 230*-925 415-1400 300*-925 415-1400 230*-1400 230-1400 145*-1400 145-1400
12 0-2000 325*-1330 600-2000 425*-1330 600-2000 325*-2000 325-2000 190*-2000 190-2000
14 0-3000 450*-1800 810-3000 575*-1800 810-3000 450*-3000 450-3000 300*-3000 300-3000
16 0-4000 580*-2350 1100-4000 750*-2350 1100-4000 580*-4000 580-4000 385*-4000 385-4000
24 x 16 0-8000 1400*-5200 2600-8000 1800*-5200 2600-8000 1400*-7500 1400-7500 720*-7500 720-7500
*Factory cfm settings (except zero) will not be made below this range because control accuracy is reduced. On pressure dependent units, minimum
cfm is always zero and there is no maximum.
Note: On controls mounted by Titus but supplied by others (FMA or Factory Mounting Authorization), these values are guidelines only. Controls
mounted on an FMA basis are calibrated in the field.
PERFORMANCE DATA
M12
Single/Dual Duct Terminals
M
650 0.02 60 51 44 41 39 32 22 63 56 50 44 44 40 25 65 59 53 47 46 45 28 66 61 55 48 48 48 30
8 700 0.02 60 52 45 42 40 33 22 63 57 50 45 44 41 25 65 60 53 47 47 45 29 67 62 56 49 49 48 31
750 0.02 61 53 46 43 40 34 23 64 58 51 46 45 41 27 66 61 54 48 48 46 30 67 63 56 50 50 49 33
800 0.03 62 54 47 43 41 34 24 65 59 52 47 46 42 28 66 62 55 49 48 47 31 68 64 57 51 50 50 34
800 0.04 58 47 43 36 34 30 19 61 53 49 42 40 35 23 62 57 52 46 44 38 26 63 59 55 48 47 40 29
850 0.04 58 48 43 37 34 31 19 61 54 49 43 41 35 23 63 58 53 46 45 38 27 64 60 55 49 47 40 29
9 900 0.05 59 49 44 37 35 31 20 62 55 50 43 41 35 24 64 58 53 47 45 38 27 65 61 56 49 48 40 30
950 0.06 59 50 44 37 35 31 20 62 56 50 43 42 36 24 64 59 54 47 45 38 28 65 62 56 49 48 40 31
1000 0.06 60 50 44 38 36 31 22 63 56 50 44 42 36 25 65 60 54 47 46 39 29 66 62 57 50 48 40 31
900 0.01 60 50 47 45 42 29 22 63 57 53 50 48 37 27 65 60 57 53 52 41 31 67 63 59 56 54 44 34
1000 0.01 60 51 48 46 43 30 22 64 58 54 51 49 38 28 66 61 57 54 53 42 31 67 64 59 56 55 45 34
10 1100 0.01 61 52 48 47 44 32 23 65 58 54 52 50 39 28 67 62 57 55 54 43 31 68 64 60 57 56 46 35
1200 0.01 62 53 48 47 45 32 24 65 59 54 53 51 40 28 67 63 58 56 55 44 33 69 65 60 58 57 47 35
1300 0.01 63 54 49 48 45 33 25 66 60 55 53 52 41 29 68 63 58 56 55 45 33 69 66 61 58 58 48 36
1200 0.01 58 50 47 41 37 30 20 62 56 52 47 43 37 26 64 59 56 50 46 41 30 66 61 58 53 49 43 32
1400 0.01 60 52 48 42 38 32 22 63 57 54 48 45 39 28 65 60 57 52 48 42 31 67 63 60 54 51 45 35
12 1600 0.01 61 53 50 43 40 34 24 64 59 55 49 46 40 29 66 62 59 53 50 44 34 68 64 61 55 52 47 36
1800 0.01 61 55 51 44 41 35 25 65 60 56 50 48 41 30 67 63 60 54 51 45 35 69 65 62 56 54 48 37
2000 0.01 62 56 52 45 43 36 26 66 61 57 51 49 43 31 68 64 61 55 52 47 36 69 67 63 57 55 49 38
1500 0.02 56 51 45 43 40 36 18 60 56 50 48 45 41 24 62 59 53 51 48 45 28 64 61 55 53 50 47 30
1800 0.03 58 53 46 44 41 36 21 62 58 51 49 46 42 27 64 60 54 52 49 45 29 66 63 56 54 51 48 33
14 2100 0.04 59 54 47 45 42 37 22 63 59 52 50 47 43 28 66 62 55 53 50 46 31 67 64 58 55 52 49 34
2400 0.05 60 55 48 46 43 38 23 64 60 53 51 48 43 29 67 63 56 54 51 47 33 69 65 58 56 53 49 35
2700 0.06 62 56 49 47 44 38 24 66 61 54 52 49 44 30 68 64 57 55 52 47 34 70 66 59 57 54 50 36
2000 0.02 55 48 43 41 39 31 36 59 53 47 45 44 38 21 61 56 50 47 47 41 24 63 58 52 49 49 44 27
2400 0.02 57 51 45 43 41 33 18 61 56 49 47 46 39 24 64 59 52 49 49 43 28 65 61 54 51 51 46 30
16 2800 0.03 59 53 46 44 42 34 21 63 58 51 48 47 41 27 66 61 54 50 50 45 30 67 63 55 52 52 48 33
3200 0.04 61 55 48 46 44 36 23 65 60 52 50 49 42 29 67 62 55 52 52 46 31 69 64 57 53 54 49 34
PERFORMANCE DATA
3600 0.05 62 56 49 47 45 37 24 66 61 54 51 50 44 30 69 64 56 53 53 48 34 71 66 58 55 55 50 36
3900 0.03 70 65 63 59 57 54 38 72 68 66 62 61 58 41 74 69 67 63 63 61 42 75 70 68 64 65 63 43
4600 0.04 73 68 66 62 59 55 41 75 71 68 64 63 60 43 77 72 70 66 65 63 46 78 73 71 67 67 64 47
40 5300 0.06 75 71 68 64 61 56 43 78 73 71 66 65 61 47 79 74 72 68 67 64 48 80 75 73 69 68 66 49
6000 0.07 77 73 71 66 63 57 47 80 75 73 68 66 62 49 81 76 74 70 68 65 50 82 77 75 71 70 67 51
6700 0.09 79 75 72 67 64 58 48 82 77 75 70 68 63 51 83 78 76 71 70 66 52 84 79 77 72 71 68 53
• Radiated sound is the noise transmitted • All performance based on tests conducted in
through the unit casing. accordance with ASHRAE 130-2008 and AHRI 880-2008.
• Min ∆Ps is the static pressure drop from the unit inlet • All NC levels determined using AHRI 885-2008
to the unit outlet with primary damper full open. Appendix E. See Terminal Unit Engineering Guidelines.
• Sound power levels are in dB, ref 10-12 watts. • Dash (-) in space denotes NC value less than NC10.
• Sound performance based on units lined with • Only highlighted data points are AHRI certified. See
standard dual density fiberglass lining. page M24 for AHRI Certified Performance Listings.
M13
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
M
650 0.02 67 61 56 53 48 41 19 70 67 60 56 53 47 25 71 70 62 57 55 51 29 72 73 64 58 57 54 33
8 700 0.02 67 62 56 54 49 41 20 70 68 60 56 53 48 27 72 71 63 58 56 52 30 73 74 64 59 58 55 34
750 0.02 68 63 57 54 49 42 20 70 69 61 57 54 48 27 72 72 63 58 56 52 30 73 75 65 60 58 55 34
800 0.03 68 64 57 55 50 42 21 71 70 62 58 54 49 28 72 73 64 59 57 53 31 74 75 66 60 59 56 34
800 0.04 67 59 56 53 49 43 17 70 64 60 57 54 49 21 71 67 62 59 57 53 24 72 69 64 60 59 56 27
850 0.04 68 60 56 53 49 43 18 70 65 60 57 54 50 22 72 68 62 59 57 54 25 73 70 64 61 59 56 28
9 900 0.05 68 61 57 54 50 43 18 71 66 61 57 55 50 23 73 68 63 59 57 54 25 74 70 65 61 59 57 28
950 0.06 69 61 57 54 50 44 19 72 66 61 58 55 50 23 73 69 63 60 58 54 27 74 71 65 61 60 57 29
1000 0.06 69 62 58 55 50 44 19 72 67 61 58 55 50 24 74 70 64 60 58 54 28 75 72 65 62 60 57 30
900 0.01 69 60 57 55 50 44 19 71 65 61 59 55 50 22 72 68 64 61 58 54 25 73 71 66 63 61 57 29
1000 0.01 70 61 58 56 50 44 20 72 66 62 60 56 51 23 73 69 65 62 59 55 27 74 72 67 64 61 57 30
10 1100 0.01 70 61 58 57 51 45 20 73 67 63 61 56 51 24 74 70 65 63 60 55 28 75 72 67 65 62 58 30
1200 0.01 71 62 59 57 52 45 22 73 68 63 61 57 52 25 75 71 66 64 60 56 29 76 73 68 66 63 59 31
1300 0.01 72 63 60 58 52 46 23 74 68 64 62 58 53 25 75 72 67 65 61 56 30 76 74 68 66 63 59 33
1200 0.01 68 62 59 55 53 46 18 71 67 63 59 57 52 24 73 70 65 62 60 56 28 74 72 67 64 62 59 30
1400 0.01 69 63 61 56 54 47 20 72 69 65 61 59 53 27 74 72 67 63 61 57 30 75 74 69 65 63 60 33
12 1600 0.01 70 64 62 57 55 48 21 73 70 66 62 59 55 28 75 73 68 64 62 58 31 76 75 70 66 64 61 34
1800 0.01 71 66 63 58 55 49 23 74 71 67 63 60 56 29 75 74 70 65 63 59 33 76 76 71 67 65 62 35
2000 0.01 71 67 64 59 56 50 24 74 72 68 64 61 56 30 76 75 71 66 64 60 34 77 77 72 68 66 63 36
1500 0.02 65 56 56 53 50 44 14 68 62 61 59 57 53 18 70 66 63 62 62 59 23 72 68 65 65 65 62 25
1800 0.03 66 58 58 53 50 44 15 69 64 62 59 58 53 21 71 67 65 63 62 59 24 73 70 67 65 65 63 28
14 2100 0.04 67 59 59 54 51 44 17 70 65 64 60 58 54 22 72 68 66 63 63 59 25 74 71 68 66 66 63 29
2400 0.05 68 60 60 54 51 44 18 71 66 65 60 59 54 23 73 69 68 64 63 59 27 74 72 69 66 66 63 30
2700 0.06 68 61 61 54 51 45 18 72 67 66 61 59 54 24 74 70 69 64 63 60 28 75 73 70 67 66 63 31
2000 0.02 65 58 57 54 52 45 14 68 62 60 58 56 51 18 70 65 62 61 59 54 22 71 67 63 63 61 57 24
2400 0.02 67 61 59 55 53 46 17 70 65 63 60 58 52 22 72 67 64 62 61 56 24 73 69 66 64 62 58 27
16 2800 0.03 68 63 61 57 55 48 20 72 67 65 61 59 54 24 74 69 66 64 62 57 27 75 71 68 66 64 60 29
3200 0.04 70 64 63 58 56 49 21 73 68 66 62 60 55 25 75 71 68 65 63 59 29 76 72 70 67 65 61 30
PERFORMANCE DATA
3600 0.05 71 66 65 59 57 50 23 74 70 68 63 61 56 28 76 72 70 66 64 60 30 78 74 71 68 66 62 33
3900 0.03 74 69 66 62 61 56 27 79 74 71 67 67 62 33 82 77 74 69 70 66 36 84 79 76 71 72 68 34
4600 0.04 75 70 67 63 63 58 28 80 76 73 68 68 64 35 83 79 76 71 71 67 38 86 81 78 73 74 70 41
40 5300 0.06 77 72 69 65 64 60 30 82 77 74 69 70 65 36 85 80 77 72 73 69 40 87 82 79 74 75 71 42
6000 0.07 78 73 70 66 65 61 31 83 78 75 71 71 67 37 86 81 78 73 74 70 41 88 83 80 75 76 73 43
6700 0.09 79 74 71 67 67 62 33 84 79 76 72 72 68 38 87 82 79 74 75 71 42 89 84 81 76 77 74 45
• Discharge sound is the noise emitted from the • All performance based on tests conducted in
unit discharge into the downstream ductwork. accordance with ASHRAE 130-2008 and AHRI 880-2008.
• Min ∆Ps is the static pressure drop from the unit inlet • All NC levels determined using AHRI 885-2008
to the unit outlet with primary damper full open. Appendix E. See Terminal Unit Engineering Guidelines.
• Sound power levels are in dB, ref 10-12 watts. • Dash (-) in space denotes NC value less than NC10.
• Sound performance based on units lined with • Only highlighted data points are AHRI certified. See
standard dual density fiberglass lining. page M24 for AHRI Certified Performance Listings.
M14
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
PERFORMANCE DATA Single/Dual Duct Terminals
PESV, AESV, DESV / HOT WATER COIL CAPACITY, MBH / 1- AND 2-ROW
Circuit 5.0 8.59 4.5 6.5 7.8 8.8 9.9 11.0 11.9 12.8 13.6
Airside ∆ Ps 0.01 0.01 0.02 0.03 0.05 0.07 0.09 0.12 0.14
1.0 0.24 5.3 8.6 11.0 12.9 14.4 15.6 16.7 17.6 18.4
Two-Row 3.0 1.66 5.5 9.4 12.5 15.0 17.1 19.0 20.7 22.2 23.5
Multi- 5.0 4.06 5.6 9.6 12.8 15.5 17.9 19.9 21.8 23.5 25.0
Circuit 7.0 7.39 5.6 9.7 13.0 15.8 18.2 20.4 22.3 24.1 25.7
Airside ∆Ps 0.01 0.02 0.04 0.07 0.10 0.13 0.18 0.22 0.27
Rows/ Head Airflow, cfm
Circuits gpm Loss 100 200 300 400 500 600 700 800 900
1.0 0.69 6.9 9.2 10.7 12.2 13.4 14.5 15.3 16.1 16.8
One-Row 2.0 2.34 7.2 9.9 11.7 13.6 15.1 16.4 17.6 18.6 19.5
Single 3.0 4.77 7.4 10.2 12.1 14.1 15.8 17.2 18.5 19.6 20.7
Sizes 7-8
Circuit 4.0 7.96 7.4 10.3 12.3 14.4 16.1 17.7 19.0 20.2 21.3
M
Airside ∆Ps 0.01 0.02 0.04 0.07 0.10 0.14 0.19 0.24 0.30
1.0 0.33 9.4 14.3 17.6 20.1 21.9 23.4 24.7 25.7 26.6
Two-Row 3.0 2.32 10.1 16.5 21.2 25.0 28.1 30.8 33.1 35.1 37.0
Multi- 5.0 5.66 10.3 17.0 22.2 26.3 29.9 32.9 35.6 38.0 40.2
Circuit 7.0 10.28 10.3 17.2 22.6 27.0 30.7 34.0 36.9 39.5 41.8
Airside ∆Ps 0.01 0.04 0.08 0.13 0.20 0.27 0.36 0.46 0.56
Rows/ Head Airflow, cfm
Circuits gpm Loss 200 300 400 500 600 700 800 900 1000
2.0 0.68 11.7 13.8 15.3 17.0 18.5 19.8 21.0 22.0 23.0
One-Row 3.0 1.40 12.1 14.4 16.0 18.0 19.7 21.2 22.5 23.7 24.8
Multi- 5.0 3.41 12.5 15.0 16.7 18.9 20.8 22.4 23.9 25.3 26.6
Sizes 9-10
Circuit 6.0 4.72 12.6 15.1 16.9 19.1 21.1 22.8 24.3 25.8 27.1
Airside ∆Ps 0.01 0.02 0.04 0.05 0.07 0.10 0.12 0.15 0.18
2.0 0.65 17.4 22.4 26.3 29.5 32.1 34.4 36.3 38.1 39.6
Two-Row 4.0 2.19 18.5 24.3 29.0 33.0 36.5 39.6 42.3 44.7 46.9
Multi- 6.0 4.43 18.8 25.0 30.1 34.5 38.3 41.7 44.8 47.6 50.1
Circuit 8.0 7.35 19.0 25.4 30.7 35.3 39.3 42.9 46.2 49.2 51.9
Airside ∆Ps 0.02 0.04 0.07 0.10 0.14 0.18 0.23 0.29 0.35
Rows/ Head Airflow, cfm
Circuits gpm Loss 300 500 700 900 1100 1300 1500 1700 1900
2.0 0.88 14.7 17.3 19.6 21.4 22.9 24.1 25.2 26.0 26.8
One-Row 3.0 1.81 16.4 19.9 23.0 25.7 28.0 29.9 31.5 32.9 34.2
PERFORMANCE DATA
Multi- 5.0 4.40 17.5 21.6 25.4 28.7 31.6 34.0 36.2 38.1 39.9
Size 12
Circuit 6.0 6.08 17.9 22.3 26.3 29.9 33.0 35.8 38.2 40.3 42.3
Airside ∆Ps 0.01 0.03 0.06 0.09 0.12 0.17 0.21 0.27 0.33
2.0 0.84 21.7 27.5 31.1 33.7 35.6 37.1 38.3 39.3 40.2
Two-Row 4.0 2.79 26.0 35.7 42.8 48.5 53.0 56.9 60.2 63.1 65.6
Multi- 6.0 5.63 27.1 37.9 46.3 53.0 58.7 63.6 67.8 71.6 75.0
Circuit 8.0 9.33 27.6 39.0 47.9 55.3 61.6 67.0 71.8 76.1 79.9
Airside ∆Ps 0.02 0.06 0.11 0.16 0.23 0.32 0.41 0.51 0.62
M15
For performance notes, see the next page.
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
Circuit 6.0 3.17 24.6 31.1 36.7 41.8 46.1 49.8 53.1 56.0 58.6
Airside ∆Ps 0.01 0.03 0.05 0.08 0.12 0.17 0.21 0.27 0.33
2.0 0.56 32.5 43.9 51.4 56.8 60.9 64.2 66.8 69.1 71.0
Two-Row 4.0 1.94 35.6 50.5 61.3 69.7 76.4 82.0 86.8 90.9 94.5
Multi- 6.0 3.89 36.8 53.2 65.5 75.3 83.4 90.3 96.3 101.5 106.1
Circuit 8.0 6.40 37.4 54.6 67.8 78.5 87.4 95.1 101.8 107.8 113.1
Airside ∆Ps 0.02 0.05 0.10 0.16 0.23 0.31 0.41 0.51 0.63
Rows/ Head Airflow, cfm
Circuits gpm Loss 600 1000 1400 1800 2200 2600 3000 3400 3800
3.0 0.98 30.1 36.2 42.1 46.8 50.6 53.8 56.5 58.9 61.0
One-Row 5.0 2.44 31.9 38.9 46.0 51.7 56.4 60.4 63.9 67.1 69.8
Multi- 7.0 4.38 32.7 40.3 47.9 54.1 59.4 63.9 67.9 71.4 74.6
Size 16
Circuit 9.0 6.83 33.2 41.1 49.1 55.6 61.2 66.0 70.3 74.1 77.5
M
Airside ∆Ps 0.02 0.04 0.07 0.11 0.16 0.21 0.27 0.34 0.41
3.0 0.50 45.4 59.2 68.5 75.3 80.7 85.0 88.5 91.5 94.1
Two-Row 5.0 1.26 49.1 66.1 78.4 87.9 95.5 101.9 107.2 111.9 115.9
Multi- 7.0 2.25 50.8 69.6 83.6 94.6 103.7 111.4 118.0 123.7 128.8
Circuit 9.0 3.46 51.8 71.7 86.8 98.9 108.9 117.5 125.0 131.5 137.3
Airside ∆Ps 0.03 0.07 0.13 0.21 0.30 0.40 0.51 0.64 0.78
Rows/ Head Airflow, cfm
Circuits gpm Loss 600 1200 1800 2400 3000 3600 4200 4800 5400
3.0 1.15 38.0 49.5 57.4 64.5 70.1 74.7 78.5 81.8 84.7
One-Row 5.0 2.90 40.3 53.8 63.4 72.4 79.8 85.9 91.1 95.7 99.7
Multi- 7.0 5.20 41.3 55.9 66.5 76.5 84.8 91.8 97.8 103.2 107.9
Size 24 x 16
Circuit 9.0 8.08 41.9 57.1 68.3 79.0 87.8 95.4 102.0 107.9 113.1
Airside ∆Ps 0.01 0.02 0.05 0.08 0.12 0.17 0.22 0.27 0.34
3.0 0.56 52.2 76.1 90.4 100.1 107.2 112.7 117.0 120.6 123.6
Two-Row 5.0 1.41 55.9 85.8 105.6 120.0 131.2 140.1 147.5 153.7 159.0
Multi- 7.0 2.51 57.6 90.6 113.5 130.8 144.6 155.9 165.4 173.5 180.6
Circuit 9.0 3.86 58.6 93.5 118.4 137.6 153.2 166.1 177.2 186.7 195.1
Airside ∆Ps 0.01 0.04 0.09 0.15 0.23 0.31 0.41 0.52 0.64
• All coil performance in accordance with AHRI 410-2001. • Water temperature drop = 2.04 x MBH/gpm.
• Heating capacities are in MBH. • Connection size is ½-in OD male solder for 1-row coil
• Data based on 180°F entering water sizes 04-08. All other coils have ⅞-in OD male solder.
PERFORMANCE DATA
and 55°F entering air. • Coils are not intended for steam applications and are
• For temperature differentials other than 125°, labeled for a maximum water temperature of 200°F.
multiply MBH by correction factors below. • Coils are tested for leakage at test pressure of 500 psi.
• Head loss is in feet of water. • Water volumes less than those shown may result
• Always supply water to lowest connection in laminar flow and reduced heating capacity.
pipe to prevent air entrapment. If possible reduce the number of coil rows to
• Air temperature rise = 927 x MBH/cfm. increase water velocity into turbulent range.
Note: Airside DPs reflects the air pressure drop of the hot water coil.
M16
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
PERFORMANCE DATA Single/Dual Duct Terminals
PESV, AESV, DESV / HOT WATER COIL CAPACITY, MBH / 3- AND 4-ROW
Circuit 6.0 8.88 6.3 11.4 15.8 19.6 22.9 25.9 28.7 31.2 33.5
Airside ∆Ps 0.01 0.03 0.06 0.10 0.14 0.20 0.26 0.33 0.40
Four- 3.0 1.59 6.5 12.1 16.9 21.1 24.7 27.9 30.7 33.3 35.6
Row 4.0 2.61 6.5 12.2 17.2 21.5 25.3 28.7 31.8 34.6 37.2
Multi- 6.0 5.28 6.5 12.3 17.4 21.9 26.0 29.6 33.0 36.0 38.8
Circuit 8.0 8.77 6.5 12.4 17.5 22.2 26.3 30.1 33.6 36.8 39.8
Airside ∆Ps 0.01 0.04 0.08 0.13 0.19 0.26 0.34 0.43 0.53
Rows/ Head Airflow, cfm
Circuits gpm Loss 100 200 300 400 500 600 700 800 900
Three- 2.0 0.79 11.5 19.2 24.8 29.2 32.7 35.6 38.1 40.2 42.0
Row 4.0 2.63 11.8 20.3 27.0 32.5 37.0 41.0 44.4 47.4 50.1
Multi- 6.0 5.31 11.9 20.8 27.9 33.7 38.8 43.2 47.0 50.5 53.6
Sizes 7-8
Circuit 8.0 8.80 11.9 21.0 28.3 34.4 39.7 44.4 48.5 52.2 55.6
M
Airside ∆Ps 0.02 0.06 0.12 0.20 0.29 0.40 0.53 0.67 0.83
Four- 4.0 2.04 12.6 22.6 30.6 37.2 42.7 47.5 51.7 55.3 58.6
Row 6.0 4.12 12.7 23.0 31.5 38.7 44.9 50.3 55.0 59.3 63.2
Multi- 8.0 6.79 12.7 23.2 32.0 39.5 46.0 51.8 56.9 61.6 65.8
Circuit 10.0 10.04 12.7 23.4 32.3 40.0 46.8 52.8 58.1 63.0 67.5
Airside ∆Ps 0.02 0.08 0.16 0.26 0.39 0.53 0.70 0.89 1.10
Rows/ Head Airflow, cfm
Circuits gpm Loss 200 300 400 500 600 700 800 900 1000
Three- 3.0 1.18 21.5 28.8 34.7 39.7 43.9 47.5 50.8 53.6 56.2
Row 5.0 2.85 22.1 30.1 36.8 42.5 47.6 52.0 56.0 59.6 62.9
Multi- 7.0 5.11 22.4 30.7 37.8 43.9 49.4 54.3 58.7 62.7 66.4
Sizes 9-10
Circuit 9.0 7.92 22.6 31.1 38.3 44.7 50.4 55.6 60.3 64.5 68.5
Airside ∆Ps 0.03 0.06 0.10 0.15 0.21 0.27 0.34 0.42 0.51
Four- 4.0 1.72 23.9 33.0 40.7 47.3 53.0 58.0 62.5 66.5 70.1
Row 5.0 2.53 24.1 33.5 41.6 48.6 54.7 60.2 65.1 69.5 73.5
Multi- 8.0 5.71 24.4 34.3 43.0 50.6 57.5 63.7 69.4 74.5 79.3
Circuit 10.0 8.41 24.6 34.6 43.5 51.4 58.5 65.0 70.9 76.4 81.5
Airside ∆Ps 0.04 0.08 0.13 0.20 0.27 0.36 0.46 0.56 0.68
Rows/ Head Airflow, cfm
Circuits gpm Loss 300 500 700 900 1100 1300 1500 1700 1900
Three- 3.0 1.50 29.7 40.6 48.3 53.9 58.4 61.9 64.8 67.3 69.4
Row 4.0 2.46 31.9 45.6 56.2 64.6 71.6 77.4 82.5 86.8 90.7
PERFORMANCE DATA
Multi- 6.0 4.94 32.6 47.5 59.3 69.0 77.2 84.3 90.5 95.9 100.8
Size 12
Circuit 8.0 8.14 33.0 48.5 61.0 71.4 80.4 88.2 95.0 101.2 106.7
Airside ∆Ps 0.03 0.09 0.16 0.24 0.35 0.47 0.60 0.75 0.91
Four- 4.5 2.67 35.2 52.0 65.3 76.0 84.9 92.4 98.8 104.4 109.4
Row 5.0 3.20 35.4 52.6 66.2 77.4 86.7 94.7 101.5 107.5 112.8
Multi- 7.0 5.71 36.1 54.5 69.7 82.5 93.5 103.2 111.7 119.3 126.1
Circuit 9.0 8.81 36.3 55.1 70.9 84.3 96.0 106.3 115.5 123.7 131.2
Airside ∆Ps 0.05 0.11 0.21 0.32 0.46 0.61 0.79 0.99 1.20
M17
For Performance Notes, see the next page.
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
Circuit 8.0 6.44 44.4 67.3 85.3 99.9 112.2 122.7 131.8 139.9 147.0
Airside ∆Ps 0.03 0.08 0.15 0.24 0.34 0.46 0.60 0.75 0.92
Four- 6.0 2.77 47.6 73.2 93.0 108.8 121.8 132.6 141.8 149.7 156.7
Row 6.0 2.77 47.6 73.2 93.0 108.8 121.8 132.6 141.8 149.7 156.7
Multi- 8.0 4.55 48.2 75.2 96.7 114.3 129.1 141.7 152.6 162.1 170.5
Circuit 10.0 6.67 48.6 76.4 99.0 117.9 133.9 147.7 159.7 170.4 180.0
Airside ∆Ps 0.04 0.10 0.20 0.31 0.45 0.61 0.79 1.00 1.22
Rows/ Head Airflow, cfm
Circuits gpm Loss 600 1000 1400 1800 2200 2600 3000 3400 3800
Three- 6.0 1.54 60.4 84.3 101.8 115.5 126.4 135.5 143.1 149.7 155.5
Row 8.0 2.54 61.9 87.8 107.4 123.0 135.9 146.7 155.9 164.0 171.0
Multi- 10.0 3.73 62.9 90.0 111.1 128.1 142.2 154.3 164.7 173.8 182.0
Size 16
Circuit 12.0 5.10 63.5 91.6 113.7 131.7 146.8 159.8 171.1 181.1 190.0
M
Airside ∆Ps 0.04 0.11 0.20 0.31 0.44 0.59 0.76 0.94 1.15
Four- 9.0 2.79 68.9 100.8 125.6 145.5 161.9 175.8 187.7 198.0 207.0
Row 10.0 3.34 69.3 101.9 127.5 148.3 165.6 180.2 192.8 203.9 213.6
Multi- 11.0 3.94 69.7 102.9 129.2 150.7 168.6 184.0 197.3 208.9 219.2
Circuit 12.0 4.57 69.9 103.6 130.5 152.7 171.3 187.2 201.1 213.3 224.2
Airside ∆Ps 0.06 0.14 0.26 0.40 0.58 0.78 1.00 1.25 1.52
Rows/ Head Airflow, cfm
Circuits gpm Loss 600 1200 1800 2400 3000 3600 4200 4800 5400
Three- 6.0 1.69 66.6 107.8 135.8 156.2 171.9 184.4 194.6 203.2 210.4
Row 8.0 2.78 67.9 112.5 144.3 168.4 187.5 203.0 216.0 227.0 236.6
Multi- 10.0 4.08 68.7 115.4 149.8 176.4 197.9 215.7 230.8 243.8 255.1
Size 24 x 16
Circuit 12.0 5.57 69.3 117.4 153.6 182.1 205.4 225.0 241.7 256.2 269.0
Airside ∆Ps 0.02 0.07 0.14 0.23 0.33 0.46 0.61 0.77 0.95
Four- 9.0 3.01 73.7 127.6 167.4 198.0 222.2 242.0 258.4 272.3 284.3
Row 10.0 3.61 74.0 129.0 170.3 202.4 228.2 249.4 267.2 282.4 295.5
Multi- 11.0 4.25 74.3 130.2 172.7 206.1 233.2 255.7 274.7 291.0 305.1
Circuit 12.0 4.93 74.5 131.1 174.7 209.3 237.6 261.2 281.2 298.5 313.6
Airside ∆Ps 0.03 0.09 0.18 0.30 0.44 0.61 0.80 1.02 1.25
• All coil performance in accordance with AHRI 410-2001. • Water temperature drop = 2.04 x MBH/gpm.
• Heating capacities are in MBH. • Connection size is ½-in OD male solder for 1-row coil
• Data based on 180°F entering water sizes 04-08. All other coils have ⅞-in OD male solder.
PERFORMANCE DATA
and 55°F entering air. • Coils are not intended for steam applications and are
• For temperature differentials other than 125°, labeled for a maximum water temperature of 200°F.
multiply MBH by correction factors below. • Coils are tested for leakage at test pressure of 500 psi.
• Head loss is in feet of water. • Water volumes less than those shown may result
• Always supply water to lowest connection in laminar flow and reduced heating capacity.
pipe to prevent air entrapment. If possible reduce the number of coil rows to
• Air temperature rise = 927 x MBH/cfm. increase water velocity into turbulent range.
Note: Airside DPs reflects the air pressure drop of the hot water coil.
M18
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
ELECTRIC COILS Single/Dual Duct Terminals
SELECTION AND CAPACITIES
Recommended Coil Selection Data
M
kW ≤ cfm x 0.0142 coil operation it is recommended that coil discharge
temperatures do not to exceed 100°F.
M
kW ≤ cfm x 0.0142
4 55-225 0.5 3.0 1.0 3.0 1.0 3.0 1.5 3.0 2.5 3.0
5 85-350 0.5 5.0 1.0 5.0 1.0 5.0 1.5 5.0 2.5 5.0
6 105-500 0.5 7.5 1.0 7.5 1.0 7.5 1.5 7.5 2.5 7.5
7 135-650 0.5 9.5 1.0 9.5 1.0 9.5 1.5 9.5 2.5 9.5
8 190-900 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 13.0
9 225-1050 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 16.0
10 300-1400 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 21.0
12 425-2000 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 25.0
14 575-3000 1.0 9.5 1.0 11.0 1.5 13.0 1.5 10.5 3.0 25.0
16 750-4000 1.0 9.5 1.0 11.0 1.5 13.0 1.5 10.5 3.0 25.0
ELECTRIC COILS
24x16 1800-8000 1.0 9.5 1.0 11.0 1.5 13.0 1.5 10.5 4.0 25.0
Note: The Titus 480V, 3-phase electric heat configuration is 4-wire wye. Contact your
Titus representative for other configuration options.
Useful formulas:
cfm x ∆T kW x 3160 kW x 3160
kW= or ∆T= or cfm =
3160 cfm ∆T
Where ∆T = air temperature rise.
M20
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
SUGGESTED SPECIFICATIONS Single/Dual Duct Terminals
ESV BASIC UNIT ELECTRIC REHEAT COILS
See Section O for control specifications. (Available on pressure independent terminals only)
1. Furnish and install Titus Model (P)(A)(D) ESV single 1. Electric coils shall be supplied and installed on the
duct, variable air volume terminals of the sizes and terminal by the terminal manufacturer. Coils shall be
capacities shown in the plans. ETL listed. Coils shall be housed in an attenuator section
2. Terminals shall be certified under the AHRI Standard integral with the terminal with element grid recessed
880 Certification Program and carry the AHRI Seal. from unit discharge a minimum of 5 inches to prevent
Noncertified terminals may be submitted after testing damage to elements during shipping and installation.
at an independent testing laboratory under conditions Elements shall be 80/20 nickel chrome, supported
selected by the engineering consultant in full compliance by ceramic isolators a maximum of 3.5 inches apart,
with AHRI Standard 880. These tests must be witnessed staggered for maximum thermal transfer and element
by the engineering consultant with all costs to be borne life and balanced to ensure equal output per step.
by the terminal manufacturer. Testing does not ensure The integral control panel shall be housed in a NEMA
acceptance. 1 enclosure with hinged access door for access to all
3. The terminal casing shall be minimum 22-gauge controls and safety devices.
galvanized steel, internally lined with ½-inch dual 2. Electric coils shall contain a primary automatic reset
density insulation which complies with UL 181 and NFPA thermal cutout, a secondary manual reset thermal
90A. All exposed insulation edges shall be coated with cutout, differential pressure airflow switch for proof
NFPA 90A approved sealant to prevent entrainment of flow, and line terminal block. Unit shall include an
of fibers in the airstream. The discharge connection optional integral door interlock type disconnect switch
shall be slip and drive construction for attachment to that will not allow the access door to be opened while
metal ductwork. The casing shall be constructed to hold power is on. Non-interlocking type disconnects are not
M
leakage to the maximum values shown in the Casing acceptable. All individual components shall be UL listed
Leakage table. or recognized.
4. The damper shall be heavy gauge steel with shaft 3. (Optional) Electric coils shall include line fusing, mercury
rotating in Delrin® self-lubricating bearings. Nylon contactors mounted and wired within the control
bearings are not acceptable. Shaft shall be clearly enclosure.
marked on the end to indicate damper position. Stickers
or other removable markings are not acceptable. The OPTIONAL LYNERGY ELECTRIC HEAT
damper shall incorporate a mechanical stop to prevent 1. Proportional electric coils shall be supplied and installed
overstroking and a synthetic seal to limit close-off on the terminal by the terminal manufacturer. Coils shall
leakage to the maximum values shown in the Damper be ETL listed. Coils shall be housed in an attenuator
Leakage table. section integral with the terminal with element grid
5. Actuators shall be capable of supplying at least 35-inch recessed from unit discharge a minimum of 5 inches
lbs. of torque to the damper shaft and shall be mounted to prevent damage to elements during shipping and
externally for service access. Terminals with internal installation. Elements shall be 80/20 nickel chrome,
actuator mounting or linkage connection must include supported by ceramic isolators a maximum of 3½
gasketed access panel, removable without disturbing inches apart, staggered for maximum thermal transfer
ductwork. Casing with access panel shall be constructed and element life, and balanced to ensure equal output
to hold leakage to the maximum values shown in the per step. The integral control panel shall be housed in a
Casing Leakage table. NEMA 1 enclosure with hinged access door for access to
6. At an inlet velocity of 2000 fpm, the minumum static all controls and safety devices.
pressure required to operate any terminal size shall not 2. Electric coils shall contain a primary automatic reset
exceed 0.13-inch wg for the basic terminal. thermal cutout, a secondary replaceable heat limiter per
7. Sound ratings for the terminal shall not exceed ____ element, differential pressure airflow switch for proof
NC at ____ static pressure. Sound performance shall be of flow, and line terminal block. Coil shall include an
AHRI certified. integral door interlock type disconnect switch, which
will not allow the access door to be opened while
power is on. Non-interlocking type disconnects are not
ACCESSORIES
SPECIFICATIONS
M22
Single/Dual Duct Terminals
ULTRALOC LINER
(Substitute the following paragraph 3 for paragraph 3 in the
ESV Basic Unit Specification.)
0 Base Unit
Model 1 with Integral Casing
M
Single Duct Attenuator Configuration
Variable 3 with Electric Coil 0R Right Hand
Volume Attenuator Section 0L Left Hand
X ESV X X X XX XXX
P Pneumatic 1 No Inlet Sensor 0 Standard ½” Inlet
E Electric 3 AeroCrossTM 1 1” Size
A Analog Electric Sensor 2 Steri-LocTM (specify)
D Digital Electric 4 UltraLoc
6 No Liner
Example: AESV 3120R 16 9 Fibre-Free
J EcoShield ½”
K EcoShield 1”
L EcoShield Foil ½”
M EcoShield Foil 1”
Analog electronically controlled single duct Lining Type
variable volume terminal, with multi-point sensor,
integral attenuator, Steri-Loc™ lining, right hand
controls, 16” inlet size.
SPECIFICATIONS
M23
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
M
Terminal Units’. These tests are conducted to verify that a
manufacturer’s published certified ratings are within the test
tolerances outlined in AHRI Standard 880 ‘Performance Rat-
ing of Air Terminals’. Any failure to demonstrate the certified
performance is punished by additional testing requirements,
mandatory performance re-rating, monetary penalties and
possible expulsion from the Certified Directory.
Product samples provided for certification testing are
standard production units with standard ½ in dual density
fiberglass lining (unless otherwise specified) and no optional
appurtenances such as add-on attenuators or heating/cool-
ing coils. The certified ratings are measured at the standard
operating points under the following test conditions:
M24
Single/Dual Duct Terminals
All Titus dual duct terminals are available with Fibre-Free and other lining options.
The Titus MDV/MDC Dual Duct Terminals have been 20°F inlet temperature differential. Additional ductwork is
specially designed for those applications where comfort not required downstream to achieve proper mixing, allowing
levels are critical, as in hospitals, research facilities, and for immediate take-off to diffusers. This is also beneficial for
other institutional applications. installations with space limitations.
DESIGN FEATURES
Like the EDV/EDC, the MDV/MDC terminals use separate The tightly sealed casing typically allows less than 1 percent
pressure independent velocity control loops for each inlet, leakage of conditioned air to the space at 1.5 inches wg.
rather than a single velocity controller for discharge volume differential static pressure, making this one of the most
control only. This provides superior temperature control energy efficient dual duct terminals. The dampers are the
during blending, as each inlet can compensate for duct improved Titus low leakage design.
pressure changes without affecting the other.
All Titus dual duct terminals are also available with
The unique internal mixing baffle design provides EcoShield, Fibre-Free and Steri-Loc lining options. Specify
for exceptional mixing characteristics. Less than 1°F the MDV/MDC and you will be providing the best performing
temperature variation is provided at the discharge with a dual duct terminal available.
M25
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
cfm Increase
As this is a non-blending application, a mixer/attenuator section is not required.
For detailed information on specific control types, refer to the following pages in
Section S:
Room Temperature Increase
cfm Increase
mixer/attenuator section is required.
M
Room Temperature Increase
flow rate higher than the minimum mix is employed. Maximum flow rates may be
close enough that equal inlet sizes may be used. A mixer/attenuator section
is required.
cfm Increase
minimum mix flow rates are the same as maximums. The result is a constant
airflow over the entire cooling and heating range. A mixer/attenuator section is
required.
cfm Increase
= Sensor Location
M26
Single/Dual Duct Terminals
EDV
• Standard 22 gauge casing with slip
FOR NON-BLENDING APPLICATIONS and drive discharge connection.
ONLY
• Controls supplied by Titus are
• Standard AeroCrossTM multi-point
factory calibrated for quicker
center averaging velocity sensors
start-up.
in each inlet for accurate flow
control.
PEDV - Basic Unit with Controls
4½” W 4½” M L
Pneumatic
Actuator
M
H D Discharge
F
A
Control Cover
(optional)
12¼” D H
Discharge
A
Control 18” Slip & Drive
F
6½” Enclosure Cleat Connection
Inlet cfm F
A D G H L M W
Size Range PEDV DEDV
4 0-225 12⅛ 3⅞ 1⅞ 2⅛ 7⅜ 8 15½ 5⅜ 24⅛
5 0-350 12⅛ 4⅞ 1⅞ 2⅛ 7⅜ 8 15½ 5⅜ 24⅛
6 0-500 12⅛ 5⅞ 1⅞ 2⅛ 7⅜ 8 15½ 3⅜ 24⅛
7 0-650 12⅛ 6⅞ ⅞ 1⅛ 7⅜ 10 15½ 3⅜ 24⅛
8 0-900 12⅛ 7⅞ ⅞ 1⅛ 7⅜ 10 15½ 3⅜ 24⅛
EDV
M
650 0.15 64 59 52 47 41 32 28 65 62 55 49 44 35 31 66 64 57 51 46 38 34
600 0.02 62 55 49 43 43 39 24 64 58 52 46 45 44 27 65 60 54 47 47 47 29
650 0.02 63 56 50 44 44 40 25 65 59 53 47 46 45 28 66 61 55 48 48 48 30
8 700 0.02 63 57 50 45 44 41 25 65 60 53 47 47 45 29 67 62 56 49 49 48 31
750 0.02 64 58 51 46 45 41 27 66 61 54 48 48 46 30 67 63 56 50 50 49 33
800 0.03 65 59 52 47 46 42 28 66 62 55 49 48 47 31 68 64 57 51 50 50 34
800 0.04 61 53 49 42 40 35 23 62 57 52 46 44 38 26 63 59 55 48 47 40 29
850 0.04 61 54 49 43 41 35 23 63 58 53 46 45 38 27 64 60 55 49 47 40 29
9 900 0.05 62 55 50 43 41 35 24 64 58 53 47 45 38 27 65 61 56 49 48 40 30
950 0.06 62 56 50 43 42 36 24 64 59 54 47 45 38 28 65 62 56 49 48 40 31
1000 0.06 63 56 50 44 42 36 25 65 60 54 47 46 39 29 66 62 57 50 48 40 31
900 0.01 63 57 53 50 48 37 27 65 60 57 53 52 41 31 67 63 59 56 54 44 34
1000 0.01 64 58 54 51 49 38 28 66 61 57 54 53 42 31 67 64 59 56 55 45 34
10 1100 0.01 65 58 54 52 50 39 28 67 62 57 55 54 43 31 68 64 60 57 56 46 35
1200 0.01 65 59 54 53 51 40 28 67 63 58 56 55 44 33 69 65 60 58 57 47 35
1300 0.01 66 60 55 53 52 41 29 68 63 58 56 55 45 33 69 66 61 58 58 48 36
1200 0.01 62 56 52 47 43 37 26 64 59 56 50 46 41 30 66 61 58 53 49 43 32
1400 0.01 63 57 54 48 45 39 28 65 60 57 52 48 42 31 67 63 60 54 51 45 35
12 1600 0.01 64 59 55 49 46 40 29 66 62 59 53 50 44 34 68 64 61 55 52 47 36
1800 0.01 65 60 56 50 48 41 30 67 63 60 54 51 45 35 69 65 62 56 54 48 37
2000 0.01 66 61 57 51 49 43 31 68 64 61 55 52 47 36 69 67 63 57 55 49 38
1500 0.02 60 56 50 48 45 41 24 62 59 53 51 48 45 28 64 61 55 53 50 47 30
1800 0.03 62 58 51 49 46 42 27 64 60 54 52 49 45 29 66 63 56 54 51 48 33
14 2100 0.04 63 59 52 50 47 43 28 66 62 55 53 50 46 31 67 64 58 55 52 49 34
2400 0.05 64 60 53 51 48 43 29 67 63 56 54 51 47 33 69 65 58 56 53 49 35
2700 0.06 66 61 54 52 49 44 30 68 64 57 55 52 47 34 70 66 59 57 54 50 36
2000 0.02 59 53 47 45 44 38 21 61 56 50 47 47 41 24 63 58 52 49 49 44 27
PERFORMANCE DATA
PERFORMANCE DATA
2400 0.02 61 56 49 47 46 39 24 64 59 52 49 49 43 28 65 61 54 51 51 46 30
16 2800 0.03 63 58 51 48 47 41 27 66 61 54 50 50 45 30 67 63 55 52 52 48 33
3200 0.04 65 60 52 50 49 42 29 67 62 55 52 52 46 31 69 64 57 53 54 49 34
3600 0.05 66 61 54 51 50 44 30 69 64 56 53 53 48 34 71 66 58 55 55 50 36
• Radiated sound is the noise transmitted • All performance based on tests conducted in
through the unit casing. accordance with ASHRAE 130-2008 and AHRI 880-2008.
• Min ∆Ps is the static pressure drop from the unit inlet • All NC levels determined using AHRI 885-2008
to the unit outlet with the cold damper full open. Appendix E. See Terminal Unit Engineering Guidelines.
• Sound power levels are in dB, ref 10-12 watts. • Dash (-) in space denotes NC value less than NC10.
• Sound performance based on units lined with • Only highlighted data points are AHRI certified. See
standard dual density fiberglass lining. page M38 for AHRI Certified Performance Listings.
M28
Single/Dual Duct Terminals
M
650 0.15 68 69 62 59 55 49 72 74 66 62 59 55
600 0.02 69 66 59 55 52 47 24 71 69 61 56 55 51 28 72 72 63 57 57 54 31
650 0.02 70 67 60 56 53 47 25 71 70 62 57 55 51 29 72 73 64 58 57 54 33
8 700 0.02 70 68 60 56 53 48 27 72 71 63 58 56 52 30 73 74 64 59 58 55 34
750 0.02 70 69 61 57 54 48 27 72 72 63 58 56 52 30 73 75 65 60 58 55 34
800 0.03 71 70 62 58 54 49 28 72 73 64 59 57 53 31 74 75 66 60 59 56 34
800 0.04 70 64 60 57 54 49 21 71 67 62 59 57 53 24 72 69 64 60 59 56 27
850 0.04 70 65 60 57 54 50 22 72 68 62 59 57 54 25 73 70 64 61 59 56 28
9 900 0.05 71 66 61 57 55 50 23 73 68 63 59 57 54 25 74 70 65 61 59 57 28
950 0.06 72 66 61 58 55 50 23 73 69 63 60 58 54 27 74 71 65 61 60 57 29
1000 0.06 72 67 61 58 55 50 24 74 70 64 60 58 54 28 75 72 65 62 60 57 30
900 0.01 71 65 61 59 55 50 22 72 68 64 61 58 54 25 73 71 66 63 61 57 29
1000 0.01 72 66 62 60 56 51 23 73 69 65 62 59 55 27 74 72 67 64 61 57 30
10 1100 0.01 73 67 63 61 56 51 24 74 70 65 63 60 55 28 75 72 67 65 62 58 30
1200 0.01 73 68 63 61 57 52 25 75 71 66 64 60 56 29 76 73 68 66 63 59 31
1300 0.01 74 68 64 62 58 53 25 75 72 67 65 61 56 30 76 74 68 66 63 59 33
1200 0.01 71 67 63 59 57 52 24 73 70 65 62 60 56 28 74 72 67 64 62 59 30
1400 0.01 72 69 65 61 59 53 27 74 72 67 63 61 57 30 75 74 69 65 63 60 33
12 1600 0.01 73 70 66 62 59 55 28 75 73 68 64 62 58 31 76 75 70 66 64 61 34
1800 0.01 74 71 67 63 60 56 29 75 74 70 65 63 59 33 76 76 71 67 65 62 35
2000 0.01 74 72 68 64 61 56 30 76 75 71 66 64 60 34 77 77 72 68 66 63 36
1500 0.02 68 62 61 59 57 53 18 70 66 63 62 62 59 23 72 68 65 65 65 62 25
1800 0.03 69 64 62 59 58 53 21 71 67 65 63 62 59 24 73 70 67 65 65 63 28
14 2100 0.04 70 65 64 60 58 54 22 72 68 66 63 63 59 25 74 71 68 66 66 63 29
2400 0.05 71 66 65 60 59 54 23 73 69 68 64 63 59 27 74 72 69 66 66 63 30
2700 0.06 72 67 66 61 59 54 24 74 70 69 64 63 60 28 75 73 70 67 66 63 31
2000 0.02 68 62 60 58 56 51 18 70 65 62 61 59 54 22 71 67 63 63 61 57 24
PERFORMANCE DATA
PERFORMANCE DATA
2400 0.02 70 65 63 60 58 52 22 72 67 64 62 61 56 24 73 69 66 64 62 58 27
16 2800 0.03 72 67 65 61 59 54 24 74 69 66 64 62 57 27 75 71 68 66 64 60 29
3200 0.04 73 68 66 62 60 55 25 75 71 68 65 63 59 29 76 72 70 67 65 61 30
3600 0.05 74 70 68 63 61 56 28 76 72 70 66 64 60 30 78 74 71 68 66 62 33
• Discharge sound is the noise emitted from the • All performance based on tests conducted in
unit discharge into the downstream ductwork. accordance with ASHRAE 130-2008 and AHRI 880-2008.
• Min ∆Ps is the static pressure drop from the unit inlet • All NC levels determined using AHRI 885-2008
to the unit outlet with the cold damper full open. Appendix E. See Terminal Unit Engineering Guidelines.
• Sound power levels are in dB, ref 10-12 watts. • Dash (-) in space denotes NC value less than NC10.
• Sound performance based on units lined with • Only highlighted data points are AHRI certified. See
standard dual density fiberglass lining. page M38 for AHRI Certified Performance Listings.
M29
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
EDV
• Standard 22-gauge casing with slip
FOR BLENDING OR NON-BLENDING and drive discharge connection.
APPLICATIONS
• Controls supplied by Titus are
• Standard AeroCrossTM multi-point
factory calibrated for quicker
center averaging velocity sensors
start-up.
in four location combinations to
match any control requirement.
M
D F
A Discharge W E
D
Slip & Drive
Cleat Connection
Controller
4½”
Pneumatic Actuator
F
D
A Discharge W E
D
Slip and Drive
Duct Connection
6½"
18"
K K
12¼"
M
650 0.74 62 56 49 44 43 38 24 65 59 52 47 46 43 28 66 61 55 48 48 46 30
600 0.40 58 52 45 39 37 35 20 60 57 49 42 40 39 25 62 60 51 44 42 42 29
650 0.47 58 53 46 39 38 36 21 61 58 49 42 41 40 27 63 61 52 44 43 43 30
8 700 0.55 59 54 46 40 38 36 22 61 59 50 43 41 40 28 63 62 53 45 43 43 31
750 0.63 59 55 47 41 39 37 23 62 60 51 44 41 41 29 64 63 53 46 43 44 33
800 0.71 60 56 47 41 39 38 24 62 60 51 44 42 42 29 64 64 54 46 44 44 34
800 0.18 62 53 45 41 42 40 24 64 56 49 44 45 45 27 66 59 52 47 48 48 29
850 0.21 63 53 45 42 42 40 25 65 57 49 45 46 45 28 66 59 52 47 48 48 29
9 900 0.23 63 54 46 42 42 40 25 66 57 50 45 46 45 29 67 60 52 47 48 48 31
950 0.26 64 54 46 42 43 40 27 66 58 50 46 46 45 29 68 61 53 48 49 49 32
1000 0.29 65 55 46 43 43 41 28 67 58 50 46 46 45 31 68 61 53 48 49 49 32
900 0.25 60 52 44 40 38 37 22 63 55 47 42 41 39 25 65 58 49 44 42 41 28
1000 0.31 60 52 45 41 39 37 22 63 56 48 43 41 40 25 66 59 50 44 43 42 29
10 1100 0.38 61 53 46 41 40 38 23 64 57 49 43 42 41 27 66 60 51 45 44 43 29
1200 0.45 61 54 47 42 40 39 23 64 58 49 44 42 42 27 66 61 51 46 44 44 30
1300 0.53 61 55 47 42 40 39 23 65 59 50 45 43 42 28 67 61 52 46 44 44 31
1200 0.25 64 56 52 50 53 52 27 68 59 55 54 57 57 32 70 62 58 57 60 61 34
1400 0.33 65 57 54 51 53 52 28 68 61 57 55 58 57 32 70 63 59 58 61 61 34
12 1600 0.44 65 58 55 52 54 52 29 68 62 58 55 58 57 32 71 64 60 58 61 61 36
1800 0.55 66 59 56 52 54 52 30 69 63 59 56 58 57 34 71 65 61 59 61 61 36
2000 0.68 66 60 57 53 54 52 31 69 64 60 56 58 58 35 72 66 62 59 62 61 37
1500 0.18 62 54 47 42 43 43 24 66 57 50 44 46 47 29 68 60 52 46 47 49 32
1800 0.25 63 56 49 43 44 44 25 67 59 52 46 47 48 31 69 61 54 47 49 50 33
14 2100 0.34 64 57 51 45 45 45 27 67 60 53 47 48 49 31 70 63 55 49 49 51 34
2400 0.45 65 58 52 46 46 46 28 68 62 55 48 49 49 32 70 64 57 50 50 52 34
2700 0.57 65 60 53 47 47 47 29 69 63 56 49 49 50 33 71 65 58 51 51 53 36
2000 0.21 65 55 50 45 47 47 28 68 59 52 47 50 51 32 70 61 53 49 51 53 34
PERFORMANCE DATA
2400 0.30 66 57 52 46 48 47 29 69 60 54 48 50 51 33 71 62 56 50 52 53 36
16 2800 0.40 66 58 54 47 48 47 29 70 61 56 50 51 51 34 72 64 58 51 53 53 37
3200 0.53 67 59 56 48 49 47 31 70 62 58 51 51 51 34 73 65 59 52 53 53 38
3600 0.67 68 60 57 49 49 47 32 71 63 59 51 52 51 36 73 66 61 53 54 53 38
• Radiated sound is the noise transmitted • All performance based on tests conducted in
through the unit casing. accordance with ASHRAE 130-2008 and AHRI 880-2008.
• Min ∆Ps is the static pressure drop from the unit inlet • All NC levels determined using AHRI 885-2008
to the unit outlet with the cold damper full open. Appendix E. See Terminal Unit Engineering Guidelines.
• Sound power levels are in dB, ref 10-12 watts. • Dash (-) in space denotes NC value less than NC10.
• Sound performance based on units lined with • Only highlighted data points are AHRI certified. See
standard dual density fiberglass lining. page M38 for AHRI Certified Performance Listings.
M31
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
M
650 0.74 65 64 58 53 55 53 22 67 67 60 55 57 56 25 68 68 62 57 59 59 27
600 0.40 61 61 55 51 53 51 18 63 64 57 53 55 54 22 65 67 59 55 57 57 25
650 0.47 62 62 55 52 54 52 20 64 65 58 54 56 55 23 65 67 60 56 58 57 25
8 700 0.55 62 63 56 53 54 52 21 64 66 59 55 57 56 24 66 68 61 56 58 58 27
750 0.63 63 63 57 53 55 53 20 65 67 60 55 57 57 24 67 69 62 57 59 59 27
800 0.71 63 64 57 54 55 54 21 65 67 60 56 58 57 24 67 70 62 58 59 60 28
800 0.18 67 61 54 52 54 52 17 70 64 57 55 57 56 21 72 67 60 57 59 58 24
850 0.21 68 61 54 52 55 52 18 70 65 58 55 57 56 22 72 67 61 57 59 59 24
9 900 0.23 68 62 55 52 55 53 18 71 65 58 55 58 57 22 73 68 61 57 59 60 25
950 0.26 69 62 55 53 55 54 19 72 66 59 56 58 57 23 74 68 61 58 60 60 25
1000 0.29 70 63 56 53 56 54 20 72 66 59 56 58 58 23 74 69 62 58 60 61 27
900 0.25 67 60 54 52 56 55 17 70 64 58 55 58 59 21 72 67 61 58 60 61 24
1000 0.31 68 61 55 53 56 56 18 71 65 59 56 59 60 22 73 68 62 58 60 62 25
10 1100 0.38 69 62 56 53 57 57 19 72 66 60 57 59 61 23 74 69 62 59 61 63 27
1200 0.45 69 63 56 54 57 58 20 73 67 60 57 60 62 24 75 70 63 59 61 64 28
1300 0.53 70 64 57 54 57 59 21 73 68 61 57 60 62 25 76 70 63 60 62 65 28
1200 0.25 67 61 55 53 56 55 17 70 65 58 56 58 58 22 73 67 61 58 60 61 24
1400 0.33 68 62 57 54 57 57 18 72 66 60 57 59 60 23 74 69 62 59 61 62 27
12 1600 0.44 70 64 58 55 58 58 21 73 67 61 58 60 61 24 75 70 64 60 62 64 28
1800 0.55 71 65 60 56 59 59 22 74 68 63 59 61 62 25 76 71 65 61 63 65 29
2000 0.68 71 66 61 57 60 60 23 75 69 64 60 62 63 27 77 72 66 62 63 66 30
1500 0.18 66 60 54 53 56 56 16 70 64 58 56 58 59 21 72 67 60 58 60 62 24
1800 0.25 68 62 56 54 57 58 18 71 66 60 57 60 61 23 74 68 62 59 61 63 25
14 2100 0.34 70 63 58 55 58 59 20 73 67 61 58 61 62 24 75 70 64 60 62 65 28
2400 0.45 71 64 59 56 59 61 22 74 68 62 59 62 64 25 77 71 65 61 63 66 29
2700 0.57 72 65 60 57 60 62 23 75 69 64 60 62 65 27 78 72 66 62 64 67 31
2000 0.21 68 60 55 53 58 58 18 71 64 58 56 60 61 22 74 67 60 58 62 64 25
PERFORMANCE DATA
2400 0.30 69 62 57 55 59 60 19 73 66 60 58 61 63 24 75 69 63 60 63 65 27
16 2800 0.40 70 64 59 56 60 61 21 74 67 62 59 62 64 25 77 70 64 61 64 67 29
3200 0.53 71 65 61 58 61 62 22 75 69 64 60 63 66 27 78 71 66 62 65 68 31
3600 0.67 72 66 62 59 61 63 23 76 70 65 61 64 67 28 79 73 67 63 65 69 32
• Discharge sound is the noise emitted from the • All performance based on tests conducted in
unit discharge into the downstream ductwork. accordance with ASHRAE 130-2008 and AHRI 880-2008.
• Min ∆Ps is the static pressure drop from the unit inlet • All NC levels determined using AHRI 885-2008
to the unit outlet with the cold damper full open. Appendix E. See Terminal Unit Engineering Guidelines.
• Sound power levels are in dB, ref 10-12 watts. • Dash (-) in space denotes NC value less than NC10.
• Sound performance based on units lined with • Only highlighted data points are AHRI certified. See
standard dual density fiberglass lining. page M38 for AHRI Certified Performance Listings.
M32
Single/Dual Duct Terminals
MDV
and drive discharge connection.
• Standard AeroCrossTM multi-point
center averaging velocity sensors • Controls supplied by Titus are
available in multiple location factory calibrated for quicker
combinations to match any start-up.
control requirement.
M
D
A Discharge W E
Controllers
4½"
Pneumatic Actuator
6½"
F
D
A Discharge W E
D
Slip and Drive
Duct Connection
6½"
18"
K K
12¼"
4 0-225 8⅞ 3⅞ 5⅞ 5⅞ 5⅜ 8¼ 34 19 1⅞ 2
5 0-350 8⅞ 4⅞ 5⅞ 5⅞ 5⅜ 8¼ 34 19 1⅞ 2
6 0-500 8⅞ 5⅞ 5⅞ 5⅞ 3⅜ 8¼ 34 19 1⅞ 2
7 0-650 10⅞ 6⅞ 7⅛ 8⅛ 6¾ 10¼ 42 23 ⅞ 1
8 0-900 10⅞ 7⅞ 7⅛ 8⅛ 3⅜ 10¼ 42 23 ⅞ 1
9 0-1050 12⅞ 8⅞ 10⅛ 11⅛ 6¾ 12¾ 50 27 - -
10 0-1400 12⅞ 9⅞ 10⅛ 11⅛ 3⅜ 12¾ 50 27 - -
12 0-2000 14⅞ 11⅞ 11⅛ 13⅛ 3⅜ 15¼ 58 31 - -
14 0-3000 16⅞ 13⅞ 12½ 16⅛ 3⅜ 18⅛ 66 35 - -
16 0-4000 18⅞ 15⅞ 15⅛ 16⅛ 3⅜ 18⅛ 72 38 - -
All dimensions are in inches.
M33
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
M
650 0.66 65 59 50 45 42 37 28 68 62 54 48 46 43 32 70 65 56 50 49 46 35
600 0.37 62 56 48 42 40 38 24 65 61 52 45 44 43 30 68 63 55 47 47 46 33
650 0.43 63 57 49 43 41 39 25 66 61 53 46 45 43 30 68 64 56 48 47 47 34
8 700 0.50 63 57 50 44 41 39 25 67 61 53 47 45 44 31 69 64 56 49 48 47 34
750 0.57 64 58 50 45 42 40 27 67 62 54 48 46 44 31 69 65 57 50 49 48 35
800 0.65 64 58 50 45 43 40 27 68 62 54 48 47 45 32 70 65 57 50 49 48 35
800 0.20 67 57 47 40 38 29 31 70 61 51 43 41 34 34 72 64 54 46 43 37 37
850 0.22 67 58 48 41 39 30 31 70 62 52 44 42 34 34 72 65 54 46 44 38 37
9 900 0.25 68 58 48 42 40 30 32 71 62 52 45 42 35 36 73 65 55 47 45 38 38
950 0.28 68 58 49 42 40 31 32 71 62 52 46 43 35 36 73 65 55 48 45 39 38
1000 0.31 68 59 49 43 41 31 32 71 63 53 46 44 36 36 73 66 56 49 46 39 38
900 0.21 63 58 51 47 47 47 27 68 63 54 50 51 51 33 71 66 57 52 54 54 36
1000 0.26 64 59 52 48 48 47 28 69 63 55 51 52 51 33 72 66 57 53 54 54 37
10 1100 0.31 65 59 53 48 49 48 28 69 64 56 51 52 52 34 73 67 58 53 55 55 38
1200 0.37 65 60 53 49 49 48 29 70 65 56 52 53 52 35 73 68 59 54 55 55 38
1300 0.44 66 61 54 49 49 48 30 70 65 57 52 53 53 35 74 68 59 54 56 55 40
1200 0.29 68 60 54 53 54 52 32 71 63 58 57 58 57 36 74 66 60 60 61 60 40
1400 0.39 69 61 55 54 55 52 33 72 65 59 58 59 58 37 75 67 61 61 62 61 41
12 1600 0.51 70 62 57 54 56 53 34 73 66 60 58 60 58 38 76 68 62 61 63 62 42
1800 0.64 70 63 58 55 57 54 34 74 67 61 59 61 59 40 77 69 63 62 64 62 43
2000 0.80 71 64 58 56 57 54 36 75 67 62 60 62 59 41 78 70 64 63 65 63 45
1500 0.16 66 58 49 41 38 31 29 70 62 52 43 40 35 34 73 65 54 45 42 37 38
1800 0.23 67 60 52 43 41 34 31 71 64 54 46 43 37 36 74 66 56 48 45 40 40
14 2100 0.31 68 61 54 45 43 36 32 72 65 56 48 46 40 37 75 68 58 50 47 42 41
2400 0.41 69 62 56 47 45 38 33 73 66 58 50 48 42 38 76 69 60 52 50 44 42
2700 0.52 70 63 57 49 47 40 34 74 67 60 51 50 44 40 77 69 62 53 51 46 43
2000 0.20 70 60 53 45 42 37 34 74 64 56 48 44 41 40 77 67 58 50 46 43 43
PERFORMANCE DATA
2400 0.28 71 61 55 47 44 40 36 75 65 58 50 47 43 41 78 68 60 52 49 46 45
16 2800 0.39 72 62 57 50 47 42 37 76 66 60 52 49 45 42 79 69 62 54 51 48 46
3200 0.50 73 63 59 51 49 44 38 77 68 62 54 51 47 43 80 70 64 56 53 50 47
3600 0.64 74 64 61 53 51 45 40 78 68 64 56 53 49 45 80 71 66 58 55 51 47
• Radiated sound is the noise transmitted • All performance based on tests conducted in
through the unit casing. accordance with ASHRAE 130-2008 and AHRI 880-2008.
• Min ∆Ps is the static pressure drop from the unit inlet • All NC levels determined using AHRI 885-2008
to the unit outlet with the cold damper full open. Appendix E. See Terminal Unit Engineering Guidelines.
• Sound power levels are in dB, ref 10-12 watts. • Dash (-) in space denotes NC value less than NC10.
• Sound performance based on units lined with • Only highlighted data points are AHRI certified. See
standard dual density fiberglass lining. page M38 for AHRI Certified Performance Listings.
M34
Single/Dual Duct Terminals
M
650 0.66 70 67 60 55 56 54 71 65 59 59 57
600 0.37 66 63 57 52 51 46 21 69 66 61 55 52 48 24 71 68 63 57 54 50 27
650 0.43 67 64 58 53 52 48 22 69 67 62 56 54 50 25 71 69 64 58 55 51 28
8 700 0.50 67 64 59 53 53 50 22 70 67 62 56 55 52 25 72 70 65 59 56 53 29
750 0.57 68 65 60 54 54 51 22 71 68 63 57 56 53 25 73 70 65 59 57 55 28
800 0.65 69 66 60 55 55 53 23 71 69 64 58 57 55 27 73 71 66 60 58 56 29
800 0.20 68 62 57 50 48 44 18 71 65 61 53 51 47 22 73 68 63 55 52 48 25
850 0.22 69 62 58 51 49 45 19 72 66 61 54 52 48 23 74 68 64 56 53 50 25
9 900 0.25 69 63 58 52 50 47 20 72 66 62 54 53 49 23 74 69 64 57 54 51 27
950 0.28 70 63 58 52 51 48 20 73 67 62 55 54 50 24 75 69 65 57 55 52 27
1000 0.31 71 63 59 53 52 49 22 73 67 62 56 54 51 24 75 70 65 58 56 53 28
900 0.21 69 63 58 54 52 46 20 73 67 62 56 54 49 24 75 69 64 58 55 50 27
1000 0.26 70 64 59 55 53 48 21 74 68 63 58 55 51 25 76 70 65 60 57 52 28
10 1100 0.31 71 65 60 56 55 50 22 75 69 64 59 57 52 27 77 71 66 61 58 54 29
1200 0.37 72 66 61 57 56 52 23 75 69 64 60 58 54 27 78 72 67 62 60 56 31
1300 0.44 73 67 62 58 58 53 24 76 70 65 60 60 56 28 79 73 68 62 61 57 32
1200 0.29 72 64 60 54 53 49 29 75 67 63 56 55 51 33 77 69 65 58 57 53 36
1400 0.39 74 66 62 56 56 52 32 76 69 65 58 58 54 34 78 71 67 60 60 56 37
12 1600 0.51 75 68 63 58 59 55 33 78 71 67 60 61 57 37 80 73 69 62 62 58 40
1800 0.64 76 69 65 60 61 57 34 79 72 68 62 63 59 38 81 75 70 64 64 61 41
2000 0.80 77 71 66 61 63 59 36 80 74 69 64 65 61 40 82 76 72 65 66 63 42
1500 0.16 71 62 58 51 51 45 28 74 66 61 53 53 47 32 76 68 63 55 54 49 34
1800 0.23 73 65 60 54 54 48 31 76 68 63 56 56 51 34 78 71 65 58 57 53 37
14 2100 0.31 75 67 62 56 57 51 33 78 70 65 59 59 54 37 80 73 67 60 60 55 40
2400 0.41 77 69 64 59 59 54 36 79 72 67 61 61 56 38 81 75 69 62 63 58 41
2700 0.52 78 71 66 60 61 56 37 81 74 69 63 63 58 41 83 76 71 64 65 60 43
2000 0.20 74 65 61 55 54 49 32 77 68 64 57 56 51 36 79 71 65 59 58 53 38
PERFORMANCE DATA
2400 0.28 76 68 63 58 58 52 34 79 71 66 60 60 55 38 81 73 68 62 61 56 41
16 2800 0.39 77 70 66 61 60 56 36 80 73 68 63 63 58 40 83 75 70 65 64 59 43
3200 0.50 79 71 67 63 63 58 38 82 75 70 65 65 60 42 84 77 72 67 66 62 45
3600 0.64 80 73 69 65 65 61 40 83 76 72 67 67 63 43 85 78 74 69 69 64 46
• Discharge sound is the noise emitted from the • All performance based on tests conducted in
unit discharge into the downstream ductwork. accordance with ASHRAE 130-2008 and AHRI 880-2008.
• Min ∆Ps is the static pressure drop from the unit inlet • All NC levels determined using AHRI 885-2008
to the unit outlet with the cold damper full open. Appendix E. See Terminal Unit Engineering Guidelines.
• Sound power levels are in dB, ref 10-12 watts. • Dash (-) in space denotes NC value less than NC10.
• Sound performance based on units lined with • Only highlighted data points are AHRI certified. See
standard dual density fiberglass lining. page M38 for AHRI Certified Performance Listings.
M35
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
M
in the airstream. The casing shall be constructed to hold AHRI certified.
leakage to the maximum values shown in the Casing
Leakage table. ACCESSORIES
STERI-LOC LINER
EDV without Mixer Casing Leakage, cfm (Substitute paragraph 3 below for paragraph 3 in the Basic
Inlet ∆Ps, in wg Unit specification).
Size 0.5 1.0 2.0 3.0
4, 5, 6 4 6 8 10 3. The terminal casing shall be minimum 22-gauge
7, 8 7 10 14 17 galvanized steel, internally lined with a non-porous,
9, 10 8 12 17 21 sealed liner which complies with UL 181 and NFPA 90A.
12 10 14 20 24 Insulation shall be 4-pound density. All cut edges must
14 13 18 25 31 be sealed from the airstream using mechanically bonded
16 14 20 28 35
metal barrier strips. Liners made of Mylar, Tedlar, Silane
EDV/EDC with Mixer and MDV/MDC or woven fiberglass cloth are not acceptable. Insulation
Casing Leakage, cfm shall be equivalent to Titus Steri-Loc or double wall
lining is acceptable. The casing shall be constructed
Inlet ∆Ps, in wg
to hold leakage to the maximum values shown in the
Size 0.5 1.0 2.0 3.0
4, 5, 6 3 5 7 8
Casing Leakage table.
7, 8 5 7 9 11
9, 10 5 7 10 13 FIBRE-FREE LINER
12 7 9 13 16 (Substitute paragraph 3 below for paragraph 3 in the Basic
14 9 13 18 23 Unit specification).
16 12 17 24 30
3. The terminal casing shall be minimum 22-gauge
4. (Delete this paragraph for EDV without mixer-attenuator) galvanized steel, internally lined with engineered
Each terminal shall include a mixer-attenuator section as polymer foam insulation which complies to UL181 and
an integral part of the terminal to minimize downstream NFPA 90A. Insulation shall be 1½ pound density, closed
SPECIFICATIONS
stratification. The terminal shall provide less than 2°F, cell foam. Exposed fiberglass is not acceptable. The
EDV/EDC (or 1°F, MDV/MDC) discharge temperature insulation shall be mechanically fastened to the unit
variation with a 20° differential in inlet temperature. casing. The casing shall be constructed to hold leakage
5. Cooling and heating inlets shall have separate damper to the maximum values shown in the Casing Leakage
assemblies for complete pressure independent control table.
of each airstream for variable or constant volume total
discharge applications. Terminals with inlet dampers ECOSHIELD
mechanically interconnected are not acceptable. The (Substitute the following paragraph 3 for paragraph 3 in the
dampers shall be heavy gauge steel with solid shaft ESV Basic Unit Specification.)
rotating in Delrin® self-lubricating bearings. Nylon
bearings are not acceptable. Shaft shall be clearly 3. The terminal casing shall be minimum 22 gauge
marked on the end to indicate damper position. Stickers galvanized steel (20 gauge for fan powered terminals),
or other removable markings are not acceptable. The internally lined with ½ in. or 1” matte or foil faced
natural fiber insulation which complies with ASTM C 739
M36 damper shall incorporate a mechanical stop to prevent
overstroking and a synthetic seal to limit close-off and NFPA 90A. The liner shall comply with ASTM G21
Single/Dual Duct Terminals
M
3B AeroCross Multi- 9 Fibre-Free (specify)
point Sensor
(hot inlet and J EcoShield ½”
total discharge
EXAMPLE: PEDV 3B100R 66 ducts) K EcoShield 1”
SPECIFICATIONS
M37
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
M
Terminal Units’. These tests are conducted to verify that a PEDV, PEDC, DEDV WITH INTEGRAL ATTENUATOR AND
manufacturer’s published certified ratings are within the test MIXING BAFFLE
tolerances outlined in AHRI Standard 880 ‘Performance Rat-
Radiated Sound Discharge Sound
ing of Air Terminals’. Any failure to demonstrate the certified Inlet Rated Min Power Power
performance is punished by additional testing requirements, Size CFM ∆Ps
mandatory performance re-rating, monetary penalties and 2 3 4 5 6 7 2 3 4 5 6 7
possible expulsion from the Certified Directory. 04 150 0.41 54 53 44 38 36 31 62 59 54 50 50 45
Product samples provided for certification testing are 05 250 0.47 56 54 47 40 39 35 62 61 56 51 53 50
standard production units with standard ½ in dual density
06 400 0.91 55 57 49 43 41 37 61 61 57 54 55 54
fiberglass lining (unless otherwise specified) and no optional
appurtenances such as add-on attenuators or heating/cool- 07 550 0.53 63 57 51 45 45 41 65 64 58 53 56 54
ing coils. The certified ratings are measured at the standard 08 700 0.55 61 59 50 43 41 40 64 66 59 55 57 56
operating points under the following test conditions:
09 900 0.23 66 57 50 45 46 45 71 65 58 55 58 57
10 1100 0.38 64 57 49 43 42 41 72 66 60 57 59 61
PEDV, PEDC, PMDV, PMDC, DEDV, DMDV
12 1600 0.44 68 62 58 55 58 57 73 67 61 58 60 61
• Rated airflow (cfm) – Based on an 14 2100 0.34 67 60 53 47 48 49 73 67 61 58 61 62
inlet velocity of 2000 fpm. 16 2800 0.40 70 61 56 50 51 51 74 67 62 59 62 64
• Rated Min ∆Ps (in wg) – Minimum static
pressure drop from the cold inlet to discharge
at rated airflow with damper full open. PEDV, DEDV WITHOUT ATTENUATOR
• Rated ∆Ps (in wg) – A static pressure drop
of 1.5 in wg from cold inlet to discharge Radiated Sound Discharge Sound
Inlet Rated Min Power Power
with the hot damper fully closed. Size CFM ∆Ps
• Rated sound power by octave band (dB, re 10-12 watts) 2 3 4 5 6 7 2 3 4 5 6 7
SPECIFICATIONS
Titus USA
605, Shiloh Road, Plano TX 75074
T. 972-212-4800
F. 972-212-4884
Email:[email protected]
www.titus-hvac.comus USA
Titus UAE