M

Single/dual duct terminal units

www.ruskintitus.com | www.titus-hvac.com | www.titus-energysolutions.com


www.ruskintitus.com | www.titus-hvac.com | www.titus-energysolutions.com

Table of Contents Single/Dual Duct Terminals


single/dual duct terminal products
Single/Dual Duct Terminal Products .............................................................................................................................................M3

single duct terminals


ESV Single Duct ............................................................................................................................................................................M4
Design Features ....................................................................................................................................................................M4
Control Strategies .................................................................................................................................................................M6
ESV - Basic Unit with Controls .............................................................................................................................................M8
Accessories ...........................................................................................................................................................................M9
Performance Data ...............................................................................................................................................................M12
Electric Coils .......................................................................................................................................................................M19
Suggested Specifications....................................................................................................................................................M21
Model Number Specification ..............................................................................................................................................M23
AHRI Certification ...............................................................................................................................................................M24

dual duct terminals


EDV/MDV Dual Duct ...................................................................................................................................................................M25
Design Features ..................................................................................................................................................................M25
Control Strategies ...............................................................................................................................................................M26
EDV - Dual Duct without Attenuator...................................................................................................................................M27

M
Performance Data ...............................................................................................................................................................M28
EDV/EDC - Dual Duct with Attenuator ................................................................................................................................M30
Performance Data ...............................................................................................................................................................M31
MDV/MDC - Dual Duct High Performance Blending ..........................................................................................................M33
Performance Data ...............................................................................................................................................................M34
Suggested Specifications....................................................................................................................................................M36
Model Number Specification ..............................................................................................................................................M37
AHRI Certification ...............................................................................................................................................................M38
SINGLE/DUAL DUCT TERMINALS

M2
www.ruskintitus.com | www.titus-hvac.com | www.titus-energysolutions.com
Single/Dual Duct Terminal Products Single/Dual Duct Terminals
SINGLE DUCT TERMINALS
pages: M4-M24

ESV
AVAILABLE CONFIGURATIONS CONTROL OPTIONS UNIT ACCESSORIES
• With integral attenuator. • Pneumatic. • Fibre Free lining.
• With water coils. • Electric. • Steri-Loc™ lining.
• With integral electric coil section. • TA1 electronic. • UltraLoc lining.
• OEM controls program. • Multi-outlet section.

M
• Factory mounting of controls by others. • Round outlet adapter.
• OEM controls (Titus Alpha BACnet). • EcoShield.
• Removable flow sensor.

DUAL DUCT TERMINALS


pages: M25-M38

SINGLE/DUAL DUCT TERMINALS


EDV
AVAILABLE CONFIGURATIONS CONTROL OPTIONS UNIT ACCESSORIES
• For non-mixing. • Pneumatic. • Fibre Free lining.
• With integral attenuator/mixing section. • OEM controls program. • Steri-Loc™ lining.
• Special high performance blending. • Factory mounting of controls by others. • EcoShield.
• OEM controls (Titus Alpha BACnet). • Removable flow sensor.

For detailed controls information, please refer to the Terminal Unit Accessories section. M3
www.ruskintitus.com | www.titus-hvac.com | www.titus-energysolutions.com

Single Duct Design Features Single/Dual Duct Terminals


LEADING THE INDUSTRY: THE TITUS ESV SINGLE DUCT VAV TERMINAL
Single duct terminals are the fundamental building blocks in cramped mechanical spaces, either in new building
for a variable air volume (VAV) system. Their primary construction or retrofit.
function is to regulate airflow to a zone, in response to
zone temperature requirements. The Titus ESV is unique Building owners will benefit from the energy efficient low
as it incorporates many design features that increase leakage design, reducing utility expenses. Control accuracy,
performance, decrease installation and service cost and especially at minimum flow rates, is easier to achieve with a
offers increased value, over and above this basic function. Titus multi-point inlet velocity sensor. Control accuracy
is critical in maintaining good air quality reducing energy
All VAV terminals are not equal! By specifying the Titus ESV, waste.
you are assured of accurate, AHRI Certified performance
ratings. All units are tested, and data shown, in accordance The ESV’s standard insulation is a dual density liner. The
with AHRI Standards. A wide selection of unit configurations, skin resists abrasion and erosion from air movement. The
accessories and control types provide considerable scope for body maximizes thermal and acoustical performance. The
problem solving and cost-effective innovation. Titus single blade damper design helps reduce noise levels
The ESV’s compact size and easy access for service saves too, for a quieter work environment.
time and expense in installation. The ESV fits easily

M
ESV Casing Leakage, cfm Damper Leakage, cfm
INLET ∆PS, IN WG INLET ∆PS, IN WG
SIZE 0.5 1.0 2.0 3.0 SIZE 1.0 2.0 4.0 6.0
4, 5, 6 2 3 4 5 4, 5, 6 3 4 6 7
7, 8 4 5 7 9 7, 8 3 4 6 7
9, 10 4 6 8 10 9, 10 3 4 6 7
12 5 7 10 12 12 3 4 6 7
14 6 9 13 16 14 3 5 7 8
16 7 10 14 17 16 4 5 7 9

MORE REASONS TO SPECIFY AND SELECT THE TITUS ESV:


Titus innovation carries through the widest array of standard reinforced surfaces that can be wiped down.
single duct terminal configurations. ETL listed electric coils,
manufactured by Titus, are installed, wired and functionally Steri–Loc adds the feature of a very high density, rigid
tested as an integral unit before shipment for quicker, insulation and special “Z-Strip” construction for an extremely
trouble-free job-site installation. Multiple outlets with rigid terminal. Sound levels are generally superior to dual
standard locking balancing dampers and integral attenuators wall construction, while offering virtually identical levels of
are also available. protection.

Titus continues to offer the most innovative and popular EcoShield is a sustainable liner comprised of recycled denim
lining alternatives for special applications including Fibre- making it environmentally friendly and contains no harmful
Free; the industry benchmark Steri-Loc; and the premium irritants or chemicals.
DESIGN FEATURES

double wall liner, UltraLoc and EcoShield which is the only


natural fiber insulation on the market. Titus - experts in DDC zone control!

Fibre-Free eliminates the requirement for foil linings and With a detailed understanding developed through years of
solid inner liners since there is no fiberglass in the airstream. selling and supporting the powerful TD1 digital controller,
Additionally, Fibre-Free minimizes mold growth since it holds and now the Titus BACnet OEM controls, Titus has industry
no moisture, is acoustically preferable to foil or solid metal leading experience in the application of Direct Digital Control
linings and maintains acceptable thermal protection. All (DDC) to terminals. This same expertise is made available
of these benefits are available at a competitive price and when your project requires quality engineering, coordination
significantly less than solid metal liners. and manufacturing for factory mounting when controls are
supplied by others.
Steri–Loc provides a smooth, nonporous skin to guard
M4 against mold and bacteria growth. Erosion is eliminated, Count on Titus - the industry leader in VAV!
as there is no glass fiber exposure to the airstream. It has
www.ruskintitus.com | www.titus-hvac.com | www.titus-energysolutions.com
Design Features (continued) Single/Dual Duct Terminals

Removable flow sensor (optional).

Unique integral fold fabrication method increases lining and


Beaded inlet for consistent roundness and low leakage
casing integrity and minimizes leakage.
construction, sized to fit standard round duct.

Standard insulation is ½-inch dual density fiberglass, to resist


erosion at surface velocities up to 5,000 fpm. Meets requirements
of NFPA 90A and UL181.

Delrin® damper bearings provide smoother damper operation.


AeroCrossTM multi-point, center averaging sensor amplifies flow
signal for best control of low flow rates. Center averaging feature
provides signal accuracy regardless of inlet duct configuration.
Damper design provides smoother airflow for reduced sound
levels and lower leakage.
DESV
Flow measurement taps included when velocity sensor is
provided, for easy balancing connections.

NEMA 1 control enclosure available for protection of electronic


controls. Double backplane construction for strength and easier
control installation, with no exposed screw tips for safe handling.
Optional Fibre-Free and reinforced sealed skin of Steri-Loc and
metal lined UltraLoc lining guard against environments favoring
bacteria and mold growth. Meets UL 181 and NFPA 225 (25/50).
M
Fibre-Free & EcoShield are ideal IAQ insulation providing
acoustical and thermal characteristics of fiberglass insulation
UL Class II transformers and disconnect switches available installed without the concern of fiberglass in the airstream.
for use with any electroniccontrol configuration.

Multiple knockouts in sizes from 7/16-inch to 11/8-inch to


accommodate almost any field connection requirement.
DESV

DESIGN FEATURES

M5
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com

SINGLE DUCT CONTROL STRATEGIES Single/Dual Duct Terminals


Variable Air Volume - VAV Cooling
Max.
As the room temperature increases over setpoint, the unit modulates the cold
airflow from the minimum (which may be zero flow) to the maximum setting.

For detailed information on specific control types, refer to the following pages in

cfm Increase
Min.
Section S:

Pneumatic: See pg. O18 Analog: See pg. O11 Digital: See pg. O5
Room Temperature Increase

VAV Cooling, Hot Water Reheat


Max.
As the room temperature increases, the unit modulates the hot water coil valve

Ho
toward the closed position. On a further increase in room temperature, the unit

tW
modulates the cold airflow from the minimum (which must be greater than zero) to

at
er
the maximum setting.

cfm Increase

Fl
ow
Min.

Pneumatic: See pg. O18 Analog: See pg. O11 Digital: See pg. O5
Room Temperature Increase

M VAV Cooling, Dual Minimum Flows with Hot Water Reheat


In the cooling mode, as the room temperature increases, the unit thermostat

Ho
Max.

tW
modulates the cold airflow from the lower minimum to the maximum setting.

at
er
Fl
In the heating mode, the unit references the alternate (higher) minimum airflow. As

ow
Alt. Min.

the room temperature decreases, the unit modulates the airflow from the maximum cfm Increase
to the higher minimum, then modulates the hot water coil valve toward the open
position. The valve operates only in the heating mode. Min.

Room Temperature Increase


Pneumatic: See pg. O18 Analog: See pg. O11 Digital: See pg. O5

VAV Cooling and VAV Heating, Local Heat Flows


In the heating mode, as the room temperature increases, the unit modulates the Max. Max.
airflow from maximum to minimum and modulates the hot water coil valve toward
the closed position.
Ho
tW
cfm Increase

A further increase in room temperature changes the operation to the cooling mode,
ate
rF

and the unit modulates the cold airflow from minimum to maximum, which is the
low

same as the heating maximum.


CONTROL STRATEGIES

Room Temperature Increase


Pneumatic: See pg. O18 Analog: See pg. O11 Digital: See pg. O5

VAV Cooling and VAV Heating, Central Heat Flows


In the heating mode, as the room temperature increases, the unit modulates the
airflow from maximum to minimum and modulates the hot water coil valve toward Max.
the closed position. Max.

A further increase in room temperature changes the operation to the cooling


cfm Increase

mode, and the unit modulates the cold airflow from minimum to maximum, which
is different from the heating maximum (usually higher). Both the heating and the
cooling maximum airflows are adjustable.
Room Temperature Increase
Pneumatic: See pg. O18 Analog: See pg. O11 Digital: See pg. O5

M6
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
Control Strategies (continued) Single/Dual Duct Terminals
Constant Volume, Hot Water Reheat
The cold airflow remains constant regardless of changes in duct pressure or room
temperature. As the room temperature increases, the unit modulates the hot water

Ho
coil valve toward the closed position.

tW
a te
cfm Increase

rF
Pneumatic: See pg. O18 Analog: See pg. O11 Digital: See pg. O5

low
Room Temperature Increase

VAV Cooling, Electric Reheat


As the room temperature increases, the unit de-energizes the electric heating coil
Step 2 Max.

one step at a time. On a further increase in room temperature, the unit modulates
the cold airflow from the minimum (which must be greater than zero) to the
Step 1

maximum setting.

cfm Increase
Min.

Pneumatic: See pg. O18 Analog: See pg. O11 Digital: See pg. O5
Room Temperature Increase

VAV Cooling, Dual Minimum Flows with Electric Reheat


In the cooling mode, as the room temperature increases, the room thermostat
modulates the cold airflow from the lower minimum to the maximum setting.
In the heating mode, as the room temperature decreases, the unit modulates the
Step 2

Alt. Min. Step 1


Max. M
airflow from the lower minimum to the higher minimum, then energizes the electric
cfm Increase
Min.
heating coil stages.

Pneumatic: See pg. O18 Analog: See pg. O11 Digital: See pg. O5
Room Temperature Increase

VAV Cooling with Morning Warmup


When provided the appropriate signal, the damper in the terminal modulates to Max.
maximum or fully open position. Heated air from the central system moves through
the duct (the flow may be pressure dependent with some control types).
cfm Increase

When the signal is removed, the unit resumes normal control of airflow. With the Min.
central system now supplying cold air, as room temperature increases, the unit
modulates the cold airflow from minimum to the maximum setting. CONTROL STRATEGIES
Pneumatic: See pg. O18 Analog: See pg. O11 Digital: See pg. O5 Room Temperature Increase

M7
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com

Basic Unit with Controls Single/Dual Duct Terminals


ESV
Available Models: • Standard dual density insulation.
PESV • Pneumatic
EESV • Electric • Standard 22-gauge casing with slip
AESV • Analog and drive discharge connection.

ESV
Electronic
DESV • Digital • Controls supplied by Titus are
Electronic factory calibrated for a quicker
start-up.
• Standard AeroCrossTM multi-point
center averaging velocity sensor
(except EESV).

PESV Pneumatic
W Actuator M L

H D

M Multi-Point
Center Averaging F 4½”
Control
Cover
(optional)
Thermostat &
20 psi Main Air
Connections for
Slip and Drive
Cleat Connection
Velocity Sensor
¼” Dia. Tubing

DESV M
L
W
AESV F G
EESV

H 12¼”
D

Control Slip & Drive


F
6½” Enclosure 18” Cleat
(Optional for cooling only) Connection

F
INLET CFM AESV
D G H L M W
SIZE RANGE PESV DESV
EESV
4 0-225 3⅞ 1⅞ 2⅛ 7⅜ 8 15½ 5⅜ 12
5 0-350 4⅞ 1⅞ 2⅛ 7⅜ 8 15½ 5⅜ 12
6 0-500 5⅞ 1⅞ 2⅛ 7⅜ 8 15½ 3⅜ 12
7 0-650 6⅞ ⅞ 1⅛ 7⅜ 10 15½ 3⅜ 12
8 0-900 7⅞ ⅞ 1⅛ 7⅜ 10 15½ 3⅜ 12
ESV

9 0-1050 8⅞ - - 5⅜ 12½ 15½ 3⅜ 14


10 0-1400 9⅞ - - 5⅜ 12½ 15½ 3⅜ 14
12 0-2000 11⅞ - - 5⅜ 15 15½ 3⅜ 16
14 0-3000 13⅞ - - 3⅜ 17½ 15½ 3⅜ 20
16 0-4000 15⅞ - - 3⅜ 18 15½ 3⅜ 24
24X16 0-8000 23⅞ - 15⅞ ⅞ 1⅛ 5⅜ 18 15 3⅜ 38

M8 All dimensions are in inches.


www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
ACCESSORIES Single/Dual Duct Terminals
INTEGRAL SOUND ATTENUATOR
Titus’ unique integral design minimizes 39½ 6½
W
casing leakage and disturbance to
airflow with no casing or insulation 18
seams.

12¼ H
INTEGRAL ELECTRIC COIL
With a rigid one piece assembly,
Titus locates the heating elements for
optimal heat transfer and insets them
for protection during shipment
and installation.

39½ 6¼ W
STANDARD FEATURES:
• Primary automatic reset thermal
cutout (one per coil).
12 H
• Secondary manual reset
thermal cutout.
• Airflow switch
(differential pressure). 365/8
• Derated nickel chrome

M
heating elements.
• Magnetic or safety contactors
(as required).
L W
• Line terminal block.
• Control terminal block.
• ETL listed.
• 80/20 nickel chrome element wire. H

OPTIONAL FEATURES:
• Class ll, 24 volt control transformer. Side View End View
• Mercury contactors.
• Door interlock disconnect switch.
• Main supply fuses.
• Dust tight construction. M 39½ L
• Removable flow sensor. W

HOT WATER REHEAT COILS H


Details on water coil features are
shown on performance pages M18-22.
Side View End View

INTEGRAL SOUND ATTENUATOR


INLET WATER COIL
WITH OPTIONAL HOT WATER H M W
SIZE L (1-2 ROW) L (3-4 ROW)
REHEAT COIL 4, 5 8 5⅜ 12 5 7¼
ACCESSORIES

6 8 3⅜ 12 5 7¼
7, 8 10 3⅜ 12 5 7¼
9, 10 12½ 3⅜ 14 5 7¼
12 15 3⅜ 16 5 7¼
14 17½ 3⅜ 20 7½ 9¾
16 18 3⅜ 24 7½ 9¾
24X16 18 3⅜ 38 5 7¼
Note: The total length of the ESV basic unit and
accessories (attenuators and coils) is the summation of
basic unit length and the accessories length.
All dimensions are in inches.
M9
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com

ACCESSORIES Single/Dual Duct Terminals


MULTI-OUTLET PLENUMS FOR SINGLE DUCT TERMINALS

2 Outlets 3 Outlets
36” 33/8” TYP. 36”
33/8” TYP.
G G
D TYP.

2 Outlets W 3 Outlets D TYP. W

D TYP. H D TYP. H

4 Outlets 5 Outlets
36” 33/8” TYP. 36”
33/8” TYP.
M G M G
D TYP.

4 Outlets W 5 Outlets D TYP. W

M D TYP. H D TYP. H

ESV Unit 2 Outlets 3 Outlets 4 Outlets 5 Outlets


Outlet Size D H W
Sizes G M G M G M G M
4, 5, 6 5⅞ 4⅜ - 4⅜ - - - - - 8 12
7, 8 7⅞ 5⅜ - 5⅜ - 5⅜ 12 - - 10 12
8 7⅞ - - - - - - 5⅜ 12 10 12
9, 10 9⅞ 5⅜ - 5⅜ - 5⅜ 14 - - 12½ 14
9, 10 7⅞ - - 5⅜ - 5⅜ 12 - - 12½ 14
12 11⅞ 6⅜ - 6⅜ - - - - - 15 16
12 9⅞ - - 6⅜ - 6⅜ 14 6⅜ 14 15 16
14 11⅞ 6⅜ - 6⅜ - - - - - 17½ 20
14 9⅞ - - 6⅜ - 6⅜ 14 6⅜ 14 17½ 20
16 11⅞ 6⅜ - 6⅜ - - - - - 18 24
16 9⅞ - - 6⅜ - 6⅜ 14 6⅜ 14 18 24

ROUND OUTLETS
Unit Size D H W
33/8“ 4“ W
4 3⅞ 8 12
5 4⅞ 8 12
6 5⅞ 8 12
ACCESSORIES

7 6⅞ 10 12
8 7⅞ 10 12
D D H 9 8⅞ 12½ 14
10 9⅞ 12½ 14
12 11⅞ 15 16
14 13⅞ 17½ 20
16 15⅞ 18 24

M10 All dimensions are in inches.


Single/Dual Duct Terminals

www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com


ACCESSORIES

REMOVABLE FLOW SENSOR

Removable Sensor
#8 Sheet metal screw Installed
6 places
Sensor
Removed

Removable flow
sensor assembly

ESV WITH ACCESS DOOR OPTION

ESV Terminal Unit


M
Gasket (Access door is sealed with
foam gasket material)

Insulation type specified per order

Access Door (Insulated)

6.00 Right Hand Unit Shown 6.00


2.25 2.25
ACCESSORIES

9.00 9.00

15.50 0.50 39.50 0.50


Basic Unit Basic Unit w/Attenuator
(Bottom View) (Bottom View)

All dimensions are in inches.


M11
PERFORMANCE DATA single / dual duct terminals
RECOMMENDED PRIMARY AIR CFM RANGES / ALL TERMINALS
Redefine your comfort zone™ | www.titus-hvac.com

Control Types:
PESV / Pneumatic
AESV / Analog Electronic
DESV / Digital Electronic

QUICK SELECTION PROCEDURE


1. Select unit inlet size based upon acoustic
parameters and/or maximum pressure
drop requirements, using pages M15-M16
2. Check inlet size selection against cfm
control limits based on control type shown
on this page
3. Select accessories (multi-outlets,
attenuators) as required
4. Select reheat coil, if required. Make your
selection using the actual heating flow
rate, not cooling.

M
cfm Ranges of Minimum and Maximum Settings
Total cfm PESV - Pneumatic PESV - Pneumatic AESV - Analog Electronic DESV - Digital
Inlet Size
Range Titus II Controller Titus I Controller TA1 Controller Typical Controller
Minimum Maximum Minimum Maximum MINIMUM MAXIMUM MINIMUM MAXIMUM
4 0-225 45*-170 80-225 55*-170 80-225 45*-225 45-225 30*-225 30-225
5 0-350 65*-270 120-350 85*-270 120-350 65*-350 65-350 40*-350 40-350
6 0-500 80*-330 150-500 105*-330 150-500 80*-500 80-500 45*-500 45-500
7 0-650 105*-425 190-650 135*-425 190-650 105*-650 105-650 70*-650 70-650
8 0-900 145*-590 265-900 190*-590 265-900 145*-900 145-900 90*-900 90-900
9 0-1050 175*-700 315-1050 225*-700 315-1050 175*-1050 175-1050 120*-1050 120-1050
10 0-1400 230*-925 415-1400 300*-925 415-1400 230*-1400 230-1400 145*-1400 145-1400
12 0-2000 325*-1330 600-2000 425*-1330 600-2000 325*-2000 325-2000 190*-2000 190-2000
14 0-3000 450*-1800 810-3000 575*-1800 810-3000 450*-3000 450-3000 300*-3000 300-3000
16 0-4000 580*-2350 1100-4000 750*-2350 1100-4000 580*-4000 580-4000 385*-4000 385-4000
24 x 16 0-8000 1400*-5200 2600-8000 1800*-5200 2600-8000 1400*-7500 1400-7500 720*-7500 720-7500

*Factory cfm settings (except zero) will not be made below this range because control accuracy is reduced. On pressure dependent units, minimum
cfm is always zero and there is no maximum.
Note: On controls mounted by Titus but supplied by others (FMA or Factory Mounting Authorization), these values are guidelines only. Controls
mounted on an FMA basis are calibrated in the field.
PERFORMANCE DATA

M12
Single/Dual Duct Terminals

www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com


PERFORMANCE DATA

PESV, AESV, DESV / RADIATED SOUND PERFORMANCE


Octave Band Sound Power, Lw
Min
Size CFM 0.5” ∆Ps 1.0” ∆Ps 1.5” ∆Ps 2.0” ∆Ps
∆Ps
2 3 4 5 6 7 NC 2 3 4 5 6 7 NC 2 3 4 5 6 7 NC 2 3 4 5 6 7 NC
100 0.02 49 45 36 33 31 26 11 52 48 39 36 35 31 15 53 50 41 37 37 34 17 55 51 43 38 39 36 18
125 0.03 52 49 39 36 32 27 16 55 52 42 38 36 32 20 57 54 44 40 39 36 22 58 55 45 41 40 38 23
4 150 0.04 55 52 41 37 34 28 20 58 55 44 40 38 34 23 60 57 46 41 40 37 25 61 58 47 42 42 39 27
175 0.06 58 55 42 39 35 29 23 61 58 46 42 39 34 27 63 59 48 43 41 38 28 64 61 49 44 43 40 30
200 0.08 60 57 44 40 36 30 25 63 60 47 43 40 35 29 65 62 49 44 42 38 31 66 63 51 45 44 41 33
150 0.01 49 44 36 32 31 25 10 53 49 41 36 35 30 16 55 51 43 38 37 33 18 57 53 45 39 39 35 21
200 0.02 53 48 39 35 34 27 15 56 53 44 38 37 32 21 59 55 46 40 40 35 23 60 57 48 42 41 37 25
5 250 0.03 55 52 41 37 35 29 20 59 56 46 40 39 34 24 62 59 49 42 41 37 28 63 61 51 44 43 39 30
300 0.04 58 54 43 39 37 30 22 62 59 48 42 41 35 28 64 61 50 44 43 38 30 65 63 52 45 44 40 33
350 0.06 60 56 45 40 38 31 24 63 61 49 43 42 36 30 66 63 52 45 44 39 33 67 65 54 47 45 41 35
300 0.07 55 49 40 35 32 28 16 59 54 45 39 37 33 22 61 57 48 41 39 36 25 63 59 50 42 41 38 28
350 0.10 57 52 42 37 34 29 20 60 57 47 41 38 34 25 62 59 50 43 40 37 28 64 62 52 44 42 39 31
6 400 0.13 58 53 44 39 35 30 21 61 58 49 42 39 35 27 63 61 52 44 42 38 30 65 63 54 46 43 40 33
450 0.16 59 55 45 40 36 31 23 62 60 50 44 40 36 29 64 63 53 46 43 39 33 66 65 55 47 45 41 35
500 0.20 59 56 47 42 37 32 24 63 61 51 45 41 37 30 65 64 54 47 44 40 34 67 67 56 49 46 42 37
450 0.07 59 48 42 38 33 24 20 61 54 48 42 38 30 23 62 57 51 45 41 33 25 63 59 53 46 43 35 28
500 0.09 60 50 43 39 34 24 22 62 55 49 43 39 30 24 63 58 52 46 42 34 27 64 60 54 48 44 36 29
7 550 0.10 60 51 44 40 35 25 22 63 57 50 45 40 31 25 64 59 53 47 43 34 28 66 62 55 49 45 37 31
600 0.12 61 53 45 42 35 25 23 63 58 51 46 41 31 27 65 61 54 48 44 35 30 66 63 56 50 46 37 33
650 0.15 62 54 46 43 36 26 24 64 59 52 47 41 32 28 65 62 55 49 44 35 31 66 64 57 51 46 38 34
600 0.02 59 50 44 40 38 32 20 62 55 49 43 43 39 24 64 58 52 46 45 44 27 65 60 54 47 47 47 29

M
650 0.02 60 51 44 41 39 32 22 63 56 50 44 44 40 25 65 59 53 47 46 45 28 66 61 55 48 48 48 30
8 700 0.02 60 52 45 42 40 33 22 63 57 50 45 44 41 25 65 60 53 47 47 45 29 67 62 56 49 49 48 31
750 0.02 61 53 46 43 40 34 23 64 58 51 46 45 41 27 66 61 54 48 48 46 30 67 63 56 50 50 49 33
800 0.03 62 54 47 43 41 34 24 65 59 52 47 46 42 28 66 62 55 49 48 47 31 68 64 57 51 50 50 34
800 0.04 58 47 43 36 34 30 19 61 53 49 42 40 35 23 62 57 52 46 44 38 26 63 59 55 48 47 40 29
850 0.04 58 48 43 37 34 31 19 61 54 49 43 41 35 23 63 58 53 46 45 38 27 64 60 55 49 47 40 29
9 900 0.05 59 49 44 37 35 31 20 62 55 50 43 41 35 24 64 58 53 47 45 38 27 65 61 56 49 48 40 30
950 0.06 59 50 44 37 35 31 20 62 56 50 43 42 36 24 64 59 54 47 45 38 28 65 62 56 49 48 40 31
1000 0.06 60 50 44 38 36 31 22 63 56 50 44 42 36 25 65 60 54 47 46 39 29 66 62 57 50 48 40 31
900 0.01 60 50 47 45 42 29 22 63 57 53 50 48 37 27 65 60 57 53 52 41 31 67 63 59 56 54 44 34
1000 0.01 60 51 48 46 43 30 22 64 58 54 51 49 38 28 66 61 57 54 53 42 31 67 64 59 56 55 45 34
10 1100 0.01 61 52 48 47 44 32 23 65 58 54 52 50 39 28 67 62 57 55 54 43 31 68 64 60 57 56 46 35
1200 0.01 62 53 48 47 45 32 24 65 59 54 53 51 40 28 67 63 58 56 55 44 33 69 65 60 58 57 47 35
1300 0.01 63 54 49 48 45 33 25 66 60 55 53 52 41 29 68 63 58 56 55 45 33 69 66 61 58 58 48 36
1200 0.01 58 50 47 41 37 30 20 62 56 52 47 43 37 26 64 59 56 50 46 41 30 66 61 58 53 49 43 32
1400 0.01 60 52 48 42 38 32 22 63 57 54 48 45 39 28 65 60 57 52 48 42 31 67 63 60 54 51 45 35
12 1600 0.01 61 53 50 43 40 34 24 64 59 55 49 46 40 29 66 62 59 53 50 44 34 68 64 61 55 52 47 36
1800 0.01 61 55 51 44 41 35 25 65 60 56 50 48 41 30 67 63 60 54 51 45 35 69 65 62 56 54 48 37
2000 0.01 62 56 52 45 43 36 26 66 61 57 51 49 43 31 68 64 61 55 52 47 36 69 67 63 57 55 49 38
1500 0.02 56 51 45 43 40 36 18 60 56 50 48 45 41 24 62 59 53 51 48 45 28 64 61 55 53 50 47 30
1800 0.03 58 53 46 44 41 36 21 62 58 51 49 46 42 27 64 60 54 52 49 45 29 66 63 56 54 51 48 33
14 2100 0.04 59 54 47 45 42 37 22 63 59 52 50 47 43 28 66 62 55 53 50 46 31 67 64 58 55 52 49 34
2400 0.05 60 55 48 46 43 38 23 64 60 53 51 48 43 29 67 63 56 54 51 47 33 69 65 58 56 53 49 35
2700 0.06 62 56 49 47 44 38 24 66 61 54 52 49 44 30 68 64 57 55 52 47 34 70 66 59 57 54 50 36
2000 0.02 55 48 43 41 39 31 36 59 53 47 45 44 38 21 61 56 50 47 47 41 24 63 58 52 49 49 44 27
2400 0.02 57 51 45 43 41 33 18 61 56 49 47 46 39 24 64 59 52 49 49 43 28 65 61 54 51 51 46 30
16 2800 0.03 59 53 46 44 42 34 21 63 58 51 48 47 41 27 66 61 54 50 50 45 30 67 63 55 52 52 48 33
3200 0.04 61 55 48 46 44 36 23 65 60 52 50 49 42 29 67 62 55 52 52 46 31 69 64 57 53 54 49 34
PERFORMANCE DATA
3600 0.05 62 56 49 47 45 37 24 66 61 54 51 50 44 30 69 64 56 53 53 48 34 71 66 58 55 55 50 36
3900 0.03 70 65 63 59 57 54 38 72 68 66 62 61 58 41 74 69 67 63 63 61 42 75 70 68 64 65 63 43
4600 0.04 73 68 66 62 59 55 41 75 71 68 64 63 60 43 77 72 70 66 65 63 46 78 73 71 67 67 64 47
40 5300 0.06 75 71 68 64 61 56 43 78 73 71 66 65 61 47 79 74 72 68 67 64 48 80 75 73 69 68 66 49
6000 0.07 77 73 71 66 63 57 47 80 75 73 68 66 62 49 81 76 74 70 68 65 50 82 77 75 71 70 67 51
6700 0.09 79 75 72 67 64 58 48 82 77 75 70 68 63 51 83 78 76 71 70 66 52 84 79 77 72 71 68 53

• Radiated sound is the noise transmitted • All performance based on tests conducted in
through the unit casing. accordance with ASHRAE 130-2008 and AHRI 880-2008.
• Min ∆Ps is the static pressure drop from the unit inlet • All NC levels determined using AHRI 885-2008
to the unit outlet with primary damper full open. Appendix E. See Terminal Unit Engineering Guidelines.
• Sound power levels are in dB, ref 10-12 watts. • Dash (-) in space denotes NC value less than NC10.
• Sound performance based on units lined with • Only highlighted data points are AHRI certified. See
standard dual density fiberglass lining. page M24 for AHRI Certified Performance Listings.

M13
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com

PERFORMANCE DATA Single/Dual Duct Terminals


PESV, AESV, DESV / DISCHARGE SOUND PERFORMANCE
Octave Band Sound Power, Lw
Min
Size CFM 0.5” ∆Ps 1.0” ∆Ps 1.5” ∆Ps 2.0” ∆Ps
∆Ps
2 3 4 5 6 7 NC 2 3 4 5 6 7 NC 2 3 4 5 6 7 NC 2 3 4 5 6 7 NC
100 0.02 62 53 46 42 40 33 17 63 56 50 46 47 41 18 64 58 53 49 50 46 19 65 59 55 51 53 49 20
125 0.03 64 57 49 44 42 35 19 65 60 53 49 49 43 20 66 61 56 52 52 47 22 67 62 58 54 55 51 23
4 150 0.04 65 60 51 47 44 36 20 67 62 56 51 50 44 23 68 64 59 54 54 49 24 68 65 60 56 57 52 24
175 0.06 67 62 53 48 45 37 23 68 65 58 53 51 45 24 69 66 61 56 55 50 25 70 68 63 58 58 53 28
200 0.08 68 64 55 50 46 38 24 69 67 60 55 53 46 27 70 69 62 58 56 51 29 71 70 64 60 59 54 30
150 0.01 60 50 46 43 41 34 14 62 55 51 47 47 42 17 64 57 54 50 51 46 19 65 59 57 52 53 49 20
200 0.02 63 54 49 46 43 36 18 65 58 55 51 49 44 20 67 61 58 53 53 48 23 68 63 60 55 55 51 24
5 250 0.03 65 57 52 49 45 38 20 67 62 57 53 51 45 23 69 64 60 56 55 50 25 70 66 62 58 57 53 27
300 0.04 66 59 54 51 47 39 18 69 64 59 55 53 46 22 70 67 62 58 56 51 25 71 69 65 60 59 54 28
350 0.06 68 61 56 52 48 40 20 70 66 61 57 54 47 24 72 69 64 60 57 52 28 73 71 66 61 60 55 30
300 0.07 60 57 53 50 45 39 14 64 62 58 54 51 46 20 67 65 61 57 54 50 23 69 67 63 58 56 53 25
350 0.10 61 59 54 52 47 40 16 66 64 60 56 52 47 22 68 67 63 59 55 51 25 70 69 65 60 58 54 28
6 400 0.13 63 60 56 54 48 41 17 67 66 61 58 53 48 24 70 69 64 60 57 52 28 71 71 66 62 59 55 30
450 0.16 64 62 57 55 49 42 20 68 67 63 59 54 49 25 71 70 66 62 58 53 29 73 73 68 63 60 56 33
500 0.20 65 63 59 56 50 43 21 69 69 64 61 55 50 28 72 72 67 63 59 54 31 74 74 69 65 61 57 34
450 0.07 64 58 53 51 47 40 15 67 63 58 54 51 46 21 68 67 60 56 54 49 25 70 69 62 58 56 52 28
500 0.09 64 59 54 52 48 40 16 67 65 59 56 52 47 23 69 68 62 58 55 50 27 70 71 63 59 57 53 30
7 550 0.1 65 61 55 54 49 41 18 68 66 60 57 53 48 24 69 70 63 59 56 51 29 71 72 64 60 58 54 31
600 0.12 65 62 56 55 49 42 20 68 67 61 58 54 48 25 70 71 63 60 57 52 30 71 73 65 61 59 55 33
650 0.15 65 63 57 56 50 43 21 68 69 62 59 55 49 28 70 72 64 61 58 53 31 72 74 66 62 59 55 34
600 0.02 66 60 55 52 48 40 18 69 66 59 55 52 47 24 71 69 61 56 55 51 28 72 72 63 57 57 54 31

M
650 0.02 67 61 56 53 48 41 19 70 67 60 56 53 47 25 71 70 62 57 55 51 29 72 73 64 58 57 54 33
8 700 0.02 67 62 56 54 49 41 20 70 68 60 56 53 48 27 72 71 63 58 56 52 30 73 74 64 59 58 55 34
750 0.02 68 63 57 54 49 42 20 70 69 61 57 54 48 27 72 72 63 58 56 52 30 73 75 65 60 58 55 34
800 0.03 68 64 57 55 50 42 21 71 70 62 58 54 49 28 72 73 64 59 57 53 31 74 75 66 60 59 56 34
800 0.04 67 59 56 53 49 43 17 70 64 60 57 54 49 21 71 67 62 59 57 53 24 72 69 64 60 59 56 27
850 0.04 68 60 56 53 49 43 18 70 65 60 57 54 50 22 72 68 62 59 57 54 25 73 70 64 61 59 56 28
9 900 0.05 68 61 57 54 50 43 18 71 66 61 57 55 50 23 73 68 63 59 57 54 25 74 70 65 61 59 57 28
950 0.06 69 61 57 54 50 44 19 72 66 61 58 55 50 23 73 69 63 60 58 54 27 74 71 65 61 60 57 29
1000 0.06 69 62 58 55 50 44 19 72 67 61 58 55 50 24 74 70 64 60 58 54 28 75 72 65 62 60 57 30
900 0.01 69 60 57 55 50 44 19 71 65 61 59 55 50 22 72 68 64 61 58 54 25 73 71 66 63 61 57 29
1000 0.01 70 61 58 56 50 44 20 72 66 62 60 56 51 23 73 69 65 62 59 55 27 74 72 67 64 61 57 30
10 1100 0.01 70 61 58 57 51 45 20 73 67 63 61 56 51 24 74 70 65 63 60 55 28 75 72 67 65 62 58 30
1200 0.01 71 62 59 57 52 45 22 73 68 63 61 57 52 25 75 71 66 64 60 56 29 76 73 68 66 63 59 31
1300 0.01 72 63 60 58 52 46 23 74 68 64 62 58 53 25 75 72 67 65 61 56 30 76 74 68 66 63 59 33
1200 0.01 68 62 59 55 53 46 18 71 67 63 59 57 52 24 73 70 65 62 60 56 28 74 72 67 64 62 59 30
1400 0.01 69 63 61 56 54 47 20 72 69 65 61 59 53 27 74 72 67 63 61 57 30 75 74 69 65 63 60 33
12 1600 0.01 70 64 62 57 55 48 21 73 70 66 62 59 55 28 75 73 68 64 62 58 31 76 75 70 66 64 61 34
1800 0.01 71 66 63 58 55 49 23 74 71 67 63 60 56 29 75 74 70 65 63 59 33 76 76 71 67 65 62 35
2000 0.01 71 67 64 59 56 50 24 74 72 68 64 61 56 30 76 75 71 66 64 60 34 77 77 72 68 66 63 36
1500 0.02 65 56 56 53 50 44 14 68 62 61 59 57 53 18 70 66 63 62 62 59 23 72 68 65 65 65 62 25
1800 0.03 66 58 58 53 50 44 15 69 64 62 59 58 53 21 71 67 65 63 62 59 24 73 70 67 65 65 63 28
14 2100 0.04 67 59 59 54 51 44 17 70 65 64 60 58 54 22 72 68 66 63 63 59 25 74 71 68 66 66 63 29
2400 0.05 68 60 60 54 51 44 18 71 66 65 60 59 54 23 73 69 68 64 63 59 27 74 72 69 66 66 63 30
2700 0.06 68 61 61 54 51 45 18 72 67 66 61 59 54 24 74 70 69 64 63 60 28 75 73 70 67 66 63 31
2000 0.02 65 58 57 54 52 45 14 68 62 60 58 56 51 18 70 65 62 61 59 54 22 71 67 63 63 61 57 24
2400 0.02 67 61 59 55 53 46 17 70 65 63 60 58 52 22 72 67 64 62 61 56 24 73 69 66 64 62 58 27
16 2800 0.03 68 63 61 57 55 48 20 72 67 65 61 59 54 24 74 69 66 64 62 57 27 75 71 68 66 64 60 29
3200 0.04 70 64 63 58 56 49 21 73 68 66 62 60 55 25 75 71 68 65 63 59 29 76 72 70 67 65 61 30
PERFORMANCE DATA

3600 0.05 71 66 65 59 57 50 23 74 70 68 63 61 56 28 76 72 70 66 64 60 30 78 74 71 68 66 62 33
3900 0.03 74 69 66 62 61 56 27 79 74 71 67 67 62 33 82 77 74 69 70 66 36 84 79 76 71 72 68 34
4600 0.04 75 70 67 63 63 58 28 80 76 73 68 68 64 35 83 79 76 71 71 67 38 86 81 78 73 74 70 41
40 5300 0.06 77 72 69 65 64 60 30 82 77 74 69 70 65 36 85 80 77 72 73 69 40 87 82 79 74 75 71 42
6000 0.07 78 73 70 66 65 61 31 83 78 75 71 71 67 37 86 81 78 73 74 70 41 88 83 80 75 76 73 43
6700 0.09 79 74 71 67 67 62 33 84 79 76 72 72 68 38 87 82 79 74 75 71 42 89 84 81 76 77 74 45

• Discharge sound is the noise emitted from the • All performance based on tests conducted in
unit discharge into the downstream ductwork. accordance with ASHRAE 130-2008 and AHRI 880-2008.
• Min ∆Ps is the static pressure drop from the unit inlet • All NC levels determined using AHRI 885-2008
to the unit outlet with primary damper full open. Appendix E. See Terminal Unit Engineering Guidelines.
• Sound power levels are in dB, ref 10-12 watts. • Dash (-) in space denotes NC value less than NC10.
• Sound performance based on units lined with • Only highlighted data points are AHRI certified. See
standard dual density fiberglass lining. page M24 for AHRI Certified Performance Listings.

M14
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
PERFORMANCE DATA Single/Dual Duct Terminals
PESV, AESV, DESV / HOT WATER COIL CAPACITY, MBH / 1- AND 2-ROW

Rows/ Head Airflow, cfm


Circuits gpm Loss 50 100 150 200 250 300 350 400 450
1.0 0.50 4.2 5.9 7.0 7.7 8.6 9.4 10.1 10.6 11.2
One-Row 2.0 1.69 4.4 6.3 7.5 8.3 9.4 10.3 11.1 11.8 12.5
Single 4.0 5.77 4.4 6.5 7.8 8.7 9.8 10.9 11.8 12.6 13.4
Sizes 4-5-6

Circuit 5.0 8.59 4.5 6.5 7.8 8.8 9.9 11.0 11.9 12.8 13.6
Airside ∆ Ps 0.01 0.01 0.02 0.03 0.05 0.07 0.09 0.12 0.14
1.0 0.24 5.3 8.6 11.0 12.9 14.4 15.6 16.7 17.6 18.4
Two-Row 3.0 1.66 5.5 9.4 12.5 15.0 17.1 19.0 20.7 22.2 23.5
Multi- 5.0 4.06 5.6 9.6 12.8 15.5 17.9 19.9 21.8 23.5 25.0
Circuit 7.0 7.39 5.6 9.7 13.0 15.8 18.2 20.4 22.3 24.1 25.7
Airside ∆Ps 0.01 0.02 0.04 0.07 0.10 0.13 0.18 0.22 0.27
Rows/ Head Airflow, cfm
Circuits gpm Loss 100 200 300 400 500 600 700 800 900
1.0 0.69 6.9 9.2 10.7 12.2 13.4 14.5 15.3 16.1 16.8
One-Row 2.0 2.34 7.2 9.9 11.7 13.6 15.1 16.4 17.6 18.6 19.5
Single 3.0 4.77 7.4 10.2 12.1 14.1 15.8 17.2 18.5 19.6 20.7
Sizes 7-8

Circuit 4.0 7.96 7.4 10.3 12.3 14.4 16.1 17.7 19.0 20.2 21.3

M
Airside ∆Ps 0.01 0.02 0.04 0.07 0.10 0.14 0.19 0.24 0.30
1.0 0.33 9.4 14.3 17.6 20.1 21.9 23.4 24.7 25.7 26.6
Two-Row 3.0 2.32 10.1 16.5 21.2 25.0 28.1 30.8 33.1 35.1 37.0
Multi- 5.0 5.66 10.3 17.0 22.2 26.3 29.9 32.9 35.6 38.0 40.2
Circuit 7.0 10.28 10.3 17.2 22.6 27.0 30.7 34.0 36.9 39.5 41.8
Airside ∆Ps 0.01 0.04 0.08 0.13 0.20 0.27 0.36 0.46 0.56
Rows/ Head Airflow, cfm
Circuits gpm Loss 200 300 400 500 600 700 800 900 1000
2.0 0.68 11.7 13.8 15.3 17.0 18.5 19.8 21.0 22.0 23.0
One-Row 3.0 1.40 12.1 14.4 16.0 18.0 19.7 21.2 22.5 23.7 24.8
Multi- 5.0 3.41 12.5 15.0 16.7 18.9 20.8 22.4 23.9 25.3 26.6
Sizes 9-10

Circuit 6.0 4.72 12.6 15.1 16.9 19.1 21.1 22.8 24.3 25.8 27.1
Airside ∆Ps 0.01 0.02 0.04 0.05 0.07 0.10 0.12 0.15 0.18
2.0 0.65 17.4 22.4 26.3 29.5 32.1 34.4 36.3 38.1 39.6
Two-Row 4.0 2.19 18.5 24.3 29.0 33.0 36.5 39.6 42.3 44.7 46.9
Multi- 6.0 4.43 18.8 25.0 30.1 34.5 38.3 41.7 44.8 47.6 50.1
Circuit 8.0 7.35 19.0 25.4 30.7 35.3 39.3 42.9 46.2 49.2 51.9
Airside ∆Ps 0.02 0.04 0.07 0.10 0.14 0.18 0.23 0.29 0.35
Rows/ Head Airflow, cfm
Circuits gpm Loss 300 500 700 900 1100 1300 1500 1700 1900
2.0 0.88 14.7 17.3 19.6 21.4 22.9 24.1 25.2 26.0 26.8
One-Row 3.0 1.81 16.4 19.9 23.0 25.7 28.0 29.9 31.5 32.9 34.2
PERFORMANCE DATA
Multi- 5.0 4.40 17.5 21.6 25.4 28.7 31.6 34.0 36.2 38.1 39.9
Size 12

Circuit 6.0 6.08 17.9 22.3 26.3 29.9 33.0 35.8 38.2 40.3 42.3
Airside ∆Ps 0.01 0.03 0.06 0.09 0.12 0.17 0.21 0.27 0.33
2.0 0.84 21.7 27.5 31.1 33.7 35.6 37.1 38.3 39.3 40.2
Two-Row 4.0 2.79 26.0 35.7 42.8 48.5 53.0 56.9 60.2 63.1 65.6
Multi- 6.0 5.63 27.1 37.9 46.3 53.0 58.7 63.6 67.8 71.6 75.0
Circuit 8.0 9.33 27.6 39.0 47.9 55.3 61.6 67.0 71.8 76.1 79.9
Airside ∆Ps 0.02 0.06 0.11 0.16 0.23 0.32 0.41 0.51 0.62

M15
For performance notes, see the next page.
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com

PERFORMANCE DATA Single/Dual Duct Terminals


PESV, AESV, DESV / HOT WATER COIL CAPACITY, MBH / 1- AND 2-ROW

Rows/ Head Airflow, cfm


Circuits gpm Loss 400 700 1000 1300 1600 1900 2200 2500 2800
2.0 0.45 21.9 26.8 30.7 34.2 36.9 39.2 41.1 42.8 44.3
One-Row 3.0 0.95 23.2 28.8 33.4 37.5 40.9 43.8 46.3 48.4 50.3
Multi- 5.0 2.31 24.3 30.6 36.0 40.9 45.0 48.5 51.6 54.3 56.7
Size 14

Circuit 6.0 3.17 24.6 31.1 36.7 41.8 46.1 49.8 53.1 56.0 58.6
Airside ∆Ps 0.01 0.03 0.05 0.08 0.12 0.17 0.21 0.27 0.33
2.0 0.56 32.5 43.9 51.4 56.8 60.9 64.2 66.8 69.1 71.0
Two-Row 4.0 1.94 35.6 50.5 61.3 69.7 76.4 82.0 86.8 90.9 94.5
Multi- 6.0 3.89 36.8 53.2 65.5 75.3 83.4 90.3 96.3 101.5 106.1
Circuit 8.0 6.40 37.4 54.6 67.8 78.5 87.4 95.1 101.8 107.8 113.1
Airside ∆Ps 0.02 0.05 0.10 0.16 0.23 0.31 0.41 0.51 0.63
Rows/ Head Airflow, cfm
Circuits gpm Loss 600 1000 1400 1800 2200 2600 3000 3400 3800
3.0 0.98 30.1 36.2 42.1 46.8 50.6 53.8 56.5 58.9 61.0
One-Row 5.0 2.44 31.9 38.9 46.0 51.7 56.4 60.4 63.9 67.1 69.8
Multi- 7.0 4.38 32.7 40.3 47.9 54.1 59.4 63.9 67.9 71.4 74.6
Size 16

Circuit 9.0 6.83 33.2 41.1 49.1 55.6 61.2 66.0 70.3 74.1 77.5

M
Airside ∆Ps 0.02 0.04 0.07 0.11 0.16 0.21 0.27 0.34 0.41
3.0 0.50 45.4 59.2 68.5 75.3 80.7 85.0 88.5 91.5 94.1
Two-Row 5.0 1.26 49.1 66.1 78.4 87.9 95.5 101.9 107.2 111.9 115.9
Multi- 7.0 2.25 50.8 69.6 83.6 94.6 103.7 111.4 118.0 123.7 128.8
Circuit 9.0 3.46 51.8 71.7 86.8 98.9 108.9 117.5 125.0 131.5 137.3
Airside ∆Ps 0.03 0.07 0.13 0.21 0.30 0.40 0.51 0.64 0.78
Rows/ Head Airflow, cfm
Circuits gpm Loss 600 1200 1800 2400 3000 3600 4200 4800 5400
3.0 1.15 38.0 49.5 57.4 64.5 70.1 74.7 78.5 81.8 84.7
One-Row 5.0 2.90 40.3 53.8 63.4 72.4 79.8 85.9 91.1 95.7 99.7
Multi- 7.0 5.20 41.3 55.9 66.5 76.5 84.8 91.8 97.8 103.2 107.9
Size 24 x 16

Circuit 9.0 8.08 41.9 57.1 68.3 79.0 87.8 95.4 102.0 107.9 113.1
Airside ∆Ps 0.01 0.02 0.05 0.08 0.12 0.17 0.22 0.27 0.34
3.0 0.56 52.2 76.1 90.4 100.1 107.2 112.7 117.0 120.6 123.6
Two-Row 5.0 1.41 55.9 85.8 105.6 120.0 131.2 140.1 147.5 153.7 159.0
Multi- 7.0 2.51 57.6 90.6 113.5 130.8 144.6 155.9 165.4 173.5 180.6
Circuit 9.0 3.86 58.6 93.5 118.4 137.6 153.2 166.1 177.2 186.7 195.1
Airside ∆Ps 0.01 0.04 0.09 0.15 0.23 0.31 0.41 0.52 0.64

• All coil performance in accordance with AHRI 410-2001. • Water temperature drop = 2.04 x MBH/gpm.
• Heating capacities are in MBH. • Connection size is ½-in OD male solder for 1-row coil
• Data based on 180°F entering water sizes 04-08. All other coils have ⅞-in OD male solder.
PERFORMANCE DATA

and 55°F entering air. • Coils are not intended for steam applications and are
• For temperature differentials other than 125°, labeled for a maximum water temperature of 200°F.
multiply MBH by correction factors below. • Coils are tested for leakage at test pressure of 500 psi.
• Head loss is in feet of water. • Water volumes less than those shown may result
• Always supply water to lowest connection in laminar flow and reduced heating capacity.
pipe to prevent air entrapment. If possible reduce the number of coil rows to
• Air temperature rise = 927 x MBH/cfm. increase water velocity into turbulent range.

Correction Factors for Other Entering Conditions


∆T 50 60 70 80 90 100 110 125 140 150
Factor 0.40 0.48 0.56 0.64 0.72 0.80 0.88 1.00 1.12 1.20

Note: Airside DPs reflects the air pressure drop of the hot water coil.
M16
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
PERFORMANCE DATA Single/Dual Duct Terminals
PESV, AESV, DESV / HOT WATER COIL CAPACITY, MBH / 3- AND 4-ROW

Rows/ Head Airflow, cfm


Circuits gpm Loss 50 100 150 200 250 300 350 400 450
Three- 2.0 1.31 6.2 11.0 14.9 18.1 20.9 23.3 25.4 27.3 28.9
Row 3.0 2.63 6.2 11.2 15.3 18.8 21.9 24.5 26.9 29.1 31.0
Multi- 5.0 6.43 6.3 11.4 15.7 19.4 22.7 25.6 28.3 30.7 32.9
Sizes 4-5-6

Circuit 6.0 8.88 6.3 11.4 15.8 19.6 22.9 25.9 28.7 31.2 33.5
Airside ∆Ps 0.01 0.03 0.06 0.10 0.14 0.20 0.26 0.33 0.40
Four- 3.0 1.59 6.5 12.1 16.9 21.1 24.7 27.9 30.7 33.3 35.6
Row 4.0 2.61 6.5 12.2 17.2 21.5 25.3 28.7 31.8 34.6 37.2
Multi- 6.0 5.28 6.5 12.3 17.4 21.9 26.0 29.6 33.0 36.0 38.8
Circuit 8.0 8.77 6.5 12.4 17.5 22.2 26.3 30.1 33.6 36.8 39.8
Airside ∆Ps 0.01 0.04 0.08 0.13 0.19 0.26 0.34 0.43 0.53
Rows/ Head Airflow, cfm
Circuits gpm Loss 100 200 300 400 500 600 700 800 900
Three- 2.0 0.79 11.5 19.2 24.8 29.2 32.7 35.6 38.1 40.2 42.0
Row 4.0 2.63 11.8 20.3 27.0 32.5 37.0 41.0 44.4 47.4 50.1
Multi- 6.0 5.31 11.9 20.8 27.9 33.7 38.8 43.2 47.0 50.5 53.6
Sizes 7-8

Circuit 8.0 8.80 11.9 21.0 28.3 34.4 39.7 44.4 48.5 52.2 55.6

M
Airside ∆Ps 0.02 0.06 0.12 0.20 0.29 0.40 0.53 0.67 0.83
Four- 4.0 2.04 12.6 22.6 30.6 37.2 42.7 47.5 51.7 55.3 58.6
Row 6.0 4.12 12.7 23.0 31.5 38.7 44.9 50.3 55.0 59.3 63.2
Multi- 8.0 6.79 12.7 23.2 32.0 39.5 46.0 51.8 56.9 61.6 65.8
Circuit 10.0 10.04 12.7 23.4 32.3 40.0 46.8 52.8 58.1 63.0 67.5
Airside ∆Ps 0.02 0.08 0.16 0.26 0.39 0.53 0.70 0.89 1.10
Rows/ Head Airflow, cfm
Circuits gpm Loss 200 300 400 500 600 700 800 900 1000
Three- 3.0 1.18 21.5 28.8 34.7 39.7 43.9 47.5 50.8 53.6 56.2
Row 5.0 2.85 22.1 30.1 36.8 42.5 47.6 52.0 56.0 59.6 62.9
Multi- 7.0 5.11 22.4 30.7 37.8 43.9 49.4 54.3 58.7 62.7 66.4
Sizes 9-10

Circuit 9.0 7.92 22.6 31.1 38.3 44.7 50.4 55.6 60.3 64.5 68.5
Airside ∆Ps 0.03 0.06 0.10 0.15 0.21 0.27 0.34 0.42 0.51
Four- 4.0 1.72 23.9 33.0 40.7 47.3 53.0 58.0 62.5 66.5 70.1
Row 5.0 2.53 24.1 33.5 41.6 48.6 54.7 60.2 65.1 69.5 73.5
Multi- 8.0 5.71 24.4 34.3 43.0 50.6 57.5 63.7 69.4 74.5 79.3
Circuit 10.0 8.41 24.6 34.6 43.5 51.4 58.5 65.0 70.9 76.4 81.5
Airside ∆Ps 0.04 0.08 0.13 0.20 0.27 0.36 0.46 0.56 0.68
Rows/ Head Airflow, cfm
Circuits gpm Loss 300 500 700 900 1100 1300 1500 1700 1900
Three- 3.0 1.50 29.7 40.6 48.3 53.9 58.4 61.9 64.8 67.3 69.4
Row 4.0 2.46 31.9 45.6 56.2 64.6 71.6 77.4 82.5 86.8 90.7
PERFORMANCE DATA
Multi- 6.0 4.94 32.6 47.5 59.3 69.0 77.2 84.3 90.5 95.9 100.8
Size 12

Circuit 8.0 8.14 33.0 48.5 61.0 71.4 80.4 88.2 95.0 101.2 106.7
Airside ∆Ps 0.03 0.09 0.16 0.24 0.35 0.47 0.60 0.75 0.91
Four- 4.5 2.67 35.2 52.0 65.3 76.0 84.9 92.4 98.8 104.4 109.4
Row 5.0 3.20 35.4 52.6 66.2 77.4 86.7 94.7 101.5 107.5 112.8
Multi- 7.0 5.71 36.1 54.5 69.7 82.5 93.5 103.2 111.7 119.3 126.1
Circuit 9.0 8.81 36.3 55.1 70.9 84.3 96.0 106.3 115.5 123.7 131.2
Airside ∆Ps 0.05 0.11 0.21 0.32 0.46 0.61 0.79 0.99 1.20

M17
For Performance Notes, see the next page.
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com

PERFORMANCE DATA Single/Dual Duct Terminals


PESV, AESV, DESV / HOT WATER COIL CAPACITY, MBH / 3- AND 4-ROW

Rows/ Head Airflow, cfm


Circuits gpm Loss 400 700 1000 1300 1600 1900 2200 2500 2800
Three- 4.0 1.95 42.5 62.2 76.5 87.5 96.3 103.5 109.5 114.7 119.1
Row 5.0 2.87 43.2 64.2 79.9 92.2 102.2 110.5 117.6 123.7 129.0
Multi- 6.0 3.93 43.7 65.6 82.2 95.5 106.4 115.6 123.5 130.4 136.5
Size 14

Circuit 8.0 6.44 44.4 67.3 85.3 99.9 112.2 122.7 131.8 139.9 147.0
Airside ∆Ps 0.03 0.08 0.15 0.24 0.34 0.46 0.60 0.75 0.92
Four- 6.0 2.77 47.6 73.2 93.0 108.8 121.8 132.6 141.8 149.7 156.7
Row 6.0 2.77 47.6 73.2 93.0 108.8 121.8 132.6 141.8 149.7 156.7
Multi- 8.0 4.55 48.2 75.2 96.7 114.3 129.1 141.7 152.6 162.1 170.5
Circuit 10.0 6.67 48.6 76.4 99.0 117.9 133.9 147.7 159.7 170.4 180.0
Airside ∆Ps 0.04 0.10 0.20 0.31 0.45 0.61 0.79 1.00 1.22
Rows/ Head Airflow, cfm
Circuits gpm Loss 600 1000 1400 1800 2200 2600 3000 3400 3800
Three- 6.0 1.54 60.4 84.3 101.8 115.5 126.4 135.5 143.1 149.7 155.5
Row 8.0 2.54 61.9 87.8 107.4 123.0 135.9 146.7 155.9 164.0 171.0
Multi- 10.0 3.73 62.9 90.0 111.1 128.1 142.2 154.3 164.7 173.8 182.0
Size 16

Circuit 12.0 5.10 63.5 91.6 113.7 131.7 146.8 159.8 171.1 181.1 190.0

M
Airside ∆Ps 0.04 0.11 0.20 0.31 0.44 0.59 0.76 0.94 1.15
Four- 9.0 2.79 68.9 100.8 125.6 145.5 161.9 175.8 187.7 198.0 207.0
Row 10.0 3.34 69.3 101.9 127.5 148.3 165.6 180.2 192.8 203.9 213.6
Multi- 11.0 3.94 69.7 102.9 129.2 150.7 168.6 184.0 197.3 208.9 219.2
Circuit 12.0 4.57 69.9 103.6 130.5 152.7 171.3 187.2 201.1 213.3 224.2
Airside ∆Ps 0.06 0.14 0.26 0.40 0.58 0.78 1.00 1.25 1.52
Rows/ Head Airflow, cfm
Circuits gpm Loss 600 1200 1800 2400 3000 3600 4200 4800 5400
Three- 6.0 1.69 66.6 107.8 135.8 156.2 171.9 184.4 194.6 203.2 210.4
Row 8.0 2.78 67.9 112.5 144.3 168.4 187.5 203.0 216.0 227.0 236.6
Multi- 10.0 4.08 68.7 115.4 149.8 176.4 197.9 215.7 230.8 243.8 255.1
Size 24 x 16

Circuit 12.0 5.57 69.3 117.4 153.6 182.1 205.4 225.0 241.7 256.2 269.0
Airside ∆Ps 0.02 0.07 0.14 0.23 0.33 0.46 0.61 0.77 0.95
Four- 9.0 3.01 73.7 127.6 167.4 198.0 222.2 242.0 258.4 272.3 284.3
Row 10.0 3.61 74.0 129.0 170.3 202.4 228.2 249.4 267.2 282.4 295.5
Multi- 11.0 4.25 74.3 130.2 172.7 206.1 233.2 255.7 274.7 291.0 305.1
Circuit 12.0 4.93 74.5 131.1 174.7 209.3 237.6 261.2 281.2 298.5 313.6
Airside ∆Ps 0.03 0.09 0.18 0.30 0.44 0.61 0.80 1.02 1.25

• All coil performance in accordance with AHRI 410-2001. • Water temperature drop = 2.04 x MBH/gpm.
• Heating capacities are in MBH. • Connection size is ½-in OD male solder for 1-row coil
• Data based on 180°F entering water sizes 04-08. All other coils have ⅞-in OD male solder.
PERFORMANCE DATA

and 55°F entering air. • Coils are not intended for steam applications and are
• For temperature differentials other than 125°, labeled for a maximum water temperature of 200°F.
multiply MBH by correction factors below. • Coils are tested for leakage at test pressure of 500 psi.
• Head loss is in feet of water. • Water volumes less than those shown may result
• Always supply water to lowest connection in laminar flow and reduced heating capacity.
pipe to prevent air entrapment. If possible reduce the number of coil rows to
• Air temperature rise = 927 x MBH/cfm. increase water velocity into turbulent range.

Correction Factors for Other Entering Conditions


∆T 50 60 70 80 90 100 110 125 140 150
Factor 0.40 0.48 0.56 0.64 0.72 0.80 0.88 1.00 1.12 1.20

Note: Airside DPs reflects the air pressure drop of the hot water coil.
M18
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
ELECTRIC COILS Single/Dual Duct Terminals
SELECTION AND CAPACITIES
Recommended Coil Selection Data

The table at the right describes the maximum recommended


kW capacities and number of stages available for
Titus single duct terminals.

To make a coil selection:


1. Check the desired kW is available in desired unit size Titus electric heating coils are specifically designed for use
and number of stages. (Required to prevent excessive with VAV terminal units. They include an extended plenum
watt density and current draw, while taking into account section and diffuser plate to minimize stratification. The
heating elements are designed to minimize hot spots and
unit size limitations.)
nuisance tripping of the thermal cutouts.
2. Check the desired minimum airflow limit is within
recommended operating range. (Ensures velocity These requirements established to prevent excessive
pressure will be sufficient to close airflow sensing temperature rise caused by low airflow and/or oversized
switch.) coils. Minimum airflow limits must be within recommended
3. Multiply desired minimum airflow limit by a factor of ranges to ensure proper operation and long service life.
0.0142 and check the result is equal to or greater than For optimum diffuser performance and maximum thermal
desired kW. (Limits temperature rise across the coil comfort, coil discharge temperatures should not be more
to 45°F.) than 15°F above desired room temperatures. For proper

M
kW ≤ cfm x 0.0142 coil operation it is recommended that coil discharge
temperatures do not to exceed 100°F.

PESV, AESV, DESV / APPLICATION DATA (STAGED HEAT)


Number 208V 240V 277V 208V 480V
Inlet Heating of 1 Phase 1 Phase 1 Phase 3 Phase 3 Phase
Size cfm Range Steps kW Range kW Range kW Range kW Range kW Range
Available Min Max Min Max Min Max Min Max Min Max
1 0.5 1.0 1.0
4 55-225 2 1.0 3.0 1.5 3.0 1.5 3.0 1.5 3.0 2.5 3.0
3 1.5 2.0 2.5
1 0.5 1.0 1.0
5 85-350 2 1.0 5.0 1.5 5.0 1.5 5.0 1.5 5.0 2.5 5.0
3 1.5 2.0 2.5
1 0.5 1.0 1.0
6 105-500 2 1.0 7.5 1.5 7.5 1.5 7.5 1.5 7.5 2.5 7.5
3 1.5 2.0 2.5
1 0.5 1.0 1.0
7 135-650 2 1.0 9.5 1.5 9.5 1.5 9.5 1.5 9.5 2.5 9.5
3 1.5 2.0 2.5
1 0.5 1.0 1.0
8 190-900 2 1.0 9.5 1.5 11.0 1.5 13.0 1.5 13.0 2.5 13.0
3 1.5 2.0 2.5
1 0.5 1.0 1.0
9 225-1050 2 1.0 9.5 1.5 11.0 1.5 13.0 1.5 16.0 2.5 16.0
3 1.5 2.0 2.5
1 0.5 1.0 1.0
10 300-1400 2 1.0 9.5 1.5 11.0 1.5 13.0 1.5 16.0 2.5 21.0
3 1.5 2.0 2.5
1 0.5 1.0 1.0
12 425-2000 2 1.0 9.5 1.5 11.0 1.5 13.0 1.5 16.0 2.5 30.0
3 1.5 2.0 2.5
ELECTRIC COILS

1 1.0 1.0 1.5 1.5


14 575-3000 2 2.0 9.5 2.0 11.0 2.0 13.0 2.0 16.0 3.0 36.0
3 3.0 3.0 3.0 3.0
1 1.0 1.0 1.5 1.5 Note: The Titus 480V, 3-phase
16 750-4000 2 2.0 9.5 2.0 11.0 2.0 13.0 2.0 16.0 3.0 36.0 electric heat configuration
3 3.0 3.0 3.0 3.0
is 4-wire wye. Contact your
1 1.0 1.0 1.5 1.5
24x16 1800-8000 2 2.0 9.5 2.0 11.0 3.0 13.0 2.0 16.0 4.0 36.0 Titus representative for other
3 3.0 3.0 4.5 3.0 configuration options.
Useful formulas:
cfm x ∆T kW x 3160 kW x 3160
kW= or ∆T= or cfm =
3160 cfm ∆T
Where ∆T = air temperature rise.
M19
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com

ELECTRIC COILS Single/Dual Duct Terminals


SELECTION AND CAPACITIES
Recommended Coil Selection Data

The table at the right describes the maximum recommended


kW capacities and number of stages available for
Titus single duct terminals.

To make a coil selection:


1. Check the desired kW is available in desired unit size
and number of stages. (Required to prevent excessive These requirements established to prevent excessive
watt density and current draw, while taking into account temperature rise caused by low airflow and/or oversized
unit size limitations.) coils. Minimum airflow limits must be within recommended
2. Check the desired minimum airflow limit is within ranges to ensure proper operation and long service life.
recommended operating range. (Ensures velocity For optimum diffuser performance and maximum thermal
pressure will be sufficient to close airflow sensing comfort, coil discharge temperatures should not be more
switch.) than 15°F above desired room temperatures. For proper
3. Multiply desired minimum airflow limit by a factor of coil operation it is recommended that coil discharge
0.0142 and check the result is equal to or greater than temperatures do not to exceed 100°F.
desired kW. (Limits temperature rise across the coil
to 45°F.)

M
kW ≤ cfm x 0.0142

PESV, AESV, DESV / APPLICATION DATA (LYNERGY HEAT)


208V 240V 277V 208V 480V
Inlet Heating cfm 1 Phase 1 Phase 1 Phase 3 Phase 3 Phase
Size Range kW Range kW Range kW Range kW Range kW Range
Min Max Min Max Min Max Min Max Min Max

4 55-225 0.5 3.0 1.0 3.0 1.0 3.0 1.5 3.0 2.5 3.0

5 85-350 0.5 5.0 1.0 5.0 1.0 5.0 1.5 5.0 2.5 5.0

6 105-500 0.5 7.5 1.0 7.5 1.0 7.5 1.5 7.5 2.5 7.5

7 135-650 0.5 9.5 1.0 9.5 1.0 9.5 1.5 9.5 2.5 9.5

8 190-900 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 13.0

9 225-1050 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 16.0

10 300-1400 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 21.0

12 425-2000 0.5 9.5 1.0 11.0 1.0 13.0 1.5 10.5 2.5 25.0

14 575-3000 1.0 9.5 1.0 11.0 1.5 13.0 1.5 10.5 3.0 25.0

16 750-4000 1.0 9.5 1.0 11.0 1.5 13.0 1.5 10.5 3.0 25.0
ELECTRIC COILS

24x16 1800-8000 1.0 9.5 1.0 11.0 1.5 13.0 1.5 10.5 4.0 25.0

Note: The Titus 480V, 3-phase electric heat configuration is 4-wire wye. Contact your
Titus representative for other configuration options.

Useful formulas:
cfm x ∆T kW x 3160 kW x 3160
kW= or ∆T= or cfm =
3160 cfm ∆T
Where ∆T = air temperature rise.

M20
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
SUGGESTED SPECIFICATIONS Single/Dual Duct Terminals
ESV BASIC UNIT ELECTRIC REHEAT COILS
See Section O for control specifications. (Available on pressure independent terminals only)

1. Furnish and install Titus Model (P)(A)(D) ESV single 1. Electric coils shall be supplied and installed on the
duct, variable air volume terminals of the sizes and terminal by the terminal manufacturer. Coils shall be
capacities shown in the plans. ETL listed. Coils shall be housed in an attenuator section
2. Terminals shall be certified under the AHRI Standard integral with the terminal with element grid recessed
880 Certification Program and carry the AHRI Seal. from unit discharge a minimum of 5 inches to prevent
Noncertified terminals may be submitted after testing damage to elements during shipping and installation.
at an independent testing laboratory under conditions Elements shall be 80/20 nickel chrome, supported
selected by the engineering consultant in full compliance by ceramic isolators a maximum of 3.5 inches apart,
with AHRI Standard 880. These tests must be witnessed staggered for maximum thermal transfer and element
by the engineering consultant with all costs to be borne life and balanced to ensure equal output per step.
by the terminal manufacturer. Testing does not ensure The integral control panel shall be housed in a NEMA
acceptance. 1 enclosure with hinged access door for access to all
3. The terminal casing shall be minimum 22-gauge controls and safety devices.
galvanized steel, internally lined with ½-inch dual 2. Electric coils shall contain a primary automatic reset
density insulation which complies with UL 181 and NFPA thermal cutout, a secondary manual reset thermal
90A. All exposed insulation edges shall be coated with cutout, differential pressure airflow switch for proof
NFPA 90A approved sealant to prevent entrainment of flow, and line terminal block. Unit shall include an
of fibers in the airstream. The discharge connection optional integral door interlock type disconnect switch
shall be slip and drive construction for attachment to that will not allow the access door to be opened while
metal ductwork. The casing shall be constructed to hold power is on. Non-interlocking type disconnects are not

M
leakage to the maximum values shown in the Casing acceptable. All individual components shall be UL listed
Leakage table. or recognized.
4. The damper shall be heavy gauge steel with shaft 3. (Optional) Electric coils shall include line fusing, mercury
rotating in Delrin® self-lubricating bearings. Nylon contactors mounted and wired within the control
bearings are not acceptable. Shaft shall be clearly enclosure.
marked on the end to indicate damper position. Stickers
or other removable markings are not acceptable. The OPTIONAL LYNERGY ELECTRIC HEAT
damper shall incorporate a mechanical stop to prevent 1. Proportional electric coils shall be supplied and installed
overstroking and a synthetic seal to limit close-off on the terminal by the terminal manufacturer. Coils shall
leakage to the maximum values shown in the Damper be ETL listed. Coils shall be housed in an attenuator
Leakage table. section integral with the terminal with element grid
5. Actuators shall be capable of supplying at least 35-inch recessed from unit discharge a minimum of 5 inches
lbs. of torque to the damper shaft and shall be mounted to prevent damage to elements during shipping and
externally for service access. Terminals with internal installation. Elements shall be 80/20 nickel chrome,
actuator mounting or linkage connection must include supported by ceramic isolators a maximum of 3½
gasketed access panel, removable without disturbing inches apart, staggered for maximum thermal transfer
ductwork. Casing with access panel shall be constructed and element life, and balanced to ensure equal output
to hold leakage to the maximum values shown in the per step. The integral control panel shall be housed in a
Casing Leakage table. NEMA 1 enclosure with hinged access door for access to
6. At an inlet velocity of 2000 fpm, the minumum static all controls and safety devices.
pressure required to operate any terminal size shall not 2. Electric coils shall contain a primary automatic reset
exceed 0.13-inch wg for the basic terminal. thermal cutout, a secondary replaceable heat limiter per
7. Sound ratings for the terminal shall not exceed ____ element, differential pressure airflow switch for proof
NC at ____ static pressure. Sound performance shall be of flow, and line terminal block. Coil shall include an
AHRI certified. integral door interlock type disconnect switch, which
will not allow the access door to be opened while
power is on. Non-interlocking type disconnects are not
ACCESSORIES
SPECIFICATIONS

acceptable. All individual components shall be UL listed


HOT WATER REHEAT COILS or recognized.
1. Hot water reheat coils shall be enclosed in a minimum
20-gauge galvanized steel casing with slip and drive 3. Heaters shall be equipped with a Lynergy Comfort
construction for attachment to metal ductwork. Coils Controller to control heater coil firing. The control panel
shall be factory installed on the terminal discharge. Fins shall include an interface to control heater coil firing
shall be rippled and corrugated heavy gauge aluminum, in proportion to the ATC signal. The ATC signal shall
mechanically bonded to tubes. Tubes shall be copper connect to low voltage universal signal interface circuitry
with minimum wall thickness of 0.016-inch with male supplied and installed by the terminal manufacturer.
solder header connections. Coils shall be leak tested The universal interface shall allow at least the following
to 300 psi with minimum burst pressure of 1800 psi at seven interface options without additional interface
ambient temperature. Number of coil rows and circuits circuitry.
shall be selected to provide performance as required per
the plans. Coil performance data shall be based on tests
run in accordance with AHRI Standard 410. M21
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com

SUGGESTED SPECIFICATIONS Single/Dual Duct Terminals


3. ATC equipment providers with 0-20mA or 4-20mA FIBRE-FREE LINER
signals shall supply and install a suitable dropping (Substitute the following paragraph 3 for paragraph 3 in the
resistor to convert the current signal to a 0-10VDC ESV Basic Unit Specification.)
signal or 2-10VDC signals:
• PWM heat 3. The terminal casing shall be minimum 22-gauge
• 2 stage heat galvanized steel, internally lined with engineered
• 0-10V / 0-20mA polymer foam insulation which complies to UL181 and
NFPA 90A. Insulation shall be 1½ pound density, closed
• 2-10V /4-20mA cell foam. Exposed fiberglass is not acceptable. The
• Incremental T-stat insulation shall be mechanically fastened to the unit
• Binary casing. The casing shall be constructed to hold leakage
• 3 point floating to the maximum values shown in the Casing Leakage
table.
4. A downstream air temperature limit and control shall
be automatically invoked by adding a downstream air ESV Casing Leakage, cfm
temperature sensor. When invoked, the downstream INLET ∆PS, IN WG
air from the heater shall not exceed an adjustable SIZE 0.5 1.0 2.0 3.0
maximum temperature set point. When the ATC’s call 4, 5, 6 2 3 4 5
for heat is less than 100%, the heater shall control the 7, 8 4 5 7 9
downstream air temperature to a point in proportion 9, 10 4 6 8 10
to the span between the heater’s probable entering 12 5 7 10 12
air temperature and the maximum air temperature set 14 6 9 13 16
point. 16 7 10 14 17

M OPTIONAL STANDARD SCR ELECTRIC HEAT


1. Proportional, modulating electric coils shall be
supplied and installed on the terminal by the terminal
manufacturer. Coils shall be ETL listed. Coils shall
be housed in an attenuator section integral with the
Damper Leakage, cfm
INLET
SIZE
4, 5, 6
1.0
3
∆PS, IN WG
2.0
4
4.0
6
6.0
7
7, 8 3 4 6 7
terminal with element grid recessed from unit discharge 9, 10 3 4 6 7
a minimum of 5 inches to prevent damage to elements 12 3 4 6 7
during shipping and installation. Elements shall be 14 3 5 7 8
80/20 nickel chrome, supported by ceramic isolators a 16 4 5 7 9
maximum of 3.5 inches apart, staggered for maximum
thermal transfer and element life, and balanced to ECOSHIELD
ensure equal output per step. The integral control panel (Substitute the following paragraph 3 for paragraph 3 in the
shall be housed in a NEMA 1 enclosure with hinged ESV Basic Unit Specification.)
access door for access to all controls and safety devices.
2. Electric coils shall contain a primary automatic reset 3. The terminal casing shall be minimum 22 gauge
thermal cutout, a secondary manual reset thermal galvanized steel (20 gauge for fan powered terminals),
cutout, proportional electronic airflow sensor for proof internally lined with ½ in. or 1” matte or foil faced
of flow, and line terminal block. The proportional natural fiber insulation which complies with ASTM C 739
electronic airflow sensor shall be totally independent and NFPA 90A. The liner shall comply with ASTM G21
of the duct static pressure and shall adjust the heater and G22 for fungi and bacterial resistance. All exposed
capacity according to the available airflow. The edges shall be coated with NFPA approved sealant to
heaters shall deliver maximum heating when needed prevent entrainment of fibers in the airstream.
with normal minimum airflow, reduce heating with
lower than minimum airflow and stop heating with no STERI-LOC LINER
airflow. Unit shall include an integral door interlock (Substitute the following paragraph 3 for paragraph 3 in the
type disconnect switch which will not allow the access ESV Basic Unit Specification.)
SPECIFICATIONS

door to be opened while power is on. Non-interlocking


type disconnects are not acceptable. All individual 3. The terminal casing shall be minimum 22-gauge
components shall be UL listed or recognized. galvanized steel, internally lined with a non-porous,
3. Heaters shall be equipped with a proportional SCR sealed liner which complies with UL 181 and NFPA 90A.
controller to modulate the heater load according to the Insulation shall be 4 lb. density. All cut edges must be
temperature control signal. The electronic controller sealed from the airstream using mechanically bonded
shall be compatible with the following input signals: metal barrier strips. Liners made of Mylar, Tedlar, Silane
or woven fiberglass cloth are not acceptable. Insulation
• Variable voltage signal 0-10 VDC shall be equivalent to Titus Steri-Loc or double wall
• Pulse width modulation AC or DC lining is acceptable. The casing shall be constructed
to hold leakage to the maximum values shown in the
Casing Leakage table.

M22
Single/Dual Duct Terminals

www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com


SUGGESTED SPECIFICATIONS

ULTRALOC LINER
(Substitute the following paragraph 3 for paragraph 3 in the
ESV Basic Unit Specification.)

3. The terminal casing shall be minimum 22-gauge


galvanized steel. The units shall be lined with 1-inch
thick matte faced insulation, meeting UL 181 and
NFPA 90A, enclosed between the unit casing and a
non-perforated internal 22-gauge sheet metal cover
extending over the fiberglass insulation, as well as
covering the liner cut edges. The discharge connection
shall be slip and drive construction for attachment to
metal ductwork. The casing shall be constructed to hold
leakage to the maximum values shown in the Casing
Leakage table.

MODEL NUMBER SPECIFICATION

0 Base Unit
Model 1 with Integral Casing

M
Single Duct Attenuator Configuration
Variable 3 with Electric Coil 0R Right Hand
Volume Attenuator Section 0L Left Hand

X ESV X X X XX XXX
P Pneumatic 1 No Inlet Sensor 0 Standard ½” Inlet
E Electric 3 AeroCrossTM 1 1” Size
A Analog Electric Sensor 2 Steri-LocTM (specify)
D Digital Electric 4 UltraLoc
6 No Liner
Example: AESV 3120R 16 9 Fibre-Free
J EcoShield ½”
K EcoShield 1”
L EcoShield Foil ½”
M EcoShield Foil 1”
Analog electronically controlled single duct Lining Type
variable volume terminal, with multi-point sensor,
integral attenuator, Steri-Loc™ lining, right hand
controls, 16” inlet size.

SPECIFICATIONS

M23
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com

SUGGESTED SPECIFICATIONS Single/Dual Duct Terminals


AHRI Directory Of Certified Performance
Titus is a charter member company and current participant PESV, AESV, DESV
in the AHRI Directory of Certified Performance. This volun-
tary certification program was developed by participating Radiated Sound Discharge Sound
Inlet Rated Min Power Power
manufacturers in conjunction with the former Air-Condi- Size CFM ∆Ps
tioning and Refrigeration Institute (ARI) in the 1990’s. It is 2 3 4 5 6 7 2 3 4 5 6 7
currently administrated by the Air-Conditioning, Heating, 04 150 0.04 60 57 46 41 40 37 68 64 59 54 54 49
and Refrigeration Institute (AHRI). The purpose of this
program is to provide for the independent verification of 05 250 0.03 62 59 49 42 41 37 69 64 60 56 55 50
manufacturers’ published performance data. Only participat- 06 400 0.13 63 61 52 44 42 38 70 69 64 60 57 52
ing products are authorized to bear the AHRI VAV Certifica- 07 550 0.10 64 59 53 47 43 34 69 70 63 59 56 51
tion Mark. Certified data may be viewed and downloaded at
08 700 0.02 65 60 53 47 47 45 72 71 63 58 56 52
www.ahrinet.org .
09 900 0.05 64 58 53 47 45 38 73 68 63 59 57 54
In order to participate in this program, member companies 10 1100 0.01 67 62 57 55 54 43 74 70 65 63 60 55
pay annual dues based on sales volume, submit published
12 1600 0.01 66 62 59 53 50 44 75 73 68 64 62 58
performance data for all applicable model types, and agree
to provide a number of randomly selected product samples 14 2100 0.04 66 62 55 53 50 46 72 68 66 63 63 59
for annual rounds of independent testing at the manufactur- 16 2800 0.03 66 61 54 50 50 45 74 69 66 64 62 57
ers’ expense. All verification testing is conducted in accor-
40 5300 0.06 79 74 72 68 67 64 85 80 77 72 73 69
dance with ASHRAE Standard 130 ‘Methods of Testing Air

M
Terminal Units’. These tests are conducted to verify that a
manufacturer’s published certified ratings are within the test
tolerances outlined in AHRI Standard 880 ‘Performance Rat-
ing of Air Terminals’. Any failure to demonstrate the certified
performance is punished by additional testing requirements,
mandatory performance re-rating, monetary penalties and
possible expulsion from the Certified Directory.
Product samples provided for certification testing are
standard production units with standard ½ in dual density
fiberglass lining (unless otherwise specified) and no optional
appurtenances such as add-on attenuators or heating/cool-
ing coils. The certified ratings are measured at the standard
operating points under the following test conditions:

PESV, EESV, AESV, DESV


• Rated airflow (cfm) – Based on an
inlet velocity of 2000 fpm.
• Rated Min ∆Ps (in wg) – Minimum static
pressure drop from the unit inlet to discharge
at rated airflow with damper full open.
• Rated ∆Ps (in wg) – A static pressure drop of
1.5 in wg from unit inlet to discharge.
• Rated sound power by octave band (dB, re 10-12 watts)
– Radiated and discharge sound performance conducted
SPECIFICATIONS

in a reverberation room that meets both the broadband


and pure tone qualifications of AHRI Standard 220.

M24
Single/Dual Duct Terminals

www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com


Dual Duct Design Features
TITUS DUAL DUCT TERMINAL - LEADERSHIP IN A RE-EMERGING TECHNOLOGY!
The concern for IAQ has led to renewed interest in the Titus dual duct terminals are available in three styles. In
benefits of dual duct systems. Dual duct systems are those instances where no blending of airstreams is required,
an ideal vehicle for alternative ventilation strategies and the EDV without the integral attenuator assembly can be an
humidity control. Additionally, total filtration of all air effective choice.
delivered to the zone is possible. Titus dual duct terminals
provide high performance and value, making them the When blending of hot and cold supply air is needed
preferred selection for these applications. for accurate temperature control with minimum flow
requirements, the EDV or EDC with integral attenuator
Titus dual duct terminals vary the airflow individually should be used.
between hot and cold inlets for highly accurate temperature
control. The attenuator reduces discharge sound levels and provides
some mixing benefit. An optional mixing baffle is available
As the ratio of hot and cold air is critical in most for use with the attenuator to provide maximum blending
applications, pressure independent controls are used with a of hot and cold airstreams. Less than 1°F temperature
separate velocity control loop to each inlet. variation is provided at the discharge with a 10°F inlet
temperature differential!

DEDV WITH OPTIONAL MDV WITH INTEGRAL MIXING


EDV NON MIXING MIXING BAFFLE ATTENUATOR, DMDV SHOWN

All Titus dual duct terminals are available with Fibre-Free and other lining options.

The Titus MDV/MDC Dual Duct Terminals have been 20°F inlet temperature differential. Additional ductwork is
specially designed for those applications where comfort not required downstream to achieve proper mixing, allowing
levels are critical, as in hospitals, research facilities, and for immediate take-off to diffusers. This is also beneficial for
other institutional applications. installations with space limitations.
DESIGN FEATURES

Like the EDV/EDC, the MDV/MDC terminals use separate The tightly sealed casing typically allows less than 1 percent
pressure independent velocity control loops for each inlet, leakage of conditioned air to the space at 1.5 inches wg.
rather than a single velocity controller for discharge volume differential static pressure, making this one of the most
control only. This provides superior temperature control energy efficient dual duct terminals. The dampers are the
during blending, as each inlet can compensate for duct improved Titus low leakage design.
pressure changes without affecting the other.
All Titus dual duct terminals are also available with
The unique internal mixing baffle design provides EcoShield, Fibre-Free and Steri-Loc lining options. Specify
for exceptional mixing characteristics. Less than 1°F the MDV/MDC and you will be providing the best performing
temperature variation is provided at the discharge with a dual duct terminal available.

M25
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com

DUAL DUCT CONTROL STRATEGIES Single/Dual Duct Terminals


VAV, Zero Minimum - non-blending
In cooling mode, as temperature approaches setpoint, cold airflow modulates from Max CLG*
maximum to zero flow. As room temperature drops below setpoint, hot airflow
modulates from zero to maximum. Heating and cooling maximum flow rates can be Max HTG

different. A deadband may be utilized.

cfm Increase
As this is a non-blending application, a mixer/attenuator section is not required.
For detailed information on specific control types, refer to the following pages in
Section S:
Room Temperature Increase

Pneumatic: O20 Digital: O6 Model: EDV

VAV, Minimum Mix Equal to Maximum HTG - blending


In cooling mode, as temperature approaches setpoint, cold air modulates from
Max CLG

maximum to a minimum mix flow rate. As temperature continues to drop, hot


airflow modulates open as cold airflow closes, maintaining a minimum total flow
rate. Lower heating flow rates require unequal inlet sizes to maintain control. A Max HTG

cfm Increase
mixer/attenuator section is required.

Pneumatic: O20 Digital: O6 Model: EDV or MDV

M
Room Temperature Increase

VAV, Minimum Mix, Unequal Maximum Flows - blending


Similar in cooling mode to the sequence above, when entering the heating mode a Max HTG Max CLG

flow rate higher than the minimum mix is employed. Maximum flow rates may be
close enough that equal inlet sizes may be used. A mixer/attenuator section
is required.
cfm Increase

Pneumatic: O20 Digital: O6 Model: EDV or MDV

Room Temperature Increase

Constant Volume Discharge - blending


In this sequence cooling and heating maximum flow rates are the same and
Max HTG Max CLG

minimum mix flow rates are the same as maximums. The result is a constant
airflow over the entire cooling and heating range. A mixer/attenuator section is
required.
cfm Increase

Pneumatic: O20 Digital: O6 Model: EDC or MDC


CONTROL STRATEGIES

Room Temperature Increase

Optional Censor Location Configuration


For blending applications with integral mixer/attenuator. Multi-point velocity sensors
are available in four different configurations to match any application and control 3A Discharge 3B
requirement. Configurations 3B and 3C are to match hot or cold inlet
control requirements. Hot Cold Hot Cold

Pneumatic: O20 Digital: O6


3C 3D

Hot Cold Inlet Hot Cold

= Sensor Location
M26
Single/Dual Duct Terminals

www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com


Dual Duct without Attentuator
EDV
Available Models:
PEDV • Pneumatic • Standard matte faced insulation
DEDV • Digital for maximum thermal and
Electronic acoustic performance.

EDV
• Standard 22 gauge casing with slip
FOR NON-BLENDING APPLICATIONS and drive discharge connection.
ONLY
• Controls supplied by Titus are
• Standard AeroCrossTM multi-point
factory calibrated for quicker
center averaging velocity sensors
start-up.
in each inlet for accurate flow
control.
PEDV - Basic Unit with Controls
4½” W 4½” M L
Pneumatic
Actuator

M
H D Discharge
F

A
Control Cover
(optional)

DEDV - Basic Unit with Controls


W M L
F G

12¼” D H
Discharge

A
Control 18” Slip & Drive
F
6½” Enclosure Cleat Connection

Inlet cfm F
A D G H L M W
Size Range PEDV DEDV
4 0-225 12⅛ 3⅞ 1⅞ 2⅛ 7⅜ 8 15½ 5⅜ 24⅛
5 0-350 12⅛ 4⅞ 1⅞ 2⅛ 7⅜ 8 15½ 5⅜ 24⅛
6 0-500 12⅛ 5⅞ 1⅞ 2⅛ 7⅜ 8 15½ 3⅜ 24⅛
7 0-650 12⅛ 6⅞ ⅞ 1⅛ 7⅜ 10 15½ 3⅜ 24⅛
8 0-900 12⅛ 7⅞ ⅞ 1⅛ 7⅜ 10 15½ 3⅜ 24⅛
EDV

9 0-1050 14⅛ 8⅞ - - 5⅜ 12½ 15½ 3⅜ 28⅛


10 0-1400 14⅛ 9⅞ - - 5⅜ 12½ 15½ 3⅜ 28⅛
12 0-2000 16⅛ 11⅞ - - 5⅜ 15 15½ 3⅜ 32⅛
14 0-3000 20⅛ 13⅞ - - 3⅜ 17½ 15½ 3⅜ 40⅛
16 0-4000 24⅛ 15⅞ - - 3⅜ 18 15½ 3⅜ 48⅛

All dimensions are in inches.


M27
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com

PERFORMANCE DATA Single/Dual Duct Terminals


PEDV, DEDV WITHOUT ATTENUATOR - RADIATED SOUND PERFORMANCE

Octave Band Sound Power, Lw


Min
Size CFM 1.0” ∆Ps 1.5” ∆Ps 2.0” ∆Ps
∆Ps
2 3 4 5 6 7 NC 2 3 4 5 6 7 NC 2 3 4 5 6 7 NC
100 0.02 52 48 39 36 35 31 15 53 50 41 37 37 34 17 55 51 43 38 39 36 18
125 0.03 55 52 42 38 36 32 20 57 54 44 40 39 36 22 58 55 45 41 40 38 23
4 150 0.04 58 55 44 40 38 34 23 60 57 46 41 40 37 25 61 58 47 42 42 39 27
175 0.06 61 58 46 42 39 34 27 63 59 48 43 41 38 28 64 61 49 44 43 40 30
200 0.08 63 60 47 43 40 35 29 65 62 49 44 42 38 31 66 63 51 45 44 41 33
150 0.01 53 49 41 36 35 30 16 55 51 43 38 37 33 18 57 53 45 39 39 35 21
200 0.02 56 53 44 38 37 32 21 59 55 46 40 40 35 23 60 57 48 42 41 37 25
5 250 0.03 59 56 46 40 39 34 24 62 59 49 42 41 37 28 63 61 51 44 43 39 30
300 0.04 62 59 48 42 41 35 28 64 61 50 44 43 38 30 65 63 52 45 44 40 33
350 0.06 63 61 49 43 42 36 30 66 63 52 45 44 39 33 67 65 54 47 45 41 35
300 0.07 59 54 45 39 37 33 22 61 57 48 41 39 36 25 63 59 50 42 41 38 28
350 0.10 60 57 47 41 38 34 25 62 59 50 43 40 37 28 64 62 52 44 42 39 31
6 400 0.13 61 58 49 42 39 35 27 63 61 52 44 42 38 30 65 63 54 46 43 40 33
450 0.16 62 60 50 44 40 36 29 64 63 53 46 43 39 33 66 65 55 47 45 41 35
500 0.20 63 61 51 45 41 37 30 65 64 54 47 44 40 34 67 67 56 49 46 42 37
450 0.07 61 54 48 42 38 30 23 62 57 51 45 41 33 25 63 59 53 46 43 35 28
500 0.09 62 55 49 43 39 30 24 63 58 52 46 42 34 27 64 60 54 48 44 36 29
7 550 0.10 63 57 50 45 40 31 25 64 59 53 47 43 34 28 66 62 55 49 45 37 31
600 0.12 63 58 51 46 41 31 27 65 61 54 48 44 35 30 66 63 56 50 46 37 33

M
650 0.15 64 59 52 47 41 32 28 65 62 55 49 44 35 31 66 64 57 51 46 38 34
600 0.02 62 55 49 43 43 39 24 64 58 52 46 45 44 27 65 60 54 47 47 47 29
650 0.02 63 56 50 44 44 40 25 65 59 53 47 46 45 28 66 61 55 48 48 48 30
8 700 0.02 63 57 50 45 44 41 25 65 60 53 47 47 45 29 67 62 56 49 49 48 31
750 0.02 64 58 51 46 45 41 27 66 61 54 48 48 46 30 67 63 56 50 50 49 33
800 0.03 65 59 52 47 46 42 28 66 62 55 49 48 47 31 68 64 57 51 50 50 34
800 0.04 61 53 49 42 40 35 23 62 57 52 46 44 38 26 63 59 55 48 47 40 29
850 0.04 61 54 49 43 41 35 23 63 58 53 46 45 38 27 64 60 55 49 47 40 29
9 900 0.05 62 55 50 43 41 35 24 64 58 53 47 45 38 27 65 61 56 49 48 40 30
950 0.06 62 56 50 43 42 36 24 64 59 54 47 45 38 28 65 62 56 49 48 40 31
1000 0.06 63 56 50 44 42 36 25 65 60 54 47 46 39 29 66 62 57 50 48 40 31
900 0.01 63 57 53 50 48 37 27 65 60 57 53 52 41 31 67 63 59 56 54 44 34
1000 0.01 64 58 54 51 49 38 28 66 61 57 54 53 42 31 67 64 59 56 55 45 34
10 1100 0.01 65 58 54 52 50 39 28 67 62 57 55 54 43 31 68 64 60 57 56 46 35
1200 0.01 65 59 54 53 51 40 28 67 63 58 56 55 44 33 69 65 60 58 57 47 35
1300 0.01 66 60 55 53 52 41 29 68 63 58 56 55 45 33 69 66 61 58 58 48 36
1200 0.01 62 56 52 47 43 37 26 64 59 56 50 46 41 30 66 61 58 53 49 43 32
1400 0.01 63 57 54 48 45 39 28 65 60 57 52 48 42 31 67 63 60 54 51 45 35
12 1600 0.01 64 59 55 49 46 40 29 66 62 59 53 50 44 34 68 64 61 55 52 47 36
1800 0.01 65 60 56 50 48 41 30 67 63 60 54 51 45 35 69 65 62 56 54 48 37
2000 0.01 66 61 57 51 49 43 31 68 64 61 55 52 47 36 69 67 63 57 55 49 38
1500 0.02 60 56 50 48 45 41 24 62 59 53 51 48 45 28 64 61 55 53 50 47 30
1800 0.03 62 58 51 49 46 42 27 64 60 54 52 49 45 29 66 63 56 54 51 48 33
14 2100 0.04 63 59 52 50 47 43 28 66 62 55 53 50 46 31 67 64 58 55 52 49 34
2400 0.05 64 60 53 51 48 43 29 67 63 56 54 51 47 33 69 65 58 56 53 49 35
2700 0.06 66 61 54 52 49 44 30 68 64 57 55 52 47 34 70 66 59 57 54 50 36
2000 0.02 59 53 47 45 44 38 21 61 56 50 47 47 41 24 63 58 52 49 49 44 27
PERFORMANCE DATA

PERFORMANCE DATA
2400 0.02 61 56 49 47 46 39 24 64 59 52 49 49 43 28 65 61 54 51 51 46 30
16 2800 0.03 63 58 51 48 47 41 27 66 61 54 50 50 45 30 67 63 55 52 52 48 33
3200 0.04 65 60 52 50 49 42 29 67 62 55 52 52 46 31 69 64 57 53 54 49 34
3600 0.05 66 61 54 51 50 44 30 69 64 56 53 53 48 34 71 66 58 55 55 50 36

• Radiated sound is the noise transmitted • All performance based on tests conducted in
through the unit casing. accordance with ASHRAE 130-2008 and AHRI 880-2008.
• Min ∆Ps is the static pressure drop from the unit inlet • All NC levels determined using AHRI 885-2008
to the unit outlet with the cold damper full open. Appendix E. See Terminal Unit Engineering Guidelines.
• Sound power levels are in dB, ref 10-12 watts. • Dash (-) in space denotes NC value less than NC10.
• Sound performance based on units lined with • Only highlighted data points are AHRI certified. See
standard dual density fiberglass lining. page M38 for AHRI Certified Performance Listings.

M28
Single/Dual Duct Terminals

www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com


PERFORMANCE DATA

PEDV, DEDV WITHOUT ATTENUATOR - DISCHARGE SOUND PERFORMANCE

Octave Band Sound Power, Lw


Min
Size CFM 1.0” ∆Ps 1.5” ∆Ps 2.0” ∆Ps
∆Ps
2 3 4 5 6 7 NC 2 3 4 5 6 7 NC 2 3 4 5 6 7 NC
100 0.02 63 56 50 46 47 41 18 64 58 53 49 50 46 19 65 59 55 51 53 49 20
125 0.03 65 60 53 49 49 43 20 66 61 56 52 52 47 22 67 62 58 54 55 51 23
4 150 0.04 67 62 56 51 50 44 23 68 64 59 54 54 49 24 68 65 60 56 57 52 24
175 0.06 68 65 58 53 51 45 24 69 66 61 56 55 50 25 70 68 63 58 58 53 28
200 0.08 69 67 60 55 53 46 27 70 69 62 58 56 51 29 71 70 64 60 59 54 30
150 0.01 62 55 51 47 47 42 17 64 57 54 50 51 46 19 65 59 57 52 53 49 20
200 0.02 65 58 55 51 49 44 20 67 61 58 53 53 48 23 68 63 60 55 55 51 24
5 250 0.03 67 62 57 53 51 45 23 69 64 60 56 55 50 25 70 66 62 58 57 53 27
300 0.04 69 64 59 55 53 46 22 70 67 62 58 56 51 25 71 69 65 60 59 54 28
350 0.06 70 66 61 57 54 47 24 72 69 64 60 57 52 28 73 71 66 61 60 55 30
300 0.07 64 62 58 54 51 46 20 67 65 61 57 54 50 23 69 67 63 58 56 53 25
350 0.10 66 64 60 56 52 47 22 68 67 63 59 55 51 25 70 69 65 60 58 54 28
6 400 0.13 67 66 61 58 53 48 24 70 69 64 60 57 52 28 71 71 66 62 59 55 30
450 0.16 68 67 63 59 54 49 25 71 70 66 62 58 53 29 73 73 68 63 60 56 33
500 0.20 69 69 64 61 55 50 28 72 72 67 63 59 54 31 74 74 69 65 61 57 34
450 0.07 67 63 58 54 51 46 21 68 67 60 56 54 49 25 70 69 62 58 56 52 28
500 0.09 67 65 59 56 52 47 23 69 68 62 58 55 50 27 70 71 63 59 57 53 30
7 550 0.1 68 66 60 57 53 48 24 69 70 63 59 56 51 29 71 72 64 60 58 54 31
600 0.12 68 67 61 58 54 48 25 70 71 63 60 57 52 30 71 73 65 61 59 55 33
28 70 72 64 61 58 53 31 34

M
650 0.15 68 69 62 59 55 49 72 74 66 62 59 55
600 0.02 69 66 59 55 52 47 24 71 69 61 56 55 51 28 72 72 63 57 57 54 31
650 0.02 70 67 60 56 53 47 25 71 70 62 57 55 51 29 72 73 64 58 57 54 33
8 700 0.02 70 68 60 56 53 48 27 72 71 63 58 56 52 30 73 74 64 59 58 55 34
750 0.02 70 69 61 57 54 48 27 72 72 63 58 56 52 30 73 75 65 60 58 55 34
800 0.03 71 70 62 58 54 49 28 72 73 64 59 57 53 31 74 75 66 60 59 56 34
800 0.04 70 64 60 57 54 49 21 71 67 62 59 57 53 24 72 69 64 60 59 56 27
850 0.04 70 65 60 57 54 50 22 72 68 62 59 57 54 25 73 70 64 61 59 56 28
9 900 0.05 71 66 61 57 55 50 23 73 68 63 59 57 54 25 74 70 65 61 59 57 28
950 0.06 72 66 61 58 55 50 23 73 69 63 60 58 54 27 74 71 65 61 60 57 29
1000 0.06 72 67 61 58 55 50 24 74 70 64 60 58 54 28 75 72 65 62 60 57 30
900 0.01 71 65 61 59 55 50 22 72 68 64 61 58 54 25 73 71 66 63 61 57 29
1000 0.01 72 66 62 60 56 51 23 73 69 65 62 59 55 27 74 72 67 64 61 57 30
10 1100 0.01 73 67 63 61 56 51 24 74 70 65 63 60 55 28 75 72 67 65 62 58 30
1200 0.01 73 68 63 61 57 52 25 75 71 66 64 60 56 29 76 73 68 66 63 59 31
1300 0.01 74 68 64 62 58 53 25 75 72 67 65 61 56 30 76 74 68 66 63 59 33
1200 0.01 71 67 63 59 57 52 24 73 70 65 62 60 56 28 74 72 67 64 62 59 30
1400 0.01 72 69 65 61 59 53 27 74 72 67 63 61 57 30 75 74 69 65 63 60 33
12 1600 0.01 73 70 66 62 59 55 28 75 73 68 64 62 58 31 76 75 70 66 64 61 34
1800 0.01 74 71 67 63 60 56 29 75 74 70 65 63 59 33 76 76 71 67 65 62 35
2000 0.01 74 72 68 64 61 56 30 76 75 71 66 64 60 34 77 77 72 68 66 63 36
1500 0.02 68 62 61 59 57 53 18 70 66 63 62 62 59 23 72 68 65 65 65 62 25
1800 0.03 69 64 62 59 58 53 21 71 67 65 63 62 59 24 73 70 67 65 65 63 28
14 2100 0.04 70 65 64 60 58 54 22 72 68 66 63 63 59 25 74 71 68 66 66 63 29
2400 0.05 71 66 65 60 59 54 23 73 69 68 64 63 59 27 74 72 69 66 66 63 30
2700 0.06 72 67 66 61 59 54 24 74 70 69 64 63 60 28 75 73 70 67 66 63 31
2000 0.02 68 62 60 58 56 51 18 70 65 62 61 59 54 22 71 67 63 63 61 57 24
PERFORMANCE DATA

PERFORMANCE DATA
2400 0.02 70 65 63 60 58 52 22 72 67 64 62 61 56 24 73 69 66 64 62 58 27
16 2800 0.03 72 67 65 61 59 54 24 74 69 66 64 62 57 27 75 71 68 66 64 60 29
3200 0.04 73 68 66 62 60 55 25 75 71 68 65 63 59 29 76 72 70 67 65 61 30
3600 0.05 74 70 68 63 61 56 28 76 72 70 66 64 60 30 78 74 71 68 66 62 33

• Discharge sound is the noise emitted from the • All performance based on tests conducted in
unit discharge into the downstream ductwork. accordance with ASHRAE 130-2008 and AHRI 880-2008.
• Min ∆Ps is the static pressure drop from the unit inlet • All NC levels determined using AHRI 885-2008
to the unit outlet with the cold damper full open. Appendix E. See Terminal Unit Engineering Guidelines.
• Sound power levels are in dB, ref 10-12 watts. • Dash (-) in space denotes NC value less than NC10.
• Sound performance based on units lined with • Only highlighted data points are AHRI certified. See
standard dual density fiberglass lining. page M38 for AHRI Certified Performance Listings.

M29
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com

Dual Duct with Attentuator Single/Dual Duct Terminals


EDV/EDC
Available Models:
PEDV/PEDC • Pneumatic • Standard matte faced insulation
DEDV • Digital for maximum thermal and
Electronic acoustic performance.

EDV
• Standard 22-gauge casing with slip
FOR BLENDING OR NON-BLENDING and drive discharge connection.
APPLICATIONS
• Controls supplied by Titus are
• Standard AeroCrossTM multi-point
factory calibrated for quicker
center averaging velocity sensors
start-up.
in four location combinations to
match any control requirement.

PEDV - Basic Unit with Controls


G L 4” H

M
D F

A Discharge W E

D
Slip & Drive
Cleat Connection

Controller
4½”

Pneumatic Actuator

DEDV - Basic Unit with Controls


G L 4" H

F
D

A Discharge W E

D
Slip and Drive
Duct Connection
6½"

18"
K K
12¼"

Inlet cfm PEDV DEDV


A D E F G H L W
Size Range J K
EDV, EDC

4 0-225 8⅞ 3⅞ 513/16 513/16 5⅜ 8⅛ 19⅛ 19 1⅞ 2


5 0-350 8⅞ 4⅞ 513/16 513/16 5⅜ 8⅛ 19⅛ 19 1⅞ 2
6 0-500 8⅞ 5⅞ 513/16 513/16 3⅜ 8⅛ 19⅛ 19 1⅞ 2
7 0-650 10⅞ 6⅞ 71/16 81/16 6¾ 10⅛ 23⅛ 23 ⅞ 1
8 0-900 10⅞ 7⅞ 71/16 81/16 3⅜ 10⅛ 23⅛ 23 ⅞ 1
9 0-1050 12⅞ 8⅞ 101/16 111/16 6¾ 12⅝ 27⅛ 27 - -
10 0-1400 12⅞ 9⅞ 101/16 111/16 3⅜ 12⅝ 27⅛ 27 - -
12 0-2000 14⅞ 11⅞ 111/16 131/16 3⅜ 15⅛ 31⅛ 31 - -
14 0-3000 16⅞ 13⅞ 129/16 161/16 3⅜ 18 35⅛ 35 - -
16 0-4000 18⅞ 15⅞ 151/16 161/16 3⅜ 18 38⅛ 38 - -
M30 All dimensions are in inches.
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com
PERFORMANCE DATA Single/Dual Duct Terminals
PEDV, PEDC, DEDV WITH INTEGRAL ATTENUATOR AND MIXING BAFFLES / RADIATED SOUND PERFORMANCE

Octave Band Sound Power, Lw


Min
Size CFM 1.0” ∆Ps 1.5” ∆Ps 2.0” ∆Ps
∆Ps
2 3 4 5 6 7 NC 2 3 4 5 6 7 NC 2 3 4 5 6 7 NC
100 0.18 46 46 37 31 29 23 12 49 49 39 33 33 28 16 52 51 41 35 35 31 18
125 0.29 48 49 40 33 31 25 16 52 52 42 36 35 29 20 54 53 44 38 37 33 21
4 150 0.41 50 51 42 35 33 26 18 54 53 44 38 36 31 21 56 55 46 40 39 34 23
175 0.56 52 52 44 37 34 28 20 55 55 46 39 38 32 23 58 57 48 41 40 36 25
200 0.73 53 54 45 38 36 29 22 57 57 48 41 39 33 25 59 59 49 43 41 37 28
150 0.17 48 45 38 32 32 25 11 51 48 41 35 35 29 15 53 50 43 36 36 32 17
200 0.30 51 48 42 35 35 28 15 54 51 44 37 37 32 18 56 54 46 39 39 35 22
5 250 0.47 53 51 44 37 37 31 18 56 54 47 40 39 35 22 58 56 49 41 41 38 24
300 0.67 55 53 47 39 38 33 21 58 56 49 41 41 37 24 60 58 51 43 43 40 27
350 0.92 57 54 48 40 40 35 22 60 58 51 43 43 39 27 62 60 53 45 44 42 29
300 0.51 51 51 43 38 36 30 18 54 54 46 40 39 34 22 57 57 48 42 41 37 25
350 0.70 52 53 44 39 37 31 21 55 56 47 42 40 35 24 57 58 50 44 42 39 27
6 400 0.91 52 54 46 41 38 32 22 55 57 49 43 41 37 25 57 60 51 45 44 40 29
450 1.15 NA NA NA NA NA NA NA 55 58 50 45 42 38 27 57 61 52 47 45 41 30
500 1.42 NA NA NA NA NA NA NA 55 60 51 46 43 39 29 58 62 53 48 45 42 31
450 0.35 59 52 46 41 40 35 20 61 56 49 43 43 40 24 63 58 51 45 45 43 27
500 0.44 60 53 47 42 41 36 22 62 57 50 44 44 41 25 64 59 52 46 46 44 28
7 550 0.53 61 54 48 43 41 37 23 63 57 51 45 45 41 25 65 60 53 47 47 45 29
600 0.63 62 55 49 43 42 37 24 64 58 52 46 45 42 27 65 61 54 48 48 45 30

M
650 0.74 62 56 49 44 43 38 24 65 59 52 47 46 43 28 66 61 55 48 48 46 30
600 0.40 58 52 45 39 37 35 20 60 57 49 42 40 39 25 62 60 51 44 42 42 29
650 0.47 58 53 46 39 38 36 21 61 58 49 42 41 40 27 63 61 52 44 43 43 30
8 700 0.55 59 54 46 40 38 36 22 61 59 50 43 41 40 28 63 62 53 45 43 43 31
750 0.63 59 55 47 41 39 37 23 62 60 51 44 41 41 29 64 63 53 46 43 44 33
800 0.71 60 56 47 41 39 38 24 62 60 51 44 42 42 29 64 64 54 46 44 44 34
800 0.18 62 53 45 41 42 40 24 64 56 49 44 45 45 27 66 59 52 47 48 48 29
850 0.21 63 53 45 42 42 40 25 65 57 49 45 46 45 28 66 59 52 47 48 48 29
9 900 0.23 63 54 46 42 42 40 25 66 57 50 45 46 45 29 67 60 52 47 48 48 31
950 0.26 64 54 46 42 43 40 27 66 58 50 46 46 45 29 68 61 53 48 49 49 32
1000 0.29 65 55 46 43 43 41 28 67 58 50 46 46 45 31 68 61 53 48 49 49 32
900 0.25 60 52 44 40 38 37 22 63 55 47 42 41 39 25 65 58 49 44 42 41 28
1000 0.31 60 52 45 41 39 37 22 63 56 48 43 41 40 25 66 59 50 44 43 42 29
10 1100 0.38 61 53 46 41 40 38 23 64 57 49 43 42 41 27 66 60 51 45 44 43 29
1200 0.45 61 54 47 42 40 39 23 64 58 49 44 42 42 27 66 61 51 46 44 44 30
1300 0.53 61 55 47 42 40 39 23 65 59 50 45 43 42 28 67 61 52 46 44 44 31
1200 0.25 64 56 52 50 53 52 27 68 59 55 54 57 57 32 70 62 58 57 60 61 34
1400 0.33 65 57 54 51 53 52 28 68 61 57 55 58 57 32 70 63 59 58 61 61 34
12 1600 0.44 65 58 55 52 54 52 29 68 62 58 55 58 57 32 71 64 60 58 61 61 36
1800 0.55 66 59 56 52 54 52 30 69 63 59 56 58 57 34 71 65 61 59 61 61 36
2000 0.68 66 60 57 53 54 52 31 69 64 60 56 58 58 35 72 66 62 59 62 61 37
1500 0.18 62 54 47 42 43 43 24 66 57 50 44 46 47 29 68 60 52 46 47 49 32
1800 0.25 63 56 49 43 44 44 25 67 59 52 46 47 48 31 69 61 54 47 49 50 33
14 2100 0.34 64 57 51 45 45 45 27 67 60 53 47 48 49 31 70 63 55 49 49 51 34
2400 0.45 65 58 52 46 46 46 28 68 62 55 48 49 49 32 70 64 57 50 50 52 34
2700 0.57 65 60 53 47 47 47 29 69 63 56 49 49 50 33 71 65 58 51 51 53 36
2000 0.21 65 55 50 45 47 47 28 68 59 52 47 50 51 32 70 61 53 49 51 53 34
PERFORMANCE DATA
2400 0.30 66 57 52 46 48 47 29 69 60 54 48 50 51 33 71 62 56 50 52 53 36
16 2800 0.40 66 58 54 47 48 47 29 70 61 56 50 51 51 34 72 64 58 51 53 53 37
3200 0.53 67 59 56 48 49 47 31 70 62 58 51 51 51 34 73 65 59 52 53 53 38
3600 0.67 68 60 57 49 49 47 32 71 63 59 51 52 51 36 73 66 61 53 54 53 38

• Radiated sound is the noise transmitted • All performance based on tests conducted in
through the unit casing. accordance with ASHRAE 130-2008 and AHRI 880-2008.
• Min ∆Ps is the static pressure drop from the unit inlet • All NC levels determined using AHRI 885-2008
to the unit outlet with the cold damper full open. Appendix E. See Terminal Unit Engineering Guidelines.
• Sound power levels are in dB, ref 10-12 watts. • Dash (-) in space denotes NC value less than NC10.
• Sound performance based on units lined with • Only highlighted data points are AHRI certified. See
standard dual density fiberglass lining. page M38 for AHRI Certified Performance Listings.

M31
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com

PERFORMANCE DATA Single/Dual Duct Terminals


PEDV, PEDC, DEDV WITH INTEGRAL ATTENUATOR AND MIXING BAFFLES / DISCHARGE SOUND PERFORMANCE

Octave Band Sound Power, Lw


Size CFM Min ∆Ps 1.0” ∆Ps 1.5” ∆Ps 2.0” ∆Ps
2 3 4 5 6 7 NC 2 3 4 5 6 7 NC 2 3 4 5 6 7 NC
100 0.18 55 52 47 44 44 36 - 56 53 48 45 45 38 10 57 54 49 46 46 39 11
125 0.29 58 55 50 47 47 40 12 59 56 51 48 48 41 14 60 57 52 49 49 43 15
4 150 0.41 60 58 53 49 49 43 16 62 59 54 50 50 45 17 63 60 55 51 52 46 18
175 0.56 62 60 55 51 51 46 18 64 61 56 52 52 47 20 65 62 57 53 54 49 21
200 0.73 64 62 57 53 53 48 21 66 63 58 54 54 50 22 67 64 59 55 55 51 23
150 0.17 53 51 46 43 45 40 - 55 53 49 45 48 43 10 56 55 50 47 49 45 12
200 0.30 57 55 50 47 48 44 12 59 57 53 49 50 47 15 60 59 54 50 52 49 17
5 250 0.47 60 58 53 49 50 47 16 62 61 56 51 53 50 20 63 62 57 53 54 52 21
300 0.67 62 61 56 51 52 50 18 64 63 58 53 54 53 21 65 65 60 55 56 55 23
350 0.92 64 63 58 53 54 52 21 66 65 60 55 56 55 23 67 67 62 56 58 57 25
300 0.51 56 56 51 49 50 48 12 59 59 54 51 53 51 16 61 61 56 52 55 54 18
350 0.70 57 57 53 50 52 49 14 60 60 56 52 54 53 17 63 62 58 54 56 55 20
6 400 0.91 58 58 55 52 53 51 15 61 61 57 54 55 54 18 64 64 60 55 57 56 22
450 1.15 NA NA NA NA NA NA NA 62 62 59 55 56 55 20 64 65 61 56 58 58 23
500 1.42 NA NA NA NA NA NA NA 63 63 60 56 57 56 21 65 66 62 57 59 59 24
450 0.35 60 60 53 49 51 48 17 62 62 56 52 54 51 20 64 64 58 53 56 54 22
500 0.44 62 61 55 50 52 49 18 64 63 57 53 55 53 21 65 65 59 54 57 55 23
7 550 0.53 63 62 56 51 53 50 20 65 64 58 53 56 54 22 66 66 60 55 57 56 24
600 0.63 64 63 57 52 54 52 21 66 66 59 54 56 55 24 67 67 61 56 58 58 25

M
650 0.74 65 64 58 53 55 53 22 67 67 60 55 57 56 25 68 68 62 57 59 59 27
600 0.40 61 61 55 51 53 51 18 63 64 57 53 55 54 22 65 67 59 55 57 57 25
650 0.47 62 62 55 52 54 52 20 64 65 58 54 56 55 23 65 67 60 56 58 57 25
8 700 0.55 62 63 56 53 54 52 21 64 66 59 55 57 56 24 66 68 61 56 58 58 27
750 0.63 63 63 57 53 55 53 20 65 67 60 55 57 57 24 67 69 62 57 59 59 27
800 0.71 63 64 57 54 55 54 21 65 67 60 56 58 57 24 67 70 62 58 59 60 28
800 0.18 67 61 54 52 54 52 17 70 64 57 55 57 56 21 72 67 60 57 59 58 24
850 0.21 68 61 54 52 55 52 18 70 65 58 55 57 56 22 72 67 61 57 59 59 24
9 900 0.23 68 62 55 52 55 53 18 71 65 58 55 58 57 22 73 68 61 57 59 60 25
950 0.26 69 62 55 53 55 54 19 72 66 59 56 58 57 23 74 68 61 58 60 60 25
1000 0.29 70 63 56 53 56 54 20 72 66 59 56 58 58 23 74 69 62 58 60 61 27
900 0.25 67 60 54 52 56 55 17 70 64 58 55 58 59 21 72 67 61 58 60 61 24
1000 0.31 68 61 55 53 56 56 18 71 65 59 56 59 60 22 73 68 62 58 60 62 25
10 1100 0.38 69 62 56 53 57 57 19 72 66 60 57 59 61 23 74 69 62 59 61 63 27
1200 0.45 69 63 56 54 57 58 20 73 67 60 57 60 62 24 75 70 63 59 61 64 28
1300 0.53 70 64 57 54 57 59 21 73 68 61 57 60 62 25 76 70 63 60 62 65 28
1200 0.25 67 61 55 53 56 55 17 70 65 58 56 58 58 22 73 67 61 58 60 61 24
1400 0.33 68 62 57 54 57 57 18 72 66 60 57 59 60 23 74 69 62 59 61 62 27
12 1600 0.44 70 64 58 55 58 58 21 73 67 61 58 60 61 24 75 70 64 60 62 64 28
1800 0.55 71 65 60 56 59 59 22 74 68 63 59 61 62 25 76 71 65 61 63 65 29
2000 0.68 71 66 61 57 60 60 23 75 69 64 60 62 63 27 77 72 66 62 63 66 30
1500 0.18 66 60 54 53 56 56 16 70 64 58 56 58 59 21 72 67 60 58 60 62 24
1800 0.25 68 62 56 54 57 58 18 71 66 60 57 60 61 23 74 68 62 59 61 63 25
14 2100 0.34 70 63 58 55 58 59 20 73 67 61 58 61 62 24 75 70 64 60 62 65 28
2400 0.45 71 64 59 56 59 61 22 74 68 62 59 62 64 25 77 71 65 61 63 66 29
2700 0.57 72 65 60 57 60 62 23 75 69 64 60 62 65 27 78 72 66 62 64 67 31
2000 0.21 68 60 55 53 58 58 18 71 64 58 56 60 61 22 74 67 60 58 62 64 25
PERFORMANCE DATA

2400 0.30 69 62 57 55 59 60 19 73 66 60 58 61 63 24 75 69 63 60 63 65 27
16 2800 0.40 70 64 59 56 60 61 21 74 67 62 59 62 64 25 77 70 64 61 64 67 29
3200 0.53 71 65 61 58 61 62 22 75 69 64 60 63 66 27 78 71 66 62 65 68 31
3600 0.67 72 66 62 59 61 63 23 76 70 65 61 64 67 28 79 73 67 63 65 69 32

• Discharge sound is the noise emitted from the • All performance based on tests conducted in
unit discharge into the downstream ductwork. accordance with ASHRAE 130-2008 and AHRI 880-2008.
• Min ∆Ps is the static pressure drop from the unit inlet • All NC levels determined using AHRI 885-2008
to the unit outlet with the cold damper full open. Appendix E. See Terminal Unit Engineering Guidelines.
• Sound power levels are in dB, ref 10-12 watts. • Dash (-) in space denotes NC value less than NC10.
• Sound performance based on units lined with • Only highlighted data points are AHRI certified. See
standard dual density fiberglass lining. page M38 for AHRI Certified Performance Listings.

M32
Single/Dual Duct Terminals

www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com


Dual Duct High Performance Blending
MDV/MDC
Available Models: • Standard matte faced insulation
PMDV/PMDC • Pneumatic for maximum thermal and
DMDV • Digital acoustic performance.
Electronic
• Standard 22-gauge casing with slip

MDV
and drive discharge connection.
• Standard AeroCrossTM multi-point
center averaging velocity sensors • Controls supplied by Titus are
available in multiple location factory calibrated for quicker
combinations to match any start-up.
control requirement.

PMDV/PMDC - Basic Unit with Controls


G L 4" H

M
D

A Discharge W E

D Slip and Drive


Duct Connection J

Controllers
4½"

Pneumatic Actuator

DMDV - Basic Unit with Controls


8"
Max
G L 4" H

6½"

F
D

A Discharge W E

D
Slip and Drive
Duct Connection
6½"

18"
K K
12¼"

Inlet cfm PMDV DMDV


A D E F G H L W
Size Range J K
MDV, MDC

4 0-225 8⅞ 3⅞ 5⅞ 5⅞ 5⅜ 8¼ 34 19 1⅞ 2
5 0-350 8⅞ 4⅞ 5⅞ 5⅞ 5⅜ 8¼ 34 19 1⅞ 2
6 0-500 8⅞ 5⅞ 5⅞ 5⅞ 3⅜ 8¼ 34 19 1⅞ 2
7 0-650 10⅞ 6⅞ 7⅛ 8⅛ 6¾ 10¼ 42 23 ⅞ 1
8 0-900 10⅞ 7⅞ 7⅛ 8⅛ 3⅜ 10¼ 42 23 ⅞ 1
9 0-1050 12⅞ 8⅞ 10⅛ 11⅛ 6¾ 12¾ 50 27 - -
10 0-1400 12⅞ 9⅞ 10⅛ 11⅛ 3⅜ 12¾ 50 27 - -
12 0-2000 14⅞ 11⅞ 11⅛ 13⅛ 3⅜ 15¼ 58 31 - -
14 0-3000 16⅞ 13⅞ 12½ 16⅛ 3⅜ 18⅛ 66 35 - -
16 0-4000 18⅞ 15⅞ 15⅛ 16⅛ 3⅜ 18⅛ 72 38 - -
All dimensions are in inches.
M33
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com

PERFORMANCE DATA Single/Dual Duct Terminals


PMDV, PMDC, DMDV / RADIATED SOUND PERFORMANCE

Octave Band Sound Power, Lw


Min
Size CFM 1.0” ∆Ps 1.5” ∆Ps 2.0” ∆Ps
∆Ps
2 3 4 5 6 7 NC 2 3 4 5 6 7 NC 2 3 4 5 6 7 NC
100 0.18 55 50 42 36 35 31 17 57 53 45 38 37 34 21 58 55 47 40 39 36 23
125 0.29 56 52 43 38 36 32 20 58 55 46 40 38 35 23 60 57 49 41 40 37 25
4 150 0.41 57 53 44 39 37 33 21 59 56 47 41 39 36 24 61 58 50 42 41 38 27
175 0.56 58 55 45 39 38 34 23 60 58 48 42 40 36 27 62 60 50 43 41 39 29
200 0.74 59 56 46 40 38 34 24 61 59 49 42 41 37 28 62 61 51 44 42 39 30
150 0.15 55 51 43 34 29 21 18 58 55 47 37 32 24 23 59 57 50 39 34 26 25
200 0.27 58 54 45 37 34 27 22 60 57 49 40 36 30 25 62 59 52 42 38 33 28
5 250 0.42 60 55 46 39 37 32 23 63 59 50 43 40 35 28 64 61 53 45 41 38 30
300 0.60 62 57 48 41 40 36 25 64 60 52 45 42 40 29 66 63 55 47 44 42 33
350 0.82 63 58 49 43 42 40 27 66 62 53 46 45 43 31 67 64 56 48 47 45 34
300 0.43 58 54 46 41 41 37 22 61 58 50 44 45 41 27 64 61 52 47 47 44 30
350 0.58 59 54 47 42 42 38 22 66 62 53 46 45 43 31 67 64 56 48 47 45 34
6 400 0.76 60 55 48 44 43 38 23 63 59 51 47 47 43 28 65 62 54 49 50 46 31
450 0.96 60 56 48 45 44 39 24 64 60 52 48 48 43 29 66 63 55 50 51 46 33
500 0.39 63 57 48 43 41 36 25 64 60 53 49 49 44 29 67 63 56 51 52 47 33
450 0.32 62 56 48 42 40 36 24 64 60 51 45 44 41 29 66 62 54 47 47 45 31
500 0.39 63 57 48 43 41 36 25 65 61 52 46 45 42 30 67 63 56 51 52 47 33
7 550 0.47 64 58 49 43 41 37 27 66 61 53 46 45 42 30 68 64 55 48 48 46 34
600 0.56 64 58 49 44 42 37 27 67 62 53 47 46 42 31 69 64 56 49 49 46 34

M
650 0.66 65 59 50 45 42 37 28 68 62 54 48 46 43 32 70 65 56 50 49 46 35
600 0.37 62 56 48 42 40 38 24 65 61 52 45 44 43 30 68 63 55 47 47 46 33
650 0.43 63 57 49 43 41 39 25 66 61 53 46 45 43 30 68 64 56 48 47 47 34
8 700 0.50 63 57 50 44 41 39 25 67 61 53 47 45 44 31 69 64 56 49 48 47 34
750 0.57 64 58 50 45 42 40 27 67 62 54 48 46 44 31 69 65 57 50 49 48 35
800 0.65 64 58 50 45 43 40 27 68 62 54 48 47 45 32 70 65 57 50 49 48 35
800 0.20 67 57 47 40 38 29 31 70 61 51 43 41 34 34 72 64 54 46 43 37 37
850 0.22 67 58 48 41 39 30 31 70 62 52 44 42 34 34 72 65 54 46 44 38 37
9 900 0.25 68 58 48 42 40 30 32 71 62 52 45 42 35 36 73 65 55 47 45 38 38
950 0.28 68 58 49 42 40 31 32 71 62 52 46 43 35 36 73 65 55 48 45 39 38
1000 0.31 68 59 49 43 41 31 32 71 63 53 46 44 36 36 73 66 56 49 46 39 38
900 0.21 63 58 51 47 47 47 27 68 63 54 50 51 51 33 71 66 57 52 54 54 36
1000 0.26 64 59 52 48 48 47 28 69 63 55 51 52 51 33 72 66 57 53 54 54 37
10 1100 0.31 65 59 53 48 49 48 28 69 64 56 51 52 52 34 73 67 58 53 55 55 38
1200 0.37 65 60 53 49 49 48 29 70 65 56 52 53 52 35 73 68 59 54 55 55 38
1300 0.44 66 61 54 49 49 48 30 70 65 57 52 53 53 35 74 68 59 54 56 55 40
1200 0.29 68 60 54 53 54 52 32 71 63 58 57 58 57 36 74 66 60 60 61 60 40
1400 0.39 69 61 55 54 55 52 33 72 65 59 58 59 58 37 75 67 61 61 62 61 41
12 1600 0.51 70 62 57 54 56 53 34 73 66 60 58 60 58 38 76 68 62 61 63 62 42
1800 0.64 70 63 58 55 57 54 34 74 67 61 59 61 59 40 77 69 63 62 64 62 43
2000 0.80 71 64 58 56 57 54 36 75 67 62 60 62 59 41 78 70 64 63 65 63 45
1500 0.16 66 58 49 41 38 31 29 70 62 52 43 40 35 34 73 65 54 45 42 37 38
1800 0.23 67 60 52 43 41 34 31 71 64 54 46 43 37 36 74 66 56 48 45 40 40
14 2100 0.31 68 61 54 45 43 36 32 72 65 56 48 46 40 37 75 68 58 50 47 42 41
2400 0.41 69 62 56 47 45 38 33 73 66 58 50 48 42 38 76 69 60 52 50 44 42
2700 0.52 70 63 57 49 47 40 34 74 67 60 51 50 44 40 77 69 62 53 51 46 43
2000 0.20 70 60 53 45 42 37 34 74 64 56 48 44 41 40 77 67 58 50 46 43 43
PERFORMANCE DATA

2400 0.28 71 61 55 47 44 40 36 75 65 58 50 47 43 41 78 68 60 52 49 46 45
16 2800 0.39 72 62 57 50 47 42 37 76 66 60 52 49 45 42 79 69 62 54 51 48 46
3200 0.50 73 63 59 51 49 44 38 77 68 62 54 51 47 43 80 70 64 56 53 50 47
3600 0.64 74 64 61 53 51 45 40 78 68 64 56 53 49 45 80 71 66 58 55 51 47

• Radiated sound is the noise transmitted • All performance based on tests conducted in
through the unit casing. accordance with ASHRAE 130-2008 and AHRI 880-2008.
• Min ∆Ps is the static pressure drop from the unit inlet • All NC levels determined using AHRI 885-2008
to the unit outlet with the cold damper full open. Appendix E. See Terminal Unit Engineering Guidelines.
• Sound power levels are in dB, ref 10-12 watts. • Dash (-) in space denotes NC value less than NC10.
• Sound performance based on units lined with • Only highlighted data points are AHRI certified. See
standard dual density fiberglass lining. page M38 for AHRI Certified Performance Listings.

M34
Single/Dual Duct Terminals

www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com


PERFORMANCE DATA

PMDV, PMDC, DMDV / DISCHARGE SOUND PERFORMANCE

Octave Band Sound Power, Lw


Min
Size CFM 1.0” ∆Ps 1.5” ∆Ps 2.0” ∆Ps
∆Ps
2 3 4 5 6 7 NC 2 3 4 5 6 7 NC 2 3 4 5 6 7 NC
100 0.18 53 51 47 44 38 28 - 55 53 49 46 40 30 10 56 54 51 48 42 32 11
125 0.29 56 54 49 46 42 34 11 58 56 52 49 44 36 14 59 57 54 51 45 37 15
4 150 0.41 59 57 52 48 45 38 15 61 59 54 51 47 40 17 62 60 56 53 49 42 18
175 0.56 61 59 53 50 48 42 17 63 61 56 53 50 44 20 64 62 58 55 51 46 21
200 0.74 63 61 55 52 50 46 20 65 63 57 54 52 47 22 66 64 59 56 54 49 23
150 0.15 56 53 49 45 38 31 10 57 55 51 47 40 33 12 59 56 53 49 42 34 14
200 0.27 60 57 52 48 44 39 15 61 59 55 51 46 40 17 63 61 57 53 47 41 20
5 250 0.42 63 61 55 51 48 45 20 64 63 58 54 50 46 22 66 64 59 56 51 47 23
300 0.60 65 63 57 53 51 50 21 67 65 60 56 53 51 23 68 67 62 58 55 52 25
350 0.82 67 66 59 55 54 54 24 69 68 62 58 56 55 27 70 69 64 60 57 56 28
300 0.43 62 59 53 50 46 39 16 65 62 56 53 48 42 20 67 64 59 55 50 43 22
350 0.58 64 61 54 52 49 43 18 69 68 62 58 56 55 27 70 69 64 60 57 56 28
6 400 0.76 65 62 55 53 51 45 20 68 65 59 56 53 48 23 69 68 61 58 54 49 27
450 0.96 66 63 56 54 53 48 21 69 67 60 57 55 50 25 70 69 63 59 56 52 28
500 0.39 67 64 57 52 52 48 22 69 68 61 58 56 53 27 71 70 63 60 58 54 29
450 0.32 65 62 56 51 50 45 20 67 65 59 53 51 47 23 69 66 61 55 52 48 24
500 0.39 67 64 57 52 52 48 22 69 66 60 55 53 50 24 71 70 63 60 58 54 29
7 550 0.47 68 65 58 53 53 50 23 70 67 61 55 55 52 25 71 69 63 57 56 53 28
600 0.56 69 66 59 54 55 52 24 71 69 62 56 57 54 28 72 70 64 58 58 55 29
25 72 70 63 57 58 56 29 73 30

M
650 0.66 70 67 60 55 56 54 71 65 59 59 57
600 0.37 66 63 57 52 51 46 21 69 66 61 55 52 48 24 71 68 63 57 54 50 27
650 0.43 67 64 58 53 52 48 22 69 67 62 56 54 50 25 71 69 64 58 55 51 28
8 700 0.50 67 64 59 53 53 50 22 70 67 62 56 55 52 25 72 70 65 59 56 53 29
750 0.57 68 65 60 54 54 51 22 71 68 63 57 56 53 25 73 70 65 59 57 55 28
800 0.65 69 66 60 55 55 53 23 71 69 64 58 57 55 27 73 71 66 60 58 56 29
800 0.20 68 62 57 50 48 44 18 71 65 61 53 51 47 22 73 68 63 55 52 48 25
850 0.22 69 62 58 51 49 45 19 72 66 61 54 52 48 23 74 68 64 56 53 50 25
9 900 0.25 69 63 58 52 50 47 20 72 66 62 54 53 49 23 74 69 64 57 54 51 27
950 0.28 70 63 58 52 51 48 20 73 67 62 55 54 50 24 75 69 65 57 55 52 27
1000 0.31 71 63 59 53 52 49 22 73 67 62 56 54 51 24 75 70 65 58 56 53 28
900 0.21 69 63 58 54 52 46 20 73 67 62 56 54 49 24 75 69 64 58 55 50 27
1000 0.26 70 64 59 55 53 48 21 74 68 63 58 55 51 25 76 70 65 60 57 52 28
10 1100 0.31 71 65 60 56 55 50 22 75 69 64 59 57 52 27 77 71 66 61 58 54 29
1200 0.37 72 66 61 57 56 52 23 75 69 64 60 58 54 27 78 72 67 62 60 56 31
1300 0.44 73 67 62 58 58 53 24 76 70 65 60 60 56 28 79 73 68 62 61 57 32
1200 0.29 72 64 60 54 53 49 29 75 67 63 56 55 51 33 77 69 65 58 57 53 36
1400 0.39 74 66 62 56 56 52 32 76 69 65 58 58 54 34 78 71 67 60 60 56 37
12 1600 0.51 75 68 63 58 59 55 33 78 71 67 60 61 57 37 80 73 69 62 62 58 40
1800 0.64 76 69 65 60 61 57 34 79 72 68 62 63 59 38 81 75 70 64 64 61 41
2000 0.80 77 71 66 61 63 59 36 80 74 69 64 65 61 40 82 76 72 65 66 63 42
1500 0.16 71 62 58 51 51 45 28 74 66 61 53 53 47 32 76 68 63 55 54 49 34
1800 0.23 73 65 60 54 54 48 31 76 68 63 56 56 51 34 78 71 65 58 57 53 37
14 2100 0.31 75 67 62 56 57 51 33 78 70 65 59 59 54 37 80 73 67 60 60 55 40
2400 0.41 77 69 64 59 59 54 36 79 72 67 61 61 56 38 81 75 69 62 63 58 41
2700 0.52 78 71 66 60 61 56 37 81 74 69 63 63 58 41 83 76 71 64 65 60 43
2000 0.20 74 65 61 55 54 49 32 77 68 64 57 56 51 36 79 71 65 59 58 53 38
PERFORMANCE DATA
2400 0.28 76 68 63 58 58 52 34 79 71 66 60 60 55 38 81 73 68 62 61 56 41
16 2800 0.39 77 70 66 61 60 56 36 80 73 68 63 63 58 40 83 75 70 65 64 59 43
3200 0.50 79 71 67 63 63 58 38 82 75 70 65 65 60 42 84 77 72 67 66 62 45
3600 0.64 80 73 69 65 65 61 40 83 76 72 67 67 63 43 85 78 74 69 69 64 46

• Discharge sound is the noise emitted from the • All performance based on tests conducted in
unit discharge into the downstream ductwork. accordance with ASHRAE 130-2008 and AHRI 880-2008.
• Min ∆Ps is the static pressure drop from the unit inlet • All NC levels determined using AHRI 885-2008
to the unit outlet with the cold damper full open. Appendix E. See Terminal Unit Engineering Guidelines.
• Sound power levels are in dB, ref 10-12 watts. • Dash (-) in space denotes NC value less than NC10.
• Sound performance based on units lined with • Only highlighted data points are AHRI certified. See
standard dual density fiberglass lining. page M38 for AHRI Certified Performance Listings.

M35
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com

SUGGESTED SPECIFICATIONS Single/Dual Duct Terminals


EDV BASIC UNIT WITHOUT ATTENUATOR leakage to the maximum values shown in the Damper
EDV/EDC BASIC UNIT WITH MIXER-ATTENUATOR Leakage table.
MDV/MDC BASIC UNIT WITH MIXER-ATTENUATOR
See Section O for control specifications. Damper Leakage, cfm
Inlet ∆Ps, in wg
1. Furnish and install Titus Model (P)(D)(EDV)(EDC) Size 1.0 2.0 4.0 6.0
(MDV)(MDC) dual duct, (variable)(constant) air volume 4, 5, 6 3 4 6 7
terminals of the sizes and capacities shown in the plans. 7, 8 3 4 6 7
9, 10 3 4 6 7
2. Terminals should be certified under the AHRI Standard 12 3 4 6 7
880 Certification Program and carry the AHRI Seal. 14 3 5 7 8
Noncertified terminals may be submitted after testing 16 4 5 7 9
at an independent testing laboratory under conditions
selected by the engineering consultant in full compliance 6. Actuators shall be capable of supplying at least 35
with AHRI Standard 880. These tests must be witnessed inches per pound of torque to the damper shaft
by the engineering consultant with all costs to be borne and shall be mounted externally for service access.
by the terminal manufacturer. Testing does not ensure Terminals with internal actuator mounting or linkage
acceptance. connection must include gasketed access panel,
3. The terminal casing shall be minimum 22-gauge removable without disturbing ductwork. Casing with
galvanized steel, internally lined with dual density access panel shall be constructed to hold leakage to the
insulation which complies with UL 181 and NFPA 90A. maximum values shown in the Casing Leakage table.
All exposed insulation edges shall be coated with NFPA 7. Sound ratings for the terminal shall not exceed ____
90A approved sealant to prevent entrainment of fibers NC at ____ static pressure. Sound performance shall be

M
in the airstream. The casing shall be constructed to hold AHRI certified.
leakage to the maximum values shown in the Casing
Leakage table. ACCESSORIES
STERI-LOC LINER
EDV without Mixer Casing Leakage, cfm (Substitute paragraph 3 below for paragraph 3 in the Basic
Inlet ∆Ps, in wg Unit specification).
Size 0.5 1.0 2.0 3.0
4, 5, 6 4 6 8 10 3. The terminal casing shall be minimum 22-gauge
7, 8 7 10 14 17 galvanized steel, internally lined with a non-porous,
9, 10 8 12 17 21 sealed liner which complies with UL 181 and NFPA 90A.
12 10 14 20 24 Insulation shall be 4-pound density. All cut edges must
14 13 18 25 31 be sealed from the airstream using mechanically bonded
16 14 20 28 35
metal barrier strips. Liners made of Mylar, Tedlar, Silane
EDV/EDC with Mixer and MDV/MDC or woven fiberglass cloth are not acceptable. Insulation
Casing Leakage, cfm shall be equivalent to Titus Steri-Loc or double wall
lining is acceptable. The casing shall be constructed
Inlet ∆Ps, in wg
to hold leakage to the maximum values shown in the
Size 0.5 1.0 2.0 3.0
4, 5, 6 3 5 7 8
Casing Leakage table.
7, 8 5 7 9 11
9, 10 5 7 10 13 FIBRE-FREE LINER
12 7 9 13 16 (Substitute paragraph 3 below for paragraph 3 in the Basic
14 9 13 18 23 Unit specification).
16 12 17 24 30
3. The terminal casing shall be minimum 22-gauge
4. (Delete this paragraph for EDV without mixer-attenuator) galvanized steel, internally lined with engineered
Each terminal shall include a mixer-attenuator section as polymer foam insulation which complies to UL181 and
an integral part of the terminal to minimize downstream NFPA 90A. Insulation shall be 1½ pound density, closed
SPECIFICATIONS

stratification. The terminal shall provide less than 2°F, cell foam. Exposed fiberglass is not acceptable. The
EDV/EDC (or 1°F, MDV/MDC) discharge temperature insulation shall be mechanically fastened to the unit
variation with a 20° differential in inlet temperature. casing. The casing shall be constructed to hold leakage
5. Cooling and heating inlets shall have separate damper to the maximum values shown in the Casing Leakage
assemblies for complete pressure independent control table.
of each airstream for variable or constant volume total
discharge applications. Terminals with inlet dampers ECOSHIELD
mechanically interconnected are not acceptable. The (Substitute the following paragraph 3 for paragraph 3 in the
dampers shall be heavy gauge steel with solid shaft ESV Basic Unit Specification.)
rotating in Delrin® self-lubricating bearings. Nylon
bearings are not acceptable. Shaft shall be clearly 3. The terminal casing shall be minimum 22 gauge
marked on the end to indicate damper position. Stickers galvanized steel (20 gauge for fan powered terminals),
or other removable markings are not acceptable. The internally lined with ½ in. or 1” matte or foil faced
natural fiber insulation which complies with ASTM C 739
M36 damper shall incorporate a mechanical stop to prevent
overstroking and a synthetic seal to limit close-off and NFPA 90A. The liner shall comply with ASTM G21
Single/Dual Duct Terminals

www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com


SUGGESTED SPECIFICATIONS

and G22 for fungi and bacterial resistance. All exposed


edges shall be coated with NFPA approved sealant to
prevent entrainment of fibers in the airstream.

MODEL NUMBER SPECIFICATION

0 Base Unit Hot


1 with Integral Mixer/ Inlet
Attenuator (EDC/EDV
only) Casing Size
2 with Integral Mixer/ Configuration (specify)
P Pneumatic Model C Constant Volume Attenuator and Mixing 0R Right Hand
D Digital Electric Dual Duct V Variable Volume Baffle (EDC/EDV only) 0L Left Hand
X X D X XX X X XX X X
E Standard 3A AeroCross Multi- 0 Standard ½” Cold
High point Sensor
M (hot and cold 1 1” Inlet
Performance
Mixing duct inlets) 2 Steri-LocTM Size

M
3B AeroCross Multi- 9 Fibre-Free (specify)
point Sensor
(hot inlet and J EcoShield ½”
total discharge
EXAMPLE: PEDV 3B100R 66 ducts) K EcoShield 1”

Pneumatically controlled, dual duct variable 3C AeroCross Multi- L EcoShield Foil ½”


point Sensor
volume terminal, with multi-point sensor in hot
(cold inlet and M EcoShield Foil 1”
inlet and total discharge locations, integral mixer/ total discharge
attenuator, standard liner, right hand cold inlet ducts) Lining Type
location, 6” cold and 6” hot inlet sizes.
3D AeroCross Multi-
point Sensor
(total discharge
only)

SPECIFICATIONS

M37
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com

SUGGESTED SPECIFICATIONS Single/Dual Duct Terminals


AHRI Directory of Certified Performance
Titus is a charter member company and current participant PMDV, PMDC, DMDV
in the AHRI Directory of Certified Performance. This volun-
tary certification program was developed by participating Radiated Sound Discharge Sound
Inlet Rated Min Power Power
manufacturers in conjunction with the former Air-Condi- Size CFM ∆Ps
tioning and Refrigeration Institute (ARI) in the 1990’s. It is 2 3 4 5 6 7 2 3 4 5 6 7
currently administrated by the Air-Conditioning, Heating, 04 150 0.41 59 56 47 41 39 36 61 59 54 51 47 40
and Refrigeration Institute (AHRI). The purpose of this
05 250 0.42 63 59 50 43 40 35 64 63 58 54 50 46
program is to provide for the independent verification of
manufacturers’ published performance data. Only participat- 06 400 0.76 63 59 51 47 47 43 68 65 59 56 53 48
ing products are authorized to bear the AHRI VAV Certifica- 07 550 0.47 66 61 53 46 45 42 70 67 61 55 55 52
tion Mark. Certified data may be viewed and downloaded at
08 700 0.50 67 61 53 47 45 44 70 67 62 56 55 52
www.ahrinet.org .
09 900 0.25 71 62 52 45 42 35 72 66 62 54 53 49
In order to participate in this program, member companies 10 1100 0.31 69 64 56 51 52 52 75 69 64 59 57 52
pay annual dues based on sales volume, submit published
12 1600 0.51 73 66 60 58 60 58 78 71 67 60 61 57
performance data for all applicable model types, and agree
to provide a number of randomly selected product samples 14 2100 0.31 72 65 56 48 46 40 78 70 65 59 59 54
for annual rounds of independent testing at the manufactur- 16 2800 0.39 76 66 60 52 49 45 80 73 68 63 63 58
ers’ expense. All verification testing is conducted in accor-
dance with ASHRAE Standard 130 ‘Methods of Testing Air

M
Terminal Units’. These tests are conducted to verify that a PEDV, PEDC, DEDV WITH INTEGRAL ATTENUATOR AND
manufacturer’s published certified ratings are within the test MIXING BAFFLE
tolerances outlined in AHRI Standard 880 ‘Performance Rat-
Radiated Sound Discharge Sound
ing of Air Terminals’. Any failure to demonstrate the certified Inlet Rated Min Power Power
performance is punished by additional testing requirements, Size CFM ∆Ps
mandatory performance re-rating, monetary penalties and 2 3 4 5 6 7 2 3 4 5 6 7
possible expulsion from the Certified Directory. 04 150 0.41 54 53 44 38 36 31 62 59 54 50 50 45
Product samples provided for certification testing are 05 250 0.47 56 54 47 40 39 35 62 61 56 51 53 50
standard production units with standard ½ in dual density
06 400 0.91 55 57 49 43 41 37 61 61 57 54 55 54
fiberglass lining (unless otherwise specified) and no optional
appurtenances such as add-on attenuators or heating/cool- 07 550 0.53 63 57 51 45 45 41 65 64 58 53 56 54
ing coils. The certified ratings are measured at the standard 08 700 0.55 61 59 50 43 41 40 64 66 59 55 57 56
operating points under the following test conditions:
09 900 0.23 66 57 50 45 46 45 71 65 58 55 58 57
10 1100 0.38 64 57 49 43 42 41 72 66 60 57 59 61
PEDV, PEDC, PMDV, PMDC, DEDV, DMDV
12 1600 0.44 68 62 58 55 58 57 73 67 61 58 60 61
• Rated airflow (cfm) – Based on an 14 2100 0.34 67 60 53 47 48 49 73 67 61 58 61 62
inlet velocity of 2000 fpm. 16 2800 0.40 70 61 56 50 51 51 74 67 62 59 62 64
• Rated Min ∆Ps (in wg) – Minimum static
pressure drop from the cold inlet to discharge
at rated airflow with damper full open. PEDV, DEDV WITHOUT ATTENUATOR
• Rated ∆Ps (in wg) – A static pressure drop
of 1.5 in wg from cold inlet to discharge Radiated Sound Discharge Sound
Inlet Rated Min Power Power
with the hot damper fully closed. Size CFM ∆Ps
• Rated sound power by octave band (dB, re 10-12 watts) 2 3 4 5 6 7 2 3 4 5 6 7
SPECIFICATIONS

– Radiated and discharge sound performance conducted 04 150 0.04 60 57 46 41 40 37 68 64 59 54 54 49


in a reverberation room that meets both the broadband
and pure tone qualifications of AHRI Standard 220. 05 250 0.03 62 59 49 42 41 37 69 64 60 56 55 50
06 400 0.13 63 61 52 44 42 38 70 69 64 60 57 52
07 550 0.10 64 59 53 47 43 34 69 70 63 59 56 51
08 700 0.02 65 60 53 47 47 45 72 71 63 58 56 52
09 900 0.05 64 58 53 47 45 38 73 68 63 59 57 54
10 1100 0.01 67 62 57 55 54 43 74 70 65 63 60 55
12 1600 0.01 66 62 59 53 50 44 75 73 68 64 62 58
14 2100 0.04 66 62 55 53 50 46 72 68 66 63 63 59
M38 16 2800 0.03 66 61 54 50 50 45 74 69 66 64 62 57
www.titus-hvac.com | www.titus-energysolutions.com | www.ruskintitus.com

Titus USA
605, Shiloh Road, Plano TX 75074

T. 972-212-4800
F. 972-212-4884
Email:[email protected]
www.titus-hvac.comus USA

Titus UAE

RUSKIN TITUS GULF (RTG)


U.A.Q. Manufacturing Plant:
P.O. BOX 4683 UAQ – UAE.
T. +971-6-56-20-320
F. +971-6-562-11-40
Email:[email protected]
www.ruskintitus.com