N2 Modbus List

This document outlines the Modbus configuration for communicating with an N2 generator system via a Prosoft MV169E-MBS communication device and a CompactLogix Allen-Bradley PLC. It lists the Modbus address, baud rate, data bits, stop bits, and parity for RS-485 communication between the PLC and SCADA system to monitor and control generator parameters.

Uploaded by

firoz
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
59 views

N2 Modbus List

This document outlines the Modbus configuration for communicating with an N2 generator system via a Prosoft MV169E-MBS communication device and a CompactLogix Allen-Bradley PLC. It lists the Modbus address, baud rate, data bits, stop bits, and parity for RS-485 communication between the PLC and SCADA system to monitor and control generator parameters.

Uploaded by

firoz
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

N2 Generator Modbus Mapping List

Modbus Configuration

N2 Generator system Modbus Configuration

Project: WHN-60S

Communication device CPU

MV169E-MBS(Prosoft) 1769-L30ER(CompactLogix_AB )

Protocol = Modbus RTU Slave_RS-485


Modbus address = 2
19200,8,1,None

Send block N2_PLC -> SCADA


Receive block SCADA -> N2_PLC

Technicalkorea_WHN60S_B_Modbus_RTU_Address_Maping_Ver1.0 Page: 1 of 3
N2_PLC --> SCADA

g
iv

in
ce

al
Sc
)e

C
(R
s

PL
es

n
/
dr

io

n
nd

ai
t
Ad
e

ec

ed
)e
k
m

s_
oc

n
(S
n

t
na

on

ec
es
bu
io

bl

ed
e
k

C
t

nn
pe

dr
a

am
od

od
oc

ca

st
t-
at

Ad
Ty

co

te
Bl

Bi
Lo

N
D
N2_PLC ->
SCADA

(ID=2) ,19200,8,1,None
1_Bit_Value N2_Genertor 40601 BOOL S N2_Generator_B_Remote 0=FALSE, 1=TRUE WRITE[0].0
1_Bit_Value N2_Genertor BOOL S N2_Generator_B_Run_Status 0=FALSE, 1=TRUE WRITE[0].1
1_Bit_Value N2_Genertor BOOL S N2_Generator_B_System_Alarm 0=FALSE, 1=TRUE WRITE[0].2
1_Bit_Value N2_Genertor BOOL S N2_Generator_B_Emergency Stop 0=FALSE, 1=TRUE WRITE[0].3
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].4
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].5
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].6
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].7
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].8
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].9
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].10
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].11
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].12
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].13
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].14
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].15
16_Bit_Value N2_Genertor 40602 INT S spare 0=FALSE, 1=TRUE WRITE[1]
16_Bit_Value N2_Genertor 40603 INT S spare 0=FALSE, 1=TRUE WRITE[2]
16_Bit_Value N2_Genertor 40604 INT S spare 0=FALSE, 1=TRUE WRITE[3]
16_Bit_Value N2_Genertor 40605 INT S spare 0=FALSE, 1=TRUE WRITE[4]
16_Bit_Value N2_Genertor 40606 INT S spare 0=FALSE, 1=TRUE WRITE[5]
16_Bit_Value N2_Genertor 40607 INT S spare 0=FALSE, 1=TRUE WRITE[6]
16_Bit_Value N2_Genertor 40608 INT S spare 0=FALSE, 1=TRUE WRITE[7]
16_Bit_Value N2_Genertor 40609 INT S spare 0=FALSE, 1=TRUE WRITE[8]
16_Bit_Value N2_Genertor 40610 INT S spare 0=FALSE, 1=TRUE WRITE[9]
32_Bit_Value N2_Genertor 40611 REAL S N2_Generator_B_Purity 0=FALSE, 1=TRUE WRITE[10]
32_Bit_Value N2_Genertor 40613 REAL S spare 0=FALSE, 1=TRUE WRITE[12]
32_Bit_Value N2_Genertor 40615 REAL S spare 0=FALSE, 1=TRUE WRITE[14]
32_Bit_Value N2_Genertor 40617 REAL S spare 0=FALSE, 1=TRUE WRITE[16]
32_Bit_Value N2_Genertor 40619 REAL S spare 0=FALSE, 1=TRUE WRITE[18]
32_Bit_Value N2_Genertor 40621 REAL S spare 0=FALSE, 1=TRUE WRITE[20]

Technicalkorea_WHN60S_B_Modbus_RTU_Address_Maping_Ver1.0 Page: 2 of 3
SCADA --> N2_PLC

g
iv

in
ce

al
)e

Sc
s

C
(R
es

PL
dr

on
/

n
Ad

nd

ti

ai
e

ec

M
s_

ed
)e
k
m

oc

nn
(S
u

s
na

t
ec
es
db
bl

ed
Co
e
e
k

nn
pe

dr
a

am
od

od
oc

st
t-
at

Ad
Ty

co

te
Bl

Bi
M

N
SCADA -N2_PLC D
1_Bit_Value 40001 BOOL R B_ RUN 0=FALSE, 1=TRUE READ[0].0
1_Bit_Value BOOL R spare READ[0].1
1_Bit_Value BOOL R spare READ[0].2
1_Bit_Value BOOL R spare READ[0].3
1_Bit_Value BOOL R spare READ[0].4
1_Bit_Value BOOL R spare READ[0].5
1_Bit_Value BOOL R spare READ[0].6
1_Bit_Value BOOL R spare READ[0].7
1_Bit_Value BOOL R spare READ[0].8
1_Bit_Value BOOL R spare READ[0].9
1_Bit_Value BOOL R spare READ[0].10
1_Bit_Value BOOL R spare READ[0].11
1_Bit_Value BOOL R spare READ[0].12
1_Bit_Value BOOL R spare READ[0].13
1_Bit_Value BOOL R spare READ[0].14
1_Bit_Value BOOL R spare READ[0].15
16_Bit_Value 40002 R spare
16_Bit_Value 40003 R spare
16_Bit_Value 40004 R spare
16_Bit_Value 40005 R spare
16_Bit_Value 40006 R spare
16_Bit_Value 40007 R spare
16_Bit_Value 40008 R spare
16_Bit_Value 40009 R spare
16_Bit_Value 40010 R spare
16_Bit_Value 40011 R spare
16_Bit_Value 40012 R spare
16_Bit_Value 40013 R spare
16_Bit_Value 40014 R spare
16_Bit_Value 40015 R spare

Technicalkorea_WHN60S_B_Modbus_RTU_Address_Maping_Ver1.0 Page: 3 of 3
Modbus Configuration

N2 Generator system Modbus Configuration

Project: WHN-60S

Communication device CPU

MV169E-MBS(Prosoft) 1769-L30ER(CompactLogix_AB )

Protocol = Modbus RTU Slave_RS-485


Modbus address = 1
19200,8,1,None

Send block N2_PLC -> SCADA


Receive block SCADA -> N2_PLC

Technicalkorea_WHN60S_A_Modbus_RTU_Address_Maping_Ver1.0 Page: 1 of 3
N2_PLC --> SCADA

g
iv

in
ce

al
Sc
)e

C
(R
s

PL
es

n
/
dr

io

n
nd

ai
t
Ad
e

ec

ed
)e
k
m

s_
oc

n
(S
n

t
na

on

ec
es
bu
io

bl

ed
e
k

C
t

nn
pe

dr
a

am
od

od
oc

ca

st
t-
at

Ad
Ty

co

te
Bl

Bi
Lo

N
D
N2_PLC ->
SCADA

(ID=1) ,19200,8,1,None
1_Bit_Value N2_Genertor 40601 BOOL S N2_Generator_A_Remote 0=FALSE, 1=TRUE WRITE[0].0
1_Bit_Value N2_Genertor BOOL S N2_Generator_A_Run_Status 0=FALSE, 1=TRUE WRITE[0].1
1_Bit_Value N2_Genertor BOOL S N2_Generator_A_System_Alarm 0=FALSE, 1=TRUE WRITE[0].2
1_Bit_Value N2_Genertor BOOL S N2_Generator_A_Emergency Stop 0=FALSE, 1=TRUE WRITE[0].3
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].4
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].5
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].6
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].7
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].8
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].9
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].10
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].11
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].12
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].13
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].14
1_Bit_Value N2_Genertor BOOL S spare 0=FALSE, 1=TRUE WRITE[0].15
16_Bit_Value N2_Genertor 40602 INT S spare 0=FALSE, 1=TRUE WRITE[1]
16_Bit_Value N2_Genertor 40603 INT S spare 0=FALSE, 1=TRUE WRITE[2]
16_Bit_Value N2_Genertor 40604 INT S spare 0=FALSE, 1=TRUE WRITE[3]
16_Bit_Value N2_Genertor 40605 INT S spare 0=FALSE, 1=TRUE WRITE[4]
16_Bit_Value N2_Genertor 40606 INT S spare 0=FALSE, 1=TRUE WRITE[5]
16_Bit_Value N2_Genertor 40607 INT S spare 0=FALSE, 1=TRUE WRITE[6]
16_Bit_Value N2_Genertor 40608 INT S spare 0=FALSE, 1=TRUE WRITE[7]
16_Bit_Value N2_Genertor 40609 INT S spare 0=FALSE, 1=TRUE WRITE[8]
16_Bit_Value N2_Genertor 40610 INT S spare 0=FALSE, 1=TRUE WRITE[9]
32_Bit_Value N2_Genertor 40611 REAL S N2_Generator_A_Purity 0=FALSE, 1=TRUE WRITE[10]
32_Bit_Value N2_Genertor 40613 REAL S spare 0=FALSE, 1=TRUE WRITE[12]
32_Bit_Value N2_Genertor 40615 REAL S spare 0=FALSE, 1=TRUE WRITE[14]
32_Bit_Value N2_Genertor 40617 REAL S spare 0=FALSE, 1=TRUE WRITE[16]
32_Bit_Value N2_Genertor 40619 REAL S spare 0=FALSE, 1=TRUE WRITE[18]
32_Bit_Value N2_Genertor 40621 REAL S spare 0=FALSE, 1=TRUE WRITE[20]

Technicalkorea_WHN60S_A_Modbus_RTU_Address_Maping_Ver1.0 Page: 2 of 3
SCADA --> N2_PLC

g
iv

in
ce

al
)e

Sc
s

C
(R
es

PL
dr

on
/

n
Ad

nd

ti

ai
e

ec

M
s_

ed
)e
k
m

oc

nn
(S
u

s
na

t
ec
es
db
bl

ed
Co
e
e
k

nn
pe

dr
a

am
od

od
oc

st
t-
at

Ad
Ty

co

te
Bl

Bi
M

N
SCADA -N2_PLC D
1_Bit_Value 40001 BOOL R A_ RUN 0=FALSE, 1=TRUE READ[0].0
1_Bit_Value BOOL R spare READ[0].1
1_Bit_Value BOOL R spare READ[0].2
1_Bit_Value BOOL R spare READ[0].3
1_Bit_Value BOOL R spare READ[0].4
1_Bit_Value BOOL R spare READ[0].5
1_Bit_Value BOOL R spare READ[0].6
1_Bit_Value BOOL R spare READ[0].7
1_Bit_Value BOOL R spare READ[0].8
1_Bit_Value BOOL R spare READ[0].9
1_Bit_Value BOOL R spare READ[0].10
1_Bit_Value BOOL R spare READ[0].11
1_Bit_Value BOOL R spare READ[0].12
1_Bit_Value BOOL R spare READ[0].13
1_Bit_Value BOOL R spare READ[0].14
1_Bit_Value BOOL R spare READ[0].15
16_Bit_Value 40002 R spare
16_Bit_Value 40003 R spare
16_Bit_Value 40004 R spare
16_Bit_Value 40005 R spare
16_Bit_Value 40006 R spare
16_Bit_Value 40007 R spare
16_Bit_Value 40008 R spare
16_Bit_Value 40009 R spare
16_Bit_Value 40010 R spare
16_Bit_Value 40011 R spare
16_Bit_Value 40012 R spare
16_Bit_Value 40013 R spare
16_Bit_Value 40014 R spare
16_Bit_Value 40015 R spare

Technicalkorea_WHN60S_A_Modbus_RTU_Address_Maping_Ver1.0 Page: 3 of 3