S7L1D-G4 Wdg.312 - Technical Data Sheet
S7L1D-G4 Wdg.312 - Technical Data Sheet
Quality Assurance
Alternators are manufactured using production procedures having a quality assurance level to BS EN ISO 9001.
Page 1 S7L1D-G4_Wdg.312_A062L872_Rev.B_22.08.2019
S7L1D-G4 Wdg.312
Electrical Data
Insulation System H
Stator Winding Double Layer Concentric
Winding Pitch 2/3
Winding Leads 6
Winding Number 312
Number of Poles 4
IP Rating IP23
Page 1 S7L1D-G4_Wdg.312_A062L872_Rev.B_22.08.2019
S7L1D-G4 Wdg.312
1 Bearing 2 Bearing
SAE Adaptor SAE 0, 00 SAE 0, 00
Moment of Inertia 45.47 kgm² 44.44 kgm²
Weight Wound Stator 1725kg 1725kg
Weight Wound Rotor 1488kg 1445kg
Weight Complete Alternator 3637kg 3604kg
Shipping weight in a Crate 3689kg 3656kg
Packing Crate Size 220 x 105 x 155 (cm) 220 x 105 x 155 (cm)
Maximum Over Speed 2250 RPM for two minutes
Bearing Drive End - BALL. 6232
Bearing Non-Drive End BALL. 6319 BALL. 6319
Page 1 S7L1D-G4_Wdg.312_A062L872_Rev.B_22.08.2019
S7L1D-G4 Wdg.312
50Hz 60Hz
Page 1 S7L1D-G4_Wdg.312_A062L872_Rev.B_22.08.2019
S7L1D-G4 Wdg.312
60Hz
Transient Voltage Dip Scaling Factor Transient Voltage Rise Scaling Factor
PF Factor
< 0.5 1 For voltage rise multiply voltage dip by 1.25
0.5 0.97
0.6 0.93
0.7 0.9
0.8 0.85
0.9 0.83
Page 1 S7L1D-G4_Wdg.312_A062L872_Rev.B_22.08.2019
S7L1D-G4 Wdg.312
50Hz
Page 1 S7L1D-G4_Wdg.312_A062L872_Rev.B_22.08.2019
S7L1D-G4 Wdg.312
480V/60Hz
Page 1 S7L1D-G4_Wdg.312_A062L872_Rev.B_22.08.2019
S7L1D-G4 Wdg.312
Class - Temp Rise Standby - 163/27°C Standby - 150/40°C Cont. H - 125/40°C Cont. F - 105/40°C
Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
50 Parallel Star (V) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
Delta (V) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
Hz
kVA 2165 2250 2250 2185 2105 2170 2170 2125 2020 2080 2080 2040 1880 1935 1935 1900
kW 1732 1800 1800 1748 1684 1736 1736 1700 1616 1664 1664 1632 1504 1548 1548 1520
Efficiency (%) 95.8 95.8 95.9 96.1 95.9 95.9 96.0 96.1 96.0 96.0 96.1 96.2 96.1 96.1 96.2 96.2
kW Input 1808 1878 1877 1820 1757 1810 1809 1769 1684 1733 1732 1697 1565 1610 1610 1579
Star (V) 416 440 460 480 416 440 460 480 416 440 460 480 416 440 460 480
60 Parallel Star (V) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
Hz Delta (V) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
kVA 2506 2675 2731 2787 2437 2600 2650 2706 2350 2500 2550 2600 2194 2325 2375 2425
kW 2005 2140 2185 2230 1950 2080 2120 2165 1880 2000 2040 2080 1755 1860 1900 1940
Efficiency (%) 95.8 95.8 95.9 96.0 95.9 95.9 96.0 96.0 96.0 96.0 96.1 96.1 96.1 96.1 96.2 96.2
kW Input 2092 2233 2278 2323 2033 2169 2209 2254 1959 2084 2124 2164 1827 1936 1976 2017
De-Rates
All values tabulated above are subject to the following reductions:
- 5% when air inlet filters are fitted
- 3% for every 500 meters by which the operating altitude exceeds 1000 meters above mean sea level
- 3% for every 5°C by which the operational ambient temperature exceeds 40°C @ Class H temperature rise
(please refer to applications for ambient temperature de-rates at other temperature rise classes)
- For any other operating conditions impacting the cooling circuit please refer to applications
Note: Requirement for operating in an ambient exceeding 60°C and altitude exceeding 4000 meters (for <690V) or
1500 meters (for >690V) must be referred to applications.
Note: Continuous development of our products means that the information contained in our data sheets
can change without notice, and specifications should always be confirmed with Cummins Generator
Technologies prior to purchase.
Page 1 S7L1D-G4_Wdg.312_A062L872_Rev.B_22.08.2019
Follow us @stamfordavk
news.stamford-avk.com
Page 1 S7L1D-G4_Wdg.312_A062L872_Rev.B_22.08.2019