Unit-2 Power Systems
Unit-2 Power Systems
Power tlow analysis is one of the basic tools used in power system studies. It is concerned
with the steady state analysis of the system when it is working undera normal balanced
operating condition. Load flow or power flow analysis is determination of the voltage.
current, real power and reactive power at various points in electrical network.
S IN AND
operaung condition of
du 1OW analysis is performed on a symmetrical steady-state
TIoW giVes Dus voltage.
POwer system under normal node of operation. The solution of load es
is
and line/transformer power flows for a given load condition. This information essentiatialfor
long term planning and operational planning.
Long Term Planning
Load flow analysis helps in investigating the effectiveness of alternative plans and
choosing the best plan for system expansion to meet the projected operating state
Operational Planning
It helps in choosing the best unit commitment plan and generation schedules to run the
system efticiently for the next day's load condition without violating the bus voltages and
line flow operating limits.
Steps for Load Flow Study
The following work has to be performed for a load flow study.
Representation of the system by single line diagram.
Determining the impedance diagram using the information in single line diagram.
Formulation of network equations.
Solution of network equations.
5.3. CLASSIFICATION OF BUSES
In the network of power system, buses become nodes
and a voltage can be specified for
each bus.
The power flow equation
P,+j
Complex bus voltage V,
i
=
V,
2 Y,*
j =1
|V,l 28,
, i=1,2, N .. (5.1)
... (5.2)
From equation (5.1) and (5.2), we know that power
system is associated with four
quantities and they are real power (P), Reactive power
(Q), Voltage magnitude | V, and
phase angle of voltage (8). In load flow problem, two
quantities are specified for each bus
and the remaining two quantities are obtained by solving
the load flow equations. The buses
are classified based on the variables specified. There are
three types of buses.
1.Slack bus or swing bus or reference bus.
2. Generator bus or voltage control bus or P-V bus or
regulated bus.
3. Load bus or P-Q bus.
Power Flow Analysis
Obtain (N- 1) complex bus voltages from the (N- 1) load flow equations. Incidentally
the specification
of | V,siack helps us to fix the voltage level of the system. In power flow
I
stucdy, at all
buses net complex flow into the network is not known in advance.
While specifying a generation schedule for a given system demand, one can fix up the
generation setting of all the generation buses except one bus because of the limitation of not
Knowing the transmission loss in advance. Therefore, it is necessary to have one bus called
slack bus.
Pa
P 2 P2 2 Ppi .(5.3)
Load
Fig. 5.1. Sample
sion lines or power transformers. Each transmission power system network
line is characterized equivalent
circuit. The transformer with off-nominal by its t
tap ratio is characterized
circuit. Shunt compensating capacitors or quivalent
reactors are by their t equ
represented as shunt susceptance.
Load flow analysis is essentially concerned
with the determination
voltages at all buses, given he network
configuration of comomplex bus
eneration and demand are characterized and the bus demar nands.
Thebus
by complex
buses respectively. powers flowing the
into out of
and ou
Power Flow Analysis
5.5
A generation schedule is nothing but a combination of MW generation of the various
generatorsS Shouid match the given system demand
plus the transmission losses. It should be
noted that there are many generation schedules available
to match the given system demand
and one such schedule is chosen for load flow analysis.
5.4.1. IDEAL LOAD FLOW PROBLEM (OR) sTATEMENT OF IDEALPOWER FLOW PROBLEM
Load flow problem is stated as follows
Given: The network configuration [line impedance and half line charging admiltance
and all the bus power injections.
P,= Po-Pp
where P, = Bus power injection.
PG Busgeneration.
PD Bus demand.
To determine the complex voltages at all the buses
The state vector X is defined as
X = [V1, V2 ,
VN, ô1, öz
N (5.4)
Once the voltages at all the buses are known, then we can compute slack bus power,
.
power flows in the transmission lines and power loss in the transmission lines.
N
5.5.POWER FLOW EQUATION (PFE)/
DEVELOPMENT OF POWER FLow MODELIN
COMPLEX VARIABLE FORM AND POLAR VARIABLE FORM
The power flow or load flow model in complex form is obtained by writing one complex
power matching equation at each bus for the Fig.5.2.
Qpi PitjQ= (PGi- Poi) +j (OGi- Opi)
PGijQci (Ppij
Vi Ni
[] =
[Y][V]
Y Yr2[V V1 V2
LY21 Y22LV2J
Z12
Y1 10+y12 UY20
Y22
20t21
Y12
Y21-21 Fig. 5.3. Two bus system
In general Y =
IY,20, |Y,| cos6+j| Yy Isin 6j (5.6)
YI V, + Y12 V2
2 Y2 V,+Y22 V2
In general, the net current
entering into ith bus
P- V; Z IY,|20,
JFi
V,
Power Flow Analysis
where V,
5.7
=|V,|28, V =|V,|2-8,
V,|28,; 8, = Phase angle of voltage
N
P-j9,=2 |V,|IY,||V,|2(0,,+8,-8)
j=I
Equating real and reactive parts, we obtain
N
P IV,|IY,|V, | cos(0,+ô,-8)
i = 1l
N
The P, andQ, equations are called as polar form of the power flow equations (or) static
load flow equations.
For an N' bus system, there will be 2N power flow equations. Each bus is characterized
by four variables P Q, V, and 8, resulting in a total of 4N variables. The power flow
equations can be solved for 2N variables if the remaining 2N variables are specified.
in Fig.5.4.
Consider N-bus system as shown
Bus I
to M are machine or
generator bus
Bus M+ l
to N are load buses. Fig. 5.4. N-bus system
Power System Analysis
5.8
Flat Voltage Start
0, for i= 1, 2, (for all buses except slack)
.... ..., N
Phase angle, 8,°=
1.0 for i = M+1,...... N (for all P-V buses)
Voltage, IV°I =
-vY j =l
N
P-/Q V Y,V, + V; Y,V,
j =l|
N
i
j=1
(5.11)
Jitl
For load bus,
equation (5.11) is applicable to find | V | and ô
values.
For slack bus,
the voltage is specified, so it will not change in
each iteration.
Power Flow Analysis
For PV Or generator bus, 5.9
() Q value is not specified
for PV bus. Adjusting
correct the voltage
magnitude to the specified the complex voltage V,
= e, *JJ, o
value| V,lspec
Vnew
IV, Ispec
Zcal
here ocalculated
Iteration process continues until the magnitudes A and AQ < O.001 p.u. (specified value).
P
0TT i
Ipi
YPi
two buses
Fig. 5.5. Line connecting
can be
connecting two buses i and j as shown in Fig..5. Ihe line
COnsider the line
admittance Ys and the two shunt admittances (halt line chargin
represented by the series
admittance) Yp; and Ypj
Line current (forward) I,= Ist lpi
=
(V-V Ys +V, x Ypi
=V,[(V-V) Ys + V, Yp, 1*
=
V,{ (V*-V,)Y +|V, PYp,}
Line power (reverse) Sji= V,
(5.15)
- v,{[v;-v;I Y$+ IV,PYP,}
(5.16)
5.7.3. COMPUTATION OF TRANSMISSION LOSS
Power loss in the transmission line ij
Sij (Loss) Sy+Si
P+j Qy + Pji +j Qji
Real power loss
Pi + Pji
.. (5.17)
Reactive power loss =
Qij +Qj
574. COMPUTATION OF
TRANSFORMER AND
LINE FLOW
A fter finding complex bus voltages, EQUATION
stransformers are the
to be computed. A common active and reactive
t equivalent flows in all t ne
and transformer is shown in Fig.5.6. circuit for transmission
For line, a =
0'i
For transformer,
Analysis
Power low 5.11]
Vi
Piy y 1
Yijs
Pyi jOji
T
jbe ibe
Fig. 5.6. Equivalent circuit of a transmission line/transformer
Power flow from in bus to the jih bus, measured at the ith bus is given by,
Py+jQy V, = V, , (5.18)
Vi
We know a V, =
(5.19)
,=(V-V,) Yjs+V,G b) . (5.20)
PtjQy (5.21)
Fortransformer:
Substituting b, = 0 in equation (5.21) and (5.22), we get
.(5.23)
Py tj 9
Cay -
i
- Im
j=1
v,*Y, V
QG +Q
Check for Q limit violation.
f (min) < QG 9(max), then 9 (spec) = Q
If Q (min) QGi, then Qi (spec) i (min) Li
If Qi (max)QGi then Q (spec)Qi
(max)QLi
If Qimit is violated, then treat this bus as P-Q bus till convergence is obtained.
Step 8: Compute V, using the equation,
Start
Read line data, tolerance (E), (
Bus Data
P for i 2... N
min.max for i= 2... M
Q; tor i = M+1.. N
Vi| tori=1,.. M
No Does
i refer to
generator
ous
Yes
= V(spec)
VneW L8*a.
Q cal- Im[ V; y Yij Vj]
QGi Q+QL
QGQi (max)
Check for QGiQi tmin)
Q limit
QGi Qi (min)
QGi Qi (max)
= Qi
L Qi (spec) o cal Qi (spec) = Qi (min)- QL
Qi (spec) (max)-Li|
Fi (spec)*di (spec)
V Vold
No
Yes
Are
V-Vi|sE No
all
N
for i 2.
Yes V V+a [V-V
losses, reactive old E =2 to N
Calculate all line flows, total line
slack bus power
power generated at P-V buses.
= iter+1
ter
/Print the results
(Stop)
Power System Analysi.
L5.14
SOLVED EXAMPLES
the system as showwn in Fig.
Example 5.1| Perform power, "Jlow of one iteration for
power, line flows and line.losses. Take
using Gauss-Seidal method. Determine slack bus
base MVA as 100. (a= 1.1).
1.05 20°-
0.0839+J0.5183- j0.005
90+j20
jo.0636 jo.0636
30 +j10 MVA
Solution:
Step 1: Formulate Ybus
vold= 1.020°
2 p.u
=
P2 30 MW 100 P.u =-0.3 p.u
Q2 10
10 MVAR =
100 P.u =-0.I p.u
Bus
SyPy+j Qi =V, IV;-V]¥ij series+| V, P Yp
From To
2 S12 V [Vi-V2]Y12 series+| V,*Yio
= 1.05 [1.05 2-0°-(1.0059 +j0.173)] x
(0.3044 +j1.88) + 1.052 x -j0.0636)
0.3556-j0.0383 p.u
Pi2 0.3556 p.u = 35.56 MW
- 3.83 MVAR
Q12 -0.0383 p.u =
S21
Va [V2 -V{]Yi2 series +| V2 ? Y20
1.05 20°.
- 1.02 p.u volt
0.0839 +j0.5183
90+j20
j0.0636 j0.0636
Solution:
Step 1: Formulate Ybus
0.3044 +j1.881
0.3044-j1.816
L-0.3044 +j1.88 0.3044 -j1.816J
Step 2: Initialize bus voltages.
yold= 1.05 20° p.u
1
.
- 20 -12.4< 100
This bus acts as generator bus.
Q2= 12.4 MVAR =-0.124 p.u
Step 4: Calculate V.
Vew Y2 Vnew
0.6+j0.124
0.3044-j1.816| 1.022-0° -E0.3044 +j1.88) * 1.05
0.9078j1.8524
0.3044-j1.816 1.073,+j0.32 = 1.12216.61°
VncW=
2
V2 (spec)
0 1.02 416.61°
Power Flow Analsis
S.17
Step 5 Using acceleration factor,
Vnew =
Vd +a VW -
acc [
V1
=1.02 + 1.1 [1.02 216.61°- 1.02]
= 1.02 + 1.1 [0.977 +j0.292 - 1.02]
0.973 +j0.32 = 1.02 218.24°
Bus voltages are V = 1.05 20°
V2 = 1.02 218.24°
Step 6: Slack bus power
S, =
P-j = Vj [Y V1+ Y12 Vl
1.05 2-0° [(0.3044 -j1.816) x 1.05 +(-0.3044 +j1.88) (1.02 218.24°)
= -0.607-j0.18 p.u
-
60.7-j 18 p.u
=
P-60.7 MW, Q18 MVAR
Real power generation PG1= P,+ PLi
= - 60.7+90 29.3 MW
Reactive power generation QG1 =
1+QL
=
18+20 = 38 MVAR
90+20
L j0.0636
jo.0636
Solution:
Step 1: Formulate Y bus
0.3044-j1.816 -0.3044 +j1.88
Y
bus L-0.3044 +j1.88 0.3044-1.816J
Step 2: Initialize bus voltages.
vola
Vo = 1.05 20° p.u
Vhew
u V
2
Y2 V2
Y2
0.6-j0._-0.3044
1.020o -(-0.3044 +j1.88)
+j1.88) 1.05
1.05
44-j1.816
Example 5.4 Using Gauss-Seidal method, determine bus voltages and reactive
power generation for the Fig. skown. Take Base MVA = 100.
V 1.05 20° 0.0839+j0.5183
30+j20
j0.0636 j0.0636 0.005
Solution:
Step 1: Formulate Ybus"
[Y10+ Y12 -Y12
bus - Y12 Y20+ Y2c+Y12 J
Admittance of shunt element
where Y2c - 7
0.3044-jl.816 0.3044 +j1.88
L-0.3044 +j1.88 0.3044-j1.811 J
Step 3: Calculate Q2
Q=-Im {
V [V Y21+V2 Y22l}
= - Im { 1.0 20° [1.05 x (-0.3044 +j1.88) + 1.0 (0.3044-j1.811)]
= -0.163 p.u
V
Step 4: Calculate
P2 PG2 -PL2 =100-0.3
30 p.u; Q2=-0.163 p.u
Vhew
P22 Ya V
1 -0.3+j0.163
L -(-0.3044 +j1.88) x 1.05
0.3044-1.811 1.02-0°
=0.973-j0.1611 = 0.986 2-9.4
= 1.0 -9.4
Reactive power generation Qoz = Q2+QL2
-0.163+0.2 0.037 p.u = 3.7 MVAR
Reactive bus power Q2 = - 0.163 p.u MVAR = - 16.3 MVAR
Example 5.5| For the system shown in Fig, determine the voltages
at the end of the
Jirst iteration by Gauss-Seidel method and also find he slack bus power,
line flows,
transmission loss. Assume base MVA as 100.
OT j0.4
j0.3 J0.2
Solution:
Bus
Voltage Generator Load
No. Qmin Qma
. 1.05 20° p.u Q MVAR MVAR
1.02 p.u 0.3 p.u
3. 0.4 p.u 0.2 p.u 10 100
Power Flow Analysis
j0.4 j0.3
Ybus -1
j0.4 4 j02 -1
j0.2
L-j5.8333 j2.5
j0.3
j3.3333
j2.5 -j7.5 j5
L j3.3333 j5-j8.3333 J
Step 2: Initialize bus voltages.
= 1.05 L0° p.u [Bus 1
is a slack bus ie., V and 8 is specified]
Note For slack bus, the specified voltage will not change in any iteration.
For generation bus, calculate V using the formula and write
vew Vspecified4 Ocalculatedvalue
Qcal
Imvd Y, V+ Y v
- j-1 j=i
0.025 p.u
5.22 N
Y, VW
V Y -2
V
v Y22 V
- Y2 V- Y23
Q 0.025 p.u
P2= 0.3 p.u (Given):
x 1.0520°-j5 x Z0°
1
w
Vew 0.3-j0.0252.5
V2 /7.51.02 20°
= 1.0199 +j0.0392
= 1.0207 2 2.2°
= 1.02 2 2.2° = 1.0192+j0.0392
View
2
= V2
V2 (spec) Z8"
P3 PG3- PL3 = 0-0.4 -0.4 p.u
- 0.2 p.u
Q3 QG3 -QL3 = 0-0.2
VICW-Y2 Vnew
V
11ew
3 Y Y31
1.00782-1.39°
=
0.1029-j0.0746 p.u
S23 P23 +j
Qs
S23 V2[V2 -V3] Y23
series
1.0192 +j0.0392[ 1.0192-j0.0392 - 1.0075 -j0.0244]j5
0.3218 +j0.072 p.u
S32
P2tj Q2
S2 Vs[V3-V;]Y2series
1.0075-j0.0244 [1.0075 +j0.0244-1.0192+j0.0392]js
-0.3218-j0.0512 p.u
S13 P13+jQ13
S13
V,[Vi-V3] Yi3 series
S31V3 [V-Vi]Y31series
1.0075-j0.0244 x [1.0075 +j0.0244 1.05] x j3.3333
-0.085-j0.1407 p.u
Transmission LoSS
Siy Loss Si + S
For line 1-2,
S12 Loss = P2 Loss jQ12 LossS12 + S21
S12 Loss = -0.1029 +j0.0808 + 0.1029-j0.0746
= 0+j0.0061
p.u = 0.61 MVAR
P12 Loss 0, Q12 Loss0.0061
Example S6Resolve the previous Example 5.5, the reactive power constraint on
generator bus-2 be changed to 10 s0, S100. Determine slack bus power. /02 in MVARJ.
Solution:
j5.8333 j2.5 j3.3333
Step 1: Ypus
Ybus j2.5 -j7.5 j5
3.3333 5 j8.3333
Step 2:Initialize bus voltages.
Vold = 1.05 Z0° p.u
vodd = 1.02 0° p.u
v =
1.020° p.u
Step 3:Calculate Q value for generator bus.
Qa - Im| 1.02
2-0° [j2.5 x 1.05
20°+-i7.5 x 1.02 20°) +j5 x 120]|
0.025 p.u
Q Q2 (min) [Q exceeds the limit, . Bus 2 will act as load bus,
Ve2
-
Y P2J2 Y,,
5 0.3-i01
Ya V -Y2 Vd
Y3s
P Vold
L
Y VeW-Y32 V2
-0.4 +j0.2
-j8.3333 1.0-0 -j3.3333 x 1.05 20-j5 x 1.0308 22.22
=
1.014-j0.024
= 1.014 L-1.36°
Vnew= 1.0520°
Vnew=
V2 1.0308 2.22°
ynew= 1.014-1.36
Slack Bus Power
S P-j Q=Vi[Y1 V+Y12 Vz+ Y13 V3]
1.05 2-0° [-j5,8333x 1.05 20°+j2.5 x (1.0308 L2.22°) +
j3.3333 (1.014 2-1.36°)
- 0.0206-j0.1794 p.u
P -0.0206 p.u = 2.06 MW -
Q1 = 0.1794 p.u = 17.94 MVAR
Example 5.7| Resolve Example 5.5, the reactive power constraint on generator bus 2
be changed to 0.04 <Q, <0.01. fGiven Q2 in p.u}
-
Solution:
Step 1: Formulate Y-bus.
-j5.8333 j2.5 j3.3333
Ypus j2.5-j7.5 jS
L
j3.3333 j5 -j8.3333BJ
= 0.025 p.u
[Q exceedsthelimit; Bus 2 will act as load bus,
Q>QQ2 (max)
p.u
. i.e., V2 = 1.020°]
Ya
V
Vnew Y2
x 120°
0.3-j0.0
2.5 1.05 20°-j5
xx 1.05 2
1.020°/2.5
1.018 +j0.04 1.0187 22.25°
Vnew
3
'3Vold
3
-
Y31
V-Y32 V2
-0.4 +j0.2
/8.3335100j3.3333
-j8.3333
x 1.05 20°-j5 (1.018 + J0.04)
1.020°
1.0068-j0.024 = 1.0071 2-1.370
Vnew= 1.05 +j0
Vew = 1.0187 L2.25°
Vey =1.00712-1.37°
3
vold 120
cal Y22 +V, Y23]}
2 -Im { V [V, Y21+V2
--Im( 1.2 [1.05 x (-2 +j5)+ 1.2(5-j14)*1-3 +/9))
= 3.06 p.u.
0 < Q <4, within the limit
. Bus 2 acts as PV bus.
P2 3 p.u., Q 3.06 p.u
Calculate V2:
Y2 V Y2 V
v2 2
V
3-/3.06
3-/14 1.2Z0-2+j5) x 1.05 --3+/9) x 1.0
= 1.236 +j0.1
= 1.24 2 0.08 rad
v 33L
P3-03
V3
Y31 V Ysa V2
=
-1+j4) x1.05-(-3xj9)x(1.196+j0.09)
1.377+j0.3= 1.41 20.22 rad
new
V = 1.0+1.0 [1.377 +j0.3 - 1]
= 1.377 +j0.3
a=1
Power Flow Analysis
new
5.29
V. v2+a "-vold
1.2+ 1.0 [1.196+j0.09 1.2] = 1.196 +j0.09
Example 5.9 Perform Gauss-Seidel load flow
for the system shown in Fig. and the
bus datais given in Table. Determine
bus voltages, slack bus power, line flows, and
transmission line losses.
H 0.04.
0.01
+j0.03
100+j50
-1 -1
0.15-y0.04 0.15 +j0.04 *0.01 +/0.03 +/0.06 0.01+0.03
5.30
Y2 V Y23 Vd
-
2 Y22 V2ld
0.9573-j0.047=0.9584 2-2.81°
Calculate V11ew
160-00 = -1 p.u
P3Pas -PL3 100
Q 50 0.5 p.u
0-QL3 100 -
Y Y, Y3 V Yy2 V
x
16.8966-j47.2014 12-0°--6.8966 +j17.2414) 1.03-
- 1.374j0.7429 p.u
P13 1.374 p.u 137.4 - MW
1
P13Loss = Pi3+P31 142.6 - 137.4 5.2 MW
Loss Q13+Q31 79.19-74.29= 4.9 MVAR
Q3
Example S.10 For the system shown in Fig, find the voltage at receiving bus at the
end of first iteration using Gauss-Seidal method, voltage at sending end is 1.02 20°p.u
Line admitance is 1.0 - j4 p.u, transformer reactance is j0.4 p.u and off nominal turns
ratio is 1.04. Assume VR 1 20° Determine slack bus ponwer, line flows, transformer
flows.
VR 120°
1.02 20 -
Solution:
T j0.4
1-j4
VR= 1
40°
Power Flow Analysis
Step 1: Formulate YbusEquivalent
5.33
circui
Yla 1-j4
-j2.4038
1-4
jo.0924 -j0.09615
-j2.3114 j2.4038 0
bus j2.4038 1-j6.5 -(1-j4)
-(1-j4) 1-j4
Step 2: Initialize bus voltages:
1.0220°
V2 1.020°
V3 1.0 20°
Step 3: Calculate Ve and e
P20, Q2=0 [because no load at bus 2]
Pa Y
V -Y2 V
2
0.0026 x 100 = MW
P -
0
L3 2 S32=
Step 5: Transformer flows:
Bus No.
From To ij series
1
2
S2
series
S21
Yi series
P21tj = 0.9928 20.06| 0.9928
L-0.06°-
2.5
0.00255 +j0,0298
Power Loss
p.u
PLoss
Pi+ Pji-0.00255 +0.00255
QLos
QLoss =0
Q,+9-0.0295 +0.0298 0:0003 p.u
= 0.03 MVAR
Example 5.11 For the sample
system
5.35
connected at all jour shon in the Fig. the generators are
buses, while the
reactive powers are
listed in table. Bus loads are at buses 2 and 3. Values of real ant
2 be a PV bus witlh V, = 1.04
4 are PQ bus. Assuming a p.u and bus 3 and bus
first Gauss Seidal iterations.
flat voltage start,
find bus
And consider the reactive voltages and hus angles the end of
BuS power limit as 0.2 S22 S1.
Pp p.u Op p.u Vp
P.u Remarks
2 1.04 20° Slack bus
0.5
1.04 p.u PV bus
1.0 0.5
4 0.3 PQ bus
-0.1 PQ bus
2-j6
1-3 0.666-j2 1
-j3
2-j6
Solution:
Step 1: Formulate Y-bus matrix. The given
values are admittances
3-j9 2 +j6 -I +j3 0
Ypus
-2 +j6 3.666-j11 0.666+j2 -1 +j3
Lo +j3-0.666 +j2
-1 3.666-j11 -2+j6
-1 +j3 2 +j6 3-j9
Step 2: Initialize bus voltages
--1+j3) x 1.0
1.051 +j0.0339 = 1.0518 21.846°= 1.0518 20.032 rad
6 0.032 rad
VeW=1.04
2 20.032 rad = 1.0395 +j0.0333
= 1.0317-j0.0894 p.u
new
V Y /old Y41 V-Y42 Vew-Y4 Vnew
0.3 +j0.1
-0x -0x 1.04-(-1+j3)x 1.0395+j0.0333
-(-2+j6) x(1.0317-j0.0894)
=
1.0343-j0.015 p.u
Example 5.12 Fig. shows a jfive bus power system.
Each line has an impedance 9
(0.05+j0.15) p.u. The line shunt admittances may be neglected.
specifications are given in Table The bus powerand vollag
Form Ybus
() Find e2, d2, V3» Vg and Vs after the first
iteration using Gauss-Seidal melhod
Assume Dzmin0.2 p.u and Q2max 0.6 p.u.
Power Flow Analysis
5.37
Bus PL
P Bus
L0 1.0 0.5 not specifiednotspecified
1.02
Specification
not specified_
L0 Slack bus
30.5 .2 1.02 PV bus
40.5 0.2 specified PQ bus
5 0.5S
0.2 not specified PQ bus_
not specified PO bus
J 0.05+j0.155
Solution:
Step 1: Form Y
bus
Ybus
2 3
2x1
0.05 +j0.5 0.05 +j0.15
0 0 -1
0.05+j0.15
3x -1 1
0.05+j0.15 *0.05+j0.15 0.05+j0.15 0.05 +j0.15
0 -1 20.05+/0.13
-
1 0
0.05 +j0.15 0.05 +j0.15
0 0
2x1
o.05+j0.15 -1
0.05+j0.15 0.05 +j0.15
-1 0
-1
0.05 +j0.15 0.05+j0.15 0.05 +j0.15 *0.05 +j0.15
2 3 5
120°
,old
VA 1Z0°
old
,
=120°
Step 3: Calculate Q, for the PV bus
Cal
Q2 - ,old
x [Y21 V+Y2 V+ Y»
,new 4 Y24
ncw
+Y2s Vs"
V4+Y2s Vs
1
-
Calculate voltages:
Pa-/2
V2 Y22 old
V
2
Y VY Y24 V-Y2sv"
1_2-j0.2448
6-j18 L
1.02
-
(-2+j6) x 1.02-(-2 +j6) x -(-2+j6) x1| 1
new
Va
old
3
- -Y3 V- Yn V - Y34 V - Y3s Vs J
0(-2
4-712 02 +j6) x 1.02 20.089- x 120
(-2+j6)**
= 0.99 j0.007 p.u
Power Flow Analysis
5.39
new
4 Ya4Lv,old* Y41 V Ya V
V-
-
- Y42
Yas Vs
0.10.2_0-0-(-2+j6)
+j6) (0.99 -j0.007)
=
--2 +j6) x 120°
0.9975 -
j0.046
5
ss L yold*
-
s V -
Ys2 V
ncw
Y$3 V3 - Ys4 V
-0.04-(-2+j6)x 1.02 -
-2+j6) x
1.02
2 0.089 -0 -
(-2+j6) x (0.9975-j0.046)
= 1.0128 -
j0.013 p.u
The most widely used method for solving simultaneous non-linear algebraic equations is
the N-R method. This method is a successive approximation procedure based on
an initial
estimate of the unknown and the use of Taylor's series expansion.
V Ni
PIj
PijO
P1,+jQl, = P, *j (5.25)
Power System Analysis
5.40
Complex power injection at the ih bus P +jQ1,
I,
(PG-PD) +jQG-On)
specificd, the complex power injection isa
Since the bus generation and demand are
specified quantity and is given by, (S5.26)
P(spec)tjQspeo) [PGi(spec)- Ppi (6pce) ]+j[QGitspec)-QDi (spec).
The current entering bus i is given by
N
N
In polar form, (5.27)
YIYy 120,; V, =| V,|48,]
Complex power at bus i,
P-/9= V , = V E Y, V
, i-2,3,..,
for N
Q N V,i4V21+
Lavl 4V]
for i= M+ 1,........,N
Real power mismatch AP P-P
Reactive power mismatch AQ » 9-0
powers are unspecified, voltage and load angle are
In slack bus, real and reactive
Specified. There is no power equation for slack bus.
Therefore slack bus does not enter the
Jacobian matrix.
AP . as,t..*08AoN*ava *i.
OP
*aIvVI 5.31)
Power System Analhsis
5.42
AQ .82* t.. ..TadN A8y+
AV, /VAVNI NI
(5.32)
a02
(5.32) can be multiplied and divided by thei
and
The voltage terms in equation (5.31)
their values and we obtain
respective voltage magnitudes without altering
OP AVN
OP OP, AV2
AP i.A87*
88,
0Q, AVN
0Q
OA8+1V2avj|V2 ...8Q, AV2
+| VNavlIVNl
N a]V»l| V»l * *|
AQ, 88 A02t..
In matrix form,
AP2 OP
082) Valv)
OP2
- P2
IVslalvl
A89
(OPN OPN
APN
AQ AV
082 88 Vlav ...Vav)
(09N QN aQN IAVN
Lao 82)
IV»l
... (5.33)
We can write [A°] =
[J°] [Ax° ], where [°] is the Jacobian matrix.
In the above equation, bus 1
is assumed to be the slack bus.
linearized relationship between The Jacobian matrix gives the
small changes in voltage angle
A/V A8, and voltage magnituac
Vwith a small change in real
and reactive power
APand AQ. We can write u
equation (5.33) as
AP
Power Flow Analysis
+â,-8,)
Vav
V,lV -2|V,FIY| sin ® 2 IV,IIV,IIYg | sin (®
j =1
OP
IV,I |sin (® +8-8,)08 i)
V -IV,|IV,IIY
The terms AP, and AQ, are the difference between the specified and calculated values
Known as the power residues, given by
AP P (spec) P
cal
AQ, Qi (spec)-9
The new estimates for bus voltages are
8 8d+A89od
Vj=V+A
Vew V,od
9.
Obtain state correction vector
Compute Y bus
Calculate Pi and Q;
N
Pi z IViIYij|lV;|cos (®ij *oj -ôj)
J1N
Q - 2 IV;|IYij li Vj| sin (0ij *8j -8,)
No
irefer to
P-V bus
Yes
Calculate Calculate APj and AQj
AP;= Pi (spec)
cal
APPi (spec)-Pi
A0Qi (spec)- a
a Qi(max) Check
or Q-limit
fQi (min)
Form J M
M
Calculate asand a V
Stop
Power System Analysi
5.46
Perform two iteration of Newton Raplhson load Jlow metkod and
Exanmple 5.13|
solution for the given system. Take base MVA as 100.
determine the powerflow
Solution: Line Data :
Bus Half line charging admittance
Line R(p.u) X (p.u)
From To
2
Bus Data
Bus PL QL
90 20
30 10
Ypus
0.3044-j1.816 -0.3044 +j1.88
L-0.3044 +j1.88 0.3044-j1.816 J
[1.842 2-1.405 1.904 21.7314
Y
bus L
1.904 21.7314 1.842 -1.405 J
[Note: Use in rad mode]
Assume the initial value i.e., 8 =0, V= 1.0.
Step 3: Calculate P,
[X]
Q2,
-L
AP2 and AQ2.
cos (1a t82-8,)+|V2l|Y22 cos
P2 V2l IV,lIY2| (2 +82-8,)}
1.0 [1.05x 1.904 cos (1.7314) + 1.842 cos(-1.405)]
= 1.05 x 1.904 (-0.15991) + 1.842 (0.16503)
= -
0.015 p.u
P2(spee) Po2- PL
30
0-100 -0.3 p.u
AP2 p cal
P2 (spec)P2
0.3-(-0.015) = 0.285
- -
Q2 -V, {IV, ||Y21| sin(12+ 81-8,) +|V2l| Y22| sin(02,2 +ô2-ö7)
-1.0 [1.05 x 1.904 sin (1.7314) + 1.0x 1.842 sin
(-1.405)]
-0.157 p.u
AQ2
2 (spec)Q2-0.1-(-0.157)
=0.057
Power Flow Analysis
5.47
Step 4: Form Jacobian matrix.
OP V2aN2
OP2
A82
AP2
V
882 LTvT AQ2.
0P2
082 V2l|V,|IY12l sin (12 +8, -8,) +|V2 lPIY22|x 0
cos
R V2l|V,|IY2l (a +88,)-1V2PIYza|x 0
= 1.05 x 1.904 x cos (1.7314)
= -0.3197
sin (0,2)
IV2la2 -IV,||V2lIY21| sin (®12 t ô-ô,)-2|V2 lY22|
= - 1.05 x 1.904 sin (1.7314)-2 x 1.842 sin (- 1.405)
1.66
Step 5:Compute AX,
Ao2
P2
[AP2|
V2 6Q2 0Q2
082
1.973 0.2897-1 -0.2855
-0.3196 1.66 X0.057J
[ 0.493 -0.086-0.285 0.145 1
0.0949 0.586 J 0.057
L
0.0064 J L
0+-0.145) = 0.145
8 +Aô2 = -
8, 8
V2 10+ 0.0064 = 1.0064
v = V2+|V2l'V17
Power System Analysis
5.48
Iteration 2:Compute mismatch vectors.
+ (-0.145)) + 1.0064x
1.0064 [1.05 x 1.904 cos (1.7314+0
P2 1.842 cos(-1405))
AP2
= - 0.297
P2 (spec)- P -0.3-(-0.297)
= -0.003
-{1.0064 [1.05 x 1.904 x sin (1.7314 +0-(-0.145)) + 1.0064 x 1.842x
02
sin-1.405)}
= - 0.078
AQ cal
Q2 (spec)-Q
= - 0.1 -(-0.078) = - 0.021
Compute Jacobian matrix.
OP2
1.0064 x 1.05 x 1.904 sin (1.7314 +0.145)1.919
82
OP2
V2la
aV2
= 1.05x 1.0064 x 1.904 cos (1.7314 +0.145) +
aQ2
1.00
1.0064 x 1.05x 1.904 x cos (1.7314 +0.145) =-0.605
2
-1.05 x 1.904 sin (1.7314 +0.145) -2 x 1.0064 x 1.842 x sin (-1.405) = 1.76
AV2
1.919 0.015 AP2
0.605 1.76 LAQ2J
LIV21
Example S.14 in
5.49
example 5.13, Bus 2 is voltage
a controlled bus having the ratng
Pe 60 M", V2 1.02 p.u. 10 < Q, < 100 MVAR. Carry out two iterations and
-
1.842 2-80.49
Solution: Y pus 1.90499.2°
1.904299.2° 1.842 2-80.49°
X=[8,] =
0 rad
Compute ,2 in radians
1.842 2-1.405 1.904 2 1.7314
Yu
Ybus
1.904 1.7314 1.8422-1.405
Check for-limit:
Q2 -IV2l{{VlIY21| sin (12+81-8)+|V2||Y22 Sin 2}
-
1.02 {1.05 x 1.904 sin (1.7314) +1.02 x 1.842 sin (-1.405)
-0.1239 p.u
Q2(min)92 <Q2(may)
So the bus acts as generator bus.
Compute AP2:
cos
P IV2l{|V,|IY2l +|V2||Y2lcos(2+82-8,)}
(a t8-5,)
1.02 {1.05x 1.904 cos (1.7314)+1.02 x 1.842 cos (-1.405)}
= (-0.3197+0.3100)
1.02
= -0.009 p.u
AP2 = P2 (spec)- P2 0.6-(-0.009) 0.609 p.u
Form Jacobian matrix:
[OP2
5= IV2l{|V,|IYl+sin (a+ô1-8,)}
= 1.02 x 1.05 x 1.904 sin (0 -0+1.7314)
= 2.013
Compute A8:
482 [JF[AP2]
= 0.303
2.013.x 0.609
= 0+0.303= 0.303 rad
8d+A8,
V"| = 1.02
Power System Analysis
5.50
Iteration 2:
PCal + 1.02 x 1.842 Cos (-1.405))
02 1.05 x 1.904 cos (1.7314 + 0-0.303)
0.606
AP2 (spec)- P2= 0.6-0.606 =- 0.006
'2
Q {1.05 x 1.904 sin (1.7314 + 0-0.303) + 1.02 x 1.842 x Sin (-1.405)
-1.02
- 0.1228
Q (min) <Q2 Q2(mas)
V21{|V,|| Y21
| sin(12 + 81 -82)}
1.02 [1.05 x 1.904 sin (1.7314 +0-0.303) ] = 2.0185
Ad2 [JF[AP2] = 1
20185 x-0.006
-0.003
8new
8 +A8, = 0.303 + (-0.003)
=
820.3 rad 17.19°
V= 1.02 p.u
Example 5.15 In Example 5.13, bus 2 is
a P-V bus having the
V2=1.02 p.. rating PG 60 MW,
10<O2 < 100 MVAR, carry out one iteration. Perform
Raphson method to determine bus voltages. load flow using Newton"
Solution:
Step 1: Form Ybus
1.842
bes- 1.904 2-1.405 1.904 1.7314
21.7314 1.842 812 in rad.
Step 2: Check for Q-limit violation. -1.405 J
a -
IV2l|VY21|sin(12-82+8)+|V2
PIY221sin
22
1.02x 1.05x 1.904 x sin
(1.7314) + 1.022
x 1.842 x sin (-1.405
- 0.1239
Power Flow Analysis
5.51
oa<Q2 (min)
Q2 10
2 (min)100D p.u MVAR
Now bus 2 will act as load bus.
V2 1.0 20
p.u
P2 IV2IIV,IIY2. cos
(2-5,+ö))+|V2FTY22|COs 022
1.0x 1.05 x 1.904 x cos (1.7314) + 1.02
x 1.842 x cos (-1.405)
-0.0157
TVav,
V2
IV,IIIIY12| cos (012-ö2 +8) +2|V,PIY22| cos 02
= 1.0 x 1.05x 1.904 x cos (1.7314) +2 x 1.0x 1.842 x cos (-1.405)
= 0.288
| cos(12 -5 +8,)
06,IV2|IV,|IY21
= 1.0x 1.05 x 1.904 x cos (1.7314)
= - 0.3197
Q2
-|V, |IV2lIY21|sin(612-02*8,)-2|V FIY221sin e,
Vla=
1.842 x sin (1405)
1.05 x 1.904 sin (1.73 14)-2 10x
x
=1.0 x-
=1.66
Power System Analysi.
5.52
Step 5: Calculate A8 and A V.
AV2 1.973-0.3197-
LTV1J 0.288 1.66. LAQ2
0.288 10.61577
1.66
3.367 L-0.3197 1.973 J L 0.2239J
0.493 0.0855 1 0.6157
L-0.095 0.586J Lo.2239 J
0.3227 rad
0.073 p.u
8 82 +A8 = 0+0.3227 0.3227 rad 18.499
AV2
V- +|Vl = 1.0+0.073= 1.073
new = 1.073218.49°
Example 5.16] Consider the three-bus system of Fig Each of the three lin
series impedance of 0.02 + j0.08 p.u anda total shunt admittance of jo.02 p.u. The
specified quantities at the buses are tabulated below:
-1.04 0 120°. 2
1.04 20°
QGs( 15 + j0.5
Solution:
0.02+jo.08
1 -1
0.02 +j0.08 0.02 +j0.08 0.02 +j0.08 0.02 +j0.08
AP P3 (spec)- P3cal = -
1.5-(0.115) = -
1.615 p.u
AQ2
2spec)2 1--0.929) =
1.929 p.u
Jacobian Matrix
oP2
=-| V2|V3||Y23| sin (23 +8,-85)
- 1.0x 1.04 x 12.12 sin (1.816) = -
12.23
Power Fow Analysis
5.55]
OP2
IV2 v, 2x|V2F|Y2l cos +| V,||V, ||Y12 cos(012 +o02)*
OP3
V2lav -IV2l|V3l|Y23|cos(23+®3-8,)
-1.0 x I.04 x 12.12x cos (1.816) =-3.05
= 22.59
cos (
V2||V, ||Y121 cos (®21t 81 -8)+|\V2l|V3||¥23 +83-8,)
+ I.0x 1.04 x 12.12 cos (1.816)
= 1.0x 1.04 x 12.12 cos (1.816)
-6.11
Y23 cos (®23-®3-8,)
-IV2||V3I
06,-I I
1.04 x 12.12
cos (1.816)
-1.0x }
= 3.06
POwe yc nalysis
ysis
5.56
OP
P2 oP2
AP2
APs oP OP
Vsav AV2
LA02J LIV21J
ne load flow studies are very important for planning, economic scheduling, control and
operations of existing systems as well as planning its future Expansion depends upon
knowing the effect of interconnections, new loads, new generating stations, or new
transmission lines, etc., before they are installed. The information of load flow is
essential for analyzing the effective alternative plans for system expansion to mee
increase load demand.
2. Why the load flow studies are important for planning the existing system as well as its
Suture expansion ?
The load flow studies are very important for planning, economic scheduling, control
and operalions of existing systems as well as planning its future expansion depends upon
knowing the effect of interconnections, new loads, new generating stations, or new
transmission lines, etc., before they are installed.
3. Whay bus admittance matrix is used in Gauss-Seidal instead of bus impedance matrix
Using bus admittance matrix is amenable to digital computer analysis, because it
could be formed and modified for network changes in subsequent cases, and requires
less computation time and memory.
4. What are the resuls obtained from load flow? (or) Why power flow analysis is made
(or) What are the information that are obtained from a power flow study?
The information obtained from the load flow studies are the magnitude and phase
angle of voltages at each bus, active and reactive power flow in
each line, and power
loss in the line. It also gives the initial conditions of the
system when the transien
behaviour of the system is to be studied.
5. What is the needfor power flow or load flow study ?
Load flow analysis is performed on a symmetrical
steady-state operating condition o
a power system under normal mode of operation. The
solution of load flow gives bu
voltages and line/transformer power flows for a given load
condition. This information
essential for long term planning and operational planning.
6. What are the data required för a loadflow study?
The network contiguration, complex power
schedules demands for all buses, real poower
generation and voltage magnitudes of all agnitude
bus.
the P-V busés and voltage mag
of the slack
PowerloW Analysis
P-iQ V
j=l
Y, V,; i=1,2,., N
10. What are the four quantities that are associated with each bus in a system?
Real power.
Reactive power.
Voltage magnitude.
Phase angle of voltage.
11. How the buses in the power system are classified ?
The buses are classified based on the variables specified. There are three types of
buses.
1. Slack bus or swing bus or reference bus.
N
cos (, +8,-8,)
:P, IV,PIY|
cos
t J
2IVYG|Vl
N
(,+ô,-8,)
Q -I V,PIY,lsinBju-2VYylIsin
power flow analysis.
20. Hrite
an equation inn loop frane of referencejor
VLoop lZL0op L'Loop
matrix. sri
Bus impedance
where [ Z/oon]
Voltage matrix.
[VLoop
Current matrix.
Loop=
Power System
5.62 Analysi
vnew
Vold +a V -vod
where V = Voltage value obtained in
the previous iteration.
o=Acelerationfactor.
V = New value of voltage obtained
in the current iteration.
25. In which methodfor solving load flow problem
acceleration factor is used
Gauss-Seidal Method
26. When the generator bus is treated as load
bus ?
If Q (max)» Substitute
QQi (max)
If ,<Q(min) Substitute Q,T Q
(min)
i.e., the rea ve power of a generator
bus violates the specified P.V
bus will act as load bus. limits, then the n
wer Flow Analysis
-
8. What is Jacobian matrix?
In matrix form,
AP
(P
1V
APN
082
AQ9 (00 00,:(D0, aQ, AV2
OIV21
LA0L6)
(09N (0000 v
Wecan write [Au°] [J°] [Ax°], where [°] is the Jacobian matrix.
In the above equation, bus is assumed to be the slack bus. The Jacobian matrix
1
gives the linearized relationship between small changes in voltage angle A8, and voltage
magnitude [AV,|with a small change in real and reactive power AP and AQ.
.What are the disadvantages of Gauss-Seidal method?
-1. Requires large number of iterations to reach convergence.
suitable for large systems.
2. Not