This document provides calculations for the fire hose system for a proposed residential building with 2 basement floors, 1 ground floor, 4 below-grade floors, and 18 above-grade floors in Doha, Qatar. It includes general project data, water supply test data, calculation project data, input data for fire hose nodes and pipes, and output data summarizing the node groupings and flows. The calculations were performed using the FIRE hydraulic calculation program to ensure the fire hose system can provide a minimum flow of 0.15 gpm/ft2 with a residual pressure of at least 100 psi at all nodes.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
62 views

04 - Demand Mode Landing Valve in at Basement

This document provides calculations for the fire hose system for a proposed residential building with 2 basement floors, 1 ground floor, 4 below-grade floors, and 18 above-grade floors in Doha, Qatar. It includes general project data, water supply test data, calculation project data, input data for fire hose nodes and pipes, and output data summarizing the node groupings and flows. The calculations were performed using the FIRE hydraulic calculation program to ensure the fire hose system can provide a minimum flow of 0.15 gpm/ft2 with a residual pressure of at least 100 psi at all nodes.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

PROPOSED (2B+G+4BES.

+18) FLOORS) RESIDEN


Fire Hose System Reports

for

SHEIKH ABDULAZIZ ABDULRAHMAN AL-THANI

AL-DAFNA - DOHA
DOHA

Prepared By:

GULF CONSULTING GROUP


GULF CONSULTING GROUP
DOHA
DOHA,QATAR

13 DEC, 2009
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Class nr 666 PROPOSED (2B+G+4BES.+18) FLOORS) RESIDEN Page 2

General Project Data Report


General Data

Project Title: PROPOSED (2B+G+4BES.+18) DEMAND MODE BASEMENT


Project File Name:
FLOORS) RESIDEN LANDING VA..fiw
Designed By: GULF CONSULTING GROUP Date: 13 DEC, 2009
Code Reference: NFPA -13 Approving Agency: CIVIL DEFENCE
CALCULATION FOR LANDING VALVE ORDINARY HAZARD AT 1ST BASEMENT DEMAND MODE
Client Name: SHEIKH ABDULAZIZ ABDULRAHMAN
Phone:
AL-THANI
Address: AL-DAFNA - DOHA City, State Zip Code: DOHA
Company Name: GULF CONSULTING GROUP Representative: AHMED M.SAMI
Company Address: DOHA City And State: DOHA,QATAR
Phone:
Building Name: PROPOSED (2B+G+4BES.+18) SHEIKH ABDULAZIZ ABDULRAHMAN
Building Owner:
FLOORS) RESIDEN AL-THANI
Contact at Building: GULF CONSULTING GROUP Phone at Building:

Project Data

Description Of Hazard: Ordinary 1 Hose System Type: Wet


Design Area Of Water Application: 120 ft² Maximum Area Per Hose: 130 ft²
Default Hose K-Factor: 25.00 K Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 250.00 gpm Outside Hose Stream Allowance: 500.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm

Hose Specifications
Make: VIKING Model: VK-
Size: 2.5" Temperature Rating: 155 F

Water Supply Test Data

Source Of Information: GOVERNEMET


Test Hydrant ID: 38 Date Of Test: 13 DEC, 2009

Hydrant Elevation: 0 ft Static Pressure: 0.00 psi


Test Flow Rate: 0.00 gpm Test Residual Pressure: 0.00 psi
Calculated System Flow Rate: 1253.87 gpm Calculated Inflow Residual Pressure: 133.07 psi
Available Inflow Residual Pressure: 0 psi

Calculation Project Data

Calculation Mode: Demand


HMD Minimum Residual Pressure: 100.00 psi Minimum Desired Flow Density: 0.15 gpm/ft²
Maximum Water Velocity: 23.00 ft/s Maximum Frictional Loss / 100 feet: 20.00 psi
Number Of Active Nodes: 10
Number Of Active Pipes: 9 Number Of Inactive Pipes: 0
Number Of Active Hoses: 2 Number Of Inactive Hoses: 0

Active Version 6.0.168 1000 Pipe Capacity


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Class nr 666 PROPOSED (2B+G+4BES.+18) FLOORS) RESIDEN Page 3

Fire Hose Input Data


Node Input Data

Fixed
Hose KFactor Pressure Node Elevation
Node No. Node Description Area Group Discharge
(K) Estimate (psi) (feet)
(gpm)

15 Hose 25.00 103.45 18.04 0.00

16 Hose 25.00 100.00 18.04 0.00

17 Fixed N/A 112.64 24.60 500.00

18 No Discharge N/A 113.60 24.61 0.00

19 Fixed N/A 114.27 24.61 250.00

20 No Discharge N/A 117.05 24.60 0.00

21 No Discharge N/A 124.32 12.50 0.00

22 No Discharge N/A 128.53 6.00 0.00

23 No Discharge N/A 129.54 6.00 0.00

24 No Discharge N/A 133.07 0.00 0.00

Active Version 6.0.168 1000 Pipe Capacity


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Class nr 666 PROPOSED (2B+G+4BES.+18) FLOORS) RESIDEN Page 4

Fire Hose Input Data


Pipe Input Data

Nominal Nominal Fitting Total CFactor


Beg. End. Type Fitting
Pipe Description Diameter Length Length Length (gpm/inch-
Node Node Group Data
(inch) (feet) (feet) (feet) psi)

15 18 SCHED 40 WET STEEL 2.500 0 3L 46.56 12.00 58.56 120

16 17 SCHED 40 WET STEEL 2.500 0 4L 56.17 16.00 72.17 120

17 18 SCHED 40 WET STEEL 8.000 0 T 141.83 35.00 176.83 120

18 19 SCHED 40 WET STEEL 8.000 0 T 36.75 35.00 71.75 120

19 20 SCHED 40 WET STEEL 8.000 0 3L 158.80 39.00 197.80 120

20 21 SCHED 40 WET STEEL 8.000 0 3L 105.30 39.00 144.30 120

21 22 SCHED 40 WET STEEL 8.000 0 TBGC 3.00 96.00 99.00 120

22 23 Alarm Check Valve 1.000 Loss

23 24 SCHED 40 WET STEEL 8.000 0 BGC 5.00 61.00 66.00 120

Active Version 6.0.168 1000 Pipe Capacity


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Class nr 666 PROPOSED (2B+G+4BES.+18) FLOORS) RESIDEN Page 5

Fire Hose Output Data


Overall Node Groupings Output Data

Pipe Segment Pipe Pipe Hose Flow Fixed Flow Beg. Node Imbalance
Beg. End. Type At Beg. Node Out (+) In (-) Residual Flow At Beg.
Flow Rate (gpm)
Node Node Group (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)

15 18 0 -253.95 254.27 0.00 0.00 103.45 0.32140

16 17 0 -249.34 250.00 0.00 0.00 100.00 0.65833

17 16 0 249.34 0.00 500.00 0.00 112.64 -0.58116


17 18 0 -749.92

18 15 0 253.95 0.00 0.00 0.00 113.60 -0.00012


18 17 0 749.92
18 19 0 -1003.87

19 18 0 1003.87 0.00 250.00 0.00 114.27 0.00003


19 20 0 -1253.87

20 19 0 1253.87 0.00 0.00 0.00 117.05 0.00000


20 21 0 -1253.87

21 20 0 1253.87 0.00 0.00 0.00 124.32 0.00000


21 22 0 -1253.87

22 21 0 1253.87 0.00 0.00 0.00 128.53 1.04381


22 23 0 -1252.83

23 22 0 1252.83 0.00 0.00 0.00 129.54 -1.04381


23 24 0 -1253.87

24 23 0 1253.87 0.00 0.00 0.00 133.07

Active Version 6.0.168 1000 Pipe Capacity


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Class nr 666 PROPOSED (2B+G+4BES.+18) FLOORS) RESIDEN Page 6

Fire Hose Output Data


Overall Pipe Output Data

F. L./ft Pipe-Len.
Beg. Nodal Hose/Fix Residual Nom. Dia. Q (gpm) PF-(psi) PE-
Elevation (psi/ft) Fit-Len. Tot-
End. KFactor (K) Discharge Pressure Inside Dia. Velocity (psi) PV-
(feet) Fittings Len. (ft)
Node (gpm) (psi) C-Value (fps) (psi)
Type-Grp

16 25.00 18.04 250.00 100.00 2.50 249.34 0.21453 56.17 15.482


17 0.00 24.60 500.00 112.64 2.469 16.71 4L 16.00 -2.838
SCHED 40 WET STEEL 120 0 72.17 0.008

15 25.00 18.04 254.27 103.45 2.50 253.95 0.22192 46.56 12.995


18 0.00 24.61 0.00 113.60 2.469 17.02 3L 12.00 -2.841
SCHED 40 WET STEEL 120 0 58.56 0.008

17 0.00 24.60 500.00 112.64 8.00 749.92 0.00543 141.83 0.960


18 0.00 24.61 0.00 113.60 7.981 4.81 T 35.00 -0.003
SCHED 40 WET STEEL 120 0 176.83 0.000

18 0.00 24.61 0.00 113.60 8.00 1003.87 0.00931 36.75 0.668


19 0.00 24.61 250.00 114.27 7.981 6.44 T 35.00 0.000
SCHED 40 WET STEEL 120 0 71.75 0.000

19 0.00 24.61 250.00 114.27 8.00 1253.87 0.01406 158.80 2.780


20 0.00 24.60 0.00 117.05 7.981 8.04 3L 39.00 0.003
SCHED 40 WET STEEL 120 0 197.80 0.000

20 0.00 24.60 0.00 117.05 8.00 1253.87 0.01406 105.30 2.028


21 0.00 12.50 0.00 124.32 7.981 8.04 3L 39.00 5.239
SCHED 40 WET STEEL 120 0 144.30 0.000

21 0.00 12.50 0.00 124.32 8.00 1253.87 0.01406 3.00 1.391


22 0.00 6.00 0.00 128.53 7.981 8.04 TBGC 96.00 2.815
SCHED 40 WET STEEL 120 0 99.00 0.000

22 ACV 6.00 128.53 1252.83


23 1.00 psi 6.00 129.54

23 0.00 6.00 0.00 129.54 8.00 1253.87 0.01406 5.00 0.928


24 0.00 0.00 0.00 133.07 7.981 8.04 BGC 61.00 2.598
SCHED 40 WET STEEL 120 0 66.00 0.000

Active Version 6.0.168 1000 Pipe Capacity


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Class nr 666 PROPOSED (2B+G+4BES.+18) FLOORS) RESIDEN Page 7

Fire Hose Output Data


Overall Hose Output Data

Node Residual Flowing Hose


Flowing Hose Area Group Hose KFactor Flowing Area
Elevation Pressure (psi) Density Discharge
Node No. Code (K) (ft²)
(feet) (gpm/ft²) (gpm)

15 25.00 18.04 103.45 130.00 1.956 254.27


Sub Totals For Non-Group 130.00 1.956 254.27

16 25.00 18.04 100.00 130.00 1.923 250.00


Sub Totals For Non-Group 130.00 1.923 250.00

Totals For All Groups 260.00 1.940 504.27

Active Version 6.0.168 1000 Pipe Capacity


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Class nr 666 PROPOSED (2B+G+4BES.+18) FLOORS) RESIDEN Page 8

Fire Hose Output Summary


Hydraulically Most Demanding Hose Node

HMD Hose Node Number: 16


HMD Actual Residual Pressure: 100.00 psi
HMD Actual GPM: 250.00 gpm

Hose Summary

Hose System Type: Wet


Specified Area Of Application: 120.00 ft²
Minimum Desired Density: 0.150 gpm/ft²
Application Average Density: 4.202 gpm/ft²
Application Average Area Per Hose: 60.00 ft²
Hose Flow: 504.27 gpm
Average Hose Flow: 252.14 gpm

Flow Velocity And Imbalance Summary

Maximum Flow Velocity ( In Pipe 15 - 18 ) 17.02 ft/sec


Maximum Velocity Pressure ( In Pipe 15 - 18 ) 0.01 psi

Allowable Maximum Nodal Pressure Imbalance: 0.1000 psi


Actual Maximum Nodal Pressure Imbalance: 0.0827 psi
Actual Average Nodal Pressure Imbalance: 0.0675 psi
Actual Maximum Nodal Flow Imbalance: -1.0438 gpm
Actual Average Nodal Flow Imbalance: 0.3649 gpm

Overall Network Summary

Number Of Unique Pipe Sections: 9


Number Of Flowing Hoses: 2

Pipe System Water Volume: 380.94 gal

Hose Flow: 504.27 gpm


Fixed Flow: 750.00 gpm
Total System Demand Flow: 1254.27 gpm

Minimum Required Residual Pressure At System Inflow Node: 133.07 psi


Demand Flow At System Inflow Node: 1253.87 gpm

Active Version 6.0.168 1000 Pipe Capacity


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Class nr 666 PROPOSED (2B+G+4BES.+18) FLOORS) RESIDEN Page 9

Fire Hose Output Data


Hydraulic Supply/Demand Graph

200

180

160

140
Pressure psi

120

100

80

60

40

20

0
0
2 4 6 8 10 12 14 16 18 20
Flowrate(x100) gpm

Adjusted Hydrant Data


Static Pressure: 0 psi
Test Residual Pressure: 0 psi
Test Flow Rate: 0 gpm

Demand Point Data


Calculated Residual Pressure: 133.07 psi
Calculated Flow Rate: 1253.88 gpm
Excess Available Inflow Residual Pressure: -133.07 psi

Active Version 6.0.168 1000 Pipe Capacity