Profibus-DP Slave Unit: Ordering Information

This document provides information on the Profibus-DP Slave Unit CQM1-PRT21, which allows CQM1(H) PLCs to communicate via Profibus-DP. The unit supports baud rates from 9.6 kbit/s to 12 Mbit/s, has a configurable slave address from 0 to 99, and can be configured for 2, 4, 6 or 8 I/O words. It provides status indicators and a communication status relay output. Specifications include operating temperature range, storage temperature, humidity tolerance, EMC compliance, I/O refresh time, current consumption and weight.

Uploaded by

p da
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
56 views4 pages

Profibus-DP Slave Unit: Ordering Information

This document provides information on the Profibus-DP Slave Unit CQM1-PRT21, which allows CQM1(H) PLCs to communicate via Profibus-DP. The unit supports baud rates from 9.6 kbit/s to 12 Mbit/s, has a configurable slave address from 0 to 99, and can be configured for 2, 4, 6 or 8 I/O words. It provides status indicators and a communication status relay output. Specifications include operating temperature range, storage temperature, humidity tolerance, EMC compliance, I/O refresh time, current consumption and weight.

Uploaded by

p da
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Profibus-DP Slave Unit CQM1-PRT21

Profibus-DP Slave for CQM1(H) PLCs


No PLC settings need to be made.
Auto-detect all Profibus-DP baud rates from
9.6 kbit/s to 12 Mbit/s.
Slave address setting, selectable from 0 to 99.
Support and indication of Profibus-DP broadcast
functions (Sync/Freeze/Clear).
Communication status available externally via
relay output.
Configurable for 2, 4, 6 or 8 words.

Ordering Information
Product Code Description
CQM1-PRT21 Profibus-DP slave unit for CQM1(H) PLCs

Specifications
Communication Specification
Applicable standard EN 50170 vol. 2
Station type Modular station, max. 1 module
Configurable with I/O-modules of 2, 4, 6 or 8 words
Data consistency By word
Bus connector 9-pin female sub-D connector (RS-485 Profibus connector)
Bus termination External
Baud rate (auto-detect) 9.6 / 19.2 / 45.45 / 93.75 / 187.5 / 500 kbit/s, 1.5 / 3 / 6 / 12 Mbit/s
Profibus address range 0 to 99, Remote setting not supported
Communication cable Type A (EN 50170 vol. 2)
Minimum slave interval time 0.5 ms
Watchdog base 10 ms, 1 ms selectable by parameter setting
Supported DP functions S Data_Exchange
S Slave_Diag
S Set_Prm
S Chk_Cfg
S Global_Control (SYNC, FREEZE, CLEAR)
S Get_Cfg
S RD_Inp
S RD_Outp
Profibus-DP GSD file OC_054D.GSD

1
CQM1-PRT21 CQM1-PRT21

Unit Specification
Host PLC system CQM1, CQM1H
Switch settings Number of I/O words
Motorola/Intel data format
Profibus-DP address
LED indicators Unit status : RUN (green LED), ERR (red LED)
Network status : COMM (green LED), BF (red LED)
WD OFF (yellow LED), CLEAR (yellow LED)
SYNC (yellow LED), FREEZE (yellow LED)
No. of occupied words Configurable by DIP switches (see note)
S 2 words in + 2 words out
S 4 words in + 4 words out
S 6 words in + 6 words out
S 8 words in + 8 words out
I/O refresh time Max. 0.16 ms
(data exchange with CPU)
Current consumption (max) 350 mA at 5 V DC (at CQM1 I/O bus)
Weight 170 g
Storage temperature -20 to +75 °C
Operating temperature 0 to +55 °C
Operating humidity 10% to 90% (non-condensing)
EMC compliance EN50081-2, EN61131-2
Circuit configuration Communication status output (COMM) terminal
CQM1-PRT21

Internal
circuit

1 A at 24 VDC max.

Note: The CQM1-PRT21 can be mounted to any CQM1- or CQM1H-series CPU. The maximum amount of I/O data that can be exchanged
with the CPU depends on the selected CPU type, and on the number and type(s) of any additional I/O unit(s). To operate with the Unit’s
maximum I/O capacity, a CQM1H-CPU51 or CQM1H-CPU61 is required.

Communication status output


The COMM relay contact output indicates if data exchange with the Profibus-DP master unit is active. This signal can be connected to a PLC
input or external signalling device. It is recommended to use this information in the PLC to judge the validity of the received data.

ON state S I/O data exchange with the Profibus-DP master is active.


OFF state S PLC Power OFF
S Fatal error in PLC CPU or I/O bus.
S No I/O data exchange with Profibus-DP master (check LED indication).
Relay type OMRON G6H-2F, non-replaceable
Maximum load 1 A at 24 V DC
ON/OFF delay less than 10 ms
Connector Phoenix MSTBA 2,5/2-G

2
CQM1-PRT21 CQM1-PRT21

Nomenclature
Top slide-lock
Unit status indicators
S RUN (green)
S ERR (red)

Profibus-DP status indicators


S COMM (green)
S BF (red)
S WD OFF (yellow)
S CLEAR (yellow)
S SYNC(yellow)
S FREEZE (yellow)
Unit setting DIP switches (inside)
S I/O size selection
S Intel/Motorola mode
Profibus-DP address switches
S 2 rotary switches (00-99)
Communication status output
S Relay contact output
Profibus-DP bus connector
S RS-485
DIN-rail lock
Bottom slide-lock

Dimensions

3
CQM1-PRT21 CQM1-PRT21

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.


To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

Cat. No. P907-E2-01 In the interest of product improvement, specifications are subject to change without notice.
OMRON EUROPE B.V.
Wegalaan 67-69
2132 JD Hoofddorp
The Netherlands Printed in The Netherlands
Phone:+31 23 568 13 00
Fax: +31 23 568 13 88

You might also like