MV Switchgear CT Inspection and Test Procedure: October 2019
MV Switchgear CT Inspection and Test Procedure: October 2019
net/publication/336373937
CITATIONS READS
0 315
2 authors:
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Ramadan Ali on 10 October 2019.
TABLE OF CONTENTS
1. Visual Inspection
2. Insulation resistance test
3. Winding resistance measurement
4. Polarity test
5. Ratio test by current primary injection
6. Magnetizing current test (minimum 2 points above )
7. Loop resistance measurement test (burden test)
8. Phase identification test
9. Verify secondary circuits, terminals, shorting/isolating links by primary injection
10. High voltage test.
11. Single point earthing check
12. Demagnetize CT cores after all tests
1. Visual Inspection
♦ Inspect for physical damage / defects
♦ Check nameplate information for correctness
♦ Check that all grounding cables are securely connected
♦ Check color coded for secondary wiring and size of wires against specs.
♦ Check proper lugs has been used in termination
♦ Check CT’s location physically and secondary terminal labeling printed
S1
MEGGER
S2
P2
INSULATION TEST ARRANGEMENT
P1
S1
MILIOHMMETER
S2
P2
CT RESISTANCE MEASURING ARRANGEMENT
4. Polarity Test
♦ Check the CT polarities on the Terminals as per the Schematic Drawing in the LV -compartment for
correct polarity.
P1
S1
+
SENSITIVE
SWITCH
AMMETER
A
S2
-
+
BATTERY
-
P2
CT POLARITY TEST ARRANGEMENT
P1
S1
AMMETER A
PRIMARY S2
INJECTION
TEST SET
P2
CT RATIO TEST ARRANGEMENT
P1
STEP UP
VARIAC TRANSFORMER S1
A
AC SUPPLY V
S2
P2
PLOTTING OF THE MAGNETIZATIOM CURVE
ARRANGEMENT
S1
S1
RELAY
S2
RELAY V
S2
A
MILIOHMMETER
CURRENT
SOURCE
P2 P2
LOOP RESISTANCE MEASURING ARRANGEMENT BURDEN TEST ARRANGEMENT