This document provides a relay setting chart for the 33kV switchyard of a 1x18MW co-generation power plant project in Kenya. It lists the recommended settings for various protection devices in the 33kV transformer control and relay panel, including overcurrent, earth fault, directional, under/over voltage, under/over frequency, and other protections. The settings are provided for numerical relays from manufacturers MICOM and are intended to coordinate protection for the transformer and interconnection equipment in the switchyard.

Uploaded by

nadalllabeed
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
586 views

Relay Setting Chart

This document provides a relay setting chart for the 33kV switchyard of a 1x18MW co-generation power plant project in Kenya. It lists the recommended settings for various protection devices in the 33kV transformer control and relay panel, including overcurrent, earth fault, directional, under/over voltage, under/over frequency, and other protections. The settings are provided for numerical relays from manufacturers MICOM and are intended to coordinate protection for the transformer and interconnection equipment in the switchyard.

Uploaded by

nadalllabeed
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

CLIENT M/s.

KWALE INTERNATIONAL SUGAR COMPANY LTD, KENYA

CONSULTANT M/s. JP MUKHERJI & ASSOCIATES PVT LTD, PUNE, MH

EPC CONTRACTOR M/s. ISGEC HEAVY ENGINEERING LTD, NOIDA, UP

PROJECT 1x18 MW CO-GEN POWER PLANT

EPC ELECTRICAL
IKE ELECTRIC PVT. LTD.
CONTRACTOR
601 - 602, MARIEGOLD NECO GARDENS,
VIMAN NAGAR,
PUNE - 411 014
MAHARASHTRA
INDIA
PHONE - 020 - 66290300 / 301
TELEFAX - 020 - 66290302

DOCUMENT TITLE RELAY SETTING CHART FOR 33KV SWITCHYARD

DOCUMENT NO. IKE-ISGEC-KWL61-DOC-233

REVISION 00

DATE 11.10.2013

NO. OF SHEETS PREPARED BY CHECKED BY APPROVED BY

**Sheets (Including
ARD KBD ABH
Title Sheet)
RELAY SETTING CHART- 33KV SWITCHYARD RELAY
Sr.No Protection Description Type ref. Setting Range Recommended Setting Remarks
I 33KV Transformer Control and Relay Panel
1 87GT, 64R, 99 Numerical Transformer MICOM P 632 Differential Protection (87GT)
Protection Relay Idiff>=0.1-2.5 Iref Idiff>:0.1 LV: CTR: 500/1A
Idiff>=2.5-30 Iref HV: CTR: 200/1 A
Idiff>>>=2.5-30 Iref NCTR: *** A
m1: 0.15-1.5 m1: 0.2
m2: 0.15-1.5 m2: 0.7
IR,m2 (1.5-10.0 Iref) 4
Op.del, trip signal:0-100S

Restricted earthfault protection(64R)


Effective setting: 10% 10%In
High Impedance relay NCTR: *** A
Stabilising resistor
(0-1000) Ohm Rst: 200 ohm

2 50/51 Numerical MICOM P341 Overcurrent protection (51) IDMT


50N/51N Interconnection In: 0.08-4In 0.75*In characterictics
67/67N, 50LBB Protection Relay T: 0-100 sec 0.1 sec 3 Sec Curve
78, 27Z, 59, 81
60, 81R, 99, 27 Inst. Overcurrent protection (50)
In: 0.08-32In 6*In CTR: 200/1A
T: 0-100 sec 0 sec (Inst) PTR: 33KV/110V

Earth fault protection (51N) IDMT


Ie: 0.08-4In 0.2*In characterictics
T: 0-100 sec 0.1 Sec 3 Sec Curve

Inst.Earth fault protection (50N)


Ie: 0.08-4In 0.3*In
T: 0-100 sec 0.5 sec

1 of 10
PREPARED BY: ARD CHECKED BY: KBD APPROVED BY: ABH
RELAY SETTING CHART- 33KV SWITCHYARD RELAY
Sr.No Protection Description Type ref. Setting Range Recommended Setting Remarks
33KV Transformer Control and Relay Panel Dir. Overcurrent protection (67)
In: 0.08-32In 0.75*In RCA: 30 deg
T: 0-100 sec 0.35 sec

Dir. Earth fault protection (67N)


Ie: 0.08-32In 0.1*In RCA: 45 deg
T: 0-100 sec 0.35 sec

Under volatge protection (27)


U<: 10-120V 80 V
T: 0-100 sec 2 sec

Over voltage protection (59)


U>: 60-185V 121 V
T: 0-100 sec 3 sec

Under frequency protection (81U)


f<: 45-65Hz 47.7 Hz PTR: 33KV/110V
T: 0-100 sec 2 sec

Over frequency protection (81O)


f>: 45-65Hz 52 Hz
T: 0-100 sec 2 sec

Local Breaker back-up protection (50LBB)


In: 0.4-4*In 1*In CTR: 200/1A
Time delay 0.3 sec

df/dt protection (81R)


df/dt: 0.1-10Hz/sec 4 Hz/ sec
T: 0-100 sec Inst Inst

2 of 10
PREPARED BY: ARD CHECKED BY: KBD APPROVED BY: ABH
RELAY SETTING CHART- 33KV SWITCHYARD RELAY
Sr.No Protection Description Type ref. Setting Range Recommended Setting Remarks
33KV Transformer Control and Relay Panel Dead band lower frequency
45-65Hz 49 Hz

Dead band upper frequency


45-65Hz 51 Hz

Voltage Balance Relay (60)


***
***

Overfluxing Protection Relay (99)


***
***

Vector surge protection (78)


dv/dt: 2-30 deg 7 deg

Standby Earth fault protection (51G)


Ie: 0.08-4In 0.3 * In CTR: 200/1 A
T: 0-100 sec 0.3 Sec IDMT curve (3 sec)

3 50/51 Numerical MICOM P111L IDMT overcurrent protection (51)


50N/51N protection relay In: 0.08-4In 0.9 * In
(LV side of GT) TMS: 0.025-1 0.1 Sec IDMT curve (3 sec)

Inst. Overcurrent protection (50)


In: 0.08-32In 6 * In CTR: 500 / 1 A
T: 0-100 sec 0 Sec PTR: 11kV / 110 V

3 of 10
PREPARED BY: ARD CHECKED BY: KBD APPROVED BY: ABH
RELAY SETTING CHART- 33KV SWITCHYARD RELAY
Sr.No Protection Description Type ref. Setting Range Recommended Setting Remarks
33KV Transformer Control and Relay Panel IDMT Earth fault protection (51N)
Ie: 0.08-4In 0.2 * In IDMT curve (3 sec)
TMS: 0.1-1 0.3 Sec

Inst.Earth fault protection (50N)


Ie: 0.08-4In 0.3 * In
T: 0-100 sec 0.3 Sec

4 27, 59 Numerical MICOM P921 Under voltage protection (27)


59D protection relay U<: 10-120V 0.8
T: 0-100 sec 0.5 sec

Over voltage protection (59)


U>: 60-185V 1.1
T: 0-100 sec 0.5 sec

Neutral displacement protection (59DLV)


V: 5.4 -20V 5.4 V
TMS 0.1 sec

NOTE: a) All settings are referred with respect to secondary values.


b) All the other functions which are not mentioned in this chart shall be disabled.

4 of 10
PREPARED BY: ARD CHECKED BY: KBD APPROVED BY: ABH
CLIENT M/s. KWALE INTERNATIONAL SUGAR COMPANY LTD, KENYA

CONSULTANT M/s. JP MUKHERJI & ASSOCIATES PVT LTD, PUNE, MH

EPC CONTRACTOR M/s. ISGEC HEAVY ENGINEERING LTD, NOIDA, UP

PROJECT 1x18 MW CO-GEN POWER PLANT

EPC ELECTRICAL
IKE ELECTRIC PVT. LTD.
CONTRACTOR
601 - 602, MARIEGOLD NECO GARDENS,
VIMAN NAGAR,
PUNE - 411 014
MAHARASHTRA
INDIA
PHONE - 020 - 66290300 / 301
TELEFAX - 020 - 66290302

DOCUMENT TITLE RELAY SETTING CHART FOR 132KV SWITCHYARD

DOCUMENT NO. IKE-ISGEC-KWL61-DOC-133

REVISION 00

DATE 11.10.2013

NO. OF SHEETS PREPARED BY CHECKED BY APPROVED BY

**Sheets (Including
ARD KBD ABH
Title Sheet)
RELAY SETTING CHART- 132KV SWITCHYARD RELAY
Sr.No Protection Description Type ref. Setting Range Recommended Setting Remarks
I 132KV Transformer Control and Relay Panel
1 87GT, 64R, 99 Numerical Transformer MICOM P 632 Differential Protection (87GT)
Protection Relay Idiff>=0.1-2.5 Iref Idiff>:0.1 LV: CTR: 1500/1A
Idiff>=2.5-30 Iref HV: CTR: 150/1 A
Idiff>>>=2.5-30 Iref NCTR: *** A
m1: 0.15-1.5 m1: 0.2
m2: 0.15-1.5 m2: 0.7
IR, m2 (1.5-10.0 Iref) 4
Op.del, trip signal:0-100S

Restricted earthfault protection(64R)


Effective setting: 10% 10%In
High Impedance relay NCTR: *** A
Stabilising resistor
(0-1000) Ohm Rst:200 ohm

2 50/51 Numerical MICOM P341 Overcurrent protection (51) IDMT


50N/51N Interconnection In: 0.08-4In 0.75*In characterictics
67/67N, 50LBB Protection Relay T: 0-100 sec 0.1 3 Sec Curve
78, 27Z, 59, 81
60, 81R, 99, 27 Inst. Overcurrent protection (50)
In: 0.08-32In 6*In CTR: 150/1A
T: 0-100 sec 0 sec (Inst) PTR: 132KV/110V

Earth fault protection (51N) IDMT


Ie: 0.08-4In 0.2*In characterictics
T: 0-100 sec 0.1 Sec 3 Sec Curve

Inst.Earth fault protection (50N)


Ie: 0.08-4In 0.3*In
T: 0-100 sec 0.5 sec

1 of 10
PREPARED BY: ARD CHECKED BY: KBD APPROVED BY: ABH
RELAY SETTING CHART- 132KV SWITCHYARD RELAY
Sr.No Protection Description Type ref. Setting Range Recommended Setting Remarks
132KV Transformer Control and Relay Panel Dir. Overcurrent protection (67)
In: 0.08-32In 0.75*In RCA: 30 deg
T: 0-100 sec 0.35 sec

Dir. Earth fault protection (67N)


Ie: 0.08-32In 0.1*In RCA: 45 deg
T: 0-100 sec 0.35 sec

Under volatge protection (27)


U<: 10-120V 80 V
T: 0-100 sec 2 sec

Over voltage protection (59)


U>: 60-185V 121 V
T: 0-100 sec 3 sec

Under frequency protection (81U)


f<: 45-65Hz 47.7 Hz PTR: 132KV/110V
T: 0-100 sec 2 sec

Over frequency protection (81O)


f>: 45-65Hz 52 Hz
T: 0-100 sec 2 sec

Local Breaker back-up protection (50LBB)


In: 0.4-4*In 1*In CTR: 150/1A
Time delay 0.3 sec

df/dt protection (81R)


df/dt: 0.1-10Hz/sec 4 Hz/ sec
T: 0-100 sec Inst

2 of 10
PREPARED BY: ARD CHECKED BY: KBD APPROVED BY: ABH
RELAY SETTING CHART- 132KV SWITCHYARD RELAY
Sr.No Protection Description Type ref. Setting Range Recommended Setting Remarks
132KV Transformer Control and Relay Panel Dead band lower frequency
45-65Hz 49 Hz

Dead band upper frequency


45-65Hz 51 Hz

Voltage Balance Relay (60)


***
***

Overfluxing Protection Relay (99)


***
***

Vector surge protection (78)


dv/dt: 2-30 deg 7 deg

Standby Earth fault protection (51G)


Ie: 0.08-4In 0.3 * In CTR: 150/1 A
T: 0-100 sec 0.3 Sec IDMT curve (3 sec)

3 50/51 Numerical MICOM P111L IDMT overcurrent protection (51)


50N/51N protection relay In: 0.08-4In 0.7 * In
(LV side of GT) TMS: 0.025-1 0.1 Sec IDMT curve (3 sec)

Inst. Overcurrent protection (50)


In: 0.08-32In 6 * In CTR: 1500 / 1 A
T: 0-100 sec 0 Sec PTR: 11kV / 110 V

3 of 10
PREPARED BY: ARD CHECKED BY: KBD APPROVED BY: ABH
RELAY SETTING CHART- 132KV SWITCHYARD RELAY
Sr.No Protection Description Type ref. Setting Range Recommended Setting Remarks
132KV Transformer Control and Relay Panel IDMT Earth fault protection (51N)
Ie: 0.08-4In 0.2 * In IDMT curve (3 sec)
TMS: 0.1-1 0.3 Sec

Inst.Earth fault protection (50N)


Ie: 0.08-4In 0.3 * In
T: 0-100 sec 0.3 Sec

4 50/51 Numerical MICOM P127 IDMT overcurrent protection (51)


50N/51N protection relay In: 0.08-4In 0.7 * In
(HV side of GT) TMS: 0.025-1 0.1 Sec IDMT curve (3 sec)

Inst. Overcurrent protection (50)


In: 0.08-32In 6 * In CTR: 1500 / 1 A
T: 0-100 sec 0 Sec PTR: 132kV / 110 V

IDMT Earth fault protection (51N)


Ie: 0.08-4In 0.2 * In IDMT curve (3 sec)
TMS: 0.1-1 0.3 Sec

Inst.Earth fault protection (50N)


Ie: 0.08-4In 0.3 * In
T: 0-100 sec 0.3 Sec

5 27, 59 Numerical MICOM P921 Under voltage protection (27)


59D protection relay U<: 10-120V 0.8
T: 0-100 sec 0.5 sec

Over voltage protection (59)


U>: 60-185V 1.1
T: 0-100 sec 0.5 sec

Neutral displacement protection (59DLV)


V: 5.4 -20V 5.4 V
TMS 0.1 sec

NOTE: a) All settings are referred with respect to secondary values.


b) All the other functions which are not mentioned in this chart shall be disabled.

4 of 10
PREPARED BY: ARD CHECKED BY: KBD APPROVED BY: ABH