LAB CHEMistry
LAB CHEMistry
t
Single phase Generation
Consider single phase
Alternator or Generator
DC supply is
given to
field wdg
R2 R1
Flux is
set up
DC supply is
given to
field wdg
R2 R1
Flux is
set up
DC supply is
given to
field wdg
R2 R1
Flux is
set up
DC supply is
given to
R2 field wdg
R1
Flux is
set up
DC supply is
given to
R2 field wdg
R1 VR
Flux is
set up
Y2
DC supply is
given to
R2 field wdg
R1
Flux is
set up
Y1
Rotate the arm
By prime mover
Two phase Generation v
Consider TWO phase t
Alternator or Generator
The emf induced in R1R2 is given by
Y2 eR=Vm sin ωt
DC supply is
VR given to
R2 field wdg
R1 -90
Flux is
VY set up
Y1
The emf induced in Y1Y2 is given by Rotate the arm
eY=Vm (sin ωt -90 ) By prime mover
Three phase Generation
Consider THREE phase
Alternator or Generator
B1 Y2
R2 R1
Y1 B2
Three phase Generation v
Consider THREE phase t
Alternator or Generator
B1 Y2
R2 R1
Y1 B2
Three phase Generation
Consider THREE phase
Alternator or Generator
B1 Y2
R2 R1
Y1 B2
VB
R2 R1
+120
-240 VR
Y1 B2 -120
VY
VR
eR=Vm sin ωt
Y
Clockwise rotation generates VY
Phase sequence R Y B eY=Vm (sin ωt -120 )
High rating generator, Pole = rotor, Phase coils = stator.
Three phase Generation
Consider THREE phase
Alternator or Generator R B Y
v
t
B
eY=Vm (sin ωt -240 )
VY e =V (sin ωt +120)
Y m
R
VR
eR=Vm sin ωt
Y
Anticlockwise rotation VB
Phase sequence R B Y eY=Vm (sin ωt -120 )
High rating generator, Pole = rotor, Phase coils = stator.
Three phase Generation
Consider THREE phase
Alternator or Generator
Draw three phase waveform
t
Three phase Generation
Consider THREE phase
Alternator or Generator
Draw three phase waveform
t
Three phase Generation
Consider THREE phase
Alternator or Generator
Draw three phase waveform
v R Y B
t
Three phase Generation
Consider THREE phase
Alternator or Generator
Draw three phase waveform
v R Y B
t
Three phase Generation
Consider THREE phase
Alternator or Generator
Draw three phase waveform
v R Y B
t
Three phase Generation
Consider THREE phase
Alternator or Generator
Draw three phase waveform
v R Y B
t
Three phase Generation
Consider THREE phase
Alternator or Generator
It can be proved that the sum of three emfs, at every
instant is ZERO.
1. Resultant = eR+eY+eB
=Vm sin ωt + Vm sin (ωt-120) +Vm sin (ωt-240)
=Vm [sin ωt + 2sin (ωt-180) cos 60]
=Vm [sin ωt - 2sin ωt cos 60] =0
2. Refer 3-ph wave diagram
2. Refer 3-ph wave diagram
Consider any instant, ie P
PL is +ve, PM is +ve, PN is -ve,
PL +PM - PN =0
v R Y B
M
L
t
P
N
3. Refer phasor diagram VB
Add any two phasors, ie VR and VY
VR + VY = -VB
VR
VR + VY + VB =0
VR + VY = VR2 +VY 2+ 2VR VY cos 120
VY -VB
= VB
4. Use complex algebra
Take VR as a reference phasor
VR = V 0 =V + j0
VY = V -120 =V (-0.5 - j0.866)
VB = V -240 =V (-0.5 + j0.866)
VR+VY+VB = 0
Some Concepts:
1. Phase Sequence:
The order of coming of maximum +ve value is called as
phase sequence or phase order.
Phase sequence is R Y B
If direction of rotation is reversed, then phase sequence is R B Y
v R Y B
t
Some Concepts:
2. Naming of Phase Sequence:
Phase sequence may be numbered, 1 2 3
or lettered A B C
But usual practice is use natural colours.
R = Red
Y = Yellow
B = Blue
3. Double Subscript Notation:
The voltage VAB means A is +ve w r t B
The current IAB means current flows from A to B
So VAB = - VBA and
IAB = - IBA and
Inter – Connection of Three Phases:
Each phase TWO terminals, one START and second FINISH
Non- interlinked three phase system has SIX terminals
R
iR
1 Individual phase current,
LOAD Vph
iR IP =
ZL
2
iB 5 Total conductors = 6
B iY 3
iB Y iY 4 Very complicated
6 Expensive
Not used in practice
Two methods of connecting phases
1. STAR (WYE) 2. DELTA (MESH)
1. STAR or WYE(Y) Connection:
R
VRY = VL
L
=V
N
V
VRY = VL
L
=V
VRN = Vph IR
θ
-
RB
N
V
IB
VYN = Vph θ VYB
B Y θ
VBN = Vph VYB = VL VYN
VBN IY
VRY = VL
L
=V
VRN = Vph IR
θ
RB
N
V
IB
VYN = Vph θ VYB
B Y θ
VBN = Vph VYB = VL VYN
VBN IY
VRY = VL
L
300
=V
VRN = Vph IR
θ
RB
N
V
IB
VYN = Vph θ VYB
B Y θ
VBN = Vph VYB = VL VYN
VBN IY
VBY
2. The voltage at neutral point is ZERO
Phasor addition of 3 phase voltages is zero
3. The angle between VRN and -VYN is 600
The Line Voltage VRY = VR2 + VY2 + 2 VR VY cos60
= VR = VR sin (ωt+ 300 )
1. STAR or WYE(Y) Connection:
Refer triangular diagram, the Line Voltage VBY = 2 cos 30 VB = VB
= VY = VR sin (ωt- 2100 )
4. As per wave diagram, at any one instant one is +ve and other
two may be –ve.
5. For balanced load, neutral wire will carry ZERO current
6. Line voltages are 300 ahead of respective phase voltage
7. Line currents and phase currents are EQUAL,
+ve current from N (source) to R,Y or B
8. Angle between line currents and corresponding line voltages
are 30 ± θ, + for lagging and – for leading
9. Total Apparent power = 3 Vp Ip = V L IL
10. Total power output = 3 Vp Ip cos θ = VL IL cos θ
Total power constant, not pulsating
1. STAR or WYE(Y) Connection:
Total power
v R Y B
Average power/phase
t
1. STAR or WYE(Y) Connection:
Connection of 3 phase load R Y B
R
IR
Z
Z Z Z
N N
IY Z Z
B Y N
Balanced Y Load
IB
1. STAR or WYE(Y) Connection:
Connection of 3 phase load R Y B
R
IR
Z
Z Z Z
N N
IY Z Z
B Y N
Balanced Y Load
IB
R R1
B2 R Y B
IR R1 Y1 B1
Z Z
N
Z Z Z
IY B1 R2
B Y Z
Y2 Y1
I Balanced Δ Load R2 Y2 B2
1. STAR or WYE(Y) Connection:
Connection of 3 phase load
Balanced Load
Impedance has same magnitude and pf
All phase current or line current are equal in magnitude
and 1200 apart in space
All voltages are equal in magnitude
and 1200 apart in space
So 3 ph balanced load can be solved by considering
single phase only.
Current through neutral wire is zero.
In unbalanced load, neutral wire current is not zero but equal to
phasor sum of all three currents.
1. STAR or WYE(Y) Connection:
Connection of single phase load
If neutral wire is available, then single phase load can be
connected between any one phase.
R
IR
Z
N
IR
B Y
2. DELTA (Δ) or MESH Connection:
R IR
R
VBR
VRY
IBR IRY
IYB IY
B Y
VYB Y IB
B
Z
Z Z
Z Z
Z
For star
VP VL
Per phase impedance, ZP or ZS = =
IP IL (1)
For delta
VP VL
Per phase impedance, ZP or ZD = =
IP IL (2)
1/2 gives
ZS = ZD or ZD = 3 ZS
Comparison between STAR and DELTA
Z
Z Z
Z Z
Z
1. Similar ends are connected dissimilar ends are connected
together together
2. Line Voltage VL = VP VL = VP
3. Line Current IL = IP IL = IP
4. 3 phase 4 wire 3 phase 3 wire
Suitable for lighting
5. Neutral can be connected to No neutral
earth for protection
Circuit Diagram
Wattmeter
2.5A,300V I = I
IR M L ph L
AR 0
2.5A C V 2.8A
RR 110 Vph
3-ph, 230V, 50Hz Supply
Switch Ω
R
2.5A
RY RB
OUTPUT
Y IY
INPUT
AY 2.8A 2.8A
110 110
B VL Ω
2.5A Ω
3-ph
IB
AB
Auto-transformer
Apparatus Required
1. Loading Rheostats: Three, 2.8 amp, 110 ohms.
2. AC Ammeters: Three, 0 – 2 amp.
3. AC Voltmeters: Two, 0 – 300 volts or One Multimeter
4. Wattmeter: One, 2.5 amp, 300 volts
5. Three Phase Autotransformer: One, 300 volts
Procedure
1. Make the connections as shown in Fig.
2. Put all the rheostats for maximum resistances.
3. Set the variac to zero output and switch on the supply.
4. Increase the voltage by variac, up to the voltage slightly less than
the rated voltage of rheostats.
5. Vary the resistances such that equal currents flow in the three
ammeters.
6. Note down the readings of wattmeter, two voltmeters and three
ammeters.
7. Increase the voltage by variac, up to the rated voltage of
rheostats, without exceeding current limits.
8. Repeat step 6.
Observations
Star connected load
Sr. Phase Line Phase Power Total
No voltage, voltage, Current = W Power
Vph VL Line current, =3W
Iph = IL
Results
Draw the phasor diagrams
VRY
VRN = Vph
IR
IB
VYB = VL
IY
VBN VYN
VBY
Widely used.
Low or high voltage
Low or high current
Various range of sizes
Weight from grams to tonnes
Electrical, Electronics, measurement and control
A transformer is
• a static electromagnetic device
or an alternating current device
It transfers electrical energy or power
1. from one electrical circuit to another electrical circuit
2. without electrical connection
3. through the medium of magnetic field
4. without change in frequency
5. from higher voltage to lower voltage or from LV to HV
It also transfers voltage, current and impedance
Due to this it is called as TRANSFORMER
Primary winding
The electrical circuit which receives energy or power
from the supply mains is called as primary winding
Secondary winding
The other circuit which delivers energy or power to the
load is called as secondary winding
Construction
Mainly consists of
1. Magnetic circuit, magnetic sheets with limb, yoke
Sheets are of I, L, T, C, U and E type
Two L
YOKE
I and C
LIMB
LIMB
YOKE
Core
2. Electric circuit, two or more windings
3. Dielectric circuit, insulated magnetic sheet, conductor,
coils, windings
If supply is Oil
connected If load is
L
O
A
connected
D
Primary Secondary
wdg wdg
Classification:
According to construction
1. Core Type
Considerable part of core is surrounded by windings
LV HV
2. Shell Type
HV
HV
LV
LV
According to Use and Application
1. Power Transformer
2. Distribution Transformer
3. Communication Transformer
4. Instrumentation Transformer
According to Winding
1. Single Phase Transformer
2. Three Phase Transformer
3. Auto - Transformer
According to Cooling
1. Natural Cooled 2. Forced Air Cooled 3. Water Cooled
4. Oil Cooled
• Symbol:
• Coil represents the winding
• Two vertical lines represent the
insulated core and
Strong magnetic coupling between
Secondary
Primary
windings
DEEWAR
Electromagnetic Induction
Michael Faraday
1791 - 1867
England – Chemist and Physicist
Initially worked as a Bookbinder
Worked with humphry Davy – Arc Lamp
Experiments
G
N
G
S
Experiments
G
N
G
S
Experiments
G
N
S
Experiments
G
N
S
When coil is moved, or magnet is moved, there is deflection
in galvanometer.
When flux linking a conductor changes, emf is induced in conductor
This phenomenon is known as electromagnetic induction.
Electromagnetic Induction
Faraday’s Law
1. First law
When the flux linking a conductor or coil changes,
an emf is induced in it.
2. Second law
The magnitude of induced emf in a coil is
directly proportional to the rate of change of flux linkage.
The magnitude of emf is proportional to number of turns, N
dΦ
emf, e = N
dt
Lenz’s Law
The direction of induced emf is such that to oppose the cause of it
dΦ
emf, e = - N
dt
Electromagnetic Induction
Induced emf:
There are two types of induced emf
1. Dynamically induced emf
2. Statically induced emf
1. Dynamically Induced emf
Flux stationery, Magnetic field stationery
Conductor or coil is moved
emf induced in this way is called Dynamically Induced emf
Conductor or coil is in dynamic or motion
For example: DC Generator
Field on stator
Coil or armature on rotor
R2 R1
Electromagnetic Induction
Induced emf:
Consider uniform magnetic field
Consider a conductor moving in same
direction of field
How much is flux cut?
No emf is induced
Now a conductor is moved
perpendicular to field
How much is flux cut?
So emf is induced
Suppose, v is velocity of conductor
l is length of conductor
dx is distance moved by conductor in dt time
Electromagnetic Induction
Ares swept by conductor = l x dx
Flux cut, dΦ = B x Area swept
= B l dx Wb
Rate of change of flux,
dΦ
= B l dx / dt = B l v
dt
emf, e = N B l v Volts
If condR moves at an angle θ with field
cos θ is parallel to field
No emf
sin θ is perpendicular to field
θ Responsible for emf
e = N B l v sin θ Volts
Electromagnetic Induction
2. Statically Induced emf
Conductor is stationery,
Flux is moving or changing
emf induced in this way is called Statically Induced emf
For example: transformer
B1 Y2
R2 R1
Y1 B2
B
Y
Electromagnetic Induction
2. Statically Induced emf
Conductor is stationery,
Flux is moving or changing
emf induced in this way is called Statically Induced emf
For example: transformer
Φm
This emf is sub-divided into
1. Self induced emf P L
O
Φm
P S L
O
N1 E1 E2 N2
A
D
Electromagnetic Induction
2. Mutually induced emf
emf induced due to flux produced by neighbouring coil
For example: secondary winding of transformer
voltage source V1 to primary, Current I flows
Alternating flux Φ is set up. emf E2 is induced secondary wdg
The flux common to both wdgs is called as mutual flux Φm
- N dΦm
em or E2= 2
dt
This E2 will oppose change in Φm
The I2 will oppose change in Φm
The property of two neighbouring coils to induce voltage in one
coil due to change in current in other is called as
mutual inductance, M dI1
em or E2= - M M = N1N2 a μ0 μr /l
dt
Operating Principle
Transformer works on the principle of electromagnetic induction
Φ
P S L
O
N1 E1 E2 N2
A
D
e1 lags Φ by 900
IΦ Φ
E1MAX = N1 ω Φmax
Primary (LV)
For ideal transformer
V1 = E1 and E2 = V2
where V2 is terminal voltage
Voltage transformation Ratio, K
E1 4.44 f N1 Φmax N1 1
= = =
E2 4.44 f N2 Φmax N2 K
Secondary (LV)
N2 E2
Primary (HV)
K= =
N1 E1
1. If N2 > N1, K > 1 , then transformer is called as
step – up transformer
2. If N2 < N1, K < 1 , then transformer is called as
step – down transformer
Ideal transformer (Reactor)
For ideal transformer
No loss
Input VA = Output VA
V 1 I1 = V 2 I2
V1 I2 1
= =
V2 I1 K
Hence the currents are in the reverse ratio of the voltage
transformation ratio, K.
Voltage Regulation
■ The voltage regulation of a transformer is defined as the ratio
arithmetical difference in the secondary terminal voltage
between no load (I2=0) and full rated load (I2=Ifl) to the full
load voltage at a given power factor with the same value of
primary voltage for both no load and rated load.
■ with the same value of primary voltage for both no load and full
load (These are magnitudes, not phasors).
Voltage Regulation
■ Full Load
■ any Load
■ = ±5%.
Voltage Regulation
■ The transformers are designed to operate at practically
constant voltage.
■ But the load terminal voltage changes because of the voltage
drop (I2Z2)in the internal impedance of the transformer
Z2=(r2+r1’)+j(x2+x1’)=R2+jX2.
■ Secondary wdg resistance, r2
■ Primary wdg resistance referred to secondary, r1‘
■ Secondary wdg leakage reactance, x2
■ Primary wdg leakage reactance referred to secondary, x1‘
■ The change in terminal voltage depends on the magnitude
and the power factor of the current, in other words, it
depends on the load impedance (its magnitude as well as its
angle).
Voltage Regulation
■ Calculation of Voltage Regulation using Circuit Parameters
By KVL
No Load Voltage,
I2 E2
V2 I 2Z 2
X
2
jI
2
θ2
I2R2
I2
Voltage Regulation
■ at Lagging Power factor
V2 I 2Z 2
X
2
jI
2
θ2
I2R2
I2
■ For lagging power factor, cosθ2
Voltage Regulation
■ at Lagging Power factor
E2 jI
2 X
I2 2
I 2Z 2
θ2 V2 I2R2
Voltage Regulation
■ at Leading Power factor
E2 jI
2 X
I2 2
I 2Z 2
θ2 V2 I2R2
R2
Z2
Maximum voltage regulation occurs at
lagging p f of the load. Z2 X2
R2 θ2= θl
load power factor =
Z2 R2
load p f angle θ2= Leakage impedance angle θl of transformer
Voltage Regulation
The magnitude of maximum voltage regulation is
Voltage Regulation
Vs
%R %R
Output
Vs & % R verses Output Curve
LOAD
LOAD
LOAD
LOAD
LOAD
Φ LOAD
M
Height =
L
O
A
Voltage
D
Φl1 Φl2
Efficiency
80
Maximum Efficiency
Pf=1.0
Rated Output
Pf=0.9
Pf=0.8
Pf=0.7
E2
Results
E2
Vs
Vs %η
%R %R
Output Output
Fig.: Vs & % R verses Fig.: Effn verses Output Curve
Output Curve
Conclusions
■ 1. The output voltage decreases
E2 as the output increases.
Vs ■ 2. Regulation increases as the
output increases
Vs
%R %R
Output
Fig.: Vs & % R verses
Output Curve
Conclusions
■ 3. The efficiency is zero at no load. It
increases as the load increases and is
maximum when variable losses are
%η equal to constant losses. Then it
decreases.
■ 4. The efficiency at rated output is less
0.8 to 0.9 1.0 than the maximum value and the rated
Output operating point is after the maximum
efficiency point
■ 5. Maximum efficiency occurs when the load on the transformer
is from 80 to 90% of full load.
EXPERIMENT NO. 7.
Terminal core
Resistive Conductor or
Alloy
Types of Rheostats
1. Single Core Rheostat or Single Bar Rheostat
Sliding Contact
Maximum
Minimum
Resistance
Terminal core
Resistive Conductor or
Alloy
Types of Rheostats
1. Single Core Rheostat or Single Bar Rheostat
Sliding Contact
Maximum
Resistance
Terminal Core
Maximum
Minimum
Resistance
Types of Rheostats
2. Double Core Rheostat or Double Bar Rheostat
Output Output
MINIMUM MAXIMUM
Resistance Resistance
2. 160 ..
… … …
Observations
• a) Armature Voltage variation
• 2) Field current (constant) = 0.9 Amp
2. 160 ..
… … …
Observations
• b) Field Current variation
• 1) Armature Voltage Va (constant) = 190 V
2. 0.9 ..
… … …
Observations
• b) Field Current variation
• 2) Armature Voltage Va (constant) = 180 V
2. 0.9 ..
… … …
Results
Plot the variation of Va Vs N & If Vs N
p
Am V
Speed N rpm
Speed N rpm
a2 =1
0.9
90
V
If =
p V
A m a1 =1
= 1 80
If V
Armature Voltage Va If
Conclusions
1. The speed of dc shunt motor is directly
proportional to the armature voltage
(N α Va).
2. The speed of dc shunt motor is inversely
proportional to the field current (N α 1/If).
3. Thus in order to increase the speed the
armature voltage should be increased and
/ or field current should be decreased.
Write down all the precautions
which are listed in Laboratory
and attach after Index page
Working Principle
(Principle of Operation)
“In 1819, it was discovered by a Danish
Language Netherlands Physicist, Hans
Christian Oersted that an electric current is
always accomplished by a certain magnetic
effects. He found that when a current is
passed through a conductor placed above
the magnetic needle, the needle turns in a
certain direction.”
which is also called as Motor Rule.
Working Principle
(Principle of Operation)
N S
+ ●
N + S
N
Opposite
N S
+
Force
Working Principle
(Principle of Operation)
Addition Opposite
N + S N S
Opposite Addition
Force
N S S
+
N
Force
Working Principle
(Principle of Operation)
N ARM S S
●
Working Principle
(Principle of Operation)
MNA
+
N ARM S S
●
N ARM S S
●
N ARM S S
●
N S S
●
New MNA
N S S
●
New MNA
AA
-
1. Three Point starter.
r1 r2
OFF/ r3
Studs 2 3 r4
START 1 4
Insulated conductor 0 5
Handle ON / RUN
NVRC
Soft iron keeper b
Spring
a
OCRC b a F A
L
+ F A
Movable soft iron
FF AA
-
1. Three Point starter.
r1 r2
OFF/ r3
Function of r4
2 3
NVRC START 1 4
0 5
1. In case of power failure, ON / RUN
Voltage of NVRC=0,
NVRC
Demagnetization, no b
magnet.
a
OCRC b a F A
L
+ F A
Spring brings handle to OFF position.
FF AA
-
1. Three Point starter.
r1 r2
OFF/ r3 Ia=V/ra
Function of r4
2 3
NVRC START 1 4
0 5
1. In case of power failure, ON / RUN
Voltage of NVRC=0,
NVRC
Demagnetization, no b
magnet.
a
OCRC b a F A
L
+ F A
Spring brings handle to OFF position.
Due to power failure, speed =0
If H fails to return to OFF position
and if supply is restored, FF AA
high Ia- flows & motor may be damaged.
1. Three Point starter.
r1 r2
OFF/ r3
Function of r4
2 3
NVRC START 1 4
0 5
2. If field becomes open, ON / RUN
Voltage of NVRC=0,
NVRC
coil is demagnetized, b
no magnet.
a
OCRC b a F A
L
+ F A
Spring brings handle to OFF position.
FF AA
-
1. Three Point starter. T=KIaIf
r1 r 2
OFF/ r3
Function of r4 Ia
2 3
NVRC START 1 4
0 5
2. If field becomes open, ON / RUN
Voltage of NVRC=0,
NVRC
coil is demagnetized, b
no magnet.
a
OCRC b a F A
L
+ F A
Spring brings handle to OFF position.
If H fails to return to OFF position
Flux decreases, speed increases FF AA
For same- load torque, high I flows & motor may be damaged.
a
1. Three Point starter.
r1 r2
OFF/ r3 Ia
Function of r4
2 3
OCRC START 1 4
0 5
If load increases, Ia increases, ON / RUN
OCRC becomes strong,
NVRC
movable soft iron moves b
upward.
a
OCRC b a F A
L
+ F A
a & b are shorted, Vab=0, NVRC is demagnetized.
H returns to OFF position,
motor is disconnected from supply. FF AA
Thus motor
- is protected from heavy load condition.
Brass Arc.
1. Three Point starter.
r1 r2
r3
Under running OFF/ r4
Ia
2 3
condition START 1 4
0 5
radd, NVRC, field wdg are ON / RUN
in series. NVRC
Since radd<< Rf, effect of b
radd is negligible. a
OCRC b a F A
L
+ F A
Sometimes brass arc is used to bypass radd.
But radd.is used to discharge the field energy
stored in field wdg when motor is FF AA
disconnected
- from supply.
1. Three Point starter.
r1 r2
r3
Under running OFF/ r4
Ia
2 3
condition, START 1 4
0 5
F, NVRC, radd, A are in ON / RUN
series. NVRC
When supply is b
disconnected a
OCRC b a F A
L
+ F A
For releasing H to 0, field energy is
dissipated in this series circuit,
and there is less spark. FF AA
-
1. Three Point starter.
r1 r2
OFF/ r3 Ia
So under r4
2 3
running START 1 4
0 5
condition, ON / RUN
to stop the motor supply
NVRC
should be disconnected.
b
Otherwise willingly or
unwillingly, if H is a
moved towards 0FF b a F A
L
+ F A
Field energy is dissipated through the
contact of H and studs.
and there is more spark and burning of FF AA
studs. -
1. Three Point starter. This is overcome in
r2 Four Point Starter.
Disadvantage OFF/ r 1 r3 Ia
2 3 r4
If speed is START 1 4
0 5
increased, ON / RUN
by decreasing field current NVRC
The force of NVRC may b
become less than spring
force. a
b a F A
L
+ F A
Handle H may return to OFF position
and the motor stops. This is not desirable.
So Three point starter can’t be used for wide FF AA
- speed control
range of
With this, speed
2. Four Point starter. can be increased
L, L1,A, F r1 r2
OFF/ r3
r
without affecting
2 3
START 1 4
4
NVRC current.
NVRC is connected 0 5
in series with R- ON / RUN
current limiting NVRC
b So, suitable for
resistance and in wide range of
parallel with F. (b a speed control
to -) b a F A
L
+ 1, there are three
If H is at F A
R
parallel circuits (+ to -) L1
1. OCRC, radd, and A
FF AA
2. OCRC and F 3. OCRC, NVRC and R.
-
EXPERIMENT NO.:6.
To study the Speed Reversal of
Three Phase
Induction Motor
Theory
1. Three-phase induction motor is the most
popular type of a. c. motor.
2. It is very commonly used for induction
drives since it is cheap, robust, efficient
and reliable.
3. It has good speed regulation and high
starting torque.
4. It requires little maintenance.
5. It has a reasonable overload capacity.
The basic principle of operation is ‘induction’
and hence the name ‘Induction Motor’.
Slot
Tooth
Rotor
Shaft
Stator core
or Stamping
IM consists of: 1. stator 2. rotor.
The stator is the stationary part and the
rotor is a rotating part. Slot
Tooth
Rotor
Shaft
Stator core
or Stamping
The stator is built up of high-grade alloy steel
laminations (cold rolled grain oriented silicon
steel sheets) to reduce eddy current losses.
Rotor
Shaft
The laminations are slotted on the inner
periphery and are insulated from each other.
The insulated stator conductors are placed
in these slots.
Rotor
Shaft
The stator conductors are connected to form
a three-phase winding.
The phase winding may be either star or delta
connected.
Rotor
Shaft
The clearance between the stator and the
rotor is called an air gap.
The air gap is kept as small as possible to
a) Reduce leakage reactance & no load current and
b) Improve the power factor.
Rotor
Shaft
The rotor is built up of thin laminations of
the same material as that of stator.
The laminated cylindrical core is mounted directly
on the shaft or a spider carried by the shaft.
Rotor
Shaft
The laminations are slotted on their outer
periphery to house the rotor conductors or
rotor bars.
Rotor
Shaft
The stator laminations are supported in a stator
frame of cast-iron or fabricated steel plate.
Stator frame is connected to coverings.
The coverings are rested on bearings which are
mounted on shaft.
Rotor
Shaft
Common constructional features for
ALL rotating electrical machines
Air Gap
Rotor Core Brushes
Φ
Shaft Slip rings
ROTOR Rotor wdg
Bearings
Stator Frame Stator wdg
STATOR
Base
There are TWO types of induction motor depending
on the types of rotor.
1. Squirrel-cage rotor or simply cage rotor. (SCIM).
2. Phase wound or wound rotor or slip ring rotor (SRIM).
Rotor
Rotor End
(Slightly
Bars
(Slightly
Bars Rings
skewed)
skewed)
Fig. 1. Cage
Rotor
The slots nearly parallel to the shaft axis or skewed .
Each slot contains an uninsulated bar conductor of
aluminium or copper.
There are TWO types of induction motor depending
on the types of rotor.
1. Squirrel-cage rotor or simply cage rotor. (SCIM).
Rotor
Rotor End
(Slightly
Bars
(Slightly
Bars Rings
skewed)
skewed)
Fig. 1. Cage
Rotor
At each end of the rotor, the rotor bar
conductors are short circuited by heavy end ring
of the same material.
There are TWO types of induction motor depending
on the types of rotor.
1. Squirrel-cage rotor or simply cage rotor. (SCIM).
2. Phase wound or wound rotor or slip ring rotor (SRIM).
Rotor
Rotor End
(Slightly
Bars
(Slightly
Bars Rings
skewed)
skewed)
Fig. 1. Cage
The conductors and the end rings look like a ‘cage’ of a bird
Rotor
or form a cage of the type which was once commonly used for
keeping squirrel;
Slightly shifted
Skewed
D
T H A
Squirrel Cage
Rotor
Parallel to
Shaft
Slightly shifted
Skewed
D
T H A
Rotor winding
In delta or Star
Rotor winding
In delta or Star
Rotor winding
In delta or Star
i Imax At ωt3=1800 or π
or t3= 10msec
i 3= 0
0 ωt
900 1800 2700 3600
At ωt4=2700 or 3π/2
or t4= 15msec
i4= -Imax
-Imax
At ωt5=3600 or 2π
or t5= 20msec
i =0
In the winding, in some conductors, current is
entering, which is represented by cross (X).
In some conductors, current is leaving,
which is represented by dot (●)
S mmf
If i=0, mmf is zero,
If i=Imax, mmf is maximum. Flux
i2
ωt ωt1 α
0 α=0
ωt2
ωt3
i2
ωt ωt1 α
0 α=0
ωt2
ωt3
i2
ωt α
0 α=0
i2
ωt α
0 α=0
The mmf, produced along the air gap periphery is
changing sinusoidally.
But not rotating, similar to three phase system.
It is stationary,
or standing,
or pulsating.
ωt α
0
α=60
Thus you will see the mmf pulsating between + Fmax
to - Fmax
Now suppose you are sitting at 600 away from the
phase axis i. e. at α = 600.
i
mmf
ωt α
0
α=60
Thus you will see the mmf pulsating between + Fmax
to - Fmax
Now suppose you are sitting at 600 away from the
phase axis i. e. at α = 600.
At time t1, ωt=00, mmf= 0Fmax
At time t2, ωt=300, mmf= 0.25 Fmax
At time t3, ωt=900, mmf= 0.5 Fmax
At time t4, ωt=2700, mmf= -0.5 Fmax
Thus you will see the mmf pulsating between + 0.5Fmax to
–0.5 Fmax
If you are sitting at 900 away from the phase axis i. e.
at α = 900.
If you are sitting at 900 away from the phase axis i. e.
at α = 900.
i
mmf
ωt α
0
α=90
If you are sitting at 900 away from the phase axis i. e.
at α = 900.
i
mmf
ωt α
0
α=90
Then you will see the mmf always zero all the
time.
Thus the mmf, produced along the air gap periphery
is changing sinusoidally.
In single phase it is not rotating.
It is stationary, or standing, or pulsating.
a2 a1
N
Torque in single phase induction motor
mmf
S
Flux
a2 a1
i
N
0 ωt
Torque in single phase induction motor
In +ve half cycle mmf
S
If torque is +ve (due to + Fmax)
Rotor moves in clockwise direction. Flux
Now after 10msec
In the –ve half cycle a2 a1
Torque is -ve (due to - Fmax)
Rotor moves in
anticlockwise direction. i
N
+
Therefore, the average
torque over a complete
cycle is ZERO. ωt
0
Hence, 1-Φ IM is
not self starting -
Two Phase System
B2
Consider TWO phase system
Two phase winding AB are displaced A2 A1
from each other by 900 electrical
space degrees along air gap periphery B1
Axis of phase A
Axis of phase B
B2
Consider TWO phase system
Two phase winding AB are displaced A2 A1
from each other by 900 electrical
space degrees along air gap periphery B1
Axis of phase A
Axis of phase B
Graphical Analysis
A
Graphical Analysis
+Φ A
ωt
-Φ
A
Graphical Analysis
B
A B
+Φ
ωt
-Φ
1. Consider an angle 00
A ωt=0
Φa0= Φm Sin(ωt)=0
Φb0= Φm Sin(ωt-90)=-Φm
Φ0
B
A B
+Φ
-Φ
1. Consider an angle 00
A ωt=0
B2
Φ0
A2 A1
Φ0
B
B1
A B
+Φ
-Φ A1= 0 & A2 =0
B1=- & B2 = +
2. Consider an angle 900
A ωt=90
Φ90 Φ = Φ Sin(90)= Φ
a90 m m
Φb90= Φm Sin(90-90) =0
B
A B
+Φ
-Φ
1. Consider an angle 900
A Φ90
Φ90 B2
A2 A1
B
B1
A B
+Φ
-Φ
3. Consider an angle 1800
A
B2
Φ180
A2 A1
B
Φ180 B1
A B
+Φ
Thus for Clockwise
AB,
Flux rotate
Clockwise, 0 90 180 270 360 ωt
Axis of phase B
Axis of phase R
Axis of phase Y
S
Consider three phase system R2
Y1 B1
Three phase winding RYB are displaced
from each other by 1200 electrical B2 Y2
space degrees along air gap periphery R1
Axis of phase B N
Axis of phase R
Axis of phase Y
Now resultant magnetic flux due to three phases
Graphical Analysis
B
Graphical Analysis
R Y B
Y
B
Graphical Analysis
R Y B
Y
B
Graphical Analysis
R Y B
Y
B
Graphical Analysis
R Y B
Y
Φb Graphical Analysis
Φr
Φr Φy Φb
+Φ
Φy
-Φ
The resultant flux, at any instant, is equal to the
phasor sum of the fluxes due to 3-phases.
1. Consider an angle 00
Φb
ωt=0
Φr0= Φm Sin(ωt)=0
Φy0= Φm Sin(ωt -120) =Φm Sin(-120)
Φr 3
=- Φm
2
Φr Φy Φb
+Φ
Φy
-Φ
= 3 Φ
Φb0= Φm Sin(ωt-240)=Φm Sin(120)
2 m
Φ0 S
Φb
R2
Y1 B1
```````
Φr B2 Y2
R1
Φr Φy Φb
+Φ
N
Φy
R1= 0 & R2 =0
-Φ Y1= – & Y2 =+
B1=+ & B2 = –
Φ0 S
Φb
R2
30 Y1 B1
```````
Φr B2 Y2
Φ0=2Φb0Cos(30) =2Φy0Cos(30) R1
3 3 Φ +Φ Φr Φy Φb
=2
2 2 m N
3 Φy
= Φm
2
0 60 120 180 240 300 360 ωt
R1= 0 & R2 =0
-Φ Y1= – & Y2 =+
B1=+ & B2 = –
2. Consider an angle 600
Φb
ωt=60
Φr60= Φm Sin(60)= 3 Φm
2
Φy60= Φm Sin(60-120) =Φm Sin(-60)
Φr 3
=- Φm
2
Φr Φy Φb
+Φ
Φy
-Φ
Φb60= Φm Sin(60-240) =Φm Sin(-180) =0
2. Consider an angle 600
Φb
R2 S
Y1 B1
```````
Φr B2 Y2
N R1
Φr Φy Φb
+Φ
Φy
R1= + & R2 =-
-Φ Y1= – & Y2 =+
B1=0 & B2=0
2. Consider an angle 600
Φb
R2 S
Y1 B1
```````
Φr B2 Y2
Φ60=2Φr60Cos(30) =2Φy60Cos(30) R1
N
3 3 Φ +Φ Φr Φy Φb
=2
2 2 m
3 Φy
= Φm
2
0 60 120 180 240 300 360 ωt
R1= + & R2 =-
-Φ Y1= – & Y2 =+
B1=0 & B2=0
3. Consider an angle 1200, ωt=120
Φb
Φr120= Φm Sin(120)= 3 Φm
2
Φy120= Φm Sin(120-120) =0
Φr
Φr Φy Φb
+Φ
Φy
-Φ
=- 3 Φ
Φb120= Φm Sin(120-240)
2 m
3. Consider an angle 1200,
Φb
N
R2
Y1 B1
```````
Φr B2 Y2
R1 S
Φr Φy Φb
+Φ
Φy
R1= + & R2 =-
-Φ Y1=0 & Y2=0
B1=- & B2=+
3. Consider an angle 1200,
Φb
N
R2
Y1 B1
```````
Φr B2 Y2
R1 S
Φr Φy Φb
+Φ
Φy
0 =2Φ
Φ120=2Φr120Cos(30) Cos(30)
60 120 180 240 300 360 ωt
b120
3 3 Φ
=2 R1= + & R2 =-
2 2 m
3 -Φ Y1=0 & Y2=0
= Φm
2 B1=- & B2=+
4. Consider an angle 1800, ωt=180
Φb
Φr180= Φm Sin(180)= 0
Φy180= Φm Sin(180-120)= 3 Φm
2
Φr
Φr Φy Φb
+Φ
Φy
-Φ
=- 3 Φ
Φb180= Φm Sin(180-240)
2 m
4. Consider an angle 1800, N
Φb
R2
Y1 B1
```````
Φr B2 Y2
R1
Φr Φy Φb
+Φ
S
Φy
0 =2Φ
Φ120=2Φy180Cos(30) Cos(30)
60 120 180 240 300 360 ωt
b120
3 3 Φ
=2 R1=0 & R2=0
2 2 m
3 -Φ Y1=+ & Y2=-
= Φm
2c B1=- & B2=+
S
B
R2
Y1 B1
```````
R B2 Y2
R1
R Y B
+Φ
N
Y
-Φ
Flux rotate Clockwise, Poles rotate Clockwise,
y
S
B
R2
B1
Y1 Y1
B1
```````
R Y2
B2 B2
Y2
R1
R Y B
+Φ
N
B
Y
Now change the
phase sequence
of motor to RBY 0 60 120 180 240 300 360 ωt
With same supply
phase sequence
-Φ
For anticlockwise Flux rotate anticlockwise,
phase sequence, Poles rotate anticlockwise,
Torque in three phase induction motorS
R2
Y1 B1
```````
B2 Y2
R1
ωt
Torque in three phase induction motorS
For clockwise RYB,
R2
Clockwise rotating magnetic field B1
Y1
is set up ```````
Torque acts on rotor continuously B2 Y2
Rotor rotates continuously R1
in clockwise direction.
N
Bar
Rotor
Shaft
B Y
Give 3-ph Supply R
Winding
Bar
Rotor
Shaft
Y open
B Y
Give 3-ph Supply R
Rotor
Shaft
Y open
B
Give 3-ph Supply R
Rotor
Shaft
B open
Y open
B
Give 3-ph Supply R
Rotor
Shaft
B open
Y open
Thus 3-ph Induction R 1-ph Induction
Motor is self Motor is not
starting and self starting
Rotor
Shaft
Thus 3-ph Induction R 1-ph Induction
Motor is self Motor is not
starting and self starting
Rotor
Shaft
Rotation of Induction Motor
B
Rotor Conductor
STATOR
ROTOR
R
B
Rotor Conductor
STATOR
ROTOR
R
Y
This has the effect as the conductor moving in
…………………… direction
Rotation of Induction Motor
B
Rotor Conductor
STATOR
M
ROTOR
R
Y
This has the effect as the conductor moving in
anticlockwise direction
Flux passes from stator to rotor
As per Fleming’s RHR, current is induced
in rotor Polarity is DOT
Rotation of Induction Motor
B
Rotor Conductor
STATOR
ROTOR
R
B
Rotor Conductor
STATOR
ROTOR
R
Y
Hence rotor rotates
Three phase induction motor is self starting
Rotation of Induction Motor
B
Rotor Conductor
STATOR
ROTOR
R
Y
As rotor rotates at synchronous speed,
No relative motion No flux cut
No current No Torque
No Rotation
Rotation of Induction Motor
B
Rotor Conductor
STATOR
ROTOR
R
sf1
Transformer and IM
Primary Stator
Secondary Rotor (Shorted)
r1 x1 I1 I2 r2/s x2
I0
V1 Rl Xm
Il Im
Rotor rotates
slip
Transformer and IM
Primary Stator
Secondary Rotor (Shorted)
r1 x1 I1 I2 x2
I0
V1 Rl Xm r2/s
Il Im
Stator Input
Rotor Input
Air gap power, Pg = I22r2/s
Torque – slip Characteristics
Mechanical
Torque = Te = Mechanical
= =
= =
Te =
For 3 ph IM
Te =
Torque – slip Characteristics
Stable
Te Unstable
TeMax T
L
TeST Teop
0 Speed Ns
1 Slip 0
Analysis of Single Phase Induction Motor
There are two theories
1. Double Revolving Field Theory
2. Cross Field Theory
1
Fmax
2
Now at instant B, consider ωt1
instant B
ωt1 ωt1 mmf
Fmax Sin (ωt1+90)
i
1 B ωt1 F
B F Fmax ωt1
2
ω ω
-Ns 0 Speed Ns
2 1 Slip 0
Backward
Tb
TR
-Ns 0 Speed Ns
2 1 Slip 0
Backward
Tb
Rotor
Shaft
Auxiliary
winding
1. Resistance Split Phase Motor:
1. Main Winding or Running Winding (M)
Highly Inductive
in order to lag the current (IM) by nearly 900
with the Voltage
2. Auxiliary winding or Starting Winding (A)
Highly Resistive
to have current (IA) nearly in phase with the Voltage
RM
Single
Phase V IM IA
supply
XM
V
RA XA
I
ΦA CS V IA
A IA
IM β IM
ΦM
M Phasor Diagram
IA leads IM The angle is 30 to 400..
This angle is sufficient to produce the torque
(1.5 to 2 times FL torque) and to rotate the rotor.
β IM
Phasor Diagram
Single phase supply R
R N is given
R N
Auxiliary
winding
Rotor
CS
Shaft
Main
winding
N
Single phase supply R
R N is given Change the dirn
of rotation
R N
Auxiliary
winding
Rotor
CS
Shaft
Main
winding
N
Single phase supply R
R N is given Change the dirn
of rotation
R N
Auxiliary
winding
Rotor
CS
Shaft
Main
winding
N
The starting wbg is disconnected by means of CS at
70 to 80% of rated speed
The typical torque speed characteristics is shown below.
Auxiliary
Te Wdg
Fan Load
Operating
Te starting
Main Point
Wdg Ns
0
Speed
70%
Applications: Fans, Blowers, Pumps, Refrigerator,
Compressor. Washing Machine.
RM
Single
Phase V IM IA
supply C
XM
V
RA XA
I
ΦA CS V
A C IA
IA IM IM
β~
= 90
ΦM
M Phasor Diagram
IA leads IM The angle is nearly 900..
The line current is reduced.
The starting torque is more due to angle β. (3 to 4 times
FL torque)
But due to capacitor cost is more.
The starting wdg and capacitor are disconnected at 70 to
80% of rated speed.
The typical torque speed characteristics is shown below.
Auxiliary
Resistor split Wdg
Te
phase motor Fan Load
Te starting Operating
Main Point
Wdg Ns
0
Speed
70%
The value of capacitor varies from 20 to 30 μF for
100W and from 60 to 100 μF for 750W
AC electrolytic capacitors are economical.
RM C2 C1
Single
Phase V IM
supply CS
XM
IA
V
C2 RA XA I
ΦA
CS V
A C1 IA
IM
IA IM
β = 90
ΦM Phasor Diagram
M Balanced two phase motor
C1 is large capacitor C2 is small capacitor (High Reactance)
The more starting torque is obtained with high capacitance
C1 + C2 +
Te Both Wdgs
Torque –speed
characteristic
C2 + Both
Wdgs Ns
0
Speed
70%
Rating : 100 to 400W
C1 is electrolytic type.
C2 should be AC paper, oil type capacitor.
The motor is used for quite operation.
Used in office equipment, fans etc.
4. Capacitor Run Motor:
RM C
Single
Phase V IM
supply
XM
IA
RA V
XA I
ΦA
C V
A IA
IM
IA IM
β = 90
ΦM Phasor Diagram
M Balanced two phase motor
Permanent split capacitor motor
The capacitor is kept permanently in the circuit.
No need of centrifugal switch.
Capacitor and auxiliary wdg are designed to get 900 phase
displacement
Torque variation is less. Operation is quieter.
Power factor is improved Efficiency is increased.
Te
Torque –speed
characteristic
0 Ns
Speed
The value of capacitor varies from 2 to 3 μF.
Shading Coil
Stator
ΦShaded pole
0 Ns
Speed
Applications: Small domestic fans
Tap - Record player
Movie projectors
Blowers,
Heaters,
Starting of IM
There are principally TWO methods
1. Full voltage starting or Direct-on-Line starting
2. Reduced voltage starting
There are three methods of reducing voltage
1. Stator reactor (or resistor) starting
2. Auto-transformer starting
3. Star-delta starting
At this stage, for this experiment, Auto-transformer
starting is used
Circuit Diagram
Switch
R
R Turn switches ON
Stator
Rotor
B Y
B
Y 3-ph
Auto-transformer
Circuit Diagram
Switch
R
R Turn switches ON
Stator
Rotor
B Y
B
Y 3-ph
Auto-transformer
Circuit Diagram
Switch
R
R Turn switches ON
Stator
Rotor
B Y
B
Rotor
Y
B
B
B ph of IM is connected to Y ph of supply
Y ph of IM is connected to
Y 3-ph B ph of supply
Auto-transformer
Circuit Diagram
Switch
R
R Turn switches ON
Stator
Rotor
Y
B
B
B ph of IM is connected to Y ph of supply
For supply RYB anti-clockwise,
Rotation of rotor is anti-clockwise
Y ph of IM is connected to
Y 3-ph B ph of supply
Auto-transformer
Apparatus Required
Three Phase Induction Motor
Three Phase Autotransformer
Procedure
1. Make the connection as shown in Fig.
2. Set up the VARIAC to zero output and switch ON
the supply
3. Increase the voltage by variac and see the
rotation of rotor of induction motor
4. Decrease the voltage and switch OFF the supply
5. Interchange any TWO terminals of the IM
6. Increase the voltage by variac and see the
rotation of rotor of induction motor
Observations
The rotation of rotor of IM is opposite to
earlier rotation of rotor of IM