Active Profile 1
Module General Profile Name 10KVA AMFP R-Jio
Power On Mode Manual
Power On Lamp Test Enable
Display Display Contrast (%) 50
Power Save Mode Disable
RS485 Communication Comm Mode MODBUS
MODBUS Slave ID 26
MODBUS Baudrate 9600
Parity Bit None
BTS Battery Montoring Enable
Low Battery Threshold 46.5
Low Battery Monitoring Delay 10
DG Run Duration 270
Cyclic Mode Cyclic Mode Disable
DG Off Time 240
DG On Time 240
Digital Inputs Digital Input A Source Remote Start / Stop
Name Auxiliary Input A
Polarity Close to Activate
Action None
Activation From Monitoring On
Activation Delay (Sec) 1
Digital Input B Source Emergency Stop
Name Auxiliary Input B
Polarity Close to Activate
Action Shutdown
Activation Always
Activation Delay (Sec) 1
Digital Input C Source Low Fuel Level Switch
Name Auxiliary Input C
Polarity Close to Activate
Action Shutdown
Activation From Monitoring On
Activation Delay (Sec) 180
Digital Input D Source User configured
Name HWT or RWL
Polarity Close to Activate
Action Shutdown
1 of 10
ENG-PRT-MFG-SM0003805.smc
2 of 10
ENG-PRT-MFG-SM0003805.smc
3 of 10
ENG-PRT-MFG-SM0003805.smc
4 of 10
ENG-PRT-MFG-SM0003805.smc
T4 100
R5 80
T5 95
R6 93
T6 90
R7 120
T7 85
R8 222
T8 65
R9 458
T9 45
R10 458
T10 45
S1 SENSOR / Dig M Sensor Selection Digital Input M
Source Genset Contactor Latched
Name Auxiliary Input M
Polarity Close to Activate
Action None
Activation From Monitoring On
Activation Delay(Sec) 1
S1 SENSOR MONITORING Action None
Threshold 100
Threshold Type Less Than Threshold
S1 Sensor Open ckt alarm Disable
Sensor Name S1 Sensor
R1 10
Val1 0
R2 30
Val2 1
R3 40
Val3 2
R4 64
Val4 3
R5 80
Val5 4
R6 96
Val6 5
R7 96
Val7 5
5 of 10
ENG-PRT-MFG-SM0003805.smc
R8 96
Val8 5
R9 96
Val9 5
R10 96
Val10 5
S2 SENSOR / Dig N Sensor Selection Digital Input N
Source Mains Contactor Latched
Name Auxiliary Input N
Polarity Close to Activate
Action None
Activation From Monitoring On
Activation Delay(Sec) 1
S2 SENSOR MONITORING Action None
Threshold 100
Threshold Type Less Than Threshold
S2 Sensor Open ckt alarm Disable
Sensor Name S2 Sensor
R1 10
Val1 0
R2 30
Val2 1
R3 40
Val3 2
R4 64
Val4 3
R5 80
Val5 4
R6 96
Val6 5
R7 96
Val7 5
R8 96
Val8 5
R9 96
Val9 5
R10 96
Val10 5
Outputs Digital Output A Source Start Relay
6 of 10
ENG-PRT-MFG-SM0003805.smc
Polarity Energise
Digital Output B Source Stop Solenoid
Polarity Energise
Digital Output C Source Preheat Output
Polarity Energise
Digital Output D Source Common Alarm
Polarity Energise
Digital Output E Source Fail To Start
Polarity Energise
Digital Output F Source Close Gen Contactor
Polarity Energise
Digital Output G Source Close Mains Contactor
Polarity Energise
Reserved Source Disable
Reserved De-energise
Reserved Source Disable
Reserved De-energise
Timers Cranking Crank Hold Time (sec) 4
Crank Rest Time (sec) 10
Manual Start Delay (sec) 3
Auto Start Delay (sec) 90
General Safety Monotoring Delay (sec) 10
Mains Detect Delay (sec) 5
Alternator Detect Delay (sec) 5
Warm-up Delay (sec) 10
Return To Mains Delay (sec) 5
Engine Cooling Time (sec) 60
Stop Action Time (sec) 30
Additional Stopping Time (sec) 10
Load Transfer Delay (sec) 5
Power Save Mode Delay (sec) 60
Screen Changeover Time (sec) 30
Reserved 10
Sounder Alarm Time (sec) 59
Test Mode Timer (mins) 1
Generator Alternator Config Alternator Present Yes
Number of Poles 4
AC System 1 Phase
Min Healthy Voltage (volt) 185