GC2111 Default Parameters

This document contains the configuration settings for a 10KVA AMFP R-Jio power generator including: - The active profile is set to 1. - The display settings include a contrast of 50% and power save mode disabled. - RS485 communication is set for MODBUS protocol with slave ID 26 and baudrate of 9600 with no parity bit. - Battery monitoring is enabled with low battery threshold of 46.5V and delay of 10 seconds, and DG run duration of 270 seconds. - Digital and analog inputs are configured including sources, names, polarities, actions and activation settings.

Uploaded by

Srinath A
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
979 views

GC2111 Default Parameters

This document contains the configuration settings for a 10KVA AMFP R-Jio power generator including: - The active profile is set to 1. - The display settings include a contrast of 50% and power save mode disabled. - RS485 communication is set for MODBUS protocol with slave ID 26 and baudrate of 9600 with no parity bit. - Battery monitoring is enabled with low battery threshold of 46.5V and delay of 10 seconds, and DG run duration of 270 seconds. - Digital and analog inputs are configured including sources, names, polarities, actions and activation settings.

Uploaded by

Srinath A
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

ENG-PRT-MFG-SM0003805.

smc

Level 0 Level 1 Level 2 Value

Active Profile 1
Module General Profile Name 10KVA AMFP R-Jio
Power On Mode Manual
Power On Lamp Test Enable
Display Display Contrast (%) 50
Power Save Mode Disable
RS485 Communication Comm Mode MODBUS
MODBUS Slave ID 26
MODBUS Baudrate 9600
Parity Bit None
BTS Battery Montoring Enable
Low Battery Threshold 46.5
Low Battery Monitoring Delay 10
DG Run Duration 270
Cyclic Mode Cyclic Mode Disable
DG Off Time 240
DG On Time 240
Digital Inputs Digital Input A Source Remote Start / Stop
Name Auxiliary Input A
Polarity Close to Activate
Action None
Activation From Monitoring On
Activation Delay (Sec) 1
Digital Input B Source Emergency Stop
Name Auxiliary Input B
Polarity Close to Activate
Action Shutdown
Activation Always
Activation Delay (Sec) 1
Digital Input C Source Low Fuel Level Switch
Name Auxiliary Input C
Polarity Close to Activate
Action Shutdown
Activation From Monitoring On
Activation Delay (Sec) 180
Digital Input D Source User configured
Name HWT or RWL
Polarity Close to Activate
Action Shutdown

1 of 10
ENG-PRT-MFG-SM0003805.smc

Level 0 Level 1 Level 2 Value

Activation From Monitoring On


Activation Delay (Sec) 10
Digital Input E Source Low Lube Oil Pressure Switch
Name Auxiliary Input E
Polarity Close to Activate
Action Shutdown
Activation From Monitoring On
Activation Delay (Sec) 15
Digital Input F Source User configured
Name Half Fuel Level
Polarity Close to Activate
Action Notification
Activation Always
Activation Delay (Sec) 10
Digital Input G Source User configured
Name High Canopy Temp
Polarity Close to Activate
Action Shutdown
Activation From Monitoring On
Activation Delay (Sec) 10
Digital Input H Source User configured
Name Canopy Door Open
Polarity Open to Activate
Action Notification
Activation Always
Activation Delay (Sec) 1
Digital Input I Source Battery Charger Fail
Name Auxiliary Input I
Polarity Open to Activate
Action Notification
Activation Always
Activation Delay (Sec) 120
Analog Inputs LOP / DIG J Sensor Selection Lube Oil Pressure
Source Not used
Name Auxiliary Input J
Polarity Close to Activate
Action None
Activation From Monitoring On
Activation Delay(Sec) 1

2 of 10
ENG-PRT-MFG-SM0003805.smc

Level 0 Level 1 Level 2 Value

LOP Shutdown Disable


LOP Shutdown threshold (%) 1.8
LOP Warning Disable
LOP Warning threshold (%) 3
LOP Sensor Open Ckt Alarm Disable
R1 10
V1 0
R2 30
V2 1
R3 48
V3 2
R4 64
V4 3
R5 80
V5 4
R6 96
V6 5
R7 96
V7 5
R8 96
V8 5
R9 96
V9 5
R10 96
V10 5
Fuel Level / DIG K Sensor selection Fuel Level Sensor
Source Not used
Name Auxiliary Input K
Polarity Close to Activate
Action None
Activation From Monitoring On
Activation Delay (Sec) 1
Fuel Level Monitoring Low Fuel Level Shutdown Disable
Low Fuel Level Shutdown threshold (%) 10
Low Fuel Level Warning Disable
Low Fuel Level Warning threshold (%) 12
Fuel Tank Capacity (Litre) 250
Fuel Theft Alarm Disable
Fuel Theft Threshold (%/Hr) 50

3 of 10
ENG-PRT-MFG-SM0003805.smc

Level 0 Level 1 Level 2 Value

Fuel Consumption (Ltr/Hr) 2.2


Reserved Enable
R1 10
L1 0
R2 27
L2 10
R3 44
L3 20
R4 61
L4 30
R5 78
L5 40
R6 95
L6 50
R7 112
L7 60
R8 129
L8 70
R9 146
L9 80
R10 180
L10 100
Engine Temp / DIG L Sensor selection Engine Temperature Sensor
Source Not used
Name Auxiliary Input L
Polarity Close to Activate
Action None
Activation From Monitoring On
Activation Delay (Sec) 1
Temp Sensor HWT Action None
HWT threshold 110
Engine Temp Open Ckt Alarm Disable
R1 46
T1 115
R2 53
T2 110
R3 60
T3 105
R4 70

4 of 10
ENG-PRT-MFG-SM0003805.smc

Level 0 Level 1 Level 2 Value

T4 100
R5 80
T5 95
R6 93
T6 90
R7 120
T7 85
R8 222
T8 65
R9 458
T9 45
R10 458
T10 45
S1 SENSOR / Dig M Sensor Selection Digital Input M
Source Genset Contactor Latched
Name Auxiliary Input M
Polarity Close to Activate
Action None
Activation From Monitoring On
Activation Delay(Sec) 1
S1 SENSOR MONITORING Action None
Threshold 100
Threshold Type Less Than Threshold
S1 Sensor Open ckt alarm Disable
Sensor Name S1 Sensor
R1 10
Val1 0
R2 30
Val2 1
R3 40
Val3 2
R4 64
Val4 3
R5 80
Val5 4
R6 96
Val6 5
R7 96
Val7 5

5 of 10
ENG-PRT-MFG-SM0003805.smc

Level 0 Level 1 Level 2 Value

R8 96
Val8 5
R9 96
Val9 5
R10 96
Val10 5
S2 SENSOR / Dig N Sensor Selection Digital Input N
Source Mains Contactor Latched
Name Auxiliary Input N
Polarity Close to Activate
Action None
Activation From Monitoring On
Activation Delay(Sec) 1
S2 SENSOR MONITORING Action None
Threshold 100
Threshold Type Less Than Threshold
S2 Sensor Open ckt alarm Disable
Sensor Name S2 Sensor
R1 10
Val1 0
R2 30
Val2 1
R3 40
Val3 2
R4 64
Val4 3
R5 80
Val5 4
R6 96
Val6 5
R7 96
Val7 5
R8 96
Val8 5
R9 96
Val9 5
R10 96
Val10 5
Outputs Digital Output A Source Start Relay

6 of 10
ENG-PRT-MFG-SM0003805.smc

Level 0 Level 1 Level 2 Value

Polarity Energise
Digital Output B Source Stop Solenoid
Polarity Energise
Digital Output C Source Preheat Output
Polarity Energise
Digital Output D Source Common Alarm
Polarity Energise
Digital Output E Source Fail To Start
Polarity Energise
Digital Output F Source Close Gen Contactor
Polarity Energise
Digital Output G Source Close Mains Contactor
Polarity Energise
Reserved Source Disable
Reserved De-energise
Reserved Source Disable
Reserved De-energise
Timers Cranking Crank Hold Time (sec) 4
Crank Rest Time (sec) 10
Manual Start Delay (sec) 3
Auto Start Delay (sec) 90
General Safety Monotoring Delay (sec) 10
Mains Detect Delay (sec) 5
Alternator Detect Delay (sec) 5
Warm-up Delay (sec) 10
Return To Mains Delay (sec) 5
Engine Cooling Time (sec) 60
Stop Action Time (sec) 30
Additional Stopping Time (sec) 10
Load Transfer Delay (sec) 5
Power Save Mode Delay (sec) 60
Screen Changeover Time (sec) 30
Reserved 10
Sounder Alarm Time (sec) 59
Test Mode Timer (mins) 1
Generator Alternator Config Alternator Present Yes
Number of Poles 4
AC System 1 Phase
Min Healthy Voltage (volt) 185

7 of 10
ENG-PRT-MFG-SM0003805.smc

Level 0 Level 1 Level 2 Value

Min Healthy Frequency (Hz) 45


Phase Reversal Detection Disable
Phase Reversal Action None
Reserved Enable
Auto-load Transfer Disable
Voltage Monitoring UV Shutdown Enable Yes
UV Shutdown Threshold (volt) 184
UV Warning Enable No
UV Warning Threshold (volt) 185
OV Shutdown Enable Yes
OV Shutdown Threshold (volt) 264
OV Warning Enable No
OV Warning Threshold(volt) 249
Frequency Monitoring UF Shutdown Enable Yes
UF Shutdown Threshold (Hz) 45
UF Warning Enable No
UF Warning Threshold (Hz) 46
OF Shutdown Enable Yes
OF Shutdown Threshold (Hz) 55
OF Warning Enable No
OF Warning Threshold (Hz) 47
Current monitoring CT Ratio 100
Over-current Action Shutdown
Over-current Threshold (Amp) 44
Over-current Delay (sec) 10
CT Location On Load Cable
Earth CT Ratio Earth CT Ratio 0
Leak Current Action None
Leak Current Threshold 5
Leak Current Delay (sec) 5
Load Monitoring Generator Rating (kVA) 8
Over-load Action Shutdown
Load Monitoring Threshold (%) 110
Over-load Delay time (sec) 10
Unbalanced Load Action None
Unbalanced Load Threshold (%) 25
Unbalanced Load Delay (sec) 10
Mains Mains Config Mains Monitoring Enable
Mains AC system 3 Phase

8 of 10
ENG-PRT-MFG-SM0003805.smc

Level 0 Level 1 Level 2 Value

Phase Reversal Detection Disable


Phase Reversal Action None
Under-voltage Monitoring Monitoring Enable Enable
Under-voltage Trip (Volt) 122
Under-voltage Return (Volt) 135
Over-voltage Monitoring Monitoring Enable Enable
Over-voltage Trip (Volt) 270
Over-voltage Return (Volt) 265
Under-frequency Monitoring Monitoring Enable Enable
Under-frequency Trip (Hz) 45
Under-frequency Return (Hz) 46
Over-frequency Monitoring Monitoring Enable Enable
Over-frequency Trip (Hz) 55
Over-frequency Return (Hz) 54
Engine Crank Disconnect Start Attempts 3
Disconnect On LOP Sensor Disable
Disconnect Pressure Threshold (bar) 2
Mon Pres Switch Before Start Enable
Mon Pres Sensor Before Start Disable
Disconnect On LLOP Switch Enable
LLOP Switch Transient Time (sec) 0.1
Alternator Frequency (Hz) 20
Engine Speed (Speed) 600
Disconnect On Charging Alt Voltage Enable
Charging Alt Voltage Threshold 8
Speed Monitoring Engine Speed Sense Source Alternator frequency
Reserved 110
Under-speed Shutdown Enable
Under-speed Threshold (RPM) 1350
Under-speed Delay (sec) 10
Over-speed Threshold (RPM) 1650
Over-speed Delay (sec) 10
Gross Over-speed Threshold (%) 120
Battery Monitoring Low Battery voltage action Notification
Low Battery Voltage Threshold (volt) 10
Low Battery Voltage Delay (sec) 60
High Battery Voltage Action Warning
High Battery Voltage Threshold (volt) 15.5
High Battery Voltage Delay (sec) 30

9 of 10
ENG-PRT-MFG-SM0003805.smc

Level 0 Level 1 Level 2 Value

Charging Alt Monitoring Charging Alt Fail Action Notification


Chrg Alt Fail Threshold (volt) 4
Chrg Alt Fail Delay (sec) 60
Preheat Preheat Timer (sec) 3
Engine Temperature Limit Disable
Engine Temperature Limit (degC) 25
Maintenance Filter Alarm Action Notification
Due At Engine Hours 500
Alarm Due Day 1
Alarm Due Month 1
Alarm Due Year 2030