SL - No Description Set Value: Panel Name Location Micom P343 Relay Setting

This document contains relay setting values for a MiCom P343 relay for a generator located in MCB AREA Unit -1 DG-1. It includes settings for voltage transformers, current transformers, system configuration, power, field failure, thermal, backup protection, overcurrent, differential, earth fault, volts/Hz, voltage protection, frequency protection, and undercurrent monitoring. Settings are provided for alarms, trips, and protection functions across these various categories.

Uploaded by

Praneeth Reddy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
166 views

SL - No Description Set Value: Panel Name Location Micom P343 Relay Setting

This document contains relay setting values for a MiCom P343 relay for a generator located in MCB AREA Unit -1 DG-1. It includes settings for voltage transformers, current transformers, system configuration, power, field failure, thermal, backup protection, overcurrent, differential, earth fault, volts/Hz, voltage protection, frequency protection, and undercurrent monitoring. Settings are provided for alarms, trips, and protection functions across these various categories.

Uploaded by

Praneeth Reddy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 5

Panel Name AMF Panel

Location MCB AREA Unit -1 DG -1


MiCom P343 RELAY SETTING
Sl.no Description Set value
1 Main VT Primary 416 v
2 Main VT Secondary 416 v
3 VN VT Primary 416 v
4 VN VT Secondary 416 v
5 Ph CT1 Polarity Inverted
6 Phase CT1 Primary 2.500 kA
7 Phase CT1 Secondary 1.000 A
8 Ph CT2 Polarity Inverted
9 Phase CT2 Primary 2.500 kA
10 Phase CT2 Secondary 1.000 A
11 E/F CT Polarity Standard
12 E/F CT Primary 2.500 kA
13 E/F CT Secondary 1.000 A
14 Isen CT Polarity Standard
15 Isen CT Primary 1.000 A
16 Isen CT Sencondary 1.000 A
17
18 System Configuration
19 Group-1
20 Winding Configuration Generator
21 Phase Seaquence Standard ABC
22 VT Reversal No swap
23 CT1 Reversal No swap
24 CT2 Reversal No swap
25 C/S Input A-N
26 C/S V Ratio Corr 1
27 C/S VT Vect Grp 0
28 Main VT Location Gen
29 Power
30 Group-1
31 Operating mode generating
32 power -1 Function Reverse
33 P>1 Setting 20.00 w
34 power 1 time delay 5.000 s
35 power 1 DO timer 0.000 s
36 P1 Poledead Inh Enabled
37 Power 2 Function Disabled
38 NPS Overpower
39 S2>CT Source IA-1,IB-1,IC-1
40 S2>1 Status Disabled
41
42 Field Fialure
43 Group-1
44 FFail Alm Status Enabled
45 FFail Alm Angle 15 deg
46 FFail Alm Delay 5s
47 Ffail 1 Status Enabled
48 Ffail 1 - Xa1 80
49 Ffail 1 - Xb1 880
50 Ffail 1 time delay 5s
51 Ffail 1 DO timer 0s
52 Ffail 2 Status Disabled
53
54 NPS Thermal
55 Group-1
56 I2 Therm>1 Alarm Enabled
57 I2 Therm>1 set 50 mA
58 I2 Therm>1 Delay 20 s
59 I2 Therm>2 Trip Enabled
60 I2 Therm>2 set 100 mA
61 I2 Therm>2 kset 15 s
62 I2 Therm>2 kreset 15 s
63 I2 Therm>2 tmax 1 ks
64 I2 Therm>2 tmin 250 ms
65
66 System Backup
67 Group-1
68 Backup Function volt controlled
69 Vector Rotation None
70 V Dep OC Char IEC S Inverse
71 V Dep OC I>set 1A
72 V Dep OC TMS 1
73 V Dep OC tReset 0s
74 V Dep OC V<1 set 320 v
75 V Dep OC k set 250 m
76
77 over current
78 group-1
79 phase O/C
80 I> CT source IA-1,IB-1,IC-1
81 I>1 Function IEC S Inverse
82 I>1 Direction Non-Directional
83 I>1 current set 1A
84 I>1TMS 1
85 I>1 tReset 0s
86 I>2 Function Disabled
87 I>3 Status Disabled
88 I>4 Status Disabled
89 I> Char Angle 30 deg
90 I> Function link 1111
91
92 NPS Over current
93 I2> CT source IA-1,IB-1,IC-1
94 I2>1 Status Disabled
95 I2>2 Status Disabled
96 I2>3 Status Disabled
97 I2>4 Status Disabled
98 I2>VTS blocking 1111
99 I2>Char angle -60.00
100 I2>V2 pol set 20.00V
101
102 Differential
103 Group-1
104 Gen Diff Func Percentage bias
105 Gen Diff Is1 100.00mA
106 Gen Diff k1 0.00%
107 Gen Diff Is2 1.200A
108 Gen Diff k2 150%
109
110 Earth Fault
111 Group-1
112 IN> Input measured
113 IN>1 Function IEC S Inverse
114 IN>1 Current 100.00mA
115 IN>1 TMS 1
116 IN>1 tRest 0s
117 IN>2 Function Disabled
118
119 Volts/Hz
120 Group-1
121 V/Hz Alarm Status Enabled
122 V/Hz Alarm Set 9.240 V/Hz
123 V/Hz Alarm Delay 10s
124 V/Hz>1 Status Enabled
125 V/Hz>1 Trip func DT
126 V/Hz>1 Trip set 9.680 V/Hz
127 V/Hz>1 Delay 60s
128 V/Hz>2 Status Enabled
129 V/Hz>2 Trip func 10.56 V/Hz
130 V/Hz>2 Trip set 3s
131 V/Hz>3 Status Enabled
132 V/Hz>3 Trip func 11.44 V/Hz
133 V/Hz>3 Trip set 2s
134 V/Hz>3 Status Enabled
135 V/Hz>3 Trip func 12.32 V/Hz
136 V/Hz>3 Trip set 1s
137
138 VOLT Protection
139 Group-1
140 Under Voltage
141 V<measurment mode Phase-Neutral
142 V<operation mode Any phase
143 V<1 Function DT
144 V<1 voltage set 200.00V
145 V<1 time delay 4s
146 V<1 Poledead Inh Enabled
147 V<2 Status Disabled
148
149 Over Voltage
150 V>measurment mode Phase-Neutral
151 V>operation mode Any phase
152 V>1 Function DT
153 V>1 voltage set 520.00V
154 V>1 time delay 10s
155 V>2 Status Disabled
156
157 NPS Over voltage
158 V2>1 Status Disabled
159
160 Freq Protection
161 Group-1
162 F<1 Status Disabled
163 F<2 Status Disabled
164 F<3 Status Disabled
165 F<4 Status Disabled
166 F<function Link 0
167
168 over Frquency
169 F>1 Status Enabled
170 F>1 Setting 51.00Hz
171 F>1 time delay 6s
172 F>2 Status Disabled
173 Turbine F port
174 Turbine F Status Disabled
175
176 CB Fail & I<
177 Group-1
178 Under Current
179 I< Current set 100mA
180 IN< current set 20.00mA
181 I<CT source IA-1,IB-1,IC-1