Apparatus Module 3
Apparatus Module 3
PRACTICAL CONSIDERATIONS -
TRANSFORMER
THREE PHASE TRANSFORMERS
Circuit Breaker
• Explain the function and operation of a circuit breaker.
• Discuss the different parts of a circuit breaker.
• Familiarize with the different types and application of indoor and outdoor circuit breakers.
Fuses
• Explain the function and operation of a fuse.
• Discuss the different parts of a fuse.
• Familiarize with the different types and application of indoor and outdoor fuses.
Power Relays
• Explain the function and operation of a power relay.
• Familiarize with the different types and application of power relays.
EE – 405 ELECTRICAL APPARATUS AND DEVICES
1ST Semester, S. Y. 2020 – 2021
Engr. Darwin M. Marasigan, REE, RME
Practical Considerations – Transformers
Power Capacity
As has already been observed, transformers must be well designed in order to achieve acceptable
power coupling, tight voltage regulation, and low exciting current distortion. Also, transformers
must be designed to carry the expected values of primary and secondary winding current without
any trouble. This means the winding conductors must be made of the proper gauge wire to avoid
any heating problems.
Ideal Transformer
An ideal transformer would have perfect coupling (no leakage inductance), perfect voltage
regulation, perfectly sinusoidal exciting current, no hysteresis or eddy current losses, and wire
thick enough to handle any amount of current. Unfortunately, the ideal transformer would have to
be infinitely large and heavy to meet these design goals. Thus, in the business
of practical transformer design, compromises must be made.
Additionally, winding conductor insulation is a concern where high voltages are encountered, as
they often are in step-up and step-down power distribution transformers. Not only do the windings
have to be well insulated from the iron core, but each winding has to be sufficiently insulated from
the other in order to maintain electrical isolation between windings.
Transformer Ratings
Respecting these limitations, transformers are rated for certain levels of primary and secondary
winding voltage and current, though the current rating is usually derived from a volt-amp (VA)
rating assigned to the transformer. For example, take a step-down transformer with a primary
voltage rating of 120 volts, a secondary voltage rating of 48 volts, and a VA rating of 1 kVA (1000
VA). The maximum winding currents can be determined as such: kVA (1000 VA). The maximum
winding currents can be determined as such:
Sometimes windings will bear current ratings in amps, but this is typically seen on small
transformers. Large transformers are almost always rated in terms of winding voltage and VA or
kVA.
Eddy-Current Loss
Resistive losses aside, the bulk of transformer power loss is due to magnetic effects in the core.
Perhaps the most significant of these “core losses” is an eddy-current loss, which is resistive power
dissipation due to the passage of induced currents through the iron of the core. Because iron is a
conductor of electricity as well as being an excellent “conductor” of magnetic flux, there will be
currents induced in the iron just as there are currents induced in the secondary windings from the
alternating magnetic field. These induced currents—as described by the perpendicularity clause
of Faraday’s Law — tend to circulate through the cross-section of the core perpendicularly to the
primary winding turns. Their circular motion gives them their unusual name: like eddies in a stream
of water that circulate rather than move in straight lines.
Iron is a fair conductor of electricity, but not as good as the copper or aluminum from which wire
windings are typically made. Consequently, these “eddy currents” must overcome significant
electrical resistance as they circulate through the core. In overcoming the resistance offered by the
iron, they dissipate power in the form of heat. Hence, we have a source of inefficiency in the
transformer that is difficult to eliminate.
Induction Heating
This phenomenon is so pronounced that it is often exploited as a means of heating ferrous (iron-
containing) materials. The photograph below shows an “induction heating” unit raising the
temperature of a large pipe section. Loops of wire covered by high-temperature insulation encircle
the pipe’s circumference, inducing eddy currents within the pipe wall by electromagnetic
induction. In order to maximize the eddy current effect, high-frequency alternating current is used
rather than power line frequency (60 Hz). The box units at the right of the picture produce the
high-frequency AC and control the amount of current in the wires to stabilize the pipe temperature
at a pre-determined “set-point.”
Dividing the iron core into thin insulated laminations minimizes eddy current loss.
Magnetic flux is higher in a transformer core driven by 50 Hz as compared to 60 Hz for the same
voltage.
Flux changing at the same rate rises to a higher level at 50 Hz than at 60 Hz.
Yet another cause of transformer saturation is the presence of DC current in the primary winding.
Any amount of DC voltage dropped across the primary winding of a transformer will cause an
additional magnetic flux in the core. This additional flux “bias” or “offset” will push the alternating
flux waveform closer to saturation in one half-cycle than the other.
Inrush Current
When a transformer is initially connected to a source of AC voltage, there may be a substantial
surge of current through the primary winding called inrush current. This is analogous to the inrush
current exhibited by an electric motor that is started up by sudden connection to a power source,
although transformer inrush is caused by a different phenomenon.
We know that the rate of change of instantaneous flux in a transformer core is proportional to the
instantaneous voltage drop across the primary winding. Or, as stated before, the voltage waveform
is the derivative of the flux waveform, and the flux waveform is the integral of the voltage
waveform. In a continuously-operating transformer, these two waveforms are phase-shifted by
90°. Since flux (Φ) is proportional to the magnetomotive force (mmf) in the core, and the mmf is
proportional to winding current, the current waveform will be in-phase with the flux waveform,
and both will be lagging the voltage waveform by 90°:
Connecting the transformer to the line at AC volt peak: Flux increases rapidly from zero, same
as steady-state operation.
Both core flux and coil current start from zero and build up to the same peak values experienced
during continuous operation. Thus, there is no “surge” or “inrush” or current in this scenario.
Alternatively, let us consider what happens if the transformer’s connection to the AC voltage
source occurs at the exact moment in time when the instantaneous voltage is at zero. During
continuous operation (when the transformer has been powered for quite some time), this is the
point in time where both flux and winding current are at their negative peaks, experiencing zero
rate-of-change (dΦ/dt = 0 and di/dt = 0). As the voltage builds to its positive peak, the flux and
Starting at e=0 V is not the same as running continuously in Figure above. These expected
waveforms are incorrect– Φ and I should start at zero.
A significant difference exists, however, between continuous-mode operation and the sudden
starting condition assumed in this scenario: during continuous operation, the flux and current levels
were at their negative peaks when voltage was at its zero points; in a transformer that has been
sitting idle, however, both magnetic flux and winding current should start at zero.
When the magnetic flux increases in response to a rising voltage, it will increase from zero upward,
not from a previously negative (magnetized) condition as we would normally have in a transformer
that’s been powered for a while. Thus, in a transformer that’s just “starting,” the flux will reach
approximately twice its normal peak magnitude as it “integrates” the area under the voltage
waveform’s first half-cycle:
Starting at e=0 V, Current also increases to twice the normal value for an unsaturated core, or
considerably higher in the (designed for) case of saturation.
EE – 405 ELECTRICAL APPARATUS AND DEVICES
1ST Semester, S. Y. 2020 – 2021
Engr. Darwin M. Marasigan, REE, RME
This is the mechanism causing inrush current in a transformer’s primary winding when connected
to an AC voltage source. As you can see, the magnitude of the inrush current strongly depends on
the exact time that electrical connection to the source is made. If the transformer happens to have
some residual magnetism in its core at the moment of connection to the source, the inrush could
be even more severe. Because of this, transformer overcurrent protection devices are usually of
the “slow-acting” variety, so as to tolerate current surges such as this without opening the circuit.
Heat and Noise
In addition to unwanted electrical effects, transformers may also exhibit undesirable physical
effects, the most notable being the production of heat and noise. Noise is primarily a nuisance
effect, but heat is a potentially serious problem because winding insulation will be damaged if
allowed to overheat. Heating may be minimized by good design, ensuring that the core does not
approach saturation levels, that eddy currents are minimized, and that the windings are not
overloaded or operated too close to maximum ampacity.
Large power transformers have their core and windings submerged in an oil bath to transfer heat
and muffle noise, and also to displace moisture which would otherwise compromise the integrity
of the winding insulation. Heat-dissipating “radiator” tubes on the outside of the transformer case
provide a convective oil flow path to transfer heat from the transformer’s core to ambient air:
Single-phase transformers are often used to supply power for residential lighting, receptacle, air-
conditioning, and heating needs. A transformer with a 120 volt AC secondary can take care of
the lighting and receptacles. But, a transformer with a 240 volt AC secondary could handle all
the residential needs mentioned. A 240 volt AC secondary could handle the heavier 240 volt
power requirements of air conditioning and heating. The same 240 volt AC secondary could
handle the 120 volt AC needs by tapping the secondary in the center. Single phase transformers
can be made even more versatile by having both the primary winding and secondary winding
made in two equal parts. The two parts of either winding can then be reconnected in series or
parallel configurations.
Single-phase transformers usually have their windings divided into two or more sections. When
the two secondary windings are connected in series, their voltage is added. When the secondary
windings are connected in parallel, their currents are added. For example, assume each secondary
winding is rated at 120 volts and 100 amps. When series-connected, it would be 240 volts at 100
amps, or 24KVA. When parallel-connected, it would be 120 volts at 200 amps, or 24KVA. In
series connections, care must be taken to connect the coils so that their voltages add. If the
reverse happens, a short-circuit current would flow in the secondary, causing the primary to draw
a short circuit from the source. This would damage the transformer, as well as the source, and
perhaps the connector.
A three phase transformer is a three-legged iron core. Each leg has a respective primary and
secondary winding. Most power is dispersed in the form of three-phase AC. Basically the power
company generators produce electricity by rotating 3 coils or windings through a magnetic field
within the generator. These coils or windings are spaced 120 degrees apart. As they rotate
through the magnetic field they generate power which is then sent out on three lines as in three-
phase power. A three phase transformers must have 3 coils or windings connected in the proper
sequence in order to match the incoming power and therefore transform the power company
voltage to the level of voltage we need and maintain the proper phasing or polarity. Three phase
transformers is a common and popular method for electric power transmission. There are many
benefits to three phase power:
Since three-phase is used so often for power distribution systems, it makes sense that we would
need three-phase transformers to be able to step voltages up or down. This is only partially true,
as regular single-phase transformers can be ganged together to transform power between two
three-phase systems in a variety of configurations, eliminating the requirement for a special
three-phase transformer. However, special three-phase transformers are built for those tasks and
are able to perform with less material requirement, less size, and less weight than their modular
counterparts.
A three-phase transformer is made of three sets of primary and secondary windings, each set
wound around one leg of an iron core assembly. Essentially it looks like three single-phase
transformers sharing a joined core as in Figure below.
Those sets of primary and secondary windings will be connected in either Δ or Y configurations
to form a complete unit. The various combinations of ways that these windings can be connected
together it will be the focus of this section.
A three phase transformer is constructed by winding three single phase transformers on a single
core. These transformers are put into an enclosure which is then filled with dielectric oil. Since it
is a dielectric, a nonconductor of electricity, it provides electrical insulation between the
windings and the case. It also used to help provide cooling and to prevent the formation of
moisture, which can deteriorate the winding insulation. There are only 4 possible transformer
combinations:
Three phase transformers are connected in delta or wye configurations. A wye-delta transformer
has its primary winding connected in a wye and its secondary winding connected in a delta. A
delta-wye transformer has its primary winding connected in delta and its secondary winding
connected in a wye.
Wye Connections:
In a wye system the voltage between any two wires will always give the same amount of voltage
on a three phase systems. However the voltage between any one of the phase conductors and the
neutral will be less than the power conductors. For example, if the voltage between the power
conductors of any two phases of a three wire system is 208v, then the voltage from any phase
conductor to ground will be 12v. This is due to the square root of three phase power. In a wye
system, the voltage between any two power conductors will always be 1.732 (which is the square
root of 3) times the voltage between the neutral and any one of the power phase conductors. The
phase-to-ground voltage can be found by dividing the phase-to-phase voltage by 1.732.
When you have a three phase transformer and it is not available in the proper size or turns ratio a
three phase conversion is needed. Single phase transformers can be connected to form a three
phase bank. When three single phase transformers are used to make a three phase transformer
bank, their primary and secondary windings are connected in a wye or delta connection.
The open delta transformer connection can be made with only two transformers instead
of three. Usually the delta transformer is used in small business where the three phase
transformer would be excessive. It should be noted that the output power of an open delta
connection is only 87% of the rated power of the two transformers. The voltage and current
values of an open delta connection are computed in the same manner as a standard delta-delta
connection when three transformers are used. The voltage and current rules for a delta
connection must be used when determining line and phase values of voltage current.
The reasons for choosing a Y or Δ configuration for transformer winding connections are
the same as for any other three-phase application: Y connections provide the opportunity for
Probably the most important aspect of connecting three sets of primary and secondary
windings together to form a three-phase transformer bank is paying attention to proper winding
phasing (the dots used to denote “polarity” of windings). Remember the proper phase
relationships between the phase windings of Δ and Y: (Figure below)
(Y) The center point of the “Y” must tie either all the “-” or all the “+” winding points together.
(Δ) The winding polarities must stack together in a complementary manner (+ to -).
Getting this phasing correct when the windings aren’t shown in regular Y or Δ configuration can
be tricky. Let me illustrate, starting with the figure below.
Inputs A1, A2, A3 may be wired either “Δ” or “Y”, as may outputs B1, B2, B3.
Three individual transformers are to be connected together to transform power from one three-
phase system to another. First, I’ll show the wiring connections for a Y-Y configuration:
Note in Figure above how all the winding ends marked with dots are connected to their
respective phases A, B, and C, while the non-dot ends are connected together to form the centers
of each “Y”. Having both primary and secondary winding sets connected in “Y” formations
allows for the use of neutral conductors (N1 and N2) in each power system.
Note how the secondary windings (bottom set, Figure above) are connected in a chain, the “dot”
side of one winding connected to the “non-dot” side of the next, forming the Δ loop. At every
Such a configuration (Figure above) would allow for the provision of multiple voltages (line-to-
line or line-to-neutral) in the second power system, from a source power system having no
neutral.
When there is no need for a neutral conductor in the secondary power system, Δ-Δ connection
schemes (Figure above) are preferred because of the inherent reliability of the Δ configuration.
EE – 405 ELECTRICAL APPARATUS AND DEVICES
1ST Semester, S. Y. 2020 – 2021
Engr. Darwin M. Marasigan, REE, RME
Phase Wiring for “V” or “open-Δ” Transformer
Considering that a Δ configuration can operate satisfactorily missing one winding, some power
system designers choose to create a three-phase transformer bank with only two transformers,
representing a Δ-Δ configuration with a missing winding in both the primary and secondary
sides:
This configuration is called “V” or “Open-Δ.” Of course, each of the two transformers has to be
oversized to handle the same amount of power as three in a standard Δ configuration, but the
overall size, weight, and cost advantages are often worth it. Bear in mind, however, that with one
winding set missing from the Δ shape, this system no longer provides the fault tolerance of a
normal Δ-Δ system. If one of the two transformers were to fail, the load voltage and current
would definitely be affected.
While three-phase devices are usually the more cost-effective option, the single-phase option
provides more versatility and can be attractive from a reliability and maintenance standpoint.
If several identical transformers are needed at one location, the single-phase option can include
the purchase of a spare unit to reduce outage time in the event of a failure.
This practice often is seen with critical autotransformer banks and generator step-up transformers
because loss of the transformer for an extended period has very significant impacts.
The connections discussed in this article will be implemented using single-phase units.
The two most commonly used three-phase winding configurations are delta and wye, named
after the Greek and English letter that each resembles. In a delta configuration, the three
Although delta windings are often operated ungrounded, a leg of the delta can be center tapped
and grounded, or a corner of the delta can be grounded. In a wye configuration, one end of each
of the three windings is connected to form a neutral. A phase is connected to the other end of the
three windings. The neutral is usually grounded.
1. Delta–Delta
Delta–delta transformers, as shown in Figure 1, often are used to supply loads that are
primarily three phase but may have a small single-phase component.
The three-phase load is typically motor load while the single-phase component is often lighting
and low voltage power. The single-phase load can be fed by grounding a center tap on one of the
legs of the delta secondary, then connecting the single-phase load between one of the phases on
the grounded leg and this grounded neutral.
The connection diagram on the left shows how a delta–delta connection can be made, either
with three single-phase transformers or with one three-phase transformer.
The dashed lines indicate the transformer outlines. The three single-phase transformer
implementation can be seen by disregarding the outer dashed outline and the bushing labels
shown at that outline, and concentrating on the three smaller (single-phase transformer) outlines.
The phasor diagram at the lower right shows the geometric relationships between the high
voltage circuit and low voltage circuit currents, and the equations at the bottom center show
those relationships mathematically.
Also, the amount of single-phase load should be kept low because the center-tapped transformer
must supply most of the single-phase load. As the single-phase load is increased, the center-
tapped transformer will increase its loading more than the other two transformers and will
eventually overload.
If one of the single-phase transformers in the delta–delta bank fails, the bank can be operated
with only two transformers forming an open delta configuration. The kVA rating of the bank is
reduced, but three-phase power is still supplied to the load.
2. Wye–Wye
Wye–wye transformers, as shown in Figure 3, can serve both three-phase and single-phase
loads. The single-phase load should be distributed as evenly as possible between each of the
three phases and neutral.
Adding a third (tertiary) winding connected in delta alleviates many of the concerns mentioned.
3. Delta–Wye
The delta–wye connection is the most commonly used three-phase transformer connection.
The wye-connected secondary allows single-phase load to be distributed among the three phases
to neutral instead of being placed all on one winding as with a four-wire delta secondary.
If one of the single-phase transformers in the delta–wye bank fails, the entire bank becomes
inoperative.
Also, since the delta–wye transformer introduces a 30° phase shift from primary to secondary as
can be seen by the phasing symbols in Figure 5, it cannot be paralleled with delta–delta and
wye–wye transformers that produce no phase shift.
Analyzing the delta–wye transformer illustrates many important concepts regarding the operation
of polyphase transformers. The analysis can be done on either a voltage or a current basis. Since
voltage (potential difference or the subtraction of two phasor quantities) is rather abstract and
The currents owing in the windings of a delta–wye transformer are shown in Figure 7. Note that
the arrows indicate instantaneous directions of the AC current and are consistent with the dot
convention.
The analysis must begin in one of the two electric circuits, either the delta- connected high
voltage circuit or the wye-connected low voltage circuit.
Since current is being used as the basis for analysis, the wye-connected circuit is selected as the
starting point, since in a wye-connected circuit, the line currents (leaving the transformer) and
the phase currents ( owing in the transformer windings) are equal. This relationship between line
and phase currents simplifies the analysis.
The analysis starts by labeling all line and phase currents. This is shown in Figure 8.
Note that lower-case subscripts indicate line currents in the low voltage circuit, and upper-case
subscripts indicate line currents in the high voltage circuit. In the low voltage circuit, the phase
currents are identical to the corresponding line currents, so they also are labeled Ia, Ib, and Ic.
EE – 405 ELECTRICAL APPARATUS AND DEVICES
1ST Semester, S. Y. 2020 – 2021
Engr. Darwin M. Marasigan, REE, RME
When the transformer windings are drawn, a particular high voltage winding corresponds to the
low voltage winding drawn parallel to it.
The high voltage phase current corresponding to Ia is labeled Ia′ . The direction of Ia′ relative to
that of Ia must honor the dot convention. The magnitude of Ia′ relative to Ia is the inverse of
the transformer turns ratio “n”, or
Ia′ = Ia
So,
Ia′ = Ia (per-unit)
Ib′ = Ib (per-unit)
Ic′ = Ic (per-unit)
(Eqs. 1)
Next, Kirchhoff’s current law can be applied to each node of the delta:
IA = Ia′− Ib′ = Ia − Ib
IB = Ib′− Ic′ = Ib − Ic
IC = Ic′− Ia′ = Ic − Ia
(Eqs. 2)
Equations above express the high voltage circuit line currents in terms of the low voltage
circuit line currents. At this point, numerical values can be substituted for Ia, Ib, and Ic. Keeping
in mind that Ia, Ib, and Ic represent a balanced set of phasors, arbitrary per-unit values are
selected to represent a-b-c phase sequencing:
Eqs. 3
EE – 405 ELECTRICAL APPARATUS AND DEVICES
1ST Semester, S. Y. 2020 – 2021
Engr. Darwin M. Marasigan, REE, RME
Substituting Eqs. 3 into Eqs. 2:
Eqs. 4
IEEE Std. C57.12.00 defines the direction in which the phasor angles shall change from one
electrical circuit to the other. In a standard delta–wye (or wye–delta) transformer, the positive-
sequence currents and voltages on the high voltage side lead the positive-sequence currents and
voltages on the low voltage side by 30°.
Note that the convention to determine a standard connection requires that the high voltage
phasors lead the low voltage phasors by 30°. No reference is made to primary or secondary. The
primary windings of a transformer are those windings to which voltage is applied. The secondary
windings have an induced voltage impressed across them.
Usually, the primary windings are the high voltage windings, but this is not always the case. A
good example of an exception is a generator step-up transformer.
The primary wye windings are typically grounded. If the secondary is a four-wire delta, the
fourth wire originating at a center tap on one of the legs of the delta is grounded.
WYE transformer coils are wired in parallel, like connecting 4 light bulbs to the hot wire.
On the 3-can transformer bank for WYE, you would observe 3 hot wires drop down from the 3 overhead
distribution lines. Each hot wire connects to 1 transformer. The Neutral wire connects to all 3
transformers.
Delta transformer coils are wired in series, like stacking batteries end to end.
On the 3-can transformer bank for Delta, you would observe 3 hot wires drop down from the 3 overhead
distribution lines. Each hot wire connects to 2 different transformers.
Using WYE on the secondary, or customer side, supplies a Neutral connection, and allows for
more voltage combinations and higher-amp service, with equal votage on all 3 legs.
Materials used for the power grid are a balance of cost, function and safety, so reducing amps using Delta
on primary side saves money overall. However not every customer application can be met using Delta
primary. There are a wide variety of volt-amp requirements at end user locations, and many ways to wire
transformers to meet electrical needs.
WYE is frequently called Star, for example Star-Delta motor starter or timer. Motors consume a
lot a of amperage when starting, so the star or wye configuration (more amps) is used for starting, and
after the motor gets going, the circuit is switched to delta (low amps) for higher efficiency. This basic
strategy meets electrical regulations intended to reduce voltage surges on the grid.
Delta - Delta
Ground wire to each transformer NOT shown
Delta – WYE
How do we know? Each hot wire connects to two transformers.... so they are wired in
series Secondary is WYE. One wire connects to all three transformers, and to Neutral. One wire
from each transformer is Hot... so they are wired in parallel System neutral connects to Neutral
EE – 405 ELECTRICAL APPARATUS AND DEVICES
1ST Semester, S. Y. 2020 – 2021
Engr. Darwin M. Marasigan, REE, RME
and ground. There are many different transformer configurations this is 'most common type of
wiring' because Delta has lower amps/ meaning less heat, so insulation on primary coil is less
expensive. Transformers can be wired different ways depending on the incoming electric supply
and end user need. Two key factors for the grid are economic performance and reliability.
Reliability is necessary because electricity must run clean without big-voltage spikes and low-
voltage brownouts. Otherwise motors and HVAC equipment will have shorter lifespan.
Normally, the Neutral service wire is located on top of other three Hot wires
Primary wires are not insulated/ Secondary wires to service are insulated.
Neutral on pole connects to Neutral going to service, and to ground wire that bonds each
transformer to the earth, illustration does not clearly show this. Installations might use bare solid
copper, or use the stranded aluminum per more recent practice.
Delta primary/ WYE secondary ... because Delta carries less amperage, so primary coils
can use smaller wire ... saves cost of transformer
Normally, the Neutral service wire is located on top of other three How wires
Primary wires are not insulated/ Secondary wires to service are insulated.
Neutral on pole connectes to Neutral going to service, and to ground wire that bonds each
transformer to the earth.
Normally, the 3 service wires to house are triplex, with 1 bare stranded Neutral and 2
insulated Hots.
The Neutral wire runs continuously across the grid to bond all grounds into one giant array of
earth connections that stablize the grid from overvoltage, short circuits, lightning etc ... and to
protect and assist circuit breakers and wires. Ground wires are present at each pole, transmission
tower, and electrical connection across the grid.
WYE Primary / DELTA secondary/ distribution transformers at substation handle high voltage
shows 3 transformers, with 3 primary coils and 3 secondary coils Primary WYE 69,000 volts ...
because 1 69,000 volt wire connects to 1 transformer Secondary Delta 4,400 volts ... because 1
4400 volt wire connects to 2 transformers
Generally 4,400 volts is lowest voltage for distribution without heat loss from high amperage
The lower the voltage, the higher the amperage.
As a result, the end user must receive low volts with higher amperage
To meet demands on the grid, transformers are used to raise and lower volts and amps in inverse
proportion
When volts are reduced, amps are increased.
EE – 405 ELECTRICAL APPARATUS AND DEVICES
1ST Semester, S. Y. 2020 – 2021
Engr. Darwin M. Marasigan, REE, RME
Why does transformer wiring differ.
1) Electricity is mathematical
For example: Cosine of phase angle is known as power factor
P is power factor
Power factor is cosine of phase difference between v and I
2) Cost
Delta configuration reduces amperage for the same amount of voltage
Generally transmission lines are higher off the ground because the air space acts as the insulator
for bare conductor wire. Air is a non-conductive insulator.
Image shows transmission lines that run from local Rosenberg substation out to another
substation in rural area of county.
Distribution lines leave from the same Rosenberg substation and distribute power in one section
of town.
Distribution lines can be identified because transformers connect to the distribution lines.
Circuit Breakers
How Circuit Breakers Work
The circuit breaker is an absolutely essential device in the modern world, and one of the
most important safety mechanisms in your home. Whenever electrical wiring in a building has
too much current flowing through it, these simple machines cut the power until somebody can fix
the problem. Without circuit breakers (or the alternative, fuses), household electricity would be
impractical because of the potential for fires and other mayhem resulting from simple wiring
problems and equipment failures.
In this article, we'll find out how circuit breakers and fuses monitor electrical current and
how they cut off the power when current levels get too high. As we'll see, the circuit breaker is
an incredibly simple solution to a potentially deadly problem.
• Voltage
• Current
• Resistance
Voltage is the "pressure" that makes an electric charge move. Current is the charge's "flow" -- the
rate at which the charge moves through the conductor, measured at any particular point. The
conductor offers a certain amount of resistance to this flow, which varies depending on the
conductor's composition and size.
Voltage, current and resistance are all interrelated -- you can't change one without changing
another. Current is equal to voltage divided by resistance (commonly written as I = v / r). This
makes intuitive sense: If you increase the pressure working on electric charge or decrease the
resistance, more charge will flow. If you decrease pressure or increase resistance, less charge
will flow.
In the electrical and electronics world, there are many cases where mishap takes place. It
will lead to severe damage to building, offices, houses, schools, industries, etc. Trusting voltage
and current are not correct, though safety measures are taken. Once circuit breakers are installed
it will control the sudden rise of voltage and current. It will help from any accident. Circuit
breakers are like the heart of the electrical system. There are different types of circuit
breakers where these are installed according to the rating of the system. In house different kind
of circuit breaker is used and for industries another type of circuit breaker is used.
Electrical circuit breaker is a switching device which can be operated automatically or manually
for protecting and controlling of electrical power system. In the modern power system the design
of the circuit breaker has changed depending upon the huge currents and to prevent from arc
while operating.
The different types of high voltage circuit breakers which includes the following
This circuit breaker will operate in the air; the quenching medium is an Arc at
atmospheric pressure. In many of the countries air circuit breaker is replaced by oil circuit
breaker. About oil circuit breaker we will discuss later in the article. Thus the importance of
This arc is made to drive in it. In achieving the cooling of the air circuit breaker, an arc
chute will help. From the refractory material, an arc chute is made. The internal walls of arc
chute are shaped in such a way that arc is not forced into close proximity. It will drive into the
winding channel projected on an arc chute wall.
The arc chute will have many small compartments and has many divisions which are
metallic separated plates. Here each of small compartments behaves as a mini arc chute and
EE – 405 ELECTRICAL APPARATUS AND DEVICES
1ST Semester, S. Y. 2020 – 2021
Engr. Darwin M. Marasigan, REE, RME
metallic separation plate acts like arc splitters. All arc voltages will be higher than the system
voltage when the arc will split into a series of arcs. It is only preferable for low voltage
application.
Air blast circuit breakers are used for system voltage of 245 KV, 420 KV and also even
more.Air blast circuit breakers are of two types:
In the axial blaster breaker the moving contact of the axial blast breaker will be in
contact. The nozzle orifice is a fixed to the contact of a breaker at a normal closed condition. A
fault occurs when high pressure is introduced into the chamber. Voltage is sufficient to sustain
high-pressure air when flowed through nozzle orifice.
In the SF6 circuit breaker the current carrying contacts operate in sulphur hexafluoride
gas is known as an SF6 circuit breaker. It is an excellent insulating property and high electro-
negativity. It can be understood that, high affinity of absorbing free electron. The negative ion is
formed when a free electron collides with the SF6 gas molecule; it is absorbed by that gas
molecule. The two different ways of attachment of electron with SF6 gas molecules are
SF6 + e = SF6
SF6 + e = SF5- + F
The negative ions which are formed will be much heavier than a free electron. Therefore,
when compared with other common gases overall mobility of the charged particle in the SF6 gas
is much less. The mobility of charged particles is majorly responsible for conducting current
through a gas. Hence, for heavier and less mobile charged particles in SF6 gas, it acquires very
high dielectric strength. This gas good heat transfer property because of low gaseous viscosity.
SF6 is 100 times more effective in arc quenching media than air circuit breaker. It is used for
both medium and high voltage electrical power system from 33KV to 800KV.
A Vacuum circuit breaker is a circuit which vacuum is used to extinct the arc. It has
dielectric recovery character, excellent interruption and can interrupt the high frequency current
which results from arc instability, superimposed on the line frequency current.
In the principle of operation of VCB will have two contacts called electrodes will remain
closed under normal operating conditions. Suppose when a fault occurs in any part of the system,
then the trip coil of the circuit breaker gets energized and finally contact gets separated.
Advantages
In this type of circuit breaker oil is used, but mineral oil is preferable. It acts better
insulating property than air. The moving contact and fixed contact are immerged inside the
insulating oil. When the separation of current takes place, then carrier contacts in the oil, the arc
in circuit breaker is initialized at the moment of separation of contacts, and because of this arc in
the oil is vaporized and decomposed in hydrogen gas and finally creates a hydrogen bubble
around the arc.
This highly compressed gas bubble around and arc prevents re-striking of the arc after
current reaches zero crossing of the cycle. The OCB is the oldest type of circuit breakers.
In the BOCB, oil is used to arc the quenching media and also for insulating media in
between earth parts of circuit breaker and current carrying contacts. The same transformer
insulating oil is used.
The working principle of the BOCB says when the current carrying contacts in the oil are
separated, then an arc is generated between the separated contacts. The arc which is established
will produce rapid growing gas bubble around the arc. The moving contacts will move away
from the fixed contact of arc and this result the resistance of the arc gets increased. Here the
increased resistance will cause the lowering the temperature. Hence the reduced formations of
gasses surround the arc.
Advantages
Disadvantages
• It will not permit high speed of interruption
• It takes long arcing time.
It is a circuit breaker which utilizes oil as the interrupting media. The minimum oil circuit
breaker will place the interrupting unit in an insulating chamber at the live potential. But
insulating material is available in interrupting chamber. It requires less amount of oil so it is
called as minimum oil circuit breaker.
Advantages
Disadvantages
In this article the different types of circuit breakers, i.e. Air Circuit Breaker, SF6 Circuit
Breaker, Vacuum Circuit Breaker and Oil Circuit Breaker have been discussed in a short detailed
just to understand the basic concept about these circuit breakers. And their subdivision is also
discussed along with advantages and disadvantages. We have discussed every concept very
clearly. If you have not understood any of the topics, you feel any information is missing or to
implement any electrical projects for engineering students, please feel free to comment in the
below section.
What is a Fuse?
A fuse is an electrical safety device built around a conductive strip that is designed to melt and
separate in the event of excessive current. Fuses are always connected in series with the
component(s) to be protected from overcurrent, so that when the fuse blows (opens) it will open
the entire circuit and stop current through the component(s). A fuse connected in one branch of
a parallel circuit, of course, would not affect current through any of the other branches.
Normally, the thin piece of fuse wire is contained within a safety sheath to minimize hazards of
arc blast if the wire burns open with violent force, as can happen in the case of severe
overcurrents. In the case of small automotive fuses, the sheath is transparent so that the fusible
element can be visually inspected. Residential wiring used to commonly employ screw-in fuses
with glass bodies and a thin, narrow metal foil strip in the middle. A photograph showing both
types of fuses is shown here:
Cartridge type fuses are popular in automotive applications, and in industrial applications when
constructed with sheath materials other than glass. Because fuses are designed to “fail” open
when their current rating is exceeded, they are typically designed to be replaced easily in a
circuit. This means they will be inserted into some type of holder rather than being directly
soldered or bolted to the circuit conductors. The following is a photograph showing a couple of
glass cartridge fuses in a multi-fuse holder:
Another type of fuse holder for cartridge-type fuses is commonly used for installation in
equipment control panels, where it is desirable to conceal all electrical contact points from
human contact. Unlike the fuse block just shown, where all the metal clips are openly exposed,
this type of fuse holder completely encloses the fuse in an insulating housing:
The most common device in use for overcurrent protection in high-current circuits today
is the circuit breaker.
EE – 405 ELECTRICAL APPARATUS AND DEVICES
1ST Semester, S. Y. 2020 – 2021
Engr. Darwin M. Marasigan, REE, RME
What is a Circuit Breaker?
Circuit breakers are specially designed switches that automatically open to stop current
in the event of an overcurrent condition. Small circuit breakers, such as those used in residential,
commercial and light industrial service are thermally operated. They contain a bimetallic strip (a
thin strip of two metals bonded back-to-back) carrying circuit current, which bends when heated.
When enough force is generated by the bimetallic strip (due to overcurrent heating of the strip),
the trip mechanism is actuated and the breaker will open. Larger circuit breakers are
automatically actuated by the strength of the magnetic field produced by current-carrying
conductors within the breaker, or can be triggered to trip by external devices monitoring the
circuit current (those devices being called protective relays).
From outside appearances, it looks like nothing more than a switch. Indeed, it could be
used as such. However, its true function is to operate as an overcurrent protection device.
It should be noted that some automobiles use inexpensive devices known as fusible
links for overcurrent protection in the battery charging circuit, due to the expense of a properly-
rated fuse and holder. A fusible link is a primitive fuse, being nothing more than a short piece of
rubber-insulated wire designed to melt open in the event of overcurrent, with no hard sheathing
of any kind. Such crude and potentially dangerous devices are never used in industry or even
residential power use, mainly due to the greater voltage and current levels encountered. As far as
this author is concerned, their application even in automotive circuits is questionable.
Fuses are primarily rated, as one might expect, in the unit for current: amps. Although
their operation depends on the self-generation of heat under conditions of excessive current by
means of the fuse’s own electrical resistance, they are engineered to contribute a negligible
amount of extra resistance to the circuits they protect. This is largely accomplished by making
the fuse wire as short as is practically possible. Just as a normal wire’s ampacity is not related to
its length (10-gauge solid copper wire will handle 40 amps of current in free air, regardless of
how long or short of a piece it is), a fuse wire of certain material and gauge will blow at a certain
current no matter how long it is. Since length is not a factor in current rating, the shorter it can be
made, the less resistance it will have end-to-end.
However, the fuse designer also has to consider what happens after a fuse blows: the
melted ends of the once-continuous wire will be separated by an air gap, with full supply voltage
between the ends. If the fuse isn’t made long enough on a high-voltage circuit, a spark may be
able to jump from one of the melted wire ends to the other, completing the circuit again:
Some large industrial fuses have replaceable wire elements, to reduce the expense. The
body of the fuse is an opaque, reusable cartridge, shielding the fuse wire from exposure and
shielding surrounding objects from the fuse wire.
There’s more to the current rating of a fuse than a single number. If a current of 35 amps
is sent through a 30 amp fuse, it may blow suddenly or delay before blowing, depending on other
aspects of its design. Some fuses are intended to blow very fast, while others are designed for
more modest “opening” times, or even for a delayed action depending on the application. The
latter fuses are sometimes called slow-blow fuses due to their intentional time-delay
characteristics.
On the other end of the fuse action spectrum, there are so-called semiconductor
fuses designed to open very quickly in the event of an overcurrent condition. Semiconductor
devices such as transistors tend to be especially intolerant of overcurrent conditions, and as such
require fast-acting protection against overcurrents in high-power applications.
In either case, the fuse successfully interrupted current to the load, but the lower circuit
fails to interrupt potentially dangerous voltage from either side of the load to ground, where a
person might be standing. The first circuit design is much safer.
As it was said before, fuses are not the only type of overcurrent protection device in use.
Switch-like devices called circuit breakers are often (and more commonly) used to open circuits
with excessive current, their popularity due to the fact that they don’t destroy themselves in the
process of breaking the circuit as fuses do. In any case, though, placement of the overcurrent
protection device in a circuit will follow the same general guidelines listed above: namely, to
“fuse” the side of the power supply not connected to ground.
EE – 405 ELECTRICAL APPARATUS AND DEVICES
1ST Semester, S. Y. 2020 – 2021
Engr. Darwin M. Marasigan, REE, RME
Although overcurrent protection placement in a circuit may determine the relative shock
hazard of that circuit under various conditions, it must be understood that such devices were
never intended to guard against electric shock. Neither fuses nor circuit breakers were designed
to open in the event of a person getting shocked; rather, they are intended to open only under
conditions of potential conductor overheating. Overcurrent devices primarily protect the
conductors of a circuit from overtemperature damage (and the fire hazards associated with overly
hot conductors), and secondarily protect specific pieces of equipment such as loads and
generators (some fast-acting fuses are designed to protect electronic devices particularly
susceptible to current surges). Since the current levels necessary for electric shock or
electrocution are much lower than the normal current levels of common power loads, a condition
of overcurrent is not indicative of shock occurring. There are other devices designed to detect
certain shock conditions (ground-fault detectors being the most popular), but these devices
strictly serve that one purpose and are uninvolved with protection of the conductors against
overheating.
REVIEW:
• A fuse is a small, thin conductor designed to melt and separate into two pieces for the
purpose of breaking a circuit in the event of excessive current.
• Fuses are primarily rated in terms of maximum current, but are also rated in terms of how
much voltage drop they will safely withstand after interrupting a circuit.
• Fuses can be designed to blow fast, slow, or anywhere in between for the same maximum
level of current.
• The best place to install a fuse in a grounded power system is on the ungrounded
conductor path to the load. That way, when the fuse blows there will only be the
grounded (safe) conductor still connected to the load, making it safer for people to be
around.
A French physicist namely “Breguet” was famous for his effort in the initial days of
telegraphy. He suggested the utilization of reduced part of conductors to guard telegraph stations
against the hits of lighting with liquefying, the slighter wires would guard equipment along with
EE – 405 ELECTRICAL APPARATUS AND DEVICES
1ST Semester, S. Y. 2020 – 2021
Engr. Darwin M. Marasigan, REE, RME
wiring in the building. In the year 1864, lighting installations and telegraph cables can be
protected by employing a variety of foil fusible essentials and wires. Finally, Thomas Alva
Edison has patented a fuse as an element of his electric distribution system in the year 1890. This
article discusses what is a fuse, types of fuses and its applications in various fields.
These are used to prevent the home appliances from the high current or overload damage.
If we use a fuse in the homes, the electrical faults cannot happen in the wiring and it doesn’t
damage the appliance s from the fire of wire burning. When the fuse gets break or damage, then
an abrupt sparkle happens which may direct to damage your home appliances. That is the reason
we require different types of fuses to guard our home-appliances against damage.
The working principle of the fuse is “heating consequence of the current”. It is fabricated
with a lean strip or thread of metallic wire. The connection of the Fuse in an electrical circuit is
always in series.
When the too much current is produced due to the heavy flow of current in the electrical
circuit, the fuse gets soften and it opens the circuit. The extreme flow of current may direct to the
collapse of the wire and prevents the supply.
The fuse can be changed by the new fuse with an appropriate rating. It can be designed
with the elements like Cu (copper), Zn (zinc), Al (aluminum) and Ag (silver). They also perform
like a circuit breaker for breaking the circuit while the abrupt fault happens in the circuit. This
works like a safety measure or protector for humans from risks. Like this, the fuse works.
The selection of a fuse can be done by calculating the fuse rating by using the above formula.
The fuses are classified into several types based on the application namely AC type
fuse and DC type fuse. Again these fuses are classified into several types. The following
diagram illustrates the electrical fuse types chart based on the AC fuse and DC fuse.
AC Fuses
The AC fuse is slighter in size and oscillated 50 to 60 times in each and every sec from
least to highest. As a result, there is no scope for Arc generation between the dissolved wires. For
this reason, they can be crammed in small size. Further, AC fuses are classified into two parts
namely HV fuses and LV fuses. Here LV& HV indicates the low voltage and high voltage.
AC Fuse
The low voltage fuses are divided into five types such as rewirable, cartridge, drop out,
striker and switch fuses.
LV Fuse
Rewirable fuses are LV fuses, which are almost used in small applications like wiring in
the house, small-scale industries, and other tiny current applications. These types of fuses include
two essential parts such as a fuse base, which has two terminals like in and out. In general, this
element is fabricated with Porcelain. Another part of this fuse is a fuse carrier, which grips the
fuse element. This element is fabricated with aluminum, tinned copper and lead. The main
advantage of a fuse carrier is, we can simply plug and remove from the base of the fuse without
the risk of shock. As the fuse is damaged due to heavy current, then we can simply eliminate the
Fuse Carrier as well as put back the fuse wire.
Rewirable Fuses
The cartridge type of fuses has entirely closed containers and the metal contact as well. The
applications of this fuse mainly include low voltage (LV), high voltage (HV), and small fuses.
Again, these types of fuses are classified into two types, they are D-type and Link-type fuses.
This type of fuse is composed with the cartridge, base of the fuse, adapter ring, and cap. The base
of the fuse includes a fuse cap, which is packed with the fuse ingredient by cartridge using an
adapter ring.
It is composed of the cartridge, fuse base, cap & adapter ring. The fuse base has the fuse cap,
which is fitted with the fuse element with a cartridge through the adapter ring. The connection of
the circuit is finished when the tilt of the cartridge builds contact through the conductor.
The link type fuse is also known as high rupturing capacity (HRC) or BS type fuse. In this sort of
fuse, the current flow with fuse element is specified under standard condition.
In this BS type fuse, the flow of current by fuse element is given under normal condition. The arc
which is generated by the fuse blown is controlled is fabricated with porcelain, ceramic, and
silver. The container of the fuse element is packed with silica sand. This type of fuse is again
categorized into two parts includes a blade type and bolted type.
The knife type fuse or plug-in type of fuses is designed with plastic. This type of fuse can
be simply changeable in the electric circuit exclusive of any load.
In bolted type fuse, plates of this fuse are conducting are set to the base of the fuse.
The striker type of fuse is employed for tripping and closing the electrical circuit. These
fuses are having plenty of force as well as displacement.
Basically, the switch type fuse is enclosed with a metal switch and also a fuse. These
fuses are mainly used in low and intermediate voltage levels.
Generally, HV fuses are used to protect the transformers like instrument transformers,
small power transformer and also used in power systems. These fuses are normally charged for
voltages over 1500V to 138000V.
The fuse component of the HRC is cut in the helix form which evades the effect of
corona at the upper voltages. It includes two fused elements namely low resistance and high
resistance, and that are located parallel by each other. The low-resistance wires take the usual
current which is blown-out as well as decreases the short-circuit current throughout the fault
state.
This type of fuse is packed with carbon tetrachloride also preserved at both the tops of the
caps. Once the error occurs when the flowing current surpasses away from the allowable limit,
and the element of the fuse is blown-out. The fluid of the fuse performs as an arc extinguishing
standard for the HRC fuse types. They may be used to protect the transformer as well as the
support protection to the breaker circuit.
These types of fuses are extensively used to protect the feeders as well as transformer due
to they’re low-priced. It is designed for 11kV; also their cracking capability is up to 250 MVA.
This type of fuse includes an unfilled open finished cylinder designed with synthetic resin-
bonded paper.
The elements of the fuse are positioned in the cylinder, and the tubes tops are linked to
appropriate equipment at every finish. The arc generating is blown off in the inside covering of
the cylinder, and the gases thus shaped destroys the arc.
In this type of fuse, the melting of fuse causes the element to drop under gravity about its
lower support. They are made for the protection of outdoor transformers.
Resettable Fuses
It is the type of fuse, commonly known as self-resetting fuses which uses a thermoplastic
conductive type thermistor known as Polymeric Positive Temperature Coefficient (PPTC). If a
fault occurs. Current increases, temperature also increase. The increase in resistance is due to
increase in temperature. The applications where it is used are military and aerospace where
replacement is not possible.
The different types of fuses and their uses have discussed are essential components in all
the electrical circuits. Some of the main applications of fuses in Electrical and Electronics
field include the following.
• Power Transformers
• Electrical Appliances, like ACs (Air Conditioners), TV, Washing Machines, Music
Systems, and many more.
EE – 405 ELECTRICAL APPARATUS AND DEVICES
1ST Semester, S. Y. 2020 – 2021
Engr. Darwin M. Marasigan, REE, RME
• Electrical Cabling in Home
• Mobile Phones
• Motor starters
• Laptops
• Power Chargers
• Cameras, Scanners, Printers, and Photocopiers
• Automobiles, electronic devices and Gaming’s
Power Relays
How Relays Work
Relays are switches that open and close circuits electromechanically or electronically. Relays
control one electrical circuit by opening and closing contacts in another circuit. As relay
diagrams show, when a relay contact is normally open (NO), there is an open contact when the
relay is not energized. When a relay contact is Normally Closed (NC), there is a closed contact
when the relay is not energized. In either case, applying electrical current to the contacts will
change their state.
Relays are generally used to switch smaller currents in a control circuit and do not usually
control power consuming devices except for small motors and Solenoids that draw low amps.
Nonetheless, relays can "control" larger voltages and amperes by having an amplifying effect
because a small voltage applied to a relays coil can result in a large voltage being switched by
the contacts.
Protective relays can prevent equipment damage by detecting electrical abnormalities, including
overcurrent, undercurrent, overloads and reverse currents. In addition, relays are also widely
used to switch starting coils, heating elements, pilot lights and audible alarms.
Electromechanical Relays
1. Frame: Heavy-duty frame that contains and supports the parts of the relay.
2. Coil: Wire is wound around a metal core. The coil of wire causes an electromagnetic
field.
3. Armature: A relays moving part. The armature opens and closes the contacts. An
attached spring returns the armature to its original position.
4. Contacts: The conducting part of the switch that makes (closes) or breaks (opens) a
circuit.
• Break -This is the number of separate places or contacts that a switch uses to open or
close a single electrical circuit. All contacts are either single break or double break. A
single break (SB) contact breaks an electrical circuit in one place, while a double break
(DB) contact breaks it in two places. Single break contacts are normally used when
switching lower power devices such as indicating lights. Double break contacts are used
when switching high-power devices such as solenoids.
• Pole -This is the number of completely isolated circuits that relays can pass through a
switch. A single-pole contact (SP) can carry current through only one circuit at a time. A
double-pole contact (DP) can carry current through two isolated circuits simultaneously.
The maximum number of poles is 12, depending upon a relays design.
• Throw -This is the number of closed contact positions per pole that are available on a
switch. A switch with a single throw contact can control only one circuit, while a double-
throw contact can control two.
2. Machine Control Relays are also operated by a magnetic coil. They are heavy-duty
relays used to control starters and other industrial components. Although they are more
expensive than general purpose relays, they are generally more durable. The biggest
advantage of machine control relays over general purpose relays is the expandable
functionality of Machine Control Relays by the adding of accessories. A wide selection
EE – 405 ELECTRICAL APPARATUS AND DEVICES
1ST Semester, S. Y. 2020 – 2021
Engr. Darwin M. Marasigan, REE, RME
of accessories is available for machine control relays, including additional poles,
convertible contacts, transient suppression of electrical noise, latching control and timing
attachments.
3. Reed Relays are a small, compact, fast operating switch design with one contact, which
is NO. Reed Relays are hermetically sealed in a glass envelope, which makes the contacts
unaffected by contaminants, fumes or humidity, allows reliable switching, and gives
contacts a higher life expectancy. The ends of the contact, which are often plated with
gold or another low resistance material to increase conductivity, are drawn together and
closed by a magnet. Reed relays are capable of switching industrial components such as
solenoids, contactors and starter motors. Reed relays consists of two reeds. When a
magnetic force is applied, such as an electromagnet or coil, it sets up a magnetic field in
which the end of the reeds assume opposite polarity. When the magnetic field is strong
enough, the attracting force of the opposite poles overcomes the stiffness of the reeds and
draws them together. When the magnetic force is removed, the reeds spring back to their
original, open position. These relays work very quickly because of the short distance
between the reeds.
Solid state relays consist of an input circuit, a control circuit and an output circuit. The Input
Circuit is the portion of a relays frame to which the control component is connected. The input
circuit performs the same function as the coil of electromechanical relays. The circuit is activated
when a voltage higher than the relays specified Pickup Voltage is applied to the relays input. The
input circuit is deactivated when the voltage applied is less than the specified minimum Dropout
voltage of the relay. The voltage range of 3 VDC to 32 VDC, commonly used with most solid-
state relays, makes it useful for most electronic circuits. The Control Circuit is the part of the
relay that determines when the output component is energized or de-energized. The control
circuit functions as the coupling between the input and output circuits. In electromechanical
relays, the coil accomplishes this function. A relays Output Circuit is the portion of the relay that
switches on the load and performs the same function as the mechanical contacts of
electromechanical relays. Solid-state relays, however, normally have only one output contact.
1. Zero-Switching Relays - relays turns ON the load when the control (minimum
operating) voltage is applied and the voltage of the load is close to zero. Zero-Switching
relays turn OFF the load when the control voltage is removed and the current in the load
is close to zero. Zero-Switching relays are the most widely used.
3. Peak Switching Relays - turns ON the load when the control voltage is present, and the
voltage of the load is at its peak. Peak Switching relays turn OFF when the control
voltage is removed and the current in the load is close to zero.
4. Analog Switching Relays - has an infinite number of possible output voltages within the
relays rated range. Analog switching relays have a built in synchronizing circuit that
controls the amount of output voltage as a function of the input voltage. This allows a
Ramp-Up function of time to be on the load. Analog Switching relays turn OFF when the
control voltage is removed and current in the load is near zero.
A relays useful life depends upon its contacts. Once contacts burn out, the relays contacts or the
entire relay has to be replaced. Mechanical Life is the number of operations (openings and
closings) a contact can perform without electrical current. A relays mechanical life is relatively
long, offering up to 1,000,000 operations. A relays Electrical life is the number of operations
(openings and closings) the contacts can perform with electrical current at a given current rating.
A relays Contact electrical life ratings range from 100,000 to
Input devices that can be used to detect or “sense” a variety of physical variables and signals and
are therefore called Sensors. But there are also a variety of electrical and electronic devices
which are classed as Output devices used to control or operate some external physical process.
These output devices are commonly called Actuators.
For example, a relay is a binary actuator as it has two stable states, either energised and latched
or de-energised and unlatched, while a motor is a continuous actuator because it can rotate
through a full 360o motion. The most common types of actuators or output devices are Electrical
Relays, Lights, Motors and Loudspeakers.
Electrical Relays can also be divided into mechanical action relays called “Electromechanical
Relays” and those which use semiconductor transistors, thyristors, triacs, etc, as their switching
device called “Solid State Relays” or SSR’s.
• Ag (fine silver)
1. Electrical and thermal conductivity are the highest of all the metals.
1. Known as “Hard silver” contacts and have better wear resistance and less tendency
to arc and weld, but slightly higher contact resistance.
1. Very little tendency to arc and weld, good wear resistance and arc extinguishing
properties.
2. Expensive.
EE – 405 ELECTRICAL APPARATUS AND DEVICES
1ST Semester, S. Y. 2020 – 2021
Engr. Darwin M. Marasigan, REE, RME
• Platinum, Gold and Silver Alloys
As well as the standard descriptions of Normally Open, (NO) and Normally Closed, (NC) used
to describe how the relays contacts are connected, relay contact arrangements can also be classed
by their actions. Electrical relays can be made up of one or more individual switch contacts with
each “contact” being referred to as a “pole”. Each one of these contacts or poles can be
connected or “thrown” together by energizing the relays coil and this gives rise to the description
of the contact types as being:
with the action of the contacts being described as “Make” (M) or “Break” (B). Then a simple
relay with one set of contacts as shown above can have a contact description of:
Examples of just some of the more common diagrams used for electrical relay contact types to
identify relays in circuit or schematic diagrams is given below but there are many more possible
configurations.
Input/Output Interface Modules, (I/O Modules) are another type of solid state relay designed
specifically to interface computers, micro-controller or PIC’s to “real world” loads and switches.
he main disadvantages of solid state relays (SSR’s) compared to that of an equivalent wattage
electromechanical relay is their higher costs, the fact that only single pole single throw (SPST)
types are available, “OFF”-state leakage currents flow through the switching device, and a high
“ON”-state voltage drop and power dissipation resulting in additional heat sinking requirements.
Also they cannot switch very small load currents or high frequency signals such as audio or
video signals although special Solid State Switches are available for this type of application.
In this tutorial about Electrical Relays, we have looked at both the electromechanical relay and
the solid state relay which can be used as an output device (actuator) to control a physical
process. In the next tutorial we will continue our look at output devices called Actuators and
especially one that converts a small electrical signal into a corresponding physical movement
using electromagnetism. The output device is called a Solenoid.
Label where each of the following electrical quantities would be found in both the “Y” and
“Delta” three-phase configurations:
Phase voltage
Line voltage
Phase current
Line current
In which circuit (Y or Delta) are the phase and line currents equal? In which circuit (Y or Delta)
are the phase and line voltages equal? Explain both answers, in terms that anyone with a basic
knowledge of electricity could understand.
Where phase and line quantities are unequal, determine which is larger.
Question 2
Explain the difference between a balanced polyphase system and an unbalanced polyphase
system. What conditions typically cause a polyphase system to become unbalanced?
Question 3
In a balanced Y-connected power system, calculate the phase voltage (Ephase) if the line voltage
(Eline) is 480 volts.
Calculate all voltages, currents, and total power in this balanced Delta-Delta system:
Eline =
Iline =
Ephase(source) =
Iphase(source) =
Ephase(load) =
Iphase(load) =
Ptotal =
Question 5
Calculate all voltages, currents, and total power in this balanced Y-Y system:
Eline =
Iline =
Ephase(source) =
Iphase(source) =
Ephase(load) =
Iphase(load) =
Ptotal =
Calculate all voltages, currents, and total power in this balanced Delta-Y system:
Eline =
Iline =
Ephase(source) =
Iphase(source) =
Ephase(load) =
Iphase(load) =
Ptotal =
Question 7
Calculate all voltages, currents, and total power in this balanced Y-Delta system:
line =
Iline =
Ephase(source) =
Iphase(source) =
Ephase(load) =
Iphase(load) =
Ptotal =
What resistor values would we have to choose in a Delta configuration to behave exactly the
same as this Y-connected resistor network?
Question 9
What will happen in each of these systems to the phase voltages of the load, if one of the source
phases fails open?
Question 10
A common three-phase source connection scheme is the Delta high-leg or Four-wire Delta,
where each phase coil outputs 240 volts:
Question 11
Identify the primary-secondary connection configuration of these three power transformers (i.e.
Y-Y, Y-Delta, Delta-Y, etc.):
Question 12
Note: fuses have been omitted from this illustration, for simplicity.
Question 14
One of the conductors connecting the secondary of a three-phase power distribution transformer
to a large office building fails open. Upon inspection, the source of the failure is obvious: the
wire overheated at a point of contact with a terminal block, until it physically separated from the
terminal.
What is strange, though, is that the overheated wire is the neutral conductor, not any one of the
“line” conductors. Based on this observation, what do you think caused the failure?
After repairing the wire, what would you do to verify the cause of the failure?
Overcurrent Protection
Question 1
What hazards might be posed by a circuit with excessive current going through its conductors
(excessive as defined by the conductors’ ampacity)? In other words, what would be bad about a
wire carrying too much current?
Also determine which type of component fault, an open or a short, would most likely be the
cause of excessive current in a circuit.
Question 2
Question 3
Show the proper placement of the fuse in this circuit, where an electric motor will be powered by
utility (120 volt AC) power:
Question 5
Are fuses and circuit breakers located at a power distribution panel rated to protect the wiring
from overcurrent, or to protect the load devices from overcurrent? Explain your answer.
Question 6
In an effort to obtain greater overcurrent ratings than a single fuse can provide, an engineer
decides to wire two 100 amp fuses in parallel, for a combined rating of 200 amps:
However, after a few years of operation, the system begins blowing fuses even when the
ammeter registers less than 200 amps of load current. Upon investigation, it is found that one of
the fuse holders had developed corrosion on a terminal lug where one of the wire connects:
Question 7
Two 150-amp circuit breakers are connected in parallel to obtain a total ampacity of 300 amperes
for an electric motor service. The system works just fine for several years, but then both breakers
begin to spuriously trip:
An electrician measures motor current using a clamp-on ammeter, and discovers the motor’s
current is no more than 228 amperes at full mechanical load. Describe what might possibly be
wrong that is causing both circuit breakers to trip.
Question 8
Based on these measurements, the electrician decides that both fuses are still in good condition,
and that the problem lies elsewhere in the circuit. Do you agree with this assessment? Why or
why not?
Question 9
Magnetic circuit breakers trip by the action of an electromagnet coil, through which all the load
current passes. When the attractive force of the magnetic field is strong enough, a mechanism
triggers to snap the breaker contacts open, thus interrupting the circuit current.
What would the time-current curve for such a circuit breaker look like?
Question 11
Shown here is the time-current curve for a dual-element fuse. Thermal-magnetic circuit breakers
exhibit similar time-current curves:
In addition to possessing a primary current rating, fuses and circuit breakers also possess
an interruption current rating, usually far in excess of their primary ratings. For example, a
typical 15 amp circuit breaker for 120 volt residential use may have an interruption rating
of 10,000 amps (10 kA)! Under what conditions could such a circuit ever bear so much current,
and why is this rating different than the breaker’s primary current rating of 15 amps?
Question 13
Find one or two real fuses and bring them with you to class for discussion. Identify as much
information as you can about your fuses prior to discussion:
• Current rating
• Voltage rating
• Interruption rating