OWNER'S MANUAL 193111-030: Charge Control
OWNER'S MANUAL 193111-030: Charge Control
AC1000
CHARGE CONTROL
DO NOT DESTROY
INTRODUCTION ................................................................................................................................. 1
How To Use This Manual ................................................................................................. 1-1
Equipment Identification ................................................................................................... 1-1
Receipt Of Equipment....................................................................................................... 1-1
TROUBLESHOOTING ...................................................................................................................... 7
WARRANTY
INTRODUCTION
How To Use This Manual CAUTION refers to possible equipment
damage. Cautions will be shown in bold
type.
Only qualified personnel should install, use, or 3. Battery Terminals – Do not touch battery terminals
service this equipment. while equipment is operating.
INITIAL SET-UP
See Location Diagram of Selector Switches included in Full Scale Digital Ammeter Selection
this manual on page 6-1.
From the data plate on the charger, note the DC output
For proper operation, the AC1000 Control must be set per circuit – Max. Amps. Set S1-1 to the “on” position
to match the charger in which it is installed. and using the Equalize and Review Switches, set the
display for the proper value per the following chart.
Cell Size Selection
From the data plate on the charger, note the number of
cells. Place the corresponding DIP switch (S2) on the
AC1000 Control in the “closed” position.
S2-1 6 Cells
DC Output
S2-2 12 Cells per Cir- Full Scale
cuit Current
S2-3 18 Cells
0 – 76 100
S2-4 24 Cells
77 – 171 200
S2-5 36 Cells 172 – 320 400
STANDARD OPERATION
1. Insure that battery size matches charger (Number of
WARNING: Do not disconnect cells and ampere hour capacity are within
a battery from this charger nameplate information).
while the charge in progress 2. Connect AC power to charger.
LED is lit; otherwise, a battery
explosion may result. 3. Connect the battery to the charger.
BATTERIES PRODUCE
4. After a five second downcount, the charger will turn
EXPLOSIVE GASES. Keep on and the “Charge in Progress” LED will light. The
sparks, flame, and cigarettes digital display will indicate output current.
away. Ventilate when charging
in an enclosed area. Always 5. The “80% Charged” LED will light when the battery
shield eyes when working voltage reaches the gassing point (Standard = 2.37
volts/cell).
near batteries.
6. When the charge termination point is reached, the
charger will turn off. The “Charge Complete” LED
will light and the “Equalize” LED will be lit if this was
an equalize charge.
- Charge termination code Digital Display — A seven segment, four digit display
is standard on the AC1000 Control. The characters are
6. Automatic, Push-to-Start, or Fault Lock-out a minimum of .56 inches tall, making the information on
Operation the digital display legible at distances exceeding ten
feet. The left hand decimal of the digital display is used
7. Manual or Automatic Equalize Operation to indicate when programmable features are selected.
The decimal will flash at a 25% duty cycle rate when
8. Dual Back-up Timer Shutdowns any programmable feature has been changed from
factory settings. A blank display is utilized for AC
9. One Part Number Control is User/Factory power fail indication.
programmable for 6-12-18-24-36 Cells
and 100-200-400 Amp Digital Ammeter Status Display LEDs — The “Charge In Progress”
LED (Amber) is illuminated whenever the charger is
10. 8-99 Hour Programmable Refresh Charge flowing current to the battery. There are four status
LEDs provided to indicate the present operating status
11. Voltage Time Feature (pT/dV/dT Disable) of the charger and battery (see Figure 5-1). A lamp test
feature is provided. See Review of Charge Cycle
12. “Cell Forming” Feature feature.
Programmable Cool Down Time — A programmable Extra Run Time —– The charge time can be
cool down feature allows the battery to cool down for extended past the normal charge termination point
0 to 8 hours before the charger signals charge com- (pT/dV/dT or VT) from 0 to 60 minutes. If equalize has
plete. During the cool down period the alphanumeric been selected, any extra run time programmed will not
display reads “Cool” . This feature allows the battery to be added. This feature may be useful in some
cool down before being returned to use and can be abnormal charging situations such as cold storage.
used to minimize the battery maximum temperature
during operation.
Figure 6-1
Delayed Start — The time from battery connection to Forming Cycles — To select any number of forming
the start of a charge sequence is programmable from cycles from 0 to 30, close DIP switch S1-8 to the “on”
0 minutes to 23 hours and 45 minutes in fifteen minute position, and using the “Equalize” and “Stop” keys to
increments. The delay time is programmed by closing select the number of forming cycles desired. Closing
DIP switch S1-5 with no battery connected to the the DIP switch to the original “off” position will store the
charger. The control is shipped from the factory with setting in the control memory.
the delayed start time set to 0.
Cool Down Delay — The battery cool down delay time
Refresh Delay — The time from a normal charge is adjustable from 0 to 8 hours in 1 hour increments.
Termination to the start of a refresh charge is The parameter is adjusted by closing DIP switch S1-9
adjustable from 8 to 99 hours in 1 hour increments. with no battery connected to the charger. The factory
The refresh delay time is programmed by closing DIP setting is 0 hours.
switch S1-6 with no battery connected to the charger.
The control is shipped from the factory with the refresh Extra Run Time — 0 to 60 minutes of extra charger
delay time set to 72 hours. run time after normal charge complete can be selected
by closing DIP switch S1-10 to the “on” position, and
Start mode — “Push to Start” or “Fault Lockout” using the “Equalize” and “Stop” keys to select the
modes of operation can be selected by closing DIP desired number of minutes. Closing the DIP switch to
switch S1-7 to the “on” position, and using the the original “off” position will store the setting in the
“Equalize” and “Stop” keys to select either mode of control memory. The control is factory set to 0 minutes
operation. The current setting will be displayed as of extra runtime after charge complete.
listed below:
TROUBLESHOOTING
Troubleshooting Table
ACTION
SYMPTOM PROBABLE CAUSES
PARAGRAPH PAGE
Battery has Low (1) Reading Not Temperature Corrected 7.13 7-6
S.G.’s (2) Bad Battery 7.14 7-6
(3) Bad Equalize Schedule 7.15 7-6
ACTION
SYMPTOM PROBABLE CAUSES
PARAGRAPH PAGE
Battery Water (1) Charger Too Large For Battery 7.22 7-6
Usage Is Too (2) Bad Equalize Schedule 7.15 7-6
High (3) Control Set For Voltage/Time 7.19 7-6
Incorrect Charge (1) Battery A.H. Not Equal To Charger A.H. 7.22 7-6
Rate (2) Bad Control Board 7.07 7-5
ACTION
SYMPTOM PROBABLE CAUSES
PARAGRAPH PAGE
Meter Reading (1) Control Board Shunt DIP Switch Set Incorrectly 7.29 7-7
Wrong (Amps) (2) Bad Output Connector 7.12 7-6
(3) Bad Harness/Connections – Loose or Incorrect 7.06 7-5
(4) Internal Power Connection 7.28 7-7
(5) Bad Control Board 7.07 7-5
(6) Bad/Incorrect Shunt 7.30 7-7
ACTION
SYMPTOM PROBABLE CAUSES
PARAGRAPH PAGE
LEDs Flashing, (1) Someone Pressed Manual Stop Button 7.17 7-6
Display Reads (2) Bad Control Board 7.07 7-5
“OFF”
(Manual Stop)
Action
7.01 Refer to the INSTALLATION chapter in the charger manual.
7.02 Disconnect AC power and replace the bad AC fuse. Reapply AC power to the charger. If the fuse (s) blows instantly,
check the connections on the input side of the contactor to make sure there are no shorts between any of the input
wires . If that’s okay, then check or change the control transformer. If the fuse (s) blow after the contactor closes,
then check the input wiring from the contactor to the main transformer (s). Refer to the charger manual and
locate the diagram for your charger to confirm that the charger is wired correctly. Also check the wires going up to
the terminal block on the transformer, the wires will have numbers that correspond to the number on the terminal
block. If they are incorrect, change them and start over. If it still blows fuse (s), the transformer will have to be
replaced.
7.03 Disconnect AC power and reset the breaker. Disconnect the control and reapply AC power to the charger. Measure
to see if 24VAC is on the output side of the control transformer. If there is, the control has failed. If there isn’t 24VAC,
then replace the control transformer. It is still possible that the control has failed; so once the control transformer is
replaced, measure to see if the 24VAC drops once the control is connected.
7.04 Check and see if any input fuses are blown. Visually inspect the control transformer for discoloration on the casing
of the input side of the control transformer. Disconnect the control before applying AC power. Once AC power is
reapplied, measure the input voltage to the control transformer, it should be the AC supply voltage (208/240/480)
(240/480/575). If not, check the control transformer input wiring. If you did read the supply voltage, then measure the
output side and you should read 24VAC. If not, replace the control transformer.
7.05 Look at the casing of the control transformer on the input side. Reference the charger manual to determine the
input. There will be four pins and each one will be labeled as follows: COM (common), 208 (208VAC), 240 (240VAC),
and 480 (480VAC). Some chargers are equipped with higher input voltage control transformers labeled as follows:
COM (common), 240 (240VAC), 480 (480VAC), and 575 (575VAC). There should always be a wire on the common
terminal no matter what voltage is applied to the charger, and the second wire will go to the pin labeled as the voltage
that is applied to operate the charger. Measure the voltage on the output side of the control transformer, it should
read approximately 24VAC.
7.06 A bad harness/connection can cause many different problems. The best way to confirm a bad harness/connection
problem is to take measurements where the harness is connected to the charger and then follow the wire (s) up the
harness to the PC boards and measure there also. The measurement should match what was measured at the
charger connection. If it doesn’t, check the following: Check the connectors at the square plugs where the control
harness connects to the charger harness, the connectors could be pressed out of the plugs. Make sure the
connectors look okay inside the edge mount connector at the PC board (s). Make sure the harness connections are
tight where they connect to the charger. Make sure the wires are crimped to the terminals tightly and also check to
make sure that they are crimped to the bare wire and not to the insulation only.
7.07 To check the Control Board for proper operation, first check the DIP Switch settings of S2. Make sure the proper cell
size is set to match the charger. Also make sure the shunt size setting matches the shunt in the charger ( See
Programming Your AC1000 Control page 6-2). If the control still does not operate properly even though the above
settings are correct, the Control Board still may need to be replaced. However, this is unlikely and all other
possibilities should be taken before this step.
7.08 Temporarily shut down any equipment on the same voltage supply line and see if the control starts to respond
normally. If the control does, then check all grounds going to the equipment that is shut down. If the problems still
exist, then return power to all the other equipment and call your local Prestolite Power Representative.
7.09 Measure the AC supply voltage coming into the charger to confirm that it matches the charger input tap settings.
7.10 Use an Ohmmeter and measure directly across the DC Fuse. A good fuse will measure almost (0) Ohms and a bad
one will measure a very high resistance, in the megohm range or greater. If for some reason a DC fuse measures
somewhere in between, replace the DC fuse and send it in to your local Prestolite Power Representative.
7.11 Refer to the DIAGRAM chapter in the owners manual and locate where the output cables connect to the charger. The
black (Negative) output cable goes into the charger and connects to a bus bar on the end of the DC fuse which is
located on the left portion of the interior panel. The red (Positive) output cable goes into the charger and connects to
the flat heat sink plate at the rear of the charger. The output connector will have a (+) and (-) symbol on it.
The (+) terminal should have the red output cable connected to it, and the (-) should have the black
output cable connected to it.
7.12 Make sure the output connector does not have any cracks on its casing that could result in a short. Make sure the
output cable lugs are making a good connection with the battery connector. You will see traces of pitting on the lug
surface from arcing if there isn’t a good connection. This could be the result of a weak retainer clip in the connector
or lugs that were soldered on incorrectly. If the lugs had too much heat applied to tem when the cables were soldered
on, the solder will wick up the cable and make it very stiff. When they are inserted into the connector, the stiff cable
forces the retainer clip down and creates poor connection between the battery connector and the charger connector.
7.13 Specific Gravity readings vary with the temperature of the electrolyte. To temperature correct the readings to match
the nameplate ratings of the battery, use the following rule of thumb: +1 S.G. point per 3 degrees F. increase of the
electrolyte temperature from 77 degrees F.
7.14 Take “Specific Gravity” readings and measure “Cell Voltages”. If acid has been spilled or the battery has been
extremely heated, it is possible that a battery’s capacity could be greatly reduced, and the acid is not capable of
increasing to the battery nameplate rating.
7.15 The proper equalize schedule is one that is tailored to the specific battery and charger operation. The AC1000
auto equalize feature can be used to automate the equalize schedule (see the “AC1000 Control Features” chapter
of this manual).
7.16 A faulty lift interrupt on a lift truck can cause the battery to be over or under discharged. Check the interrupt voltage
of the interrupt following the procedures found in your truck and/or lift interrupt operators’ manual (s).
7.17 Repeated manual disconnecting of the battery from the charger before complete can cause long term battery damage
and lead to inefficient truck/battery operations. When it is necessary to stop the charge cycle before charge
complete, always terminate the charge cycle by pressing the STOP button before disconnecting the battery from the
charger.
7.18 If the application requires a larger AH battery than is presently in use, the only long term solution is to replace the
battery with one of the proper AH rating.
7.19 Set the control to PDV/DT termination (see the “Initial Set-Up” chapter of this manual).
7.20 If fully discharged batteries are desired for efficient operations, lift interrupts can be installed on the trucks to allow
the operators to recognize a fully discharged battery.
7.21 A cool down can be programmed into the AC1000 control to add a specified cool down time between charge
termination and the signaling of charge complete (see the “Programming Your AC1000 Control” chapter of this
manual). A delayed start can be programmed into the AC1000 control to add a specified delay time between battery
connection and the start on the charge (see the “Programming Your AC1000 Control” chapter of this manual).
7.22 Check the charger A.H. rating. If it does not match the battery nameplate A.H. rating ( it should be within 20% of the
battery nameplate rating), then the battery should be charged using a charger with the correct output rating to match
the battery rating within 20%.
7.23 Check and tighten all sheet metal fasteners (screws and bolts).
7.24 If the contactor is not functioning properly, then check the voltage across the contactor coil. If the voltage is
24VAC +/- 10%, replace the contactor with a properly functioning part.
7.26 Check transformer for visible damage. Coat the transformer coil with a Prestolite approved (contact Prestolite
Service) air dry varnish. If that fails to reduce the noise level, drive a shim of the proper material (contact
Prestolite Service) between coil and core.
7.27 Check for and tighten any loose fasteners on the rack. Remove any lightweight loose objects that are on the rack
near the charger.
7.28 Check charger internal connection points that visually appear to be poorly connected or heat damaged. Any
connections that appear loose or overheated must be re-lugged. Recheck any repaired connections by performing
a continuity test.
7.29 Check the shunt size DIP switch setting (see the “Initial Set-Up” chapter in this manual) and ensure that it matches
the shunt in the charger.
7.30 Replace damaged and/or incorrect shunt with one of correct size.
7.31 Reconnect transformer primary wiring to match the schematic in the charger manual.
7.32 Reconnect transformer secondary wiring to match the schematic in the charger manual.
7.33 Check the diode as described below. If it tests faulty, replace with a diode of the proper type.
Connect a VOM set on the 1k Ohms scale; positive to diode anode, negative to diode cathode . The VOM should
read a low impedance (near short circuit). Reverse the meter leads; in this direction, the meter should read a high
impedance (> 1K Ohms). (A DVM may be used if it is set to the diode scale.) A high impedance will be indicated
by an over range indication (usually OL); a low impedance will be indicated by a low reading of about 1.00 .
7.34 AC fuses are most likely to have failed. Visually inspect the transformer. If a winding has failed, the winding will
appear to be burnt or look black. The varnish might be flaking off. Refer to the “Diagram” chapter in the charger
manual and locate the diagram for your charger. On the diagram, there will be a winding configuration for the
transformer . With power removed, disconnect the diodes from the transformer. Reapply AC to the charger.
Measure the transformer secondary voltage. If less than 25 VAC is present, replace the transformer.
7.35 Refer to the “Installation” chapter in the charger manual and reconnect the input primary jumpers to match the input
voltage. Be sure to connect the control transformer primary properly.
7.36 Check the charger A.H. rating. If the battery A.H. rating exceeds the charger nameplate rating by more than 20%,
then the battery should be charged using a charger with a higher A.H. capacity.
7.37 If the battery has been over discharged and the open cell voltage is less than 1.75 volts/cell, then the low battery
reject feature is enabled. The control will not start the charge until the battery voltage rises or the user overrides
the low battery reject mode. See the “AC1000 Control Features” chapter of this manual for details concerning the
low battery reject feature. An over discharged battery could be indicative of a faulty lift interrupt.
7.38 The battery connected to the charger may be the wrong cell size for the charger. Check the nameplate on the battery
and verify that it matches the cell size of the charger.
7.39 Hold in the “Manual Stop” and “Equalize” buttons simultaneously for two seconds until the display reads “EEEE”.
Release the two buttons. The control should now function properly.
7.40 Measure the DC voltage between connector pins J3-5 and J3-1 on the control PC board: positive of DMM to J1-5,
negative of DMM to J1-3. The measured voltage should be between 1.00 and 1.86 VDC. If the measured voltage is
out of range, remove the jumper from the connector and inspect it for loose or damaged connections.
PARTS LIST
Ametek/Prestolite Power (hereinafter called “Prestolite”) warrants that each new and unused Industrial Battery Charger manufactured
and supplied by it is of good workmanship and is free from any inherent mechanical defects, provided that (1) the product is installed and
operated in accordance with generally accepted industrial standards and in accordance with the printed instructions of Prestolite, (2) the
product is used under normal conditions for which designed, (3) the product is not subjected to misuse, negligence or accident, and (4)
the product receives proper care, protection and maintenance under supervision of competent personnel. This warranty is subject to the
following provisions:
1. PRODUCTS AND PARTS WARRANTED. Subject to the exceptions listed below each Industrial Battery Charger is warranted for a period of
one (1) year from the date of it’s shipment by Prestolite, provided the charger is used in accordance with Prestolite’s published performance
rating for the unit involved. The exceptions to this warranty are as follows:
a) Power transformers and silicon diodes on unit (s) shipped after January 1, 1997 are warranted for ten (10) years after Prestolite’s
shipment of the unit(s) of which they are a part, provided however that during the last nine (9) years of this 10 year period the
warranty covers parts replacement only – no labor or other services are provided by Prestolite, nor shall Prestolite be obligated to
reimburse the owner or any other person for any work performed.
b) Primary switch contacts, fuses, bulbs, and filters are not warranted unless found to be defective prior to use.
2. COMMENCEMENT OF WARRANTY TIME PERIODS. The warranty periods indicated in the Warranty Schedule shall commence on the date
of shipment by Prestolite.
3. PERSONS COVERED BY WARRANTY. This warranty is extended by Prestolite only to the purchaser of new equipment from Prestolite or one
of its authorized distributors. The products purchased under this agreement shall be used exclusively by the buyer and its employees and by no
other persons; and therefore there shall be no third party beneficiary to this warranty.
4. LIMITATION OF REMEDY. The existence of claimed defects in any product covered by this warranty is subject to Prestolite’s factory in-
spection and judgement. Prestolite’s liability is limited to repair of any defects found by Prestolite to exist or, at Prestolite’s option, the re-
placement of the defective product. F.O.B. factory after the defective product has been returned by the purchaser at its expense to Presto-
lite’s shipping place. Replacement and exchange parts will be warranted for the remainder of the original Industrial Battery Charger Warranty or
for a period of ninety (90) days, whichever is greater.
Prestolite and its authorized distributors or dealers shall not be liable for direct or indirect, special or consequential damages in excess of such
repair or replacement. In no event shall the purchaser be entitled to recover for contingent expenses resulting from, but not limited to, tele-
phone calls, telegrams, travel expenses, lodging, duties and taxes, labor, rental or replacement equipment, loss of business or profits or other
commercial losses.
5. USE OF DEFECTIVE PRODUCT. Continued use of an Industrial Battery Charger after discovery of a defect VOIDS ALL WARRANTIES.
6. ALTERED EQUIPMENT. Except as authorized in writing, the warranty specified does not cover any equipment that has been altered by any
party other than Prestolite.
EXCEPT AS STATED ABOVE, ALL OTHER WARRANTIES AND CONDITIONS, EITHER EXPRESSED OR IMPLIED, INCLUDING IMPLIED WAR-
RANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE EXCLUDED AND BUYER ASSUMES ALL RISK AND
LIABILITY RESULTING FROM USE OF THE GOODS. AMETEK/PRESTOLITE POWER NEITHER ASSUMES NOR AUTHORIZES ANY PER-
SONS TO ASSUME FOR AMETEK/PRESTOLITE POWER ANY OTHER LIABILITY IN CONNECTION WITH THE SALE OR USE OF THE GOODS
SOLD, AND THERE ARE NO ORAL AGREEMENTS OR WARRANTIES COLLATERAL TO OR AFFECTING THIS WRITTEN WARRANTY.
WARNING
At all times, safety must be considered an important factor in the installation, servicing, and operation of the product, and skilled, quali-
fied technical assistance should be utilized.
AMETEK/PRESTOLITE POWER
TROY, OHIO USA