Manual Paddle Flow Switch Fps
Manual Paddle Flow Switch Fps
for
Paddle Bellows Flow Monitor
Model: FPS-P...
FPS
1. Contents
1. Contents ........................................................................................................ 2
2. Note .............................................................................................................. 3
3. Instrument Inspection .................................................................................... 3
4. Regulation Use.............................................................................................. 4
5. Operating Principle........................................................................................ 5
6. Mechanical Connection ................................................................................. 5
7. Electrical Connection .................................................................................... 6
8. Setting the Limit Contact ............................................................................... 6
9. Maintenance ................................................................................................. 7
10. Technical Information .................................................................................... 7
11. Order Codes ................................................................................................. 8
12. Dimensions ................................................................................................... 9
13. EU Declaration of Conformance.................................................................. 10
2. Note
Please read these operating instructions before unpacking and putting the unit into
operation. Follow the instructions precisely as described herein.
The devices are only to be used, maintained and serviced by persons familiar with
these operating instructions and in accordance with local regulations applying to
Health & Safety and prevention of accidents.
When used in machines, the measuring unit should be used only when the
machines fulfil the EC-machine guidelines.
3. Instrument Inspection
Instruments are inspected before shipping and sent out in perfect condition.
Should damage to a device be visible, we recommend a thorough inspection of the
delivery packaging. In case of damage, please inform your parcel service /
forwarding agent immediately, since they are responsible for damages during
transit.
Scope of delivery:
The standard delivery includes:
Flow Monitor Model: FPS
Operating Instructions
4. Regulation Use
The model FPS is installed for monitoring flow of liquid medias in pipes with
diameter between 1" and 8".
The instrument is provided with an adjustable limit switch.
Only media which does not affect the materials of construction can be used in
the instrument. This device shall not be used in hazardous areas or for
flammable liquids.
Material-combinations
FPS-1115 P, FPS-1120 P FPS-2100 P / FPS-3100 P FPS-2200 P / FPS-3200 P
FPS-5100 P / FPS-6100 P FPS-5200 P / FPS-6200 P
Housing: Basic plate zinc plated / cover ABS
Paddle: st. steel
Lever Arm brass Ms 58 brass Ms 58 st. steel AISI 316 L
Connection brass Ms 58 brass Ms 58 st. steel AISI 316 L
T-Piece cast iron --- ---
5. Operating Principle
The KOBOLD flow monitor FPS operates according to the proven paddle bellows
principle. The flowing medium acts on the paddle thus actuating a microswitch.
Switching point can be freely adjusted and the device mated to different nominal
pipe sizes by means of the replaceable paddle in conjunction with the additional
adjustment features. The electrical device section is separated hermetically from
the process fluid by means of a bellows.
The Special Switching Range version of the flow monitor has been designed for
minimum switching values. See table in Section 11 Order Codes, for switching
values. The devices can be installed in any position.
6. Mechanical Connection
Before installation
• Please ensure whether the actual flow matches the switching range of the
instrument
• Please ensure whether the allowable maximum operating pressure and
operating temperature of the instruments will not be exceeded.
• Please ensure a straight run of 5 x pipe diameters at inlet and outlet is being
used.
Installation
• Using sealing tape screw the flow monitor into a T piece according to DIN 2950
with 1" outlet. The arrow on the housing must point in the direction of flow.
• The unit can be fitted in any position. If the unit is installed in a vertical pipe the
weight of the paddle and the lever must be compensated with the range screw.
This leads to changes in switching value (see Section 8 Setting the Limit Contact)
• A suitable filter must be connected upstream for soiled media. This applies
especially to fibrous soiling.
7. Electrical Connection
Make sure that the voltage and current values in your plant do not exceed the
respective voltage and current values specified for the flow monitor.
Make sure that the electrical supply lines are de-energized.
Remove the flow monitor housing by undoing the four screws.
Connect the flow monitor as shown in the wiring diagram.
Red-white opens if the flow rate drops to the set value. Red-blue close
simultaneously and can be used as a signal contact
9. Maintenance
In cases where the flow medium is uncontaminated, the FPS will
remain maintenance-free. Large dirt particles can block the paddle / lever arm.
Depending on the amount of dirt present in the medium, we recommend that the
Instrument is checked at regular intervals.
Electrical details
Dust-proof microswitch, single-pole changeover contact (SPDT)
Switching voltage: max. 24-250 VAC
Switching current: max. 8 A (inductive load)
max. 15 A (resistive load)
Case: ABS
Protection type: IP 65
12. Dimensions
1" NPT
Mounting Instructions
1" NPT
to which this declaration relates is in conformity with the standards noted below:
EN 60730-2:15:2010
Automatic electrical controls for household and similar use - Part 2-15: Particular
requirements for automatic electrical air flow, water flow and water level sensing
controls