transmission in either print or digital form is not permitted without ASHRAE’s prior written permission.
3 · Central Plant
Figure 3.14 Parallel chillers with individual pumping for each chiller.
Figure 3.15 Parallel chiller arrangement with headered constant-speed pumping.
Series Chillers Arrangement
To improve chiller performance, chillers may be arranged in-series such that two chillers form a single module. The CHW return will enter the upsteam chiller in the module to be cooled prior to entering the downstream chiller. The condenser water will start with the downstream chiller then continue to the upstream chiller for series counterflow configuration or alternatively each chiller will have its own condenser circuit, refer to Figures 3.17 to 3.18. The advantage of the series arrangement over the parallel arrangement is the increased overall chiller-module efficiency, especially where large CHW Ts are used. However, other plant components such as primary pumps and condenser pumps might have higher-power consumption since the combined chiller pressure requirements at the combined series chillers flows must be considered. Thus, total plant energy consumption, taking into consideration the chiller-loading percentages according to load profile and the energy wastages due to pumping energy, has to be evaluated for any efficiency gains. Due to higher pump head in series chiller arrangement, chillers should be a single pass type to mitigate the higher pump head.