Introduction To Substations - Part - 01
Introduction To Substations - Part - 01
SUBSTATION
(Part-I)
AMIT K. SINGH
Due to limitation of Generating size , Power is generated in Medium Voltage Range.
Generally terminal voltage of large generators is 11 kV in India. Generator with high terminal voltages up to 20 kV is being
made. Step up voltage depends upon following.
i). Length of transmission line for interconnection with the power system.
ii). Power to be transmitted.
For the purpose of standardization in India transmission lines may be classified for operating at 66 kV and above.
33 kV is sub transmission, 11 kV and below may be classified as distribution.
Line --> 200
KVA---> 1000000
VOLT.
VOLT.
X
POWER POWER
(MW) (MW)
X
CURRENT
CURRENT
SUBSTATION:
The assembly of apparatus which can be used to change the characteristics of electrical supply is called a substation.
FUNCTIONS OF SUBSTATION
- GENERATING SUBSTATION.
- GRID SUBSTATION.
- SWITCH SUBSTATION.
- DISTRIBUTION SUBSTATION.
- CONVERTER STATION.
GENERATING SUBSTATION:
GRID SUBSTATION:
Grid Station is an interconnection point between two transmission line circuits (Rings), those are serving/connecting two
geographic regions. Grid Station has transformer depending on the possibly different voltages, so that the voltage levels can
be adjusted as needed
SWITCH SUBSTATION:
A switching station is a
substation without transformers
and operating only at a single
voltage level.
An important function performed
by a substation is switching,
which is the connecting and
disconnecting of transmission
lines or other components to and
from the system.
The function of the switching
station is to isolate the faulty
portion of the system in the
shortest possible time. De-
energizing faulty equipment
protects it from further damage,
and isolating a fault helps keep
the rest of the electrical grid
operating with stability.
DISTRIBUTION SUBSTATION:
CONVERTER SUBSTATION:
Starting point for planning a substation is its single line diagram (SLD) which relates to circuit configuration, number of bus
bars and its type and other associated equipment. However from erection and installation point of view layout of any
substation is the most vital and key engineering because the single line diagram, bus switching scheme is to be translated
into a layout of appropriate bay widths, section and ground clearances so as to physically achieve the feeder switching
required for ease in erection and maintenance.
- Creepage.
- Earth clearance.
- Phase clearance.
- Ground clearance.
- Sectional Safety Working Clearance.
CREEPAGE DISTANCE & CLEARANCE
Creepage (Leakage distance) is the shortest path between two
conductive parts (or between a conductive part and the bounding
surface of the equipment) measured along the surface of
the insulation.
The leakage current flows from the live conductor to the earth
through such surface layers. The leakage properties (creepage
properties) of an insulators in substation are characterized by
the length of the leakage path. While designing the insulator sheds,
the leakage distance for insulators requirement should be satisfied. Clearance is the shortest distance between two
conductive parts (or between a conductive part
and the bounding surface of the equipment)
measured through air. Clearance distance helps
prevent dielectric breakdown between electrodes
caused by the ionization of air.
The dielectric breakdown level is further
influenced by relative humidity, temperature, and
degree of pollution in the environment.
Dry arcing distance and creepage distance:
• Pollution degree 1. No pollution or only dry, nonconductive pollution occurs. The pollution has no influence (example:
sealed or potted products).
• Pollution degree 2. Normally only nonconductive pollution occurs. Occasionally a temporary conductivity caused by
condensation must be expected (example: product used in typical office environment).
• Pollution degree 3. Conductive pollution occurs, or dry, nonconductive pollution occurs that becomes conductive due to
expected condensation (example: products used in heavy industrial environments that are typically exposed to pollution
such as dust).
• Pollution degree 4. Pollution generates persistent conductivity caused, for instance, by conductive dust or by rain or
snow
GROUND CLEARANCE :
The ground clearance is the distance between ground level and bottom of any insulator in an outdoor substation.
This clearance is kept as 2.5 meters for all voltage levels. When atmospheric conditions or ambient conditions
The minimum vertical distance from the bottom of the are different from standardized conditions than
lowest porcelain part of the bushing,porcelain enclosures appropriate correction factor should be applied by
or supporting insulators to the bottom of the equipment finding the withstand voltage in that condition that is
base, where it rests onthe foundation pad shall be 2.5 actual BIL testing in new non-standard
meters. ambient/atmospheric condition. Than based on
This means that support structure from plinth up to the dielectric strength of air required phase to phase and
bottom of insulator or top of the metallic earthed part of phase to earth clearance can be calculated.
the equipment below insulator should be at 2.5 meters.
ALLOWABLE ELECTRICAL FIELD :
“The regular influence of electric field may be harmful to Researches carried out in USSR had derived following limits
400 kV – 765 kV switchyard staff health. There is no well of electric field intensity tolerable by human beings within
defined guideline in India for the limits of electrostatic a period of time.
levels in substation”
Dead Tank - The switching unit is located within a metallic container which is kept a earth
potential. As the incoming/outgoing conductors are taken through insulated bushings, it is
possible to place current transformers on these (with a Live Tank arrangement this is not
possible and separate CTs are required).
DISCONNECTOR / ISOLATOR : HORIZONTAL CENTRE BREAK (HCB):
Disconnectors are used for galvanic isolation of networks
or sections of switchgear installations. As an
independent air-insulated device, they form a visible
isolating distance in their open position. They are
suitable for switching small currents (< 0.5 A) or also
larger currents if the voltage does not change
significantly between the contacts of a disconnector
pole during switching (commutation currents)
TYPE OF DISCONNECTORS :
Rated in:
- Power (usually MVA/KVA)
- Insulation (cooling type)
- Voltage rating
- Winding connections
- Voltage regulation (tap changers)
- Class (cooling design)