67% found this document useful (3 votes)
6K views52 pages

Rish Master3450 Manual

The document provides an operating manual for the RISH Master 3450, a 3-phase multi-function digital meter. It includes 20 measurement reading screens that can be cycled through, displaying parameters such as voltage, current, power, energy and minimum/maximum readings. The manual also describes programming and configuration options, RS485 communication, installation instructions and specifications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
67% found this document useful (3 votes)
6K views52 pages

Rish Master3450 Manual

The document provides an operating manual for the RISH Master 3450, a 3-phase multi-function digital meter. It includes 20 measurement reading screens that can be cycled through, displaying parameters such as voltage, current, power, energy and minimum/maximum readings. The manual also describes programming and configuration options, RS485 communication, installation instructions and specifications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 52

Operating Manual

RISH Master 3450

Product Photo

IC 15000764 Rev.E - 03/2013


RISH Master 3450

RISH Master 3450 - Three Phase (3W/4W)


Three Phase Multi-function Digital Meter
Installation & Operating Instructions
Section Contents
1. Introduction
2. Measurement Reading Screens
3. Programming
3.1 Password Protection
3.2 Menu selection
3.2.1 System type
3.2.2 Potential transformer Primary value
3.2.3 Current transformer Primary value
3.2.4 Current transformer Secondary value
3.2.5 Energy Display Modbus
3.2.6 Reset of Parameters
3.2.7 Modbus address
3.2.8 Auto scrolling / fixed screen
3.2.9 Noise current cut-off
3.2.10 Baud rate
3.2.11 Parity and stop bits
3.2.12 Energy rate
3.2.13 Energy Digit reset count
4. RS 485 ( ModBus ) output
4.1 Accessing 3X register for reading measured values
4.2 Accessing 4X register for reading and writing
4.3 User Assignable Modbus Register
1
5. Phaser Diagram
6. Installation
6.1 EMC Installation Requirements
6.2 Case Dimensions and Panel Cut-out
6.3 Wiring
6.4 Auxiliary Supply
6.5 Fusing
6.6 Earth / Ground Connections
7. Connection Diagrams
8. Specification
9. Connection for RS 485
10. Input terminal numbers marking

1. Introduction
The Rish Master 3450 is a DIN Rail mounted 96 x 96mm DIN Quadratic Digital metering
System for the measurement of important electrical parameters like AC Voltage, Current,
Frequency, Power, Energy(Active / Reactive / Apparent) . The instrument integrates
accurate measurement technology (All Voltages & Current measurements are True RMS
Upto 15th Harmonic) with 2 line LCD display With backlit.

Rish Master 3450 can be configured and programmed at


RISH Master 3450
SysV 239.6 V
site for the following : PT Primary, CT Primary, CT
SysA 5.002  Secondary (5A or1A) & 3 phase 3W or 3 Phase 4W System.
The front panel has two push buttons through which the User
B A Gnd
RS485 may scroll through the available measurement readings,
reset the energy (Import/Export) Min/Max (System
Voltage & System Current) & configure the product.
DOWN UP
2. Measurement Reading Screens
In normal operation the user is presented with one of the measurement reading screens
out of several screens. These screens may be scrolled through one at a time in
incremental order by pressing the “UP key” and in decremental order by pressing “DOWN
key”.
2
TABLE 1:

Measured Parameters Unit of measurement


System Voltage Volts
System Current Amps
Voltage VL1-N(4wire only) Volts
Voltage VL2-N(4wire only) Volts
Voltage VL3-N(4wire only) Volts
Voltage VL1-L2 Volts
Voltage VL2-L3 Volts
Voltage VL3-L1 Volts
Current L1 Amps
Current L2 Amps
Current L3 Amps
Neutral Current ( 4 wire only ) Amps
Frequency Hz
Phase Angle L1 (4wire only) Degree
Phase Angle L2 (4wire only) Degree
Phase Angle L3 (4wire only) Degree
Power Factor (system ) —
Power Factor L1 (4 wire only) —
Power Factor L2 (4 wire only) —
Power Factor L3 (4 wire only) —
Active Power (System) W
Active Power L1 (4 wire only) W
Active Power L2 (4 wire only) W
Active Power L3 (4 wire only) W
3
Measured Parameters Unit of measurement
Reactive Power (System) Var
Reactive Power L1 (4wire only) Var
Reactive Power L2 (4wire only) Var
Reactive Power L3 (4wire only) Var
Apparent Power (System) VA
Apparent Power L1 (4 wire only) VA
Apparent Power L2 (4 wire only) VA
Apparent Power L3 (4 wire only) VA
Active Import Energy (8 Digit resolution) kWh
Active Export Energy (8 Digit resolution) kWh
Reactive Import Energy (8 Digit resolution) kVArh
Reactive Export Energy (8 Digit resolution) kVArh
Apparent Energy (8 Digit resolution) kVAh
Max value System Voltage Volt
Max value System Current Amp
Min value System Voltage Volt
Min value System Current Amp

Screen 1 : System screen Screen 2 : System Power


(System Voltage, System Current )

RISH Master 3450 RISH Master 3450


SysV 239.6 V System Power
SysA 4.996 A SysP 6.612 kW
B A Gnd B A Gnd
RS485 RS485

4
Screen 3 : Line to Screen 4 : Line to neutral Screen 5 : Line to
neutral Voltage Voltage (VL2-N, VL3-N) lineVoltage (VL1-L2)
(VL1-N)(4 Wire only) (4 Wire only)

RISH Master 3450 RISH Master 3450 RISH Master 3450


Line-Neutral (V) L2N 240.3 V Line-Line (V)
L1N 238.9 V L3N 238.9 V L12 415.2 V
B A Gnd B A Gnd B A Gnd
RS485 RS485 RS485

Screen 6 : Line to Screen 7 : Line Screen 8: line


line Voltage Current (L1) Currents (L2, L3)
(VL2-L3, VL3-L1))

RISH Master 3450 RISH Master 3450 RISH Master 3450


L23 414.7 V Line Current IL2 4.998 A
L31 415.1 V IL1 4.998 A IL3 4.998 A
B A Gnd B A Gnd B A Gnd
RS485 RS485 RS485

Screen 9 : System Screen 10 : Neutral Screen 11 : System


Power factor, Current (4 Wire only) Active Power
Frequency

RISH Master 3450 RISH Master 3450 RISH Master 3450


SyPF 1.000 Neutral Current System Power
Freq 50.02 Hz In 0.015 A SysP 3.612 kW
B A Gnd B A Gnd B A Gnd
RS485 RS485 RS485

5
Screen 12 : System Powers Screen 13 : Active Screen 14 : Active
(Reactive & Apparent) Energy (Import) energy (export)

RISH Master 3450 RISH Master 3450 RISH Master 3450


SysQ 1.612 VAr ActiveEnergy Imp ActiveEnergy Exp
SysS 3.622 kVA 02.006012 kWh 836.96582 kWh
B A Gnd B A Gnd B A Gnd
RS485 RS485 RS485

Screen 15 : Reactive Screen 16 : Reactive Screen 17 :


Energy (Import) energy (export) Apparent energy

RISH Master 3450 RISH Master 3450 RISH Master 3450


ReactiveEner Imp ReactiveEner Exp Apparent Energy
04.012034 kVArh 08.132194 kVArh 840.37521 kVAh
B A Gnd B A Gnd B A Gnd
RS485 RS485 RS485

Screen 18 : Min Screen 19 : Max Screen 20 : Phase


values (System values (System 1 Active Power
Voltage, Current) Voltage, Current) (4 Wire only)

RISH Master 3450 RISH Master 3450 RISH Master 3450


MinV 160.3 V MaxV 271.3 V Phase1 Power
MinI 2.076 A MaxI 5.826 A P1 1.195 kW
B A Gnd B A Gnd B A Gnd
RS485 RS485 RS485

6
Screen 21 : Phase Screen 22 : Phase Screen 23 : Phase
1 Power (Reactive / 2 Active Power 2 Power (Reactive/
Apparent) (4 wire only) (4 wire only) Apparent )(4 wire only)

RISH Master 3450 RISH Master 3450 RISH Master 3450


Q1 1.383 VAr Phase2 Power Q2 1.485 VAr
S1 1.201 kVA P2 1.197 kW S2 1.205 kVA
B A Gnd B A Gnd B A Gnd
RS485 RS485 RS485

Screen 24: Phase Screen 25 : Phase Screen 26 : Phase


3 Power Active 3 Power (Reactive / angle (phase 1)
( for 4 Wire only ) Apparent) (4wire only) ( for 4 Wire only )

RISH Master 3450 RISH Master 3450 RISH Master 3450


Phase3 Power Q3 1.124 VAr Phase Angle
P3 2.001 kW S3 1.215 kVA Phi1 000.1
B A Gnd B A Gnd B A Gnd
RS485 RS485 RS485

Screen 27 : Phase Screen 28 : Power Screen 29 : Power


angle (phase 2, 3) factor (phase 1) factor (phase 2,3)
( for 4 Wire only ) ( for 4 Wire only ) ( for 4 Wire only )

RISH Master 3450 RISH Master 3450 RISH Master 3450


Phi2 000.2 Power Factor PF2 0.992
Phi3 000.4 PF1 0.996 PF3 0.989
B A Gnd B A Gnd B A Gnd
RS485 RS485 RS485

7
Rish Master 3450 SetUP Parameter Screen CODE (PassWord) : UP KEY
Change password Enter password
(Section 3.1.1) : DOWN
(Section 3.1) KEY

Sys Type PT PRI CT PRI CT SEC Energy OP RESET


(Sec 3.2.1) (Sec 3.2.2) (Sec 3.2.3) (Sec 3.2.4) Reset Parameter)
(Sec 3.2.5) (Sec 3.2.6)

Select Set PT Set CT Set CT Set Energy NONE :No parameter,


System Primary Primary Secondary output ALL : All parameters,
Type 5A/1A 1 : Wh Energy: Energy,
3 - 3P3Wire 2 : Kwh MAX : Max values,

8
4 - 3P4Wire Enr rst 3 : Mwh
Applicable MIN : Min values,
cnt Select any one option
(Sec 3.2.13) to all Energy using “DOWN” key.

Set energy Exit Set UP &


digit reset Return to
count (7to14) Normal Operation

Energy Parity/ Baud Rate 30mA Auto MODBUS ADD


rate Stop bits (Baud Rate) Cutoff (Auto Scrolling) Modbus Address
(Sec 3.2.12) (Sec 3.2.11) (Sec 3.2.10) (Sec 3.2.9) (Sec 3.2.8) (Sec 3.2.7)

Set energy Set Combination Set baud rate Noise Screen Auto Set Modbus
Update Rate of Parity & no. 2400/4800/ current scrolling Address
(1 to 60min) Of Stop bit 9600/19200 cutoff Enable Enable / Disable
/ Disable
3. Programming
The following sections comprise step by step procedures for configuring the Rish Master
3450 for individual user requirements.
To access the set-UP screens, press and hold the “DOWN” and “ UP” Key simultaneously
For 5 seconds. This will take the User into the Password Protection Entry Stage (Section
3.1).
3.1. Password Protection
Password protection can be enabled to prevent unauthorised access to set-UP screens,
by default password protection is not enabled. Password protection is enabled by
selecting a four digit number other than 0000, setting a password of 0000 disables the
password protection.

Enter Password,prompt for first digit. (*Denotes that the digit


RISH Master 3450 will be flashing.
CODE : *---
Press “ (DOWN) ” key to scroll the value of the first digit From
0 through 9, the value will wrap from 9 round to 0. Press “UP ”
B A Gnd
Rs485 key to advance to next digit.
In the special case, where password is “0000”, pressing the
“UP” key when prompted for first digit will advance to the
password “confirmed” screen.

Enter Password, first digit entered, prompt for second digit.


RISH Master 3450 (*Denotes that the digit will be flashing).
CODE : 1*--
Press “(DOWN) ” key to scroll the value of the first digit From 0
through 9, the value will wrap from 9 round to 0. Press “UP” key
B A Gnd
Rs485 to advance to next digit.

9
Enter Password, second digit entered, prompt for third digit.
RISH Master 3450 (*Denotes that the digit will be flashing.
CODE : 12*-
Press “ DOWN ” key to scroll the value of the first digit From 0
through 9, the value will wrap from 9 round to 0.
B A Gnd
Rs485 Press “UP ” key to advance to next digit.

Enter Password, third digit entered, prompt for fourth digit.


RISH Master 3450 (* Denotes that digit will be flashing).
CODE : 123*
Use the “DOWN” key to scroll the value of the fourth digit from
0 through to 9, the value will wrap from 9 round to 0.
B A Gnd
Rs485 Press the “UP” key to advance to verification of the password.

Enter Password, fourth digit entered, awaiting verification of


RISH Master 3450 the password.
CODE : 1234

B A Gnd
Rs485

Password confirmed.
Pressing “DOWN” key will advance to the “New/change Password”
RISH Master 3450 entry stage (section 3.1.1)
CODE : 1234
SET OK Pressing the “UP” key will advance to the Menu selection screen.
(See section 3.2).
B A Gnd
Rs485

10
Password Incorrect.
The unit has not accepted the Password entered.
RISH Master 3450 Pressing the “DOWN” key will return to the Enter Password
CODE : 1334
INVALID
stage.
Pressing the “UP” key exits the Password menu &
B A Gnd
Rs485 returns operation to the measurement reading mode.

3.1.1 Change Password


New / Change Password
(* indicates that this digit will be flashing).
RISH Master 3450 Pressing the “DOWN” key will scroll the value of the
CODE : *---
first digit from 0 through to 9, the value will wrap from
EdiT
9 round to 0. Pressing the “UP” key to advance the
B A Gnd
Rs485
operation to the next digit & sets the first digit, in this
case “2”.

New / Change Password, first digit entered, prompting for


RISH Master 3450 second digit.
CODE : 2*-- (* indicates that this digit will be flashing).
EdiT
Pressing the “DOWN” key will scroll the value of the second
B A Gnd digit from 0 through to 9, the value will wrap from 9 round to 0.
Rs485
Pressing the “UP” key to advance the operation to the
next digit and sets the second digit, in this case to “3”.

New / Change Password, second digit entered, prompting for


RISH Master 3450 third digit. (* indicates that this digit will be flashing).
CODE : 23*-
EdiT Pressing the “ DOWN” key will scroll the value of the third digit
B A Gnd
from 0 through to 9, the value will wrap from 9 round to 0.
Rs485
Pressing the “UP” key to advance the operation to the next digit
and sets the third digit, in this case to “4”
11
New / Change Password, third digit entered, prompting for
RISH Master 3450 fourth digit.
CODE : 234*
EdiT (* indicates that this digit will be flashing).
B A Gnd
Pressing the “DOWN” key will scroll the value of the fourth
Rs485
digit from 0 through to 9, the value will wrap from 9 round to 0.
Pressing the “UP” key to advance the operation to the “New
Password Confirmed” and sets the fourth digit, in this case to “5”

New Password confirmed.


Pressing the “DOWN” key will return to the “New/Change
RISH Master 3450 Password”.
CODE : 2345
SET OK Pressing the “UP” key will advances to the system type
Selection screen.(see section 3.2.1).
B A Gnd
Rs485

3.2 Menu selection


3.2.1 System type selection
This screen is used to set the system type.
RISH Master 3450 System type “3” for 3 phase 3 wire & “4” for 3 phase 4 wire
SysType : 4
system. Pressing “UP” key accepts the present
value and advances to the “Potential transformer Primary value
B A Gnd
Rs485
edit menu 3.2.2
Pressing “DOWN” key will enter system type Edit mode and
scroll between 3 and 4.
Pressing “UP” key advances to the system type confirmation
menu.

12
System Type Conformation
Pressing “UP” sets the displayed value and will advance to
RISH Master 3450
“Potential Transformer Primary Value
SysType : 4
SET OK Edit” menu. (See section 3.2.2)
Pressing “DOWN” key will return to the system type “Edit” menu.
B A Gnd
Rs485

3.2.2 Potential Transformer primary Value


The nominal full scale voltage which will be displayed as Line to Line voltage in
four wire or 3 wire system. The value represent the voltage in KVLL.
Maximum Potential transformer primary value can be set to 692.8 KVLL or restricted
to 666 MVA depends on previously set Current transformer (CT) primary value.
The minimum value allowed is 100VLL.
Pressing “UP” key accepts the present value and then
RISH Master 3450
PT PRI : 0.415 k
advances to Current transformer (CT) Primary value edit
VLL menu (section 3.2.3).
B A Gnd Pressing “DOWN” key enters into “Potential Transformer
RS485
Primary Value Edit” mode.
Initially the multiplier must be selected. Pressing the “DOWN”
key will move the decimal point position to the right unit it reaches # # # .# after which
it will return to # # # #.
Pressing “UP” key selects the present multiplier (decimal point position) and advances
to the “potential Transformer primary digit Edit” mode.
Potential Transformer Primary Digit edit
(* denotes that the digit will be flashing)
RISH Master 3450
 PT PRI : *.415 k
Pressing the “DOWN” key will scroll the value of the most significant
EdiT digit from 0 through to 9 unless the presently displayed
Potential Transformer Primary Value together with the
B A Gnd
RS485
Current Transformer Primary Value, previously set, would result
in maximum power of greater than 666MVA per phase, in which
case the digit range will be restricted.
13
Pressing “UP” key accepts the present value at the cursor position and advances the cursor
to the next less significant digit.
When the least significant digit has been set, pressing “DOWN” key will advance to the
“Potential Transformer Primary Value Confirmation” stage.
Potential transformer Primary value Confirmation
If scaling is to be corrected, pressing “DOWN” key will return to
RISH Master 3450 the “Potential Transformer Primary Value Edit” stage with the
PT PRI : *.415 k
SET OK
digits flashing indicating that the multiplier (decimal point position)
should be selected.
B A Gnd
RS485 Pressing “UP” key sets the displayed value and then it will advance
to Current transformer Primary Value selection menu (section3.2.3).

3.2.3 Current Transformer Primary Value


The nominal Full Scale Current that will be displayed as the Line currents. This screen
enables the user to display the Line currents inclusive of the transformer ratios, the values
displayed represent the Current in Amps.
Maximum Current transformer primary value can be set to 9999 A or restricted
to 666 MVAdepends on previously set Potential transformer (PT) Primary value.
Pressing “UP” key accepts the present value and advances to the Current transformer
Secondary value menu (section 3.2.4)
Pressing “DOWN” key will enter the “Current transformer
RISH Master 3450
CT PRI : 0005 A Transformer Primary Value Edit” mode. This will scroll the
value of the most significant digit from 0 through to 9, unless
the presently displayed Current Transformer Primary Value
B A Gnd
RS485 together with the Potential Transformer Primary Value results
in a maximum power of greater than 666MVA in which case
the digit range will be restricted, the value will wrap.
Example:
If primary value of PT is set as 692.8 KVLL (max value) then primary value of Current is
restricted to 1157A.
14
Pressing “UP” key will advance curser to next less significant digit. (*Denotes that decimal
point will be flashing).
The Maximum Power restriction of 666 MVA referr to 120% of nominal current and 120% of
Nominal voltage, i.e. 462.8MVA nominal power per phase.
When the least significant digit has been set, pressing “UP” key will advance to the
“Current Transformer Primary Value Confirmation” stage.
The minimum value allowed is 1, the value will be forced to 1 if the display contains zero

Current Transformer Primary value confirmation


RISH Master 3450
CT PRI : 2500 A If the set value is to be corrected, pressing “DOWN” key Will
SET OK re-enter the CT primary value edit stage.
B A Gnd Pressing “UP” key, sets the displayed value as CT primary and
RS485
advances to Current transformer Secondary menu (section 3.2.4).

3.2.4 Current Transformer Secondary Value


The screen is used to set the secondary value for Current
RISH Master 3450 Transformer.
CT SEC : 5 A Pressing “UP” key accepts the present value and advances to
Energy display on mdbus menu. (section 3.2.5).
B A Gnd
RS485
Pressing “DOWN” key enter into CT secondary value Edit and
scrolls the value between 1 (OR) 5.
After selecting the desired value, Pressing “UP” Enters into CT
secondary value confirmation screen.

RISH Master 3450


CT Secondary value confirmation
CT SEC : 5 A Pressing “DOWN” key reenters the CT secondary value edit menu.
SET OK
Pressing “UP” key sets the displayed value as CT secondary
B A Gnd
RS485 and advances to Energy display on modbus menu (section 3.2.5).

15
3.2.5 Energy Display on modbus
This screen enable user to set energy in terms of Wh / KWh / MWh on RS 485 Output
depending as per the requirement .Same applicable for all types of energy.
Pressing “ UP ” key accepts the presents value
RISH Master 3450 and advances to the “Reset parameter”menu (See section 3.2.6).
Energy OP : 0001*
EdiT Pressing the “ DOWN ” key will enter the “Energy Display
B A Gnd
On Modbus Edit” mode and scroll the value through the values
RS485
1,2 & 3 wrapping back to 1
1 : Energy In Wh
2 : Energy in KWh
3: Energy in MWh.
Pressing the “ UP” key advances to the “Energy Display
On Modbus Confirmation” menu.

Energy Display On Modbus Confirmation.


RISH Master 3450
Energy OP : 0001 This screen will only appear following an edit of the Energy
SET OK Display On Modbus.
B A Gnd
RS485
Pressing the “DOWN” key will enter the “Energy Display
On Modbus Edit” stage by blanking the bottom line of the
display.
Pressing “UP” key sets the displayed value and will advance to
the “Reset parameter” menu. (See section 3.2.6)

Note : Default value is set to ‘2’ i.e. Energy on Modbus will be in terms
of KWh/KVArh/KVAh resp.

16
3.2.6 RESET of parameters
This screen is used to Reset the different parameters .
RISH Master 3450
Pressing “UP” key resets the displayed parameters
RESET PARAMETER
 ALL and advances to modbus address menu (section 3.2.7).
B A Gnd
Pressing “DOWN” key scrolls the parameters to Reset From
RS485 None, Energy, Min, Max, All and back to None.
Select the parameters which is to be Reset with “DOWN” Key.
To reset the selected parameter press “UP” key.
After pressing “UP” key, it acknowledges the reset of parameter with “DONE” on display
as shown.
Further if another parameter is to be reset, press “DOWN” Key
RISH Master 3450
RESET PARAMETER to scroll the parameter again.
 DONE Pressing “UP” key after DONE message displayed, advances
B A Gnd the operation to modbus address menu. (Section 3.2.7)
RS485

3.2.7 Modbus Address


This screen allows the user to set device address of instrument for RS 485 communication.
The range of allowable address is 1 to 247. Pressing “DOWN” key enters into the
Modbus Address edit mode.
Enter Address, prompt for first digit.
RISH Master 3450
* denotes that the Digit will be flashing.
MODBUS ADD : 0*01
EdiT Pressing “DOWN” key scrolls the value of flashing digit from
0 to 2 and back to 0.
B A Gnd
RS485
Pressing “UP” key changes the curser position to next Less
significant digit.

17
Enter Address, first digit entered, prompt for second digit
RISH Master 3450
MODBUS ADD : 01*1 * denotes that the Digit will be flashing.
EdiT Pressing “DOWN” key scrolls the value of flashing digit from
B A Gnd
0 to 9 and back to 0.
RS485
Pressing “UP” key changes the curser position to next Less
significant digit.

Enter address, second digit entered, prompt for third digit.


RISH Master 3450
MODBUS ADD : 013* * denotes that the Digit will be flashing.
EdiT Pressing “DOWN” key scrolls the value of flashing digit from
B A Gnd
0 to 9 and back to 0.
RS485
Pressing “UP” key enters the modbus address Confirmation screen.

Modbus address Confirmation


RISH Master 3450
MODBUS ADD : 0132
Pressing “UP” key sets the modbus address & enters Into Auto
SET OK scrolling selection menu (section3.2.8).
Pressing “DOWN” key re-enters into Modbus address Setting
B A Gnd
RS485 menu.

3.2.8 Auto scrolling


This screen allows user to enable screen scrolling.
RISH Master 3450 Auto scrolling Edit.
AUTO SCROLL
Disable Pressing “DOWN” key scrolls between enable and disable.
Select enable for Auto scrolling of screen and select Disable
B A Gnd
RS485 for fixed screen.
Pressing “UP” key enters into Auto scrolling Confirmation
screen

18
Auto Scrolling Confirmation
RISH Master 3450
AUTO SCROLL Pressing “UP” key, sets the selected option and advances to
SET OK noise current cutoff menu (section 3.2.9)
B A Gnd
RS485 Pressing “DOWN” key re-enters the auto scroll menu.

3.2.9 Noise current Cut-off


This screen allows user to set low noise current cutoff at 30mA.
RISH Master 3450
30mA Cutoff Pressing “DOWN” key enters into edit mode and scrolls between
Disable Enable and disable.
B A Gnd Pressing “UP” key accepts the selected option and enters Into
RS485
30mA cutoff confirmation screen.

30mA cutoff confirmation


RISH Master 3450
30mA Cutoff Pressing “UP” key sets the selected option and advances to
SET OK Baud rate selection menu (section 3.2.10).
B A Gnd
RS485
Pressing “DOWN” key re-enters into 30mA cutoff
selection menu.

3.2.10 Baud Rate


This screen allows user to set the baud rate for Rs485
RISH Master 3450 communication.
Baud Rate : 4800
Pressing “UP” key sets the present value and advances to Parity
EdiT
and stop bits menu (Section 3.2.11).
B A Gnd
RS485
Pressing “DOWN” key enters into Baud rate Edit mode & scrolls
The values from 2400,4800,9600 to 19200 & Back to 2400.

Pressing ‘UP’ key will advance to baud rate Confirmation screen.


19
Baud rate Confirmation
Pressing “DOWN” keys re-enters into baud rate edit mode.
RISH Master 3450
Baud Rate : 9600 Pressing “UP” key sets the displayed value as baud rate and
SET OK advances the operation to parity and stop bit menu
B A Gnd (section 3.2.11).
RS485

3.2.11 Parity and Stop bits


This menu allows user to set parity and number of stop bits for
RISH Master 3450 Rs485 communication interface.
Parity: NONE
StopBit : 2 The parity and number of stop bits are to be set in same menu.
B A Gnd
Pressing “UP” key sets the displayed combination of Parity and
RS485
stop bits and advances the operation to Energy rate selection
menu (section 3.2.12).
Pressing “DOWN” key enters into edit mode and scrolls the
Combination from Parity :None Stop bit :1,Parity :None Stop bit :2
Parity :Even Stop bit:1, Parity : Odd Stop bit :1 and back to Parity :None Stop bit :1.
After selecting the desired combination, pressing “UP” Key enters into parity and number of
stop bit confirmation screen.

Parity and number of stop bit confirmation


Pressing “DOWN” key re-enters into the Parity and stop bit
RISH Master 3450 Edit menu.
Parity: Even
StopBit : 1 Pressing “UP” key, sets the displayed values and advances
the operation to Energy rate selection menu. (section 3.2.12).
B A Gnd
RS485

20
3.2.12 Energy rate
This menu allows user to set the energy reading Update rate
RISH Master 3450 from 1 to 60 minutes.
Energy Rate : 00*1
EdiT
Pressing “DOWN” key enters into energy rate edit menu and
st
B A Gnd
RS485
scrolls the value of 10s digit from 0 to 6. If 1 digit is greater
than 0 then 10s digit will wrap back to 0 from 5.
* denotes that the digit will be flashing.
Pressing “UP” key shifts the curser position from 10s digit to 1s digit. Value of 1st digit
scrolls from 0 to 9 and again Wraps back to 0.
After setting desired value of 1s digit pressing “UP” key Enters into energy rate
confirmation screen.
Energy rate confirmation
Pressing “DOWN” key re-enters into energy rate edit menu.
RISH Master 3450
Energy rate : 0015 Pressing “UP” key sets the displayed value as energy update
SET OK rate and then advance the operation to Energy digit reset
B A Gnd
count menu (section 3.2.13).
RS485
If energy rate is set to “00”, then it sets “01” min as default
value.

3.2.13 Energy Digit reset count


This screen enables user for setting maximum energy count after which energy will
rollback to zero depends upon setting of Wh,KWh, & MWh.
Pressing the “ UP” key sets the displayed value and then
RISH Master 3450 exits from setup menu and starts normal operation.
Enr rst cnt : 0007*
EdiT Pressing the “DOWN” key will enter the Energy digit reset
count edit mode. This will scroll the value of reset count from
B A Gnd
RS485 7 to 14 for Wh, from 7 to 12 for KWh & from 7 to 9 for MWh.
E.g. If energy display on modbus is set Wh & If you set Energy
digit count to 10 then energy will reset after “9,999,999,999” & then will Rollback to zero.
21
Pressing “UP ” key will advance to Energy digit reset count confirmation screen.
Energy digit reset count confirmation
Pressing the “ DOWN ” key will re-enter Energy digit reset
RISH Master 3450 count edit mode.
Enr rst cnt : 0007
SET OK Pressing the “ UP ” key sets the displayed value and will
B A Gnd
exits from setup menu and starts normal operation.
RS485

Note
1) Default value is set to “8” i.e if energy count crosses 8 digit it will rollback to zero.
2) If Energy displays on modbus is set to (2) & energy digit reset count is set to 12.Energy screen
on display will show “-------” i.e energy overflow .when energy crosses the 11 digit count......
3) If Energy displays on modbus is set to (3) & energy digit reset count is set to 9.Energy screen
on display will show “-------” i.e energy overflow .when energy crosses the 8 digit count......

4. RS 485 ( ModBus ) Output


RISH MASTER 3450 supports MODBUS (RS485) RTU protocol ( 2-wire ) .
Connection should be made using twisted pair shielded cable. All "A" and "B" connections
are daisy chained together. The screens should also be connected to “Gnd” terminal. To
avoid the possibility of loop currents an Earth connection should be made at one point on
the network.Loop (ring) topology does not require any
termination load. Line topology may or may not require terminating loads depending on the
type and length of cable used. The impedance of the termination load should match the
impedance of the cable and be at both ends of the line. The cable should be terminated at
each end with a 120 ohm (1/4 Watt min.) resistor.
RS 485 network supports maximum length of 1.2km. Including the Master, a maximum
of 32 instruments can be connected in RS485 network.The permissible address range for
RISH MASTER 3450 is between 1 and 247 for 32 instruments. Broadcast Mode
(address 0) is not allowed.

22
The maximum latency time of an RISH MASTER 3450 is 200ms i.e. this is the amount of
time that can pass before the first response character is output.
After sending any query through software ( of the Master) , it must allow 200ms of time to
elapse before assuming that the RISH MASTER 3450 is not going to respond. If slave
does not respond within 200 ms,
Master can ignore the previous query and can issue fresh query to the slave.
The each byte in RTU mode has following format
8-bit binary, hexadecimal 0-9, A-F
2 hexadecimal characters contained in each 8-bit field of
the message
Format of Data Bytes 4 bytes (32 bits) per parameter.
Floating point format ( to IEEE 754)
Most significant byte first (Alternative least significant byte first)
Error Checking Bytes 2 byte Cyclic Redundancy Check (CRC)
Byte format 1 start bit,
8 data bits, least significant bit sent first
1 bit for even/odd parity
1 stop bit if parity is used; 1 or 2 bits if no parity
Communication Baud Rate is user selectable from the front panel between 2400, 4800,
9600, 19200 bps.
Function code
03 Read Holding Registers Read content of read /write location ( 4X )
04 Read input Registers Read content of read only location ( 3X )
16 Presets Multiple Registers Set the content of read / write locations ( 4X )
Exception Cases : An exception code will be generated when Rish Master 3450 receives
ModBus query with valid parity & error check but which contains some other error ( e.g.
Attempt to set floating point variable to an invalid value) The response generated will be
“Function code” ORed with HEX (80H). The exception codes are listed below
23
01 Illegal function The function code is not supported by 3450
02 Illegal Data Address Attempt to access an invalid address or an attempt to read
or write part of a floating point value
03 Illegal Data Value Attempt to set a floating point variable to an invalid value

4.1 Accessing 3 X register for reading measured values


Two consecutive 16 bit registers represent one parameter. Refer table 4 for the addresses
of 3X registers (Parameters measured by the instruments).
Each parameter is held in the 3X registers. Modbus Code 04 is used to access all
parameters.
Example
To read parameter ,
Volts 3 : Start address= 04 (Hex) Number of registers = 02
Note : Number of registers = Number of parameters x 2
Each Query for reading the data must be restricted to 20 parameters or less. Exceeding
the 20 parameter limit will cause a ModBus exception code to be returned.
Query
01 (Hex) 04 (Hex) 00 (Hex) 04(Hex) 00 (Hex) 02(Hex) 30 (Hex) 0A (Hex)

Device Function Start Start Number of Number of CRC CRC


Address Code Address Address Registers Hi Registers Lo Low High
High Low

Start Address High : Most significant 8 bits of starting address of the parameter requested.
Start Address low :Least significant 8 bits of starting address of the parameter requested.
Number of register Hi : Most significant 8 bits of Number of registers requested.
Number of register Lo : Least significant 8 bits of Number of registers requested.
(Note : Two consecutive 16 bit register represent one parameter.)

24
Response: Volt3 (219.25V)
01 (Hex) 04 (Hex) 04 (Hex) 43(Hex) 5B (Hex) 41(Hex) 21 (Hex) 6F (Hex) 9B (Hex)

Device Function Byte Data Data Data Data CRC CRC


Address Code Count Register1 Register1 Register2 Register2 Low High
High Byte Low Byte High Byte Low Byte

Byte Count : Total number of data bytes received.


Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter requested.
Data register 1 Low Byte : Least significant 8 bits of Data register 1 of the parameter requested.
Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested.
Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested.
(Note : Two consecutive 16 bit register represent one parameter.)

Table 4 : 3 X register addresses (measured parameters)


Modbus Start
Address Parameter Parameter Address Hex
3P 4W 3P 3W
(Register) No. High Byte Low Byte
30001 1 Volts 1 00 0
30003 2 Volts 2 00 2
30005 3 Volts 3 00 4
30007 4 Current 1 00 6
30009 5 Current 2 00 8
30011 6 Current 3 00 A
30013 7 KW1 00 C X
30015 8 KW2 00 E X
30017 9 KW3 00 10 X
30019 10 KVA1 00 12 X
30021 11 KVA2 00 14 X
30023 12 KVA3 00 16 X
25
Modbus Start
Address Parameter Parameter Address Hex
3P 4W 3P 3W
(Register) No. High Byte Low Byte
30025 13 KVAR1 00 18 X
30027 14 KVAR2 00 1A X
30029 15 KVAR3 00 1C X
30031 16 PF1 00 1E X
30033 17 PF2 00 20 X
30035 18 PF3 00 22 X
30037 19 Phase Angle 1 00 24 X
30039 20 Phase Angle 2 00 26 X
30041 21 Phase Angle 3 00 28 X
30043 22 Volts Ave 00 2A
30045 23 Volts Sum 00 2C
30047 24 Current Ave 00 2E
30049 25 Current Sum 00 30
30051 26 Kwatts Ave 00 32
30053 27 Kwatts Sum 00 34
30055 28 KVA Ave 00 36
30057 29 KVA Sum 00 38
30059 30 KVAr Ave 00 3A
30061 31 KVAr Sum 00 3C
30063 32 PF Ave 00 3E
30065 33 PF Sum 00 40 X
30067 34 Phase Angle Ave 00 42
30069 35 Phase Angle Sum 00 44 X
30071 36 Freq 00 46
30073 37 Kwh Import 00 48
26
Modbus Start
Address Parameter Parameter Address Hex
3P 4W 3P 3W
(Register) No. High Byte Low Byte
30075 38 KWh Export 00 4A
30077 39 KVARh Import 00 4C
30079 40 KVARh Export 00 4E
30081 41 KVAh 00 50
30083 42 — — — — —
30085 43 — — — — —
30087 44 — — — — —
30089 45 — — — — —
30091 46 — — — — —
30093 47 — — — — —
30095 48 — — — — —
30097 49 — — — — —
30099 50 — — — — —
30101 51 — — — — —
30103 52 — — — — —
30105 53 — — — — —
30107 54 — — — — —
30133 67 Volts Ave Max 00 84
30135 68 Volts Ave Min 00 86
30141 71 Current Ave Max 00 8C
30143 72 Current Ave Min 00 8E
30145 73 Active Import Energy(KWh)* 00 90
30147 74 Active Export Energy (KWh)* 00 92
30149 75 Reactive Import Energy (KVARh)* 00 94
30151 76 Reactive Export Energy (KVARh)* 00 96
27
Modbus Start
Address Parameter Parameter Address Hex
3P 4W 3P 3W
(Register) No. High Byte Low Byte
30153 77 Apparent Energy (KVAh)* 00 98
30201 101 VL 1 - 2 ( Calculated ) 00 C8 X
30203 102 VL 2 - 3 ( Calculated ) 00 CA X
30205 103 VL 3 - 1 ( Calculated ) 00 CC X
30225 113 I neutral 00 E0 X
30227 114 — — — — —
30229 115 — — — — —
30231 116 — — — — —
Note :
Parameters 1,2,3 are L-N Voltage for 3P 4W & L-L Voltage for 3P 3W .
If product of CT_Primary and PT_Primary(VLN for 3P 4W & 3P 3W) is less than 1200
then limit for voltage and power are as shown in above table 4.
If product of CT_Primary and PT_Primary(VLN for 3P 4W & 3P 3W) is greater than or
equal to 1200 then all voltages are in KV and all powers are in Mega(M) & other
parameter remain same.
*Note1 :
The values are updated depending on update rate which is settable by user.
For example, if user set update rate 15 mins, then the values on these registers
(marked with *) will get updated on every 15 mins.
4.2 Accessing 4 X register for Reading & Writing
Each setting is held in the 4X registers .ModBus code 03 is used to read the current
setting and code 16 is used to write/change the setting.
Refer Table 5 for 4 X Register addresses.
Example : Reading System type
System type : Start address= 0A (Hex) Number of registers = 02
Note :Number of registers = Number of Parameters x 2
28
Query
Device Address 01 (Hex)
Function Code 03 (Hex)
Start Address High 00 (Hex)
Start Address Low 0A (Hex)
Number of Registers Hi 00 (Hex)
Number of Registers Lo 02 (Hex)
CRC Low E4 (Hex)
CRC High 09 (Hex)
Start Address High : Most significant 8 bits of starting address of the parameter requested.
Start Address low :Least significant 8 bits of starting address of the parameter requested.
Number of register Hi : Most significant 8 bits of Number of registers requested.
Number of register Lo : Least significant 8 bits of Number of registers requested.
(Note : Two consecutive 16 bit register represent one parameter.)

Response: System Type ( 3phase 4 wire = 3 )


Device Address 01 (Hex)
Function Code 03 (Hex)
Byte Count 04 (Hex)
Data Register1 High Byte 40 (Hex)
Data Register1Low Byte 40 (Hex)
Data Register2 High Byte 00 (Hex)
Data Register2 Low Byte 00(Hex)
CRC Low EE (Hex)
CRC High 27 (Hex)
29
Byte Count : Total number of data bytes received.
Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter requested.
Data register 1 Low Byte : Least significant 8 bits of Data register 1 of the parameter requested.
Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter requested.
Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter requested.
(Note : Two consecutive 16 bit register represent one parameter.)

Example : Writing System type


System type : Start address= 0A (Hex) Number of registers = 02
Query : ( Change System type to 3phase 3wire = 2 )
Device Address 01 (Hex)
Function Code 10 (Hex)
Starting Address Hi 00 (Hex)
Starting Address Lo 0A(Hex)
Number of Registers Hi 00 (Hex)
Number of Registers Lo 02(Hex)
Byte Count 04 (Hex)
Data Register-1High Byte 40 (Hex)
Data Register-1 Low Byte 00(Hex)
Data Register-2 High Byte 00(Hex)
Data Register-2 Low Byte 00(Hex)
CRC Low 66 (Hex)
CRC High 10 (Hex)
Byte Count : Total number of data bytes received.
Data register 1 High Byte : Most significant 8 bits of Data register 1 of the parameter
requested.

30
Data register 1 Low Byte : Least significant 8 bits of Data register 1 of the parameter
requested.
Data register 2 High Byte : Most significant 8 bits of Data register 2 of the parameter
requested.
Data register 2 Low Byte : Least significant 8 bits of Data register 2 of the parameter
requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Response
Device Address 01 (Hex)
Function Code 10 (Hex)
Start Address High 00 (Hex)
Start Address Low 0A(Hex)
Number of Registers Hi 00 (Hex)
Number of Registers Lo 02(Hex)
CRC Low 61 (Hex)
CRC High CA (Hex)
Start Address High : Most significant 8 bits of starting address of the parameter requested.
Start Address low :Least significant 8 bits of starting address of the parameter requested.
Number of register Hi : Most significant 8 bits of Number of registers requested.
Number of register Lo : Least significant 8 bits of Number of registers requested.
(Note : Two consecutive 16 bit register represent one parameter.)

Table 5 : 4 X register addresses


Address Parameter Parameter Read / Write Modbus Start Address Hex
(Register) No. High Byte Low Byte
40001 1 — — — —
40003 2 — — — —
31
Address Parameter Parameter Read / Write Modbus Start Address Hex
(Register) No. High Byte Low Byte
40005 3 Energy display on modbus R/Wp 00 04
40007 4 Sys Voltage R 00 06
40009 5 Sys Current R 00 08
40011 6 Sys Type R/Wp 00 0A
40013 7 — — — —
40015 8 Energy Reset W 00 0E
40017 9 — — — —
40019 10 RS 485 Set-UP Code R/Wp 00 12
40021 11 .
Node Address. R/Wp 00 14
40023 12 — — — —
40025 13 Min Reset Wp 00 18
40027 14 Max Reset Wp 00 1A
40029 15 — — — —
40031 16 — — — —
40033 17 PT Primary R/Wp 00 20
40035 18 CT Primary R/Wp 00 22
40037 19 System Power R 00 24
40039 20 Energy digit reset count R/Wp 00 26
40041 21 Register Order/Word Order R/Wp 00 28
40043 22 CT Secondary R/Wp 00 2A
40045 23 — — — —
40047 24 — — — —
40049 25 — — — —
40051 26 — — — —
40053 27 — — — —
32
Address Parameter Parameter Read / Write Modbus Start Address Hex
(Register) No. High Byte Low Byte
40055 28 — — — —
40057 29 — — — —
40059 30 — — — —
40061 31 — — — —
40063 32 — — — —
40065 33 — — — —
40067 34 — — — —
40069 35 — — — —
40071 36 Password R/W 00 46
40073 37 — — — —
40075 38 — — — —
40077 39 Auto scroll R/Wp 00 4C
40079 40 30mA Noise Current Elimination R/Wp 00 4E
40081 41 Energy Update Rate R/Wp 00 50

Explanation for 4 X register


Address Parameter Description
40001 - -
40003 - -
40005 Energy Display This address is used to set energy display on modbus in Wh,
on Modbus Kwh & MWh. Write one of the following value to this
address.
1 = Energy in Wh. 2 = Energy in KWh.
3 = Energy in MWh.
Applicable for all Energy type
33
Address Parameter Description
40007 System This address is read only and displays System Voltage
Voltage
40009 System This address is read only and displays System Current
Current
40011 System This address is used to set the System type.
Type Write one of the following value to this address.
2 = 3 Phase 3 Wire
3 = 3 Phase 4 Wire.
Writing any other value will return error .
40013 - -
40015 Reset Energy This address is used to reset the Energy Counter.
Counter Write zero value to this register to reset the energy counter.
Writing any other value will return an error.
40017 - -

40019 Rs485 Set-UP This address is used to set the baud rate, Parity,
Code Number of stop bits. Refer to Table 6 for details.
40021 Node This register address is used to set Device address
Address between 1 to 247 .
40023 - -

40025 Min - Reset This address is used to reset the Min parameters value.
Write Zero value to this register to reset the Min parameters.
Writing any other value will return an error.

40027 Max - Reset This address is used to reset the Max parameters value.
Write Zero value to this register to reset the Max
parameters.
Writing any other value will return an error.
34
Address Parameter Description
40029 - -

40031 - -

40033 PT Primary This address allows the user to set PT Primary value.
The maximum settable value is 692.8kV & also depends
on the per phase 666 MVA Restriction of power combined
with CT primary.
40035 CT Pimary This address allows the user to set CT Primary value.
The maximum settable value is 9999 & also depends on
the per phase 666 MVA Restriction of power combined with
PT primary.
40037 Sys Power System Power (Read Only) is the Nominal system power
based on the values of Nominal system volts and
Nominal system current.
40039 Energy digit This address is used to set the rollover count for energy. If Energy
Reset Count on Modbus is in Wh ,rollover count can be from 7 to 14.If it is in
KWh then rollover count can be from 7 to 12 & for MWh rollover
count can be from 7 to 9.
40041 Word Order Word Order controls the order in which RISH Master 3450
receives or sends floating - point numbers:- normal or
reversed register order. In normal mode, the two registers
that make UP a floating point numbers are sent most
significant bytes first. In reversed register mode, the two
registers that make UP a floating point numbers are sent
least significant bytes first.
To set the mode, write the value ‘2141.0’ into this register-
the instrument will detect the order used to send this value
and set that order for all ModBus transaction involving
floating point numbers.
35
Address Parameter Description
40043 CT secondary This address is used to read and write the CT secondary
value write one of the following values to this address.
1=1A CT secondary
5=5A CT secondary
writing any other value will return an error.
40045 - -
40071 Password This address is used to set & reset the password.
Valid Range of Password can be set is 0000 - 9999 .
1) If password lock is present & if this location is read it will
return zero.
2) If Password lock is absent & if this location is read it will
return One.
3) If password lock is present & to disable this lock
first send valid password to this location then write
“0000” to this location
4) If password lock is present & to modify 4X parameter
first send valid password to this location so that 4X
parameter will be accessible for modification.
5) If for in any of the above case invalid password is send
then meter will return exceptional error 2.
40077 Auto scroll This address is used to activate or de-activatethe auto
scrolling write
0-Deactivate
1-Activate
Writing any other value will return an error.
40079 30mA Noise This address is used to activate or de-activatethe 30 mA
current noise current elimination write
Elimination 0-Deactivate
30 (Decimal)-Activate
Writing any other value will return an error.
36
Address Parameter Description
40080 Energy This address is used to sate the time in minutes for updation of
Update energy parameter. This enable the user to update energy parameter
Rate according to set time. The time can be adjusted from 1 minute to
60 minutes. Writing any other value will return an error.

Table 6 : RS 485 Set-up Code


Baud Rate Parity Stop Bit Decimal value
19200 NONE 01 12
19200 NONE 02 13
19200 EVEN 01 14
19200 ODD 01 15
9600 NONE 01 08
9600 NONE 02 09
9600 EVEN 01 10
9600 ODD 01 11
4800 NONE 01 04
4800 NONE 02 05
4800 EVEN 01 06
4800 ODD 01 07
2400 NONE 01 00
2400 NONE 02 01
2400 EVEN 01 02
2400 ODD 01 03
NOTE
Codes not listed in the table above may give rise to unpredictable results including loss of
communication. Excise caution when attempting to change mode via direct Modbus writes.
4.3 User Assignable Modbus Registers
The Rish master 3450 contains the 20 user assignable registers in the address range
of 0x200 (30513) to 0x226 (30551) (see Table 7).
Any of the parameter addresses ( 3X register addresses Table 4)) accessible in the
instrument can be mapped to these 20 user assignable registers.

37
Parameters (3X registers addresses ) that resides in different locations may be accessed
by the single request by re-mapping them to adjacent address in the user assignable
registers area.
The actual address of the parameters ( 3X registers addresses) which are to be assessed
via address 0x200 to 0x226 are specified in 4x Register 0x200 to 0x213 (see Table 8).
Table 7 : User Assignable 3X Data Registers
Address Parameter Modbus Start Address (Hex)
Assignable Register
(Register) Number High Byte Low Byte
30513 257 Assignable Reg 1 02 00
30515 258 Assignable Reg 2 02 02
30517 259 Assignable Reg 3 02 04
30519 260 Assignable Reg 4 02 06
30521 261 Assignable Reg 5 02 08
30523 262 Assignable Reg 6 02 0A
30525 263 Assignable Reg 7 02 0C
30527 264 Assignable Reg 8 02 0E
30529 265 Assignable Reg 9 02 10
30531 266 Assignable Reg 10 02 12
30533 267 Assignable Reg 11 02 14
30535 268 Assignable Reg 12 02 16
30537 269 Assignable Reg 13 02 18
30539 270 Assignable Reg 14 02 1A
30541 271 Assignable Reg 15 02 1C
30543 272 Assignable Reg 16 02 1E
30545 273 Assignable Reg 17 02 20
30547 274 Assignable Reg 18 02 22
30549 275 Assignable Reg 19 02 24
30551 276 Assignable Reg 20 02 26
38
Table 8 : User Assignable mapping register ( 4X registers)
Address Parameter Modbus Start Address (Hex)
Mapping Register
(Register) Number High Byte Low Byte
40513 257 Mapped Add for register #0x0200 02 00
40514 258 Mapped Add for register #0x0202 02 01
40515 259 Mapped Add for register #0x0204 02 02
40516 260 Mapped Add for register #0x0206 02 03
40517 261 Mapped Add for register #0x0208 02 04
40518 262 Mapped Add for register #0x020A 02 05
40519 263 Mapped Add for register #0x020C 02 06
40520 264 Mapped Add for register #0x020E 02 07
40521 265 Mapped Add for register #0x0210 02 08
40522 266 Mapped Add for register #0x0212 02 09
40523 267 Mapped Add for register #0x0214 02 0A
40524 268 Mapped Add for register #0x0216 02 0B
40527 269 Mapped Add for register #0x0218 02 0C
40528 270 Mapped Add for register #0x021A 02 0D
40529 271 Mapped Add for register #0x021C 02 0E
40530 272 Mapped Add for register #0x021E 02 0F
40531 273 Mapped Add for register #0x0220 02 10
40532 274 Mapped Add for register #0x0222 02 11
40533 275 Mapped Add for register #0x0224 02 12
40534 276 Mapped Add for register #0x0226 02 13
Example
Assigning parameter to user assignable registers
To access the voltage2 (3X address 0x0002) and Power Factor1 (3X address 0x001E)
through user assignable register assign these addresses to 4x register (Table 10 ) 0x0200
and 0x0201 respectively .
39
Assigning Query
Device Address 01 (Hex)
Function Code 10 (Hex)
Starting Address Hi 02 (Hex)
Starting Address Lo 00 (Hex)
Number of Registers Hi 00 (Hex)*
Number of Registers Lo 02(Hex)*
Byte Count 04 (Hex)

Data Register-1High Byte


Data Register-1 Low Byte
00 (Hex)
02 (Hex) } Voltage 2 *
(3X Address 0x0002)

Data Register-2 High Byte

Data Register-2 Low Byte


00 (Hex)

1E (Hex) } Power Factor 1 *


(3X Address 0x001E)

CRC Low CB (Hex)


CRC High 07 (Hex)

* Note :
Parameters should be assigned in Multiple of two i.e. 2,4,6,8.......20.
Response
Device Address 01 (Hex)
Function Code 10 (Hex)
Start Address High 02 (Hex)
Start Address Low 00 (Hex)

40
Response
Number of Registers Hi 00 (Hex)
Number of Registers Lo 02 (Hex)
CRC Low 40 (Hex)
CRC High 70 (Hex)

Reading Parameter data through User Assignable Registers


In assigning query Voltage2 and Power Factor1 parameters were assigned to 0x 200
and 0x201(Table10) which will point to user assignable 3xregisters 0x200 and 0x202
(table9). So to read Voltage2 and PowerFactor1 data reading query should be as below.
Query
Device Address 01 (Hex)
Function Code 04 (Hex)
Start Address High 02 (Hex)
Start Address Low 00 (Hex)
Number of Registers Hi 00 (Hex)
Number of Registers Lo 04 (Hex) **
CRC Low F0 (Hex)
CRC High 71 (Hex)
Start Address High : Most significant 8 bits of starting address of User assignable register.
Start Address low :Least significant 8 bits of starting address of User assignable register.
Number of register Hi : Most significant 8 bits of Number of registers requested.
Number of register Lo : Least significant 8 bits of Number of registers requested.

41
**Note
Two consecutive 16 bit register represent one parameter.
Since two parameters are requested four registers are required

Response : (Volt2 = 219.30 / Power Factor1 = 1.0)


Device Address 01 (Hex)
Function Code 04 (Hex)
Byte count 08 (Hex)

}
Data Register-1High Byte 43 (Hex)
Data Register-1 Low Byte 5B (Hex)
Voltage 2 Data
Data Register-2 High Byte 4E (Hex)
Data Register-2 Low Byte 04 (Hex)

}
Data Register-3 High Byte 3F (Hex)
Data Register-3 Low Byte 80 (Hex)
Power Factor 1Data
Data Register-4 High Byte 00 (Hex)
Data Register-4 Low Byte 00 (Hex)
CRC Low 79 (Hex)
CRC High 3F (Hex)

42
User Assignable mapping User Assignable Data
Registers Registers
( 4X Registers Table10 ) ( 3X Registers Table 9 )
(Starting (Starting
Address) Address)
0x200 Voltage 2 (0x0002) 0x200 0x200 0x201
(16 bit) (16 bit)

0x201 Power Factor 1 (0x001E) 0x202 0x202 0x203


(16 bit) (16 bit)

0x202 Wh Import (0x0048) 0x204 0x204 0x205


(16 bit) (16 bit)

0x203 Frequency (0x0046) 0x206 0x206 0x207


(16 bit) (16 bit)

0x212 Current 1 (0x0006) 0x224 0x225


0x224 (16 bit) (16 bit)

0x213 VAh (0x0050) 0x226 0x227


0x226 (16 bit) (16 bit)

To get the data through User assignable Register use following steps
1) Assign starting addresses(Table3) of parameters of interest to a
“User assignable mapping registers” in a sequence in which they are to be accessed
(see section “Assigning parameter to user assignable registers”)
2) Once the parameters are mapped data can be acquired by using
“User assignable data register “ Starting address . i.e to access data of Voltage2,
Power factor1,Wh import, Frequency send query with starting address 0x200
with number of register 8 or individually parameters can be accessed
for example if current1 to be accessed use starting address 0x212.
(See section Reading Parameter data through User Assignable Registers)

43
0 0
5. Phaser Diagram Quadrant 1 : 0 to 90
Quadrant 2 : 900 to 1800
Quadrant 3 : 1800 to 2700
0 0
Quadrant 4 : 270 to 360
Capactive Inductive
0 degrees (+1.000)
330 degrees (+0.866) 30 degrees (+0.866)
60 degrees (+0.500)
300 degrees (+0.500)

44
270 degrees (0.000) 90 degrees (0.000)

120 degrees (-0.500)


240 degrees (-0.500)
210 degrees (-0.866) 150 degrees (-0.866)

180 degrees (-1.000)


Inductive Capactive
Sign of Sign of Sign of Inductive /
Connections Quadrant Active Reactive Power Capacitive
Power ( P ) Power ( Q ) Factor ( PF )
Import 1 +P +Q + L
Import 4 +P -Q + C
Export 2 -P +Q - C
Export 3 -P -Q - L
Inductive means Current lags Voltage
Capacitive means Current leads Voltage
When RISH Master 3450 displays Active power ( P )with “ + ” ( positive sign ) ,
the connection is “ Import ” .
When RISH Master 3450 displays Active power ( P )with “ - ” ( negative sign ) ,
the connection is “ Export ” .
6. Installation
Mounting of Rish master 3450 is to be done on standard DIN rail strip.

The Rish Master 3450 should RishMaster 3450


DIN RAIL
be mounted in a reasonably
stable ambient temperature
and where the operating
temperature is within the
0
range -5 to 60 C . Vibration
should be kept to a minimum
and the product should not be
mounted where it will be
subjected to excessive direct
sunlight.

Additional
Caution
1. In the interest of safety and functionality this product must be installed by a
qualified engineer, abiding by any local regulations.
45
Caution
2. Voltages dangerous to human life are present at some of the terminal
connections of this unit. Ensure that all supplies are de-energised before
attempting any connection or disconnection.
3. These products do not have internal fuses therefore external fuses must be
used to ensure safety under fault conditions.
6.1 EMC Installation Requirements
This product has been designed to meet the certification of the EU directives when
installed to a good code of practice for EMC in industrial environments, e.g.
1. Screened output and low signal input leads or have provision for fitting RF
suppression components, such as ferrite absorbers, line filters etc., in the event that
RF fields cause problems.
Note: It is good practice to install sensitive electronic instruments that are performing
critical functions, in EMC enclosures that protect against electrical interference which
could cause a disturbance in function.
2. Avoid routing leads alongside cables and products that are, or could be, a source of
interference.
3. To protect the product against permanent damage, surge transients must be limited
to 2kV pk. It is good EMC practice to suppress differential surges to 2kV at the
source. The unit has been designed to automatically recover in the event of a high
level of transients. In extreme circumstances it may be necessary to temporarily
disconnect the auxiliary supply for a period of greater than 5 seconds to restore
correct operation.
The Current inputs of these products are designed for connection in to systems via
Current Transformers only, where one side is grounded.
4. ESD precautions must be taken at all times when handling this product.
6.2 Case Dimensions 3.78” 4.6”
96mm 117mm

3.78”
FRONT DISPLAY
96mm AREA

46
6.3 Wiring 3-PHASE 4-WIRE UNBALANCED LOAD
DIGITAL METERING SYSTEM
2 5 8 11 1 3 4 6 7 9 13 14
Input connections are made directly to
screw-type terminals with indirect wire
pressure. Choice of cable should meet
L N
local regulations. Terminal for both Current AUX
2 SUPPLY
and Voltage inputs will accept upto 3mm x L1
P1 S1
L
2 diameter cables. L2
L3
P1 S1
P1 S1
O
A
D
Note : It is recommended to use wire
N

with lug for connection with meter. 8. Specifications


6.4 Auxiliary Supply System
Rish Master 3450 should ideally be 3 Phase 3 Wire / 4 Wire programmable
powered from a dedicated AC / DC supply. at site
6.5 Fusing Inputs
It is recommended that all voltage lines are Nominal Input 63.5VL-N (110VL-L)
fitted with 1 amp HRC fuses. Voltage
(Three wire & Four
6.6 Earth/Ground Connections wire)
For safety reasons, CT secondary Max continuous 120% of Rated
connections should be grounded in input voltage Value
accordance with local regulations. Max short duration 2 x Rated Value
input voltage (1S application
repeated 10 times
7. Connection Diagrams at 10s intervals)
3-PHASE 3-WIRE UNBALANCED LOAD Nominal input 0.2VA approx.
DIGITAL METERING SYSTEM
2 5 8 3 4 6 7 9 voltage burden per phase
System PT primary 100 VLL to 692.8
value KVLL
L N Nominal Input 1A / 5A AC rms
AUX
SUPPLY Current programmable
P1 S1
L1
L2
L
O
at site
P1 S1
L3
N
A
D Max continuous 120% of Rated
input current Value
47
Nominal input 0.4VA approx. Power Factor + 1 % of Unity
current burden per phase Angle + 1 % of range
Max short duration 20 x Rated Value (0 - 360)
current input (1s application Reference conditions for Accuracy
repeated 5 times at
Reference 0
23 C + 2 C
0
5 min. intervals)
temperature
System CT Primary Std. Values 1A to
Input frequency 50 or 60Hz + 2%
values 9999A (1 or 5 Amp
Input waveform Sinusoidal (distortion
secondaries)
factor 0.005)
Auxiliary Supply Input Voltage? Rated value
Auxiliary Supply 12V-48V DC + 10% Auxiliary supply Rated Value + 1 %
100V-250V AC/DC + 10% voltage
Auxiliary supply Auxiliary supply Rated Value + 1 %
<4VA approx.
burden frequency
Power Factor 0.8 Lag…1…0.8
Operating Measuring Ranges
Lead
Voltage 5 ... 120 % of Rated
Value Nominal range of use of influence
Current 5 ... 120 % of Rated quantities for measurands
Value Voltage 5 .. 120 % of Rated
Frequency 40 ... 70 Hz Value
Power Factor 0.6 Lag ... 1... 0.6 Current 5 .. 120 % of Rated
Lead Value
Accuracy Input frequency Rated Value + 10 %
0
Voltage + 0.5 % of range Temperature 0 to 50 C
Current + 0.5 % of range Auxiliary supply Rated Value + 10 %
Frequency + 0.15% of mid voltage
frequency Auxiliary supply Rated Value + 10 %
Active Power + 0.5 % of range frequency
0
Re- Active Power + 0.5 % of range Temperature 0.025% / C for
Apparent Power + 0.5 % of range Coefficient Voltage (50..120%
Active Energy + 1.0 % of range of Rated Value)
Apparant Energy + 1.0 % of range
Re - Active Energy + 2.0 % of range
48
(For Rated value 0
0.05% / C for Environmental
range of use Current ( 10..120% Operating 0
-5 to 60 C
0
0... 50 C ) of Rated Value ) temperature
Error change due to 2 * Error allowed for Storage temperature -20 to +65 0C
variation of an the reference Relative humidity 0 .. 90 % RH
influence quantity condition applied in Warm UP time 3 minute (minimum)
the test. Shock 15g in 3 planes
Display Vibration 10 .. 55 Hz, 0.15mm
LCD 2 Line Display with amplitude
backlit Enclosure
Update Approx. 1 seconds Style 96mm x 96mm DIN
Controls Quadratic
User Interface Two push buttons Material Polycarbonate
Housing, Self
Standards extinguish & non
dripping as per
Terms, definitions IEC60688
UL 94 V-0
and test methods
Terminals? Screw-type
EMC Immunity IEC 61326
terminals
10V/m min-Level 3
Depth < 80 mm
industrial low level
Weight Approx 460 gms
electromagnetic
radiation ModBus ( RS 485 ) Option
environment Protocol ModBus ( RS 485 )
IEC 61000-4-3. Baud Rate 19200 , 9600 , 4800
Safety IEC 61010-1 : 2010 or 2400
IP for water & dust IEC 60529 ( Programmable)
Parity Odd or Even, with 1
Isolation
stop bit, or None
Dielectric voltage 2.2 kV RMS 50 Hz with 1 or 2 stop bits
withstand test for 1 minute Format of databytes 4 bytes per
between circuits between all parameter Floating
and accessible electrical circuits point format as per
surfaces IEEE 754
49
Error checking 2 bytes CRC 10. Input Terminal Number marking
bytes
2 5 8 11 13 14
Byte format 1 start bit, 8 data
bits,
Least significant bit
sent first RISH Master 3450
RISHABH
9. Connection for RS 485 output Inst. Pvt. Ltd.
B A Gnd
RS 485 RS485

1 3 4 6 7 9

B A Gnd

The Information contained in these installation instructions is for use only by installers trained
to make electrical power installations and is intended to describe the correct method of
installation for this product. However, ‘Rishabh Instruments’ has no control over the field
conditions which influence product installation.
It is the user's responsibility to determine the suitability of the installation method in the user's
field conditions. ‘Rishabh Instruments’ only obligations are those in ‘Rishabh Instruments’
standard Conditions of Sale for this product and in no case will ‘Rishabh Instruments’ be
liable for any other incidental, indirect or consequential damages arising from the use or
misuse of the products.

RISHABH INSTRUMENTS PVT. LTD.


F-31, MIDC, Satpur, Nasik-422007, India
Tel. :+91 253 2202160,2202202
Fax. :+91 253 2351064
E-mail : [email protected]
www.rishabh.co.in
50

You might also like