We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF or read online on Scribd
You are on page 1/ 48
ABB
Asea Brown Boveri
DICON
Adjustment Report
MG /MSE
SETTING
RECORD
"“DICON"
Hull-No.:
Shipyard:
Shipname:
Shipping company:
Diesel Manufacturer/Type:
Diesel-no.:
Order-no.+
Approved by
Classification:
Date:
Name
Signature:
Data of Diesel:
Nominal spee
Ignition Speed:
DICON adjusted and ail func-
tions tested as registered
in this record
Overspeed: Date:
Nominal power: Name:
Pick-up: Company/Dept:
Tacho-generator: Signature:
QS-Freigabe ABB
DICON /E2 Adjust.-Report Print: E 03.93 Index: 1 1CONTENTS
- Preface
= Activation of Initialization Procedure
- Initialization/Setting Routines and
Figures (Records)
- Setting Pocedure for the Analog Speed Input
- Diagrams - Start phase - Timing
- Stop phase - Timing
Preface
This setting record must be completed for each
individual unit. All set parameters should be recorded
and entered in the input fields during initialization
routine. ‘The DICON operating manual should be used
together with this record. Especially follow the
Setting Procedure for the Analog Speed Input before
attempting an initialization. A copy of this record
should always be kept where the DICON device is used.
The alphanumeric block on the front panel contains keys
with up to four different symbols. Numeric values are
directly entered by pushing the keys, letters are
entered with a combination of the SHIFT- and IMMED-keys
as the following example shows:
call key combination
1 1 1
ABB A SHIFT + 1
B IMMED + 1
c SHIFT + IMMED + 1
Start of Initialization Routine
Make sure that you have calculated the calibration
values for R224, figures 9 and 46, before you go
through this routine.
- Push the red Reset-pushbutton on the back of the
unit.
- Hold the Reset-pushbutton depressed and operate the
PROG-Key on the front.
- Release the Reset-pushbutton and when the
initialization picture (Fig. 1) appears on the
display, release the PROG-Key. The initialization
routine is now activated.
DICON /E2 Adjust.-Report Print: E 03.93 Index: 1 Page: 2Initialization/Setting Routines and Figures
The following parameter figures,which require numeric
input values indicate their present preset values in
round brackets, symbolized by "X" in the figures of
this record.Range unit and type of input are indicated
in square brackets in the bottom line of the display.
Figure 1
PROGRAM -
First figure of
initialization INITIALIZATION:
procedure.
Acknowledgement of 1 EE EEE
this figure is done
by pushing ENTER- FOR DICON XXXX
key.
"XXxXX" stands for
serial number of
the device.
Figure 2 * PASSWORD FOR *
Enter the password INITIALIZATION:
which you find in
your DICON manual.
2
Figure 3
only if power ASV-INIT ONLY
management. ASV-
parameter is 3
entered:
YES = 1 [YES=1]
Otherwise with
ENTER to normal
programinitialization.
DICON /E2 Adjust.-Report Print: E 03.93 Index: 1 Page: 3Figure 4
OPERATI HOURS
Enter actual
operating hours of OF DI Le
Diesel.
4 ( KX)
Figure 5 NUM
Enter serial number OF D EL:
of Diesel.
5 ( xX)
1...8)
Figure 6 PRIO Y
Enter number of OF pI Li
priority of Diesel.
6 ( XX)
1. ..8)
DICON /E2 Adjust.-Report Print: E 03.93Figure 7
Enter maximum power
for analog input.
Figure 8
Select mode of
actual speed
measuring:
0 = both signals
1 = digital
2 = analog
Figure 9
Enter maximum speed
Consult Setting
Procedure for
Anolog Speed Input.
Only if 0 or 2 is
selected in fig.8!
POWER
OF DIESEL:
7 (1) (XXX)
[IN KW]
CHOOSE SPEED-
INPUT-MODE:
8 ( x)
[0,1,2]
RPM-MAXIMUM
FOR ANALOG.INPUT
9 (XXxXxX)
[CIN R/mingj
DICON /E2 Adjust.-Report Print: E 03.93 Index:
1 Page: 5Figure 10
PICK-UPS
Enter number of
pulses per revolu- FOR DIGIT.INPUT
tion multiplicated
with 10. (XXEXK
Only if 0 orl is
selected in fig. 8! [/ 10] [n/R
For different kind of pick
ups you can choise position
of dip-switch at terminal
board:
Magnet. = 1) (y [] JON = normal
Figure 11 MAK.SPEED-INPUT
Enter maximum speed DIFFERENCE:
difference of both
speed signals. ey (XxXxxX)
Only if 0 is
selected in fig.8! [IN R/min]
Date: 04.08.1993 Index: 1.2
DICON /E2 Adjust.-Report Print: E 03.93 Index: 1 Page: 6Figure 12
** STARTPHASE **
Enter maximum
number of start NO. OF ATTEMPTS
Figure 13 ** STARTPHASE **
Enter preglow time. PREGLOW-TIME:
13 ( XXX)
Figure 14 ** STARTPHASE **
Enter maximum time STARTTIME:
for a start
attempt. 14 ( XxX)
Figure 15 ** STARTPHASE ¥*
Enter breaktime BREAKTIME:
between startphases
15 ( xxx)
[IN SEC}
DICON /E2 Adjust.-Report Print: E 03.93 Index: 1 Page: 7Figure 16
Enter monitoring
time from exceeding
ignition speed to
xeaching nominal
speed.
Figure 17
Enter total
monitoring time
from exceeding
ignition speed to
main circuit
breaker "ON"
feedback signal.
Figure 18
Enter interval
between reaching
nominal speed to
"ON" signal of main
circuit breaker.
Figure 19
Enter closing time
of main circuit
breaker.
DICON /E2 Adjust.-Report Print: E 03.93
od RTPHASE **
RUN G-UP-TIME:
16 ( ¥xx)
[IN SEC]
** RTPHASE ¥**
STA TO-OPER.-
a7 TIME
cx [IN SEC]
** RTP EB +
REA TO EL.
18 TIME
(x [IN SEC]
”* RTPHASE +*
cLo BREAKER -
19 TIME
(x [IN SEC]
Index: 1 Page: 8Figure 20
Select whether
start procedure can
only be initiated
with completely
stopped Diesel or
not.
Figure 21
Select function of
“Preglow"-output:
0 = preglow funct.
1 = boostervalve
2 = fuelvalve-
function
Pigure 22
Selection of alarm
priority 3.
Yes=1
an additional
Diesel will be
started.
NO=0
The alarm is
indicated at the
display and the
output "Diesel
Fault" is send.
** STARTPHASE **
START AT 0-RPM?
20 ( x)
YES=1 NO=0
CHOOSE FUNCTION
FOR PREGLOW-
21 OUTPUT
( x) c0,1,2)
ALARM-PRIORITY 3
START-NE-DIESEL?
22 ( x)
YES=1 NO=0
Date: 06.03.1992 Index: 1.1
DICON /E2 Adjust.-Report Print: E 03.93Figure 26
START-NEXT-DIES.
Enter if a
"start-next-diesel- AFTER 1.START
signal” should be
generated, after 26 ATTEMPT
N 0
the first start
attempt has failed. x)
1
1
l/s
Figure 27
STATE OF
Enter blackout~
function. BLACKOUT
0 = Start signal
to all Diesels. 27 ( x)
1 = “Start-Next-
Diesel"-Signal [0/1)
Figure 28
DELAYTIME FOR
Enter delaytime
for blackout- BLACKOUT:
function.
28 (x x)
[MAX.60 SEC]
Figure 29
STOP-ORDER AFTER
0 = no stop after
return of BLACKOUT-~START:
mains.
1 = stop after 29 ( x)
return of
mains.
[YES=1/NO0=0}
DICON /E2 Adjust.-Report Print: E 03.93 Index: 1 Page: 10Figure 30
DELAYTIME FOR
Only in case of 1
in fig. 29. BLACKOUT-STOP:
Delay of stop after
return of mains. 30 ( XxX)
[in SEC]
Figure 31
FUNCTION FOR
Conditions for
switchover from STAND-BY
atomatic/manual:
0 = in case of 31 ouTPUT:
failure reset
to manual ( x) [1/0]
1 = reset to normal
only after
manual = input
order
Figure 32 STAND-BY OUTPUT
Changing of sStand- SELECT:
By Modus:
0 = automatic pre- 32 ( x)
selected, no
stand-by, if 0:CHANGE 1:DISPL
Diesel engine
is working.
1 = automatic =
stand-by
Figure 33 FUNCTION FOR
Switchover Alarm ALARM 6-INPUT:
No.6:
0 = alarmfunction 33 ( x)
l= input — high >
preglowtime = 0 [1/0]
sec.
DICON /E2 Adjust.-Report Print: E 03.93 Index: 1 PagFigure 40
* STOPPHASE lelal
Enter delaytime for
stop signal after a AL.2-STOP-DELAY-
2nd priority
alarm. 40 TIME
( xxXX) [IN SEC}
Figure 41 * STOPPHASE *
Enter cooling-down COOLING -DOWN-=-
time of Diesel
engine, running 41 TIME
without load.
( XxX) [IN SEC]
* STOPPHASE **
Figure 42
RUNNING-DOWN-
Enter monitoring
time from giving 42 TIME
stop command to
falling below ( xxx) [IN SEC]
ignition speed.
”* STOPPHASE “*
Figure 43
STOP-DEL - FIXED
Enter stop-delay
time of stop valve 43 TIME
after falling below
ignition speed. ( XxX) [IN SEC}
DICON /E2 Adjust.-Report Print: E 03.93 Index: 1 Page: 12Figure 44
* RPM-VALUES **
Enter ignition
speed value. IGNITION:
44 (XxXxXX)
[IN R/min]
Figure 45
** RPM-VALUES **
Enter nominal speed
value. NOMINAL:
45 (XXxXX)
Figure 46
** RPM-VALUES **
Enter overspeed
value. OVERSPEED:
46 (XxXxXxX)
DICON /E2 Adjust.-Report Print: E 03.93 Index: 1 Page: 13Figure 47
CHOOSE FUNCTION
Select function for
output "Function". FOR OUTPUT NO.A6
0 = loadcomputer
(optional) 47 t x)
1 = prelubrication
2 = speed signal [0.04]
3 = power signal
4 = emergency stop
output
Figure 48 TIME FOR
Enter prelubrica- PRELUBRICATION:
tion time.
Only if 1 is 48 ( XxX)
selected in figure
47 or 47 IT! [IN SEC]
Figure 49
Enter breaktime PRELUBRICATION
between prelubrica-
tion cycles. OFF:
Only if 1 is
selected in figure 49 ( XxX)
47 or 47 II!
[IN sec}
Date: 26.05.1993 Index: 1.4
DICON /E2 Adjust.-Report Print: E 03.93 Inde:
1 PagFigure 50
Enter speedlimit SPEED-VALUE
value for a status
change of the FOR OUTPUT A6:
output "Function".
Only if 2 is 50 (XXX)
selected in figure
471 [IN R/min]
Figure 51
Enter powerlimit
value fora status POWER-VALUE **
change of output
“ FUNCTION" . FOR OUTPUT A6:
Only if 3 is
selected in figure 51 (¥xXxXX)
471
[in kw]
The version of terminal board CMA114-1 contains a new
output called "function 2". This output offers the same
functions as the output "function" (figure 47). The
output “function 2" can be picked up on the terminals
no. 61 & 62.
Figure 47 II
CHOOSE FUNCTION
1: Cyclic
prelubrication FOR OUTPUT NO AS:
(fig. 48 & 49).
2: Output depending 47 ( x)
on speed (fig.
50). [i.e 4]
3: Output depending
on power (fig.
51).
4: Output for
additional 2nd
stopvalve used
in case of
Immediate stop.
See ereeteeeeeeHIMPORTANDH aa R EERE REE
If both outputs (A6 & A9) are equally configured, this
function can only be parameterized in figure 47.
Date: 26.05.1993 Index: 1.4
DICON /E2 Adjust.-Report Print: £03.93 Index: 1 Page: 15Figure 50
Enter speedlimit SPEED-VALUE
value for a status
change of __ the FOR OUTPUT A6:
output "Function".
Only if 2. is 50 (XXX)
selected in figure
47s CIN R/min]
Pigure 51
Enter powerlimit
value for a status POWER-VALUE +*
change of output
“ FUNCTION" FOR OUTPUT A6:
Only if 3 is
selected in figure 51 (XxXxXX)
474
[in kw]
The version of terminal board CMA114-1 contains a new
output called “function 2". This output offers the same
functions as the output "function" (figure 47). The
output "function 2" can be picked up on the terminals
no. 61 & 62.
Figure 47 IT
CHOOSE FUNCTION
1: Cyclic
prelubrication FOR OUTPUT NO AQ:
(fig. 48 & 49).
2: Output depending 47 ( x)
on speed (fig.
50). Tl... 4]
3: Output depending
on power (fig.
51).
4: Output for
additional 2nd
stopvalve used
in case of
Immediate stop.
JESS SNES DHSS ESO UOLTIIDOR TAC SSH nonin Sn
If both outputs (A6 & A9) are equally configured, this
function can only be parameterized in figure 47.
Date: 26.05.1993 Index: 1.4
DICON /E2 Adjust.-Report Print: E 03.93 Index: 1 Page: 15Figure 52
ouTPu ° OF
Select logic of
output "Stand-by". STAND :
0 = normal
1 = inverse 52 x)
PO EG=1
Figure 53
ouTPU ° OF
Select logic of
output "Operation". OPERA N
0 = normal
1 = inverse 53 x)
PO EG=l
Figure 54
ouTPU ° OF
Select logic of
output "Diesel- DIESE A :
Fault".
0 = normal 54 x)
1 = inverse
PO EG=1
Figure 55
ourTPU ° OF
Select logic of
output "Function". PUNCT :
0 = normal
1 = inverse 55 x)
Only if lor 2 is
selected in fig.47! PO EG=1
DICON /E2 Adjust.-Report Print: E 03.93 16Initialization of alarms
Iinitialization
alarm.
Figure 56
Skip alarm
initilization — by
entering 0.
of alarms is done seperately for each
Broken wire monitoring:
Alarm 1 - 6
Alarm 1
Alarm 2
Alarm 6
Alarm 5
Alarm 4
Alarm 3
INITIALIZATION
OF ALARMS?
56 E/E/E/E/E
NO = 0
on
oN
6
5
CO)
4
3
oO oO
OFF <-- --> ON
Date: 04.08.1993 Index: 1.1
DICON /E2 Adjust.-Report Print: F 03.93 Index: 1 Page: 17Figure Al
1. ALARM AL
Alphanumeric input
of alarmname. ALARMNAME:
ALARM 1
Figure A2
1. ALARM a2
Select logic of
actual alarm. ALARM-LOGIC:
0 = NO (normally
open contact) ( x)
1 = NC (normally
closed contact) POS=0 / NEG=1
Figure a3
1. ALARM a3
Enter priority
group of actual PRIORITY-GROUP:
alarm.
immed. stop ( x)
delayed stop
announcement of C1,2,3)]
alarm only
Figure a4 1. ALARM ad
Enter delaytime of ALARMDELAYTIME:
alarm.
( xx)
[IN SEC]
Figure A5 1. ALARM AS
Select 1, if alarm ALARM BLOCKED:
should be blocked
during running-up- ( x)
phase.
YES=1 / NOF=O
DICON /E2 Adjust.-Report Print: E 03.93 Index: 1 Page: 18Figure Al
2.ALARM Al
Alphanumeric input
of alarmname. ALARMNAME:
ALARM 2
Figure A2
Select logic of
actual alarm. ALARM-LOGIC:
0 = NO (normally
open contact) ( x)
1 = NC (normally
closed contact) POS=0 / NEG=1
Figure A3 2.ALARM a3
Enter priority PRIORITY-GROUP:
of ~ actual
immed. stop
delayed stop [1,2,
announcement of
alarm only
Figure A4 2.ALARM a4
Enter delaytime of ALARMDELAYTIME:?:
alarm.
Figure a5 2.ALARM aS
Determine, if alarm ALARM BLOCKED:
is blocked during
running-up-phase. ( x)
DICON /E2 Adjust.-Report Print: E 03.93 Index: 1 Page: 19Figure Al
3. ALARM AL
Alphanumeric input
of alarmname. ALARMNAME:
ALARM 3
Figure A2
3. ALARM a2
Select logic of
actual alarm. ALARM-LOGIC:
0 = NO (normally
open contact) ( x)
1 = NC (normally
closed contact) POS=0 / NEG=1
Figure a3 3. ALARM a3
Enter priority PRIORITY-GROUP:
group of actual
alarm. ( x)
1 = immed. stop
2 = delayed stop C1,2,3)
3 = announcement of
alarm only
Figure A4 3. ALARM a4
Enter delaytime of ALARMDELAYTIME:
alarm.
( xxx)
[IN SEC]
Figure A5 3.ALARM AS
Determine,if alarm ALARM BLOCKED:
is blocked during
running-up-phase. ( x)
YES=1 / NO=O
DICON /E2 Adjust.-Report Print: E 03.93 Index: 1 Page: 20Figure Al
Alphanumeric input
of alarmname. ALARMNAME
Figure A2
Select logic of
actual alarm. ALARM-LOGIC
0 = NO (normally
open contact) ( x)
1 = NC (normally
closed contact) POS=0 / NEG=1
Figure a3 4. ALARM a3
Enter priority PRIORITY-GROUP:
group of actual
alarn. ( x)
1 = immed. stop
2 = delayed stop C1,2,3)
3 = announcement of
alarm only
Figure a4 4. ALARM a4
ALARMDELAYTIME:
Enter delaytime of
alarm. ( Xxx)
[IN SEC]
ee
Figure A5 4.ALARM AS
Determine, if alarm ALARM BLOCKED:
is blocked during
running-up-phase. ( x)
YES=1 / NOF=O
DICON /E2 Adjust.-Report Print: E 03.93 Index: 1 Page: 21Figure Al
Alphanumeric input
of alarmname.
Figure A2
Select logic of
actual alarm.
0 = NO (normally
open contact)
1 = NC (normally
closed contact)
Figure A3
Enter priority
group of actual
alarm.
1 = immed. stop
delayed stop
3 = announcement of
alarm only
Figure A4
Enter delaytime of
alarm.
Figure A5
Determine, if alarm
is blocked during
running-up-phase.
DICON /E2 Adjust.-Report Print: E 03.93
5. ALARM AL
ALARMNAME:
ALARM 5
5. ALARM a2
ALARM-LOGIC:
x)
POS=0 / NEG=1
5. ALARM a3
PRIORITY-GROUP:
x)
C1,2,3]
5. ALARM aa
ALARMDELAYTIME:
XXX)
tr SEC]
5.ALARM AS
ALARM LOCKED
x)
YES=1 NO=0
PagtFigure Al
6. ALARM AL
Alphanumeric input
of alarmname. ALARMNAME:
ALARM 6
Figure a2
6.ALARM a2
Select logic of
actual alarm. ALARM-LOGIC:
0 = NO (normally
open contact) ( x)
1 = NC (normally
closed contact) POS=0 / NEG#=1
Figure A3 6. ALARM a3
Enter priority PRIORITY-GROUP?:
group of actual
alarm. ( x)
1 = immed. stop
2 = delayed stop [1,2,31
3 = announcement of
alarm only
Figure A4 6. ALARM Aa
Enter delaytime of ALARMDELAYTIME:
alarm.
( xx)
[IN SEC]
Figure AS 6. ALARM AS
Determine, if alarm ALARM BLOCKED:
is blocked during
running-up-phase. t x)
YES=1 / NO=O0
DICON /E2 Adjust.-Report Print: E 03.93 Index: 1 Page: 23Figure Al
7. ALARM AL
Alphanumeric input
of alarmname. ALARMNAME?
ALARM 7
Figure A2
7.ALARM a2
Select logic of
actual alarm. ALARM-LOGIC:
0 = NO (normally
open contact) ( x)
1 = NC (normally
closed contact) POS=0 / NEG=#=1
Figure A3 7.ALARM a3
Enter priority PRIORITY-GROUP:
group of actual
alarm ( x)
1 = immed. stop
2 = delayed stop C1,2,3]
3 = announcement of
alarm only
Figure A4 7.ALARM aa
Enter delaytime of ALARMDELAYTIME:?:
alarm.
( XXX)
[IN SEC]
Figure A5 7.ALARM AS
Determine, if alarm ALARM BLOCKED:
is blocked during
running-up-phase. rl x)
YES=1 / NO=O
DICON /E2 Adjust.-Report Print: E 03.93 Index: 1 PagFigure Al
8. ALARM Al
Alphanumeric input
of alarmname. ALARMNAME?:
>> short circuit <<
SHORTCIRCUIT
Figure a2 ey
8. ALARM a2
0 = NO (normally ALARM-LOGIC:
open contact)
1 = NC (normally ( x)
closed contact)
Figure A3 8. ALARM 23
1 = immed. stop PRIORITY-GROUP:
2 = delayed stop
3 = announcement of ( x)
alarm only
[1,2,3)}
Figure A4 8. ALARM a4
ALARMDELAYTIME:
( xXx)
| [IN SEC}
Figure AS 8. ALARM AS
ALARM BLOCKED:
( x)
YES=1 / NO=O
DICON /E2 Adjust.-Report Print: E 03.93 Index: 1 Page: 25Figure Al
Alphanumeric input
of alarmname. ALARMNAME
>> Broken wire
inputs <<
Figure A3
9. ALARM 33
1 = immed.stop PRIORITY-GROUP:
2 = delayed stop
3 = announcement of t x)
alarm only
C1,2,3)
Figure A4
9.ALAR a4
ALARMDELAYTIME:
( xx)
[IN SEC]
Figure A5
ALARM BLOCKED
DICON /E2 Adjust.-Report Print: E 03.93 Index: 1 Page: 26Figure Al
10.A AL
Alphanumeric input
of alarmname. LARM :
>> Broken wire
outputs <<
ROKE RE ovum.
Figure A3 LOLA a3
immed. stop RIO GR Pi
delayed stop
announcement of ( x)
alarm only
C1 13)
Figure a4 1O.A a4
LAR YTIME:
( Xx)
IN EC]
Figure AS
10.A aS
LARM cK :
DICON /E2 Adjust.-Report Print
E 03.93Figure Al
11. ALARM Al
Alphanumeric input
of alarmname. ALARMNAME:
>> overspeed <<
Figure A3 11. ALARM a3
Enter priority PRIORITY-GROUP:
group of actual
alarm. ( x)
1 = immed. stop
2 = delayed stop [1,2,3]
3 = announcement of
alarm only
Figure A4 11.ALARM a4
ALARMDELAYTIME:
( XxX)
[IN SEC]
DICON /E2 Adjust.-Report Print: £03.93 Index: 1 Page: 28Figure Al 12.ALARM Al
Alphanumeric input ALARMNAME
of alarmname.
>> tacho/pickup-
fault <<
TACHO/PICKUP-FA.
Figure A4 12.ALARM ad
Enter delaytime of ALARMDELAYTIME:
alarm.
( XXX)
[LIN SEC]
DICON /E2 Adjust.-Report Print: E 03.93 Index: 1 Page: 29Initialization of parameters for power management
If the DICON device is provided with power management
functions, the initialization procedure for these
functions will follow. The "Code for ASV-Function",
which is marked as the “Power Management License No."
on the back of the device, has to be entered.
If the option is not used, the initialization setting
routine is now completed.
Figure 57
CODE FOR
For device with
Power management ASV-FUNCTION:
functions enter the
correct ASV- 57
Code. For device
without these
functions finish
initilization by
acknowledging this
figure via ENTER.
DICON /E2 Adjust.-Report Print: E 03.93 Index: 1 Pag1.7 Calibration and Correction of Analog Speed Signal
- Determination of overspeed set-point for DICON
- Determination of max. speed range for DICON
- Determination of R224 for adapting the 1/G voltage to
DICON signal voltage.
Example:
Output Voltage T/G: 15 V DC @ 1000 min-1
Nominal Speed: 1500 min-1
Overspeed: 1,25 x Nominal Speed
= 1,25 x 1500 min-l = 1875 min-1
Value for figure 46: 1875
Max. speed range for DICON: 2000 min-1
Value for figure 9: 2000
Output voltage of T/G @ 2000 min i5V_x_ 2000 UPM = 30 v
1500 UPM
Determination of R224: 30V_- 5V x 4.7 KQ = 23,5 Kg
BV
Solder a suitable resistor combination to the solder points
on the terminal board marked R224.
Correction of DICON
Run up the Diesel engine to nominal speed and measure the
actual speed (e.g. via frequency).
Example: Actual speed: 1510 min-1
DICON indication: 1475 min
Correction: 1510 x 2000 = 2047
1475,
Call up figure 10 and enter 2047
For example, if DICON shows 1580 as
actual speed, the correction for figure
9 is
1510 x 2000 = 1956
1580
Now the analog speed indication is correctly calibrated.
Attention
If a T/G with AC output is installed, a suitable bridge-
connected rectifier with a 10uF smoothing capacitor must be
installed between the T/G output and terminals 20/21 of the
terminal board.
Date:.24.04.92 Index: 1.1
DICON /E2 Adjust.-Report Print: E 03.93 Index: 1 Page: 312. Fix input resistance for speed on DICON at 30V.
R224
30V = SV + 4.7 kQ = 23.5 k@
Sv
The Diesel engine is started and sped up to nominal speed.
Now the speed can be read on the DICON and on the Diesel
engine (for example in connection with the mains fre-
quency) .Now the speed of the Diesel engine is for example
1510 1/min. 1475 1/min are indicated on the DICON. Now the
speed is readjusted on the DICON.
1510 * 2000 = 2047
1475
Now turn back to initialization, and put the value of 2047
into figure 9.
If 1580 1/min is indicated on the DICON, proceed as above.
1510 * 2000 = 1911
1580
In figure 9 the value of 1911 is put in.
If an AC- or three-phase tacho-generator is used, a bridge-
connected rectifier in combination with a smoothing capaci-
tor of 10uF has to be connected to the terminals 20 and 21.
DICON /E2 Adjust.-Report Print: EB 03.93 Index: 1 Page:
32STARTOWASE THANG
Taaagrane der Sheps
MALL,
VL,
Sse A eae 58 cov, acon =
~ mn [20 bE3 00013 fF]_STOPPHASE-TING _
nkangrne eer Sonpiane
DESEL contaoL “DLOW JE
Siae ta fa bes o007 FI i I =
I rence Le} abso ae eno
5 0704 Ostnn Ce ha tr
1 thtg oe {Gacrematgn teary
ewan | A143 ew ion so ent
eau e @ srr aman or nigeone ma
a sete sone 2} arcana we nemingannie as
‘Somes Hetty [2] @ seamen
oso 21 @ sme
isatemte HH @ nomen
+ @
3] @
i
JANIS nce oes cute cx wow
feeereciseess | 1ermnAl Boao tnt ne ocscannow |_| 30 0€3 0001} [> £,Setting Record for Power-Management-System
Figure 57 CODE FOR
Enter _ licence-no. ASV-FUNCTION:
for ASV-Function.
57
Figure 58 * SERIAL PORT *
Address of DICON.In ADDRESS OF DICON
circle main no
DICON-devices with 58 ( xX)
identical addresses
are allowed. Tl. . .8)
Figure 59 * SERIAL PORT *
Rate of transfer BAUDRATE:
for serial communi-
cation. 59 ( x)
1 + 1200 baud
2: 2400 baud (1,2,3,4)
3: 4800 baud
4 : 9600 baud
(4 is commendable)
Figure 60
STATE OF DICON:
Master/Slave-
Selection. Only one MASTER/SLAVE
DICON device in
circle main can be 60 ( x)
selected as Master.
The ASV-display can [MAS:1 / SLA:0 ]
only be called via
Master device.
Date: 19.03.1992 Index: 1.1
DICON /E4 Adj.Report ASV Print: E 03.93 Index: 1 Page: 1Figure 61
NUMBER OF
Number of DICON
devices in net- DICONS
work.
61 ( XX)
Tl... 20)
Figure 62 STOP DIESEL
Selection of HIGHEST/LO
stoporder priority
If 1 is selected, 62 PRI
the Diesel engine
with the highest ( x) H
oz
o
®
3
0
e
"
e
priority is stop-
ped.
If 0 is selected,
the Diesel engine
with the lowest
priority is stop-
ped.
Figure 63 START DIESEL AT
Criterion for start SINGLE OR TOTAL
of new Diesel.
0: total loadlimit 63 LOADLIM.
1: single loadlimit
( x) {s
1/@
01
Figure 64 LIMIT OF LOAD-
Limit of loadrate, RATE F. START-N-
requiring start of
a new Diesel en- 64 DIESEL
gine.
( xX) [in &® ]
DICON /E4 Adj.Report ASV Print: E 03.93 Index: 1 Page: 2Figure 65
LIMIT OF LOAD-
Limit of loadrate,
at which a Diesel RATE F. STOP-NEXT
engine should be
stopped. Load minus 65 DIESEL
one Diesel.
( xx) [in @ ]
Figure 66
STARTDELAYTIME:
Delaytime for start
of a new Diesel.
66 ( XXX)
CIN SEC]
Figure 67
STOP-DELAYTIME
Delaytime for stop
of a Diesel.
67 ( xxx)
(IN SEC]
Figure 68
SECOND
Second-start-time
is set after start START-TIME:
or stop of a Diesel
engine. 68 ( XxX)
Only after this
time anew Diesel [IN SEC]
engine can be
started or stopped.
DICON /E4 Adj.Report ASV Print: E 03.93 Index: 1 Page: 3Figure 69
INDEPENDENT
If this loadlimit LIMIT OF
is exceeded by a
Diesel a new Diesel 69 OVERLOAD
is started.
( XKxK) [in #8]
Figure 70 TIME FOR
Delaytime for OVERLOAD:
independent load-
limit. 70
( XxX) [in sec]
Figure 71 VALUE FOR
Limit for low LOW FREQUENCY:
frequency alarm.
n (XxXxXX)
[in RPM]
Figure 72 DELAYTIME FOR
Delaytime for low LOW FREQUENCY:
frequency.
2 ( XxX)
[in sec]
DICON /E4 Adj.Report ASV Print: E 03.93 Index: 1 Page: 4Figure 73 to max. 80
Nominal load of all Diesel engines of circuit network
including those of Master. Depending on the number of.
DICONs (see fig. 61), the respective number of values
is interogated. With the help of actual load values and
nominal load values, the Master controlls the ASV-
system.
Figure 73
NOMINAL LOAD
Nominal load for
Diesel address 1. FOR DIESELADDR.1
3 (XXX)
fin kw]
Figure 74
NOMINAL LOAD
Nominal load for
Diesel address 2. FOR DIESELADDR. 2
14 (XXX)
fin kw]
Figure 75
NOMINAL LOAD
Nominal load for
Diesel address 3. FOR DIESELADDR. 3
75 (XxXxXxX)
Cin kw]
Figure 76
NOMINAL LOAD
Nominal load for
Diesel address 4. FOR DIESELADDR. 4
16 (XxXxXX)
[in kW]
DICON /E4 Adj.Report ASV Print: E 03.93 Index: 1 Page: 5Figure 77 NOMINAL LOAD
Nominal load for FOR DIESELADDR. 5
Diesel address 5.
7 (XxXxXxX)
Figure 78 NOMINAL LOAD
Nominal load for FOR DIESELADDR. 6
Diesel address 6.
78 (XxXxXX)
Cin kw]
Figure 79 NOMINAL LOAD
Nominal load for FOR DIESELADDR.7
Diesel address 7.
719 (XxXxXxX)
Cin kw
Figure 80 NOMINAL LOAD
Nominal load for FOR DIESELADDR. 8
Diesel address 8.
80 (XXxXX)
[in kw]
DICON /E4 Adj.Report ASV Print: E 03.93 Index: 1 Page: 6Figure 81
Function for alarm
input:
0: alarm input
1 + block stopping
2 + loadcomputer
3% special func-
tion
Figure 82
In case devices are
provided with
loadcomputer func-
tion, a license-no.
must
be entered
here. Otherwise,
acknowledge = with
ENTER.
DICON /E4 Adj.Report ASV Print
81
FUNCTION FOR
ALARM 7:
( x)
(0, 1, 2, 3)
82
CODE
FOR
LOAD-COMPUTER
E 03.93
Index: 1 Page: 73. Loadcomputer
3.1. Description of Function
The loadcomputer directs and controlls the connection of
consumers to the board network.
This function is totally integrated in the software - just
like that concerning the power management-control unit -
therefore requiring no further hardware equipment.
A consumer demand can be transmitted via alarm 7-input to
each DICON switched in the communication mains.
This information is transmitted to the Master starting to
process the load demand. If the relative load, including
consumer power, exceeds the power limit entered in the
power management-control unit (fig. 64), one or two Diesel
engines are started according to demand. If the power
reserves of the mains are so stable as to allow the consu-
mer to be switched on, the output function of the respecti-
ve DICON, having demanded a consumer, is set.
Setting of the Loadcomputer
To this end the function for alarm No.7 (fig. 81) must be
set on Loadcomputer-Function (select No. 2).
The output for function (cf. fig. 47) has to be set on
No.0, so the consumer can be connected to the mains.
The values for the consumer demand must be set on the DICON
selected as the Master, so they can’t be deleted.
If one of the values contains a zero, the demand of the
respective consumer won’t be precessed any longer.
DICON /E6 Discr.Loadcom. Print: E 03.93 Index: 2 PageSetting Record for Loadcomputer
In the following figures, consumer loads are entered, which
are demanded via alarm 7-input for each terminal board (CMA
114).
Figure 90 CONSUMER DEMAND
Consumer demand for FO DICONADDR.1
DICON address 1.
90 (XXX)
C kW
Figure 91 CONSUMER DEMAND
Consumer demand for FO DICONADDR. 2
DICON address 2.
a1 (XxXxXxX)
C kW]
Figure 92 CONSUMER DEMAND
Consumer demand for FO DICONADDR. 3
DICON address 3.
92 (XxX)
{ kW]
Figure 93 CONSUMER DEMAND
Consumer demand for FO DICONADDR. 4
DICON address 4.
93 (XxXxXX)
( kW]
DICON /E6 Discr.Loadcom.
Print: E 03.93 Index: 2 Page: 2Figure 94
Consumer demand for
DICON address 5.
Figure 95
Consumer demand for
DICON address 6.
Figure 96
Consumer demand for
DICON address 7.
Figure 97
Consumer demand for
DICON address 8.
DICON /E6 Discr.Loadcom.
CONSUMER DEMAND
FOR DICONADDR.5
94 (XxXxXX)
[ kW]
CONSUMER DEMAND
FOR DICONADDR. 6
95 (XXX)
tC kWwod
CONSUMER DEMAND
FOR DICONADDR.7
96 (XEXXK)
C kWod
CONSUMER DEMAND
FOR CONADDR. 8
97 (XXXK)
Ct kW
Print: E 03.93 Index: 2 Page: 3Figure 98 START/STOPLIMITS
When the actual SETTING SPEED -~
speed-value is
descending _—_ under 98 POINT
this speed-limit it
will influence the (XxXxXX) [LIN RPM]
start/stop-limits
in figure 64 - 65.
Figure 99 START/STOPLIMITS
The effect of the INFLUENCE OF DROP
influence (fig. 98)
must be adjusted by 99 (Xxx)
this factor.
FACTOR 8 (1 = 1000)
The factor descripes the following form :
F = _10 $ Speeddifference * 100
X % Loaddifference
X is the loaddifference per cent. It means: How much
must the loadlimit of start and stop descend (in $),
when the actual speed is falling down at about 10 %.
Date: 03.08.1993 Index: 1.2
DICON /E6 Discr.Loadcom. Print: £ 03.93 Index: 2 Page: 4