1. This document provides information on 300/362kV 50/63kA SF6 gas insulated switchgear equipped with hydraulic operated gas circuit breakers (GCB). 2. Key features of the switchgear include compact design requiring 40-50% less space than conventional open-air systems, reliability over 35 years of operation, and adaptability to both indoor and outdoor installations in varied climates. 3. Technical specifications are provided for ratings, typical construction with horizontally arranged circuit breakers, and modular components like the hydraulic operated GCB.

Uploaded by

Kishore Sarkar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
178 views

300/362kV 50/63ka SF Gas Insulated Switchgear: TYPE MFPT-300-50/63L

1. This document provides information on 300/362kV 50/63kA SF6 gas insulated switchgear equipped with hydraulic operated gas circuit breakers (GCB). 2. Key features of the switchgear include compact design requiring 40-50% less space than conventional open-air systems, reliability over 35 years of operation, and adaptability to both indoor and outdoor installations in varied climates. 3. Technical specifications are provided for ratings, typical construction with horizontally arranged circuit breakers, and modular components like the hydraulic operated GCB.

Uploaded by

Kishore Sarkar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

Ref. No.

GIS362(P1)H

300/362kV 50/63kA
SF6 GAS INSULATED SWITCHGEAR
EQUIPPED WITH HYDRAULIC OPERATED GCB

TYPE:MFPT-300-50/63L
Ref. No. GIS362(P1)H

1. DESIGN CONCEPT
1.1 Superb Characteristics of GIS This feature includes few gas leakage rate for many
Over 35 years of successful experiences, GIS have years, but even in the event of a total SF6 gas pressure
become the prevailing substation design due to their
loss, JAPAN AE POWER GIS still effectively insulates
superb characteristics raised as follows.
the switchgear at nominal system voltage.

Small Space: 1.2.3 Quality


362-kV GIS designs take only 40-50% of the space All JAPAN AE POWER GIS are pre-assembled and
required by conventional open-air type switchyard. tested in the manufacturing plant to secure high quality
level in each product.
Environmental Adaptability:
GIS is suitable for installation almost anywhere, urban
1.2.4 Easy Maintenance
or rural areas, indoor or outdoor, seashore,
mountainous areas, tropical or desert climate conditions. Breaker contacts replacement is the most difficult work
in the maintenance program. In JAPAN AE POWER
Ultimate Safety Design: GIS design, hand holes being provided in the breaker
All high-voltage parts are totally encapsulated in the tanks give direct access to the breaker contacts. There
grounded metal enclosures which secures ultimate is no need to disassemble the circuit breaker out of GIS
safety to the workers and engineers. assembly, or to employ special tools or a mobile crane
for such purpose.
High Reliable and Stable Operation:
Since all high voltage parts are sealed inside of inert
SF6 gas atmosphere, highly reliable and stable 1.2.5 Environmental Adaptability
operation of the substation can be secured, regardless of JAPAN AE POWER GIS is the most suitable GIS to be
climatic or environmental disturbance of the location. adapted to any particular location because of their
compactness and low profile design.
Earthquake Proof Design:
This feature assures many customers in seismic areas 1.2.6 Significant Savings in Installation Time and
from chatastophic damage of the entire switchyard,
Cost
once a severe earthquake strikes the area.
JAPAN AE POWER GIS are assembled and tested in
Extended Maintenance Intervals: the manufacturing plant and shipped to the site with
Reliable and stable operation means extended fewer disassembly for shipment. This approach
maintenance intervals. minimizes the number of on-site assembly and
connections, which means significant savings in
installation time and cost.

1.2 Features of JAPAN AE POWER Gas


Insulated Switchgear

1.2.1 Compactness
JAPAN AE POWER offers a choice of standard
isolated-phase GIS. One break GCB for 362kV rating
makes significant contribution to this feature

1.2.2 Reliability
JAPAN AE POWER GIS have proven their high
performance and reliability over more than 35 years
and 6000 bays in this rating’s field operation.

: Jointly owned by Hitachi Ltd., Fuji Electric Co., Ltd. and Meidensha Corporation page 1 of 4
Ref. No.GIS362(P1)H

2. TYPE & RATING


2.1 Typical 300/362 kV GIS Construction
A low profile design in which the circuit breakers are located horizontally benefits the customers for easy access to
the breaker, reduced breaker vibration, and safe installation work. This configuration is able to satisfy customer
requirements for any type of external connection without altering the basic GIS bay module.

2.2 Rating (Applicable standard : IEC, ANSI)

Rated voltage (kV) 300 362


Type; CB/DS/ES/CT/VT/LA Isolated-phase type
Main Busbar Three-phase common enclosure type
Rated interrupting current (kA) 50 / 63
Rated lightning impulse withstand voltage (kVp) 950 / 1050 1050 / 1175 / 1300
Rated power-frequency withstand voltage (kV) 380 / 460 450 / 520 / 555
Rated normal current (A) 2000 / 2500 / 3150/4000
Rated short-time withstand current (kA) 50 / 63
Rated duration of short circuit (sec.) 3
Rated pressure of CB 0.6
compressed SF6
gas (MPa) BUSBAR/DS/ES/CT/VT/LA 0.6
Arrangement (Cable-Feeder)
BUSBAR

DS DS
VT BUSBAR
ES
HSES
ES
DS
ES DS
CT

CB CT CT DS
CH
CT CB

ES
DS

VT HSES

CH

Bay dimensions; Length/Width/Height (approx. m) L 6.5 / W2.5 / H 3.8


Operating CB Hydraulic
Mechanism; DS Motor
ES/HSES Motor / Motor Spring / Manual

page 2 of 4
Ref. No. GIS362(P1)H

3. ARRANEGMENT
3.1 Cross Section of Typical 300/362kV GIS (Cable-Feeder)

BUSBAR
DS
ES
VT

HSES
DS
DS
ES

CT CT

CH
CB

Closing Resistor

3.2 Arrangement

Cable Connection Bushing Connection

GIB Connection

page 3 of 4
Ref. No. GIS362(P1)H

4. MODULAR COMPONENTS
4.1 Gas Circuit Breaker

End Cover Stationary Side Moving Side Hydraulic Operation


for Maintenance Interrupter Gas Tank Interrupter Conductor Mechanism
Supporting Insulator

Closing Resistor Accumulator Insulating Operating Rod Linear Driving Shaft


(20 or 30)

Stationary Insulated Shield Main Puffer Puffer Insulated


Arcing Contact Nozzle Contact Cylinder Piston Operating Rod

Conductor Moving Shield Current Conductor


Arcing Contact Collector

(a) Closed Position (b) Open Position

Construction of Interrupter

page 4 of 4
The Right Solution in Power Transmission and Distribution