1. The document discusses 1-2-3 KVC vertical axis multistage centrifugal pump pressure booster sets that can pump liquids from 1 to 36 cubic meters per hour. 2. The sets use 1, 2, or 3 vertical axis multistage electric pumps made of galvanized steel and stainless steel with control panels to protect the pumps. 3. The control panels for the 2 and 3 pump sets include components like pressure switches, contactors, and displays to monitor and control the pumps.

Uploaded by

Didel Dragu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
92 views10 pages

Fisa Tefnica Grup Pompare Hidranti Exteriori

1. The document discusses 1-2-3 KVC vertical axis multistage centrifugal pump pressure booster sets that can pump liquids from 1 to 36 cubic meters per hour. 2. The sets use 1, 2, or 3 vertical axis multistage electric pumps made of galvanized steel and stainless steel with control panels to protect the pumps. 3. The control panels for the 2 and 3 pump sets include components like pressure switches, contactors, and displays to monitor and control the pumps.

Uploaded by

Didel Dragu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

1-2-3 KVC

PRESSURE BOOSTER SETS WITH 1 - 2 - 3 VERTICAL AXIS MULTISTAGE CENTRIFUGAL PUMPS

E.BOX
TECHNICAL DATA
PAG 174 Operating range: from 1 to 36 m3/h.
Pumped liquid: clean, free of solids and abrasives, non
viscous, non aggressive, non crystallised and chemically neutral,
with properties similar to water.
Pumped liquid temperature range: from 0 °C to +50 °C
Maximum ambient temperature: +40 °C.
Maximum operating pressure: PN16.
Special executions on request: contact our sales network.
Protection class: IP44.
IE2 motors as standard from 0,75 kW to 5,5 kW - IE3 ≥ 7,5 kW.
PRESSURE SETS

APPLICATIONS
Water lifting sets particularly suited for domestic use, and small civil, agricultural, or industrial systems. The use of vertical axis multistage centrifugal
electric pumps ensures high performance results. Their main features are limited space requirements, sturdiness, absolute reliability, and extremely quiet
operation.
CONSTRUCTION FEATURES
HYDRAULIC SECTION
1 - 2 - 3 KVC vertical axis multistage electric pump; galvanised steel metal sheet base; AISI 304 STAINLESS STEEL suction and delivery manifold (1 KVC
without suction manifold); 1 - 2 - 3 membrane tanks; ball valves with unions at the suction and the delivery of each pump; check valve with unions at the
suction of each pump; 1 1/4" are supply connections at the suction of each pump; 2 stainless steel female plugs for closing the manifolds; axial gauge
with isolator valve; galvanised steel electric control panel support.
ELECTRICAL SECTION
1 KVC SET
Single phase version. 1 2-pole pressure switch connected to the electric pump, with power input plug.
Three phase version. Remote motor protector control panel with reset pushbutton, 1 2-pole pressure switch connected to the electric pump.
2 KVC SET
Supplied in an IP 55 protection class self-extinguishing thermoplastic material box, the control panel protects the electric pumps from abnormal
conditions such as: overload and overtemperature (with automatic reset), short circuit (with fuses - Plus model only), pump current surges (amperometric
protection), abnormal voltage, dry run, quick starts, pressure sensor fault, or inconsistency of the external protection commands.
FRONT PANEL COMPONENTS:
General disconnector with padlockable door lock. AUT-0-MAN operation selection pushbuttons. Alarm RESET pushbutton. Display for all models.
Operation, stop, alarm notification lamps.
PANEL INTERNAL COMPONENTS:
Electronic control card with protection fuses and contactors. Power input connection terminal (single phase or three phase).
Dry run or overpressure pressure switch connection terminals (optional). Alarm notification N.O. contacts. Function selection mini dip switch (pressure
transmitter or pressure switches, standard or additional tanks).
3 KVC SET
IP 55 protection class self-extinguishing, shock-resistant plastic electric control panel. The control panel includes the general switch, the electric
pump protection thermal magnetic circuit breakers, the electric pump start order switch system, 24 V low voltage circuit for the control of the pressure
switches, MAN-0-AUT selectors. (Operation pushbuttons for single phase control panel), notification lamps at the front of the panel. Installed on
appropriate support on the pump base. Three pump start/stop pre-calibrated pressure switches.
The electric control panel of 2 KVC and 3 KVC sets is ready for the connection of:
Dry run protection float or pressure switch kit (*).
Overpressure stop pressure switch kit (*).
(*) available separately as optional.
The sets are supplied in a sturdy cardboard packaging on wooden pallet and installation / maintenance manual with electric diagram.

MATERIALS 36 7

304
16
N. PARTS* MATERIALS N. PARTS* MATERIALS 8

1 PUMP BODY TECHNOPOLYMER A 57a INTERMEDIATE STAGE TECHNOPOLYMER B 4

4 IMPELLER TECHNOPOLYMER B 69 LINER AISI 304 STAINLESS STEEL 6


6 DIFFUSER TECHNOPOLYMER B X5 CrNi 1810 UNI 6900/71 69 98
AISI 303 STAINLESS STEEL 98 DIFFUSER BODY TECHNOPOLYMER B
7 SHAFT WITH ROTOR X10 CrNi 1089 UNI 6900/71 271 CENTERING BUSHING BRONZE B14 57a
271
16 MECHANICAL SEAL SILICON CARBIDE/SILICON 304 CONVEYOR TECHNOPOLYMER B
28
28 OR RING EPDM RUBBER 8 DNM (standard for KVCX only)
AISI 304 STAINLESS STEEL 1
36 SEAL HOLDING DISC X5 CrNi 1810 UNI 6900/71
* In contact with the liquid.

DAB PUMPS reserves the right to make modifications without notice.

72
1 KVC 50 - CIVIL USE PRESSURE BOOSTER SETS
Pumped liquid temperature range: from -10 °C to +50 °C - Maximum ambient temperature: +40 °C

0 2 4 6 8 10 12 14 16 18 20 22 Q US gpm
0 2 4 6 8 10 12 14 16 18 Q IMP gpm

P H H
kPa m ft
MEI : see page 145
900 75/50
90

280

800
80
65/50
240
700
70

55/50
600 200
60

500 50
40/50
160

400 40
30/50 120

300 30

PRESSURE SETS
80

200 20

40
100 10

0 0 0
3
0 1 2 3 4 5 Q m /h

0 0,2 0,4 0,6 0,8 1 1,2 1,4 Q l/s


0 10 20 30 40 50 60 70 80 Q l/min

The performance curves are based on kinematic viscosity values = 1 mm2/s and density equivalent to 1000 kg/m3
Curve tolerance according to ISO 9906.

P2 NOMINAL MAX OBTAINABLE PRESSURE SWITCH


POWER INPUT In FLOW
MODEL PRESSURE CALIBRATION
50 Hz kW HP A m3/h BAR BAR
1 KVC 30/50 M 1x 220-240 v 0.55 0.75 4 4,5 - 1 4 2,5 – 3,5

1 KVC 30/50 T 3x 400 v 0.55 0.75 1.4 4,5 - 1 4 2,5 – 3,5

1 KVC 40/50 M 1x 220-240 v 0.8 1.1 5.6 4,5 – 1 5.2 4–5

1 KVC 40/50 T 3x 400 v 0.8 1.1 2.2 4,5 – 1 5.2 4–5

1 KVC 55/50 M 1x 220-240 v 1 1.36 6.4 4,5 – 1 6.5 5–6

1 KVC 55/50 T 3x 400 v 1 1.36 2.6 4,5 – 1 6.5 5–6

1 KVC 65/50 M 1x 220-240 v 1.1 1.5 7.4 4,5 – 1 8 6,5 – 7,5

1 KVC 65/50 T 3x 400 v 1.1 1.5 3.1 4,5 – 1 8 6,5 – 7,5

1 KVC 75/50 M 1x 220-240 v 1.5 2 9 4,5 – 1 9 7,5 – 8,5

1 KVC 75/50 T 3x 400 v 1.5 2 3.6 4,5 – 1 9 7,5 – 8,5

Ø MANIFOLDS WEIGHT kg
MODEL A B C D H H2 H3 H4
DNA (suc.) DNM (del.) Single-phase three-phase
1KVC 30/50 630 300 300 260 730 60 290 450 1” 1/4 1” 1/2 26 26

1KVC 40/50 630 300 300 260 730 60 290 450 1” 1/4 1” 1/2 28 28

1KVC 55/50 630 300 300 260 730 60 290 450 1” 1/4 1” 1/2 29 29

1KVC 65/50 630 300 300 260 730 60 290 450 1” 1/4 1” 1/2 32 32

1KVC 75/50 630 300 300 260 730 60 290 450 1” 1/4 1” 1/2 33 32

DAB PUMPS reserves the right to make modifications without notice.

73
1 KVC 80 - CIVIL USE PRESSURE BOOSTER SETS
Pumped liquid temperature range: from -10 °C to +50 °C - Maximum ambient temperature: +40 °C

0 5 10 15 20 25 30 Q US gpm
0 5 10 15 20 25 Q IMP gpm

P H H
kPa m ft

900
MEI : see page 145
90 65/80
280

800
80
55/80
240
700
70

45/80
600 200
60

40/80
500 50 160

400 30/80
40
120

300 30
PRESSURE SETS

80

200 20

40
100 10

0 0 0
3
0 1 2 3 4 5 6 7 Q m /h

0 0,5 1 1,5 2 Q l/s


0 20 40 60 80 100 120 Q l/min

The performance curves are based on kinematic viscosity values = 1 mm2/s and density equivalent to 1000 kg/m3
Curve tolerance according to ISO 9906.

P2 NOMINAL MAX OBTAINABLE PRESSURE SWITCH


POWER INPUT In FLOW
MODEL PRESSURE CALIBRATION
50 Hz kW HP A m3/h BAR BAR
1 KVC 30/80 M 1x 220-240 v 0.8 1.1 5.6 7-2 4.5 3–4

1 KVC 30/80 T 3x 400 v 0.8 1.1 2.2 7-2 4.5 3–4

1 KVC 40/80 M 1x 220-240 v 1 1.36 6.5 7–2 5.5 4–5 4–5

1 KVC 40/80 T 3x 400 v 1 1.36 2.6 7–2 5.5 4–5

1 KVC 45/80 M 1x 220-240 v 1.1 1.5 7.4 7–2 6.8 5–6 2,5 – 3,5

1 KVC 45/80 T 3x 400 v 1.1 1.5 3.1 7–2 6.8 5–6

1 KVC 55/80 M 1x 220-240 v 1.5 2 9 7–2 8 6–7 4–5

1 KVC 55/80 T 3x 400 v 1.5 2 3.6 7–2 8 6–7

1 KVC 65/80 T 3x 400 v 2.2 3 4 7-2 9.2 7–8

Ø MANIFOLDS WEIGHT kg
MODEL A B C D H H2 H3 H4
DNA (suc.) DNM (del.) Single-phase Three-phase
1KVC 30/80 620 300 300 260 730 60 290 450 1” 1/4 1” 1/2 28 27

1KVC 40/80 620 300 300 260 730 60 290 450 1” 1/4 1” 1/2 29 29

1KVC 45/80 620 300 300 260 730 60 290 450 1” 1/4 1” 1/2 32 32

1KVC 55/80 620 300 300 260 730 60 290 450 1” 1/44 1” 1/2 33 32

1KVC 65/80 620 300 300 260 730 60 290 450 1” 1/4 1” 1/2 - 34

DAB PUMPS reserves the right to make modifications without notice.

74
1 KVC 120 - CIVIL USE PRESSURE BOOSTER SETS
Pumped liquid temperature range: from -10 °C to +50 °C - Maximum ambient temperature: +40 °C

0 5 10 15 20 25 30 35 40 45 50 Q US gpm
0 5 10 15 20 25 30 35 40 Q IMP gpm
P H H
kPa m ft
1100 MEI : see page 145
110
350
85/120
1000
100

900 300
90
70/120
800
80
250
60/120
700
70

600 60 200
45/120

500 50
150
35/120
400 40

PRESSURE SETS
300 30 100

200 20
50
100 10

0 0 0
0 1 2 3 4 5 6 7 8 9 10 11 12 Q m3/h

0 0,5 1 1,5 2 2,5 3 Q l/s


0 20 40 60 80 100 120 140 160 180 200 Q l/min

The performance curves are based on kinematic viscosity values = 1 mm2/s and density equivalent to 1000 kg/m3
Curve tolerance according to ISO 9906.

P2 NOMINAL MAX OBTAINABLE PRESSURE SWITCH


POWER INPUT In FLOW
MODEL PRESSURE CALIBRATION
50 Hz kW HP A m3/h BAR BAR
1 KVC 35/120 M 1x 220-240 v 1.1 1.5 7.4 11 – 2 4.5 3–4

1 KVC 35/120 T 3x 400 v 1.1 1.5 3.5 11 – 2 4.5 3–4

1 KVC 45/120 M 1x 220-240 v 1.85 2.5 12 11 – 2 6 4,5 – 5,5

1 KVC 45/120 T 3x 400 v 1.85 2.5 4.6 11 – 2 6 4,5 – 5,5

1 KVC 60/120 T 3x 400 v 2.2 3 5.4 11 – 2 7.5 5,5 – 6,5

1 KVC 70/120 T 3x 400 v 3 4 6.8 11 – 2 9 7–8

1 KVC 85/120 T 3x 400 v 3 4 7.8 11 – 2 10.5 9 – 10

Ø MANIFOLDS WEIGHT kg
MODEL A B C D H H2 H3 H4
DNA (suc.) DNM (del.) Single-phase Three-phase
1KVC 35/120 620 300 300 260 730 260 290 450 1” 1/4 1” 1/2 32 32

1KVC 45/120 620 300 300 260 730 260 290 450 1” 1/4 1” 1/2 44 34

1KVC 60/120 620 300 300 260 730 260 290 450 1” 1/4 1” 1/2 - 36

1KVC 70/120 620 300 300 260 730 260 290 450 1” 1/4 1” 1/2 - 38

1KVC 85/120 620 300 300 260 730 260 290 450 1” 1/4 1” 1/2 - 39

DAB PUMPS reserves the right to make modifications without notice.

75
2 KVC 50 - CIVIL USE PRESSURE BOOSTER SETS
Pumped liquid temperature range: from -10 °C to +50 °C - Maximum ambient temperature: +40 °C

0 8 16 24 32 40 Q US gpm

0 8 16 24 32 Q IMP gpm

P H H
kPa m ft
MEI : see page 145
900 75/50
90

280

800
80
65/50
240
700
70

55/50
600 200
60

500 50 40/50
160

400 40
30/50 120

300 30
PRESSURE SETS

80

200 20

40
100 10

0 0 0
3
0 2 4 6 8 10 Q m /h

0 0,4 0,8 1,2 1,6 2 2,4 2,8 Q l/s


0 20 40 60 80 100 120 140 160 Q l/min

The performance curves are based on kinematic viscosity values = 1 mm2/s and density equivalent to 1000 kg/m3
Curve tolerance according to ISO 9906.

P2 NOMINAL MAX OBTAINABLE STANDARD


POWER INPUT In FLOW
MODEL PRESSURE PRESSURE
50 Hz kW HP A m3/h BAR BAR
2KVC 30/50 M 1x 220-240 v 2x 0,55 2x 0,75 2x 4 9-1 4 2.5

2KVC 30/50 T 3x 400 v 2x 0,55 2x 0,75 2x 1,4 9–1 4 2.5

2KVC 40/50 M 1x 220-240 v 2x 0,8 2x 1,1 2x 5,6 9–1 5.2 3.5

2KVC 40/50 T 3x 400 v 2x 0,8 2x 1,1 2x 2,2 9–1 5.2 3.5

2KVC 55/50 M 1x 220-240 v 2x 1 2x 1,36 2x 6,4 9–1 6.5 4.5

2KVC 55/50 T 3x 400 v 2x 1 2x 1,36 2x 2,6 9–1 6.5 4.5

2KVC 65/50 M 1x 220-240 v 2x 1,1 2x 1,5 2x 7,4 9–1 8 5.5

2KVC 65/50 T 3x 400 v 2x 1,1 2x 1,5 2x 3,1 9–1 8 5.5

2KVC 75/50 M 1x 220-240 v 2x 1,5 2x 2 2x 9 9–1 9 6.5

2KVC 75/50 T 3x 400 v 2x 1,5 2x 2 2x 3,6 9–1 9 6.5

Ø MANIFOLDS WEIGHT kg
MODEL A B C D H H1 H2 H3 H4
DNA (suc.) DNM (del.) Single-phase Three-phase
2KVC 30/50 760 550 500 560 800 920 95 260 610 2” 2” 70 70

2KVC 40/50 760 550 500 560 800 920 95 260 610 2” 2” 74 74

2KVC 55/50 760 550 500 560 800 920 95 260 610 2” 2” 76 76

2KVC 65/50 760 550 500 560 800 920 95 260 610 2” 2” 82 81

2KVC 75/50 760 550 500 560 800 920 95 260 610 2” 2” 84 83

DAB PUMPS reserves the right to make modifications without notice.

76
2 KVC 80 - CIVIL USE PRESSURE BOOSTER SETS
Pumped liquid temperature range: from -10 °C to +50 °C - Maximum ambient temperature: +40 °C

0 10 20 30 40 50 60 Q US gpm
0 10 20 30 40 50 Q IMP gpm

P H H
kPa m ft

900
MEI : see page 145
90 65/80
280

800
80
55/80
240
700
70

45/80
600 200
60

40/80
500 50 160

400 30/80
40
120

300 30

PRESSURE SETS
80

200 20

40
100 10

0 0 0
0 2 4 6 8 10 12 14 Q m3/h

0 1 2 3 4 Q l/s
0 40 80 120 160 200 240 Q l/min

The performance curves are based on kinematic viscosity values = 1 mm2/s and density equivalent to 1000 kg/m3
Curve tolerance according to ISO 9906.

P2 NOMINAL MAX OBTAINABLE STANDARD


POWER INPUT In FLOW
MODEL PRESSURE PRESSURE
50 Hz kW HP A m3/h BAR BAR
2 KVC 30/80 M 1x 220-240 v 2x 0,8 2x 1,1 2x 5,6 14 - 2 4.5 3

2 KVC 30/80 T 3x 400 v 2x 0,8 2x 1,1 2x 2,2 14 – 2 4.5 3

2 KVC 40/80 M 1x 220-240 v 2x 1 2x 1,36 2x 6,5 14 – 2 5.5 4

2 KVC 40/80 T 3x 400 v 2x 1 2x 1,36 2x 2,6 14 – 2 5.5 4

2 KVC 45/80 M 1x 220-240 v 2x 1,1 2x 1,5 2x 7,4 14 – 2 6.8 5

2 KVC 45/80 T 3x 400 v 2x 1,1 2x 1,5 2x 3,1 14 – 2 6.8 5

2 KVC 55/80 M 1x 220-240 v 2x 1,5 2x 2 2x 9 14 – 2 8 6

2 KVC 55/80 T 3x 400 v 2x 1,5 2x 2 2x 3,6 14 – 2 8 6

2 KVC 65/80 T 3x 400 v 2x 2,2 2x 3 2x 4 14 – 2 9.2 7

Ø MANIFOLDS WEIGHT kg
MODEL A B C D H H1 H2 H3 H4
DNA (suc.) DNM (del.) Single-phase Three-phase
2KVC 30/80 760 550 500 560 800 920 95 260 610 2” 2” 73 73

2KVC 40/80 760 550 500 560 800 920 95 260 610 2” 2” 76 76

2KVC 45/80 760 550 500 560 800 920 95 260 610 2” 2” 82 82

2KVC 55/80 760 550 500 560 800 920 95 260 610 2” 2” 84 82

2KVC 65/80 760 550 500 560 800 920 95 260 610 2” 2” - 85

DAB PUMPS reserves the right to make modifications without notice.

77
2 KVC 120 - CIVIL USE PRESSURE BOOSTER SETS
Pumped liquid temperature range: from -10 °C to +50 °C - Maximum ambient temperature: +40 °C

0 20 40 60 80 100 Q US gpm

0 20 40 60 80 Q IMP gpm

P H H
kPa m ft
1100 MEI : see page 145
110
350
85/120
1000
100

900 300
90
70/120
800
80
250
60/120
700
70

600 200
60
45/120
500 50
150
35/120
400 40
PRESSURE SETS

300 30 100

200 20
50

100 10

0 0 0
0 2 4 6 8 10 12 14 16 18 20 22 24 Q m 3/h

0 1 2 3 4 5 6 Q l/s

0 40 80 120 160 200 240 280 320 360 400 Q l/min

The performance curves are based on kinematic viscosity values = 1 mm2/s and density equivalent to 1000 kg/m3
Curve tolerance according to ISO 9906.

P2 NOMINAL MAX OBTAINABLE STANDARD


POWER INPUT In FLOW
MODEL PRESSURE PRESSURE
50 Hz kW HP A m3/h BAR BAR
2 KVC 35/120 M 1x 220-240 v 2x 1,1 2x 1,5 2x 7,4 22 – 2 4.5 3

2 KVC 35/120 T 3x 400 v 2x 1,1 2x 1,5 2x 3,5 22 – 2 4.5 3

2 KVC 45/120 M 1x 220-240 v 2x 1,85 2x 2,5 2x 12 22 – 2 6 4

2 KVC 45/120 T 3x 400 v 2x 1,85 2x 2,5 2x 4,6 22 – 2 6 4

2 KVC 60/120 T 3x 400 v 2x 2,2 2x 3 2x 5,4 22 – 2 7.5 5

2 KVC 70/120 T 3x 400 v 2x 3 2x 4 2x 6,8 22 – 2 9 6

2 KVC 85/120 T 3x 400 v 2x 3 2x 4 2x 7,8 22 – 2 10.5 7

Ø MANIFOLDS WEIGHT kg
MODEL A B C D H H1 H2 H3 H4
DNA (suc.) DNM (del.) Single-phase Three-phase
2KVC 35/120 760 550 500 560 800 920 95 260 610 2” 2” 82 82

2KVC 45/120 760 550 500 560 800 920 95 260 610 2” 2” 86 86

2KVC 60/120 760 550 500 560 800 920 95 260 610 2” 2” - 90

2KVC 70/120 760 550 500 560 800 920 95 260 610 2” 2” - 94

2KVC 85/120 760 550 500 560 800 920 95 260 610 2” 2” - 95

DAB PUMPS reserves the right to make modifications without notice.

78
3 KVC 50 - CIVIL USE PRESSURE BOOSTER SETS
Pumped liquid temperature range: from -10 °C to +50 °C - Maximum ambient temperature: +40 °C

0 6 12 18 24 30 36 42 48 54 60 66 Q US gpm
0 6 12 18 24 30 36 42 48 54 Q IMP gpm

P H H
kPa m ft
MEI : see page 145
900 75/50
90

280

800
80
65/50
240
700
70

55/50
600 200
60

500 50
40/50
160

400 40
30/50 120

300 30

PRESSURE SETS
80

200 20

40
100 10

0 0 0
3
0 3 6 9 12 15 Q m /h
0 0,6 1,2 1,8 2,4 3 3,6 4,2 Q l/s
0 30 60 90 120 150 180 210 240 Q l/min

The performance curves are based on kinematic viscosity values = 1 mm2/s anddensity equivalent to 1000 kg/m3
Curve tolerance according to ISO 9906.

P2 NOMINAL MAX OBTAINABLE PRESSURE SWITCH


POWER INPUT In FLOW
MODEL PRESSURE CALIBRATION
50 Hz kW HP A m3/h BAR BAR
3KVC 30/50 M 1x 220-240 v 3x 0,55 3x 0,75 3x 4 13,5 - 1 4 1,5 – 3,5

3KVC 30/50 T 3x 400 v 3x 0,55 3x 0,75 3x 1,4 13,5 - 1 4 1,5 – 3,5

3KVC 40/50 M 1x 220-240 v 3x 0,8 3x 1,1 3x 5,6 13,5 – 1 5.2 3–5

3KVC 40/50 T 3x 400 v 3x 0,8 3x 1,1 3x 2,2 13,5 – 1 5.2 3–5

3KVC 55/50 M 1x 220-240 v 3x 1 3x 1,36 3x 6,4 13,5 – 1 6.5 4–6

3KVC 55/50 T 3x 400 v 3x 1 3x 1,36 3x 2,6 13,5 – 1 6.5 4–6

3KVC 65/50 M 1x 220-240 v 3x 1,1 3x 1,5 3x 7,4 13,5 – 1 8 5,5 – 7,5

3KVC 65/50 T 3x 400 v 3x 1,1 3x 1,5 3x 3,1 13,5 – 1 8 5,5 – 7,5

3KVC 75/50 M 1x 220-240 v 3x 1,5 3x 2 3x 9 13,5 – 1 9 6,5 – 8,5

3KVC 75/50 T 3x 400 v 3x 1,5 3x 2 3x 3,6 13,5 – 1 9 6,5 – 8,5

Ø MANIFOLDS WEIGHT kg
MODEL A B C D H H1 H2 H3 H4
DNA (suc.) DNM (del.) Single-phase Three-phase
3KVC 30/50 650 900 810 850 950 1100 100 410 610 2” 1/2 2” 1/2 109 109

3KVC 40/50 650 900 810 850 950 1100 100 410 610 2” 1/2 2” 1/2 115 115

3KVC 55/50 650 900 810 850 950 1100 100 410 610 2” 1/2 2” 1/2 119 119

3KVC 65/50 650 900 810 850 950 1100 100 410 610 2” 1/2 2” 1/2 128 127

3KVC 75/50 650 900 810 850 950 1100 100 410 610 2” 1/2 2” 1/2 132 130

DAB PUMPS reserves the right to make modifications without notice.

79
3 KVC 80 - CIVIL USE PRESSURE BOOSTER SETS
Pumped liquid temperature range: from -10 °C to +50 °C - Maximum ambient temperature: +40 °C

0 15 30 45 60 75 90 Q US gpm
0 15 30 45 60 75 Q IMP gpm

P H H
kPa m ft

900
MEI : see page 145
90 65/80
280

800
80
55/80
240
700
70

45/80
600 200
60

40/80
500 50 160

400 30/80
40
120

300 30
PRESSURE SETS

80

200 20

40
100 10

0 0 0
3
0 3 6 9 12 15 18 21 Q m /h
0 1,5 3 4,5 6 Q l/s
0 60 120 180 240 300 360 Q l/min

The performance curves are based on kinematic viscosity values = 1 mm2/s and density equivalent to 1000 kg/m3
Curve tolerance according to ISO 9906.

P2 NOMINAL MAX OBTAINABLE PRESSURE SWITCH


POWER INPUT In FLOW
MODEL PRESSURE CALIBRATION
50 Hz kW HP A m3/h BAR BAR
3KVC 30/80 M 1x 220-240 v 3x 0,8 3x 1,1 3x 5,6 21 - 2 4.5 2–4

3KVC 30/80 T 3x 400 v 3x 0,8 3x 1,1 3x 2,2 21 - 2 4.5 2–4

3KVC 40/80 M 1x 220-240 v 3x 1 3x 1,36 3x 6,5 21 – 2 5.5 3–5

3KVC 40/80 T 3x 400 v 3x 1 3x 1,36 3x 2,6 21 – 2 5.5 3–5

3KVC 45/80 M 1x 220-240 v 3x 1,1 3x 1,5 3x 7,4 21 – 2 6.8 4–6

3KVC 45/80 T 3x 400 v 3x 1,1 3x 1,5 3x 3,1 21 – 2 6.8 4–6

3KVC 55/80 M 1x 220-240 v 3x 1,5 3x 2 3x 9 21 – 2 8 5–7

3KVC 55/80 T 3x 400 v 3x 1,5 3x 2 3x 3,6 21 – 2 8 5–7

3KVC 65/80 T 3x 400 v 3x 2,2 3x 3 3x 4 21 - 2 9.2 6–8

Ø MANIFOLDS WEIGHT kg
MODEL A B C D H H1 H2 H3 H4
DNA (suc.) DNM (del.) Single-phase Three-phase
3KVC 30/80 650 900 810 850 950 1100 100 410 610 2” 1/2 2” 1/2 115 114

3KVC 40/80 650 900 810 850 950 1100 100 410 610 2” 1/2 2” 1/2 119 119

3KVC 45/80 650 900 810 850 950 1100 100 410 610 2” 1/2 2” 1/2 128 128

3KVC 55/80 650 900 810 850 950 1100 100 410 610 2” 1/2 2” 1/2 131 128

3KVC 65/80 650 900 810 850 950 1100 100 410 610 2” 1/2 2” 1/2 - 133

DAB PUMPS reserves the right to make modifications without notice.

80
3 KVC 120 - CIVIL USE PRESSURE BOOSTER SETS
Pumped liquid temperature range: from -10 °C to +50 °C - Maximum ambient temperature: +40 °C

0 15 20 45 60 75 90 105 120 135 150 Q US gpm

0 15 20 45 60 75 90 105 120 Q IMP gpm


P H H
kPa m ft
1100 MEI : see page 145
110
350
85/120
1000
100

900 300
90
70/120
800
80
250
60/120
700
70

600 200
60
45/120
500 50
150
35/120
400 40

PRESSURE SETS
300 30 100

200 20
50

100 10

0 0 0
0 3 6 9 12 15 18 21 24 27 30 33 36 Q m3/h

0 1,5 3 4,5 6 7,5 9 Q l/s


0 60 120 180 240 300 360 420 480 540 600 Q l/min

The performance curves are based on kinematic viscosity values = 1 mm2/s and density equivalent to 1000 kg/m3
Curve tolerance according to ISO 9906.

P2 NOMINAL MAX OBTAINABLE PRESSURE SWITCH


POWER INPUT In FLOW
MODEL PRESSURE CALIBRATION
50 Hz kW HP A m3/h BAR BAR
3KVC 35/120 M 1x 220-240 v 3x 1,1 3x 1,5 3x 7,4 33 – 2 4.5 2–4

3KVC 35/120 T 3x 400 v 3x 1,1 3x 1,5 3x 3,5 33 – 2 4.5 2–4

3KVC 45/120 M 1x 220-240 v 3x 1,85 3x 2,5 3x 12 33 – 2 6 3,5 – 5,5

3KVC 45/120 T 3x 400 v 3x 1,85 3x 2,5 3x 4,6 33 – 2 6 3,5 – 5,5

3KVC 60/120 T 3x 400 v 3x 2,2 3x 3 3x 5,4 33 – 2 7.5 4,5 – 6,5

3KVC 70/120 T 3x 400 v 3x 3 3x 4 3x 6,8 33 – 2 9 6–8

3KVC 85/120 T 3x 400 v 3x 3 3x 4 3x 7,8 33 – 2 10.5 8 – 10

Ø MANIFOLDS WEIGHT kg
MODEL A B C D H H1 H2 H3 H4
DNA (suc.) DNM (del.) Single-phase Three-phase
3KVC 35/120 650 900 810 850 950 1100 100 410 610 2” 1/2 2” 1/2 128 128

3KVC 45/120 650 900 810 850 950 1100 100 410 610 2” 1/2 2” 1/2 134 134

3KVC 60/120 650 900 810 850 950 1100 100 410 610 2” 1/2 2” 1/2 - 140

3KVC 70/120 650 900 810 850 950 1100 100 410 610 2” 1/2 2” 1/2 - 146

3KVC 85/120 650 900 810 850 950 1100 100 410 610 2” 1/2 2” 1/2 - 148

DAB PUMPS reserves the right to make modifications without notice.

81

You might also like