100% found this document useful (1 vote)
520 views

Method Statement For Precommissioning & Commissioning of Extract Fans

This document outlines the pre-commissioning and commissioning procedures for extract fans. The purpose is to ensure the fans are installed correctly and functioning as intended. The pre-commissioning procedure involves checks of the fan installation, components, electrical connections, and cleaning. The commissioning procedure involves starting the fan, checking rotation and vibration, adjusting air flows, testing controls, and recording performance readings. Checklists and records are provided as attachments.

Uploaded by

vin ss
Copyright
© © All Rights Reserved
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
520 views

Method Statement For Precommissioning & Commissioning of Extract Fans

This document outlines the pre-commissioning and commissioning procedures for extract fans. The purpose is to ensure the fans are installed correctly and functioning as intended. The pre-commissioning procedure involves checks of the fan installation, components, electrical connections, and cleaning. The commissioning procedure involves starting the fan, checking rotation and vibration, adjusting air flows, testing controls, and recording performance readings. Checklists and records are provided as attachments.

Uploaded by

vin ss
Copyright
© © All Rights Reserved
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 3

METHOD STATEMENT FOR

PRECOMMISSIONING &
COMMISSIONING OF
EXTRACT FANS
 HVAC Method Statements
 Testing & Commissioning

600



 0
 


 Share

The purpose of this procedure is to define the step by step method to implement the
correct practices for thepre-commissioning & commissioning of Extract Fansthrough
the guidelines contained herein so as to ensure that the job execution complies with the
project requirements and serves the intended function to satisfactory level.

Pre-commissioning Procedure for Extract Fans

1. Ensure that the extract fan installation is complete and mechanical completion is


approved.
2. Ensure that no damage occurs between mechanical completion & pre-
commissioning.
3. Repair all damages to the equipment finish paint.
4. Check the fan is installed as per the approved shop drawings and manufacturer’s
instructions.
5. Check that the vibration isolators are fixed.
6. Check by hand that the fan is rotating freely.
7. Check duct connections and grilles as per approved shop drawing and respective
method statement.
8. Check that the motor & the pulley are aligned & the belt tension is correct.
9. Check all VCDs and fire dampers are open.
10. Check for proper electrical power, control and earthing connections as per
manufacturer’s recommendations. Field wiring to be pre-tested for continuity and
insulation resistance.
11. Check the internal & external surface of the fan is cleaned.
12. Check the fan impellers are statically & dynamically balanced.
13. Set earth leakage and overload relays as per motor nameplate rating.

Commissioning Procedure for Extract


Fans
1. Ensure that all the pre-commissioning checks are carried out successfully.
2. Start the fan for a moment & check the direction of rotation of the  fan / motor is
correct.
3. Upon ensuring correct direction of rotation, start the fan and run for 5 minutes.
4. Check for any undue vibration or noise.
5. Measure air flow in the main supply air duct and adjust, if required to set design
value.
6. Similarly measure air flow in all the branches / outlets. Set to correct value by
adjusting splitter damper, volume control damper, etc in the ducts.
7. Check any control / safety devices for proper functionality.
8. Check & record the currect & voltage on all phases.
9. Check & record the static head & total head.
10. Record all readings in the final performance check lis.
11. Check the interface with BMS & Fire alarm system.

ATTACHMENTS

 Pre-commissioning check sheet for Extract Fans


 Commissioning check sheet for Extract Fans
 Performance Test Record for Extract Fans
 Pre-commissioning & Commissioning plan for HVAC System
 Risk Assessment

You might also like