Field Data: Item Description Symbol Unit Value Step 1 Rectangle-1 (GIS Hall)

This document summarizes the steps to design an earthing system according to IEEE 80:2013 standards. It includes calculating the required conductor size based on fault current specifications, determining touch and step voltage criteria, designing the initial grid layout, calculating the grid resistance and current, and validating that the mesh and step voltages meet safety thresholds. The design is for earthing a 324 square meter area with a soil resistivity of 50 ohm-meters and a 7.05 kA fault current.

Uploaded by

MELVIN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
163 views

Field Data: Item Description Symbol Unit Value Step 1 Rectangle-1 (GIS Hall)

This document summarizes the steps to design an earthing system according to IEEE 80:2013 standards. It includes calculating the required conductor size based on fault current specifications, determining touch and step voltage criteria, designing the initial grid layout, calculating the grid resistance and current, and validating that the mesh and step voltages meet safety thresholds. The design is for earthing a 324 square meter area with a soil resistivity of 50 ohm-meters and a 7.05 kA fault current.

Uploaded by

MELVIN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

EARTHING DESIGN AS PER IEEE 80: 2013 - AT A GLANCE

ITEM DESCRIPTION SYMBOL UNIT VALUE

STEP 1
FIELD DATA
1 Rectangle-1 (GIS Hall)
Length L1 m 20
Width B1 m 12
2 Rectangle-2 (Transformer Yard)
Length L2 m 14
Width B2 m 6
3 Total enclosed area by ground grid A (m2) 324
4 Soil resistivity U :m 50

STEP 2
CONDUCTOR SIZE
5 Symmetrical fault current Ig (=IF) kA 7.05
6 Duration of fault current tc s 3
7 Material Thermal Capacity per unit volume TCAP J/cm3/ºC 3.9
8 Ground conductor thermal coefficient of resistivity at 0ºC D0 - 0.003413
9 Reference temperature Tr ºC 20
10 Ground conductor thermal coefficient of resistivity at reference temperature Dr - 0.0032
11 Ground conductor resistivity at reference temperature Ur P:cm 20.1
12 K0 = 1 / D0 Ko - 293
13 Maximum allowable temperature Tm ºC 419
14 Ambient temperature Ta ºC 45
Amm2 2
15 Required conductor cross-section area mm 152.70
16 Required conductor diameter dmin mm 13.94
17 Recommended conductor diameter considering allowance for corrosion dc mm 16.27
18 Actual diameter of conductor chosen d mm 25

STEP 3
TOUCH & STEP CRITERIA
19 Surface layer thickness hs m 0.15
20 Duration of shock for determining allowable body current ts m 1
21 Surface layer resistivity Us :m 4000
22 Reflection Factor K 0.975
23 Surface layer derating factor Cs - 0.772
24 Tolerable step voltage for body weight of 50 kg Estep50 V 2265.25
25 Tolerable step voltage for body weight of 70 kg Estep70 V 3065.90
26 Tolerable touch voltage for body weight of 50 kg Etouch50 V 653.31
27 Tolerable touch voltage for body weight of 70 kg Etouch70 V 884.22
28 Metal-to-metal touch voltage for body weight of 50 kg Emm-touch50 V 116.00
29 Metal-to-metal touch voltage for body weight of 70 kg Emm-touch70 V 157.00

STEP 4
INITIAL DESIGN
30 No. of parallel conductors in N alignment in Rectangle-1 - 7
31 No. of parallel conductors in E alignment in Rectangle-1 - 11
32 No. of parallel conductors in N alignment in Rectangle-2 - 4
33 No. of parallel conductors in E alignment in Rectangle-2 - 8
34 Spacing between parallel conductors in N alignment direction D m 2.00
35 Spacing between parallel conductors in E alignment direction D m 2.00
36 Number of ground rods nR m 20
37 Length of each ground rod Lr m 6
38 Depth of burial of ground grid conductors h m 0.5
39 Total lenth of ground rod LR m 120
40 Total length of grid conductors Lc m 376
41 Total effective length of grounding system conductors LT m 496
STEP 5
GRID RESISTANCE
42 Resistance of grounding system Rg : 1.274

STEP 6 AND 7
GRID CURRENT & GPR
43 Fault Current Division Factor Sf 0.5
44 Decrement factor Df 1
45 Maximum grid current IG A 3525
46 Ground Potential Rise GPR V 4490.85
47 GPR (I G xR g ) < E touch50 ? NO
48 GPR (I G xR g ) < E touch70 ? NO

STEP 8
MESH & STEP VOLTAGES
49 Corrective weighting factor Kii 1
50 Corrective weighting factor Kh 1.2247
51 Grid reference depth h0 m 1
52 Max length in horizontal direction Lx m 20
53 Max length in vertical direction Ly m 18
54 Peripheral length of the grid Lp m 76
55 Geometric factor na 9.895
56 Geometric factor nb 1.027
57 Geometric factor nc 1.069
58 Geometric factor nd 1.000
59 Geometric factor composed of na, nb, nc & nd n 10.864
60 Diameter of the conductor d m 0.025
61 Spacing factor for mesh voltage Km 0.3043
62 Correction factor for grid geometry (Irregularity factor) Ki 2.2518
63 Effective length for mesh voltage Lm m 594.65
64 Actual mesh voltage Em V 203.10
65 Maximum mesh voltage for GIS for body weight of 50 kg Em50-GIS V 233.89
66 Maximum mesh voltage for GIS for body weight of 70 kg Em70-GIS V 256.70
67 Spacing factor for step voltage Ks 0.6044
68 Effective length for step voltage Ls m 384
69 Actual step voltage Es V 624.67

STEP 9
70 E m < E touch50 ? YES
71 E m < E touch70 ? YES
72 E m50-GIS < E touch50 ? YES
73 E m70-GIS < E touch70 ? YES

STEP 10
74 E s < E step50 ? YES
75 E s < E step70 ? YES