Vk3521 Quick Response Pendent Sprinkler (K8.0) : Technical Data
Vk3521 Quick Response Pendent Sprinkler (K8.0) : Technical Data
1. DESCRIPTION
The Viking VK3521 Quick Response Pendent Sprinkler is a small thermosensitive
glass bulb spray sprinkler available with various finishes and temperature ratings
to meet design requirements. The special Polyester and Electroless Nickel PTFE
(ENT) coatings can be used in decorative applications where colors are desired.
In addition, these coatings have been investigated for installation in corrosive
environments and are Listed and Approved as indicated in the Approval Chart.
2. LISTINGS AND APPROVALS
5. OPERATION
During fire conditions, when the temperature around the sprinkler reaches its operating temperature, the heat-sensitive liquid in the
glass bulb expands, causing the bulb to shatter, releasing the pip cap assembly. Water flowing through the sprinkler orifice strikes
the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking Sprinkler Model VK3521 is available through a network of domestic and international distributors. See The Viking Corporation
web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
Form No. F_021316 20.11.17 Rev 20.2 Replaces Form No. F_021316 Rev 20.1
(Added max torque spec.)
Page 2 of 5
6. The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart. These tests cannot and
do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed
environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway.
3/4” NPT
20 mm BSPT 2”
(51 mm)
APPROVAL CHART
Viking Quick Response Pendent Sprinkler
VK3521 K8.0 (115 metric)
Maximum 175 PSI (12 Bar) WWP
Thread Size Listings and Approvals2
Sprinkler Base
Part Number1 NPT BSPT
UL FM
Inch mm
19925 3/4 -- A1, B2X, B3Y A1, B2X, B3Y
19937 -- 20 A1, B2X, B3Y A1, B2X, B3Y
Approved Temperature Rating Codes:
A = 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141 °C)
B = 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)
Approved Finish Codes:
1 = Brass, Chrome, White Polyester 3,4
, Black Polyester 3,4, and ENT 4,5
2 = Brass, Chrome, White Polyester 3,4
, and Black Polyester 3,4
3 = ENT 4,5
Approved Escutcheon Codes:
X = Installed with Viking Recessed Escutcheons Models NP-1, NP-2, and NP-3, or Viking Standard Surface Mounted
Escutcheons
Y = Installed with Viking Model NP-1 Recessed Escutcheon OR Standard Surface Mounted Escutcheons
Footnotes
1 Base Part number is shown. For complete part number, refer to Viking’s current price schedule.
2 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
3 Other colors are available upon request with the same Listings and Approvals as the standard colors.
4 cULus Listed as corrosion resistant.
5 FM Approved as corrosion resistant.
DESIGN CRITERIA - UL
DESIGN CRITERIA - FM
FM Approval Requirements:
The Viking VK3521 Quick Response Pendent Sprinkler is FM Approved as quick response Non-Storage Pendent sprinkler as
indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss
Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not
limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable
spacing, and deflector distance below the ceiling.
NOTE: The FM Installation guidelines may differ from UL and/or NFPA criteria.
IMPORTANT: Always refer to Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 for
general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest
edition of Viking Technical Data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and
also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
1. Install the escutcheon inner ring 2. Carefully slide the wrench** sideways 3. Install the sprinkler and escutcheon
onto the sprinkler threads. around the protective cap then push assembly into the pipe fitting. Be sure
upwards to engage with the sprinkler the escutcheon outer ring contacts
wrench flats. the surface of the finished ceiling.
1. Install the escutcheon inner ring 2. Carefully slide the wrench sideways
onto the sprinkler threads. around the protective cap then
push upwards to engage with the
sprinkler wrench flats.
1. Install the escutcheon onto the 2. Carefully slide the wrench** sideways 3. Install the sprinkler and escutcheon
sprinkler threads. around the protective cap then push assembly into the pipe fitting. Be sure
upwards to engage with the sprinkler the escutcheon contacts the surface
wrench flats. of the finished ceiling.
1-7/16”
(37 mm)
Form No. F_021316 20.11.17 Rev 20.2 Replaces Form No. F_021316 Rev 20.1
(Added max torque spec.)