Vk3521 Quick Response Pendent Sprinkler (K8.0) : Technical Data

This document provides technical data on the Viking VK3521 Quick Response Pendent Sprinkler, including: 1. A description of the sprinkler, its finishes, temperature ratings, and approvals. 2. Specifications for the sprinkler including operating pressure, water pressure rating, thread size, K-factor, and materials. 3. Instructions for installation, operation, inspection, testing and maintenance. 4. Information on ordering, including part numbers for different finishes and temperature ratings. Accessories like wrenches and sprinkler cabinets are also listed.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
100 views

Vk3521 Quick Response Pendent Sprinkler (K8.0) : Technical Data

This document provides technical data on the Viking VK3521 Quick Response Pendent Sprinkler, including: 1. A description of the sprinkler, its finishes, temperature ratings, and approvals. 2. Specifications for the sprinkler including operating pressure, water pressure rating, thread size, K-factor, and materials. 3. Instructions for installation, operation, inspection, testing and maintenance. 4. Information on ordering, including part numbers for different finishes and temperature ratings. Accessories like wrenches and sprinkler cabinets are also listed.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Page 1 of 5

VK3521 QUICK RESPONSE


TECHNICAL DATA PENDENT SPRINKLER (K8.0)

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

1. DESCRIPTION
The Viking VK3521 Quick Response Pendent Sprinkler is a small thermosensitive
glass bulb spray sprinkler available with various finishes and temperature ratings
to meet design requirements. The special Polyester and Electroless Nickel PTFE
(ENT) coatings can be used in decorative applications where colors are desired.
In addition, these coatings have been investigated for installation in corrosive
environments and are Listed and Approved as indicated in the Approval Chart.
2. LISTINGS AND APPROVALS

UL Listed: Category VNIV

FM Approved: Class 2001, 2015, 2043


Approved for use in FM Approved vacuum dry sprinkler sytems
with a maximum supervisory vacuum pressure of -3psi (-207mbar)
Refer to the Approval Chart and Design Criteria for requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Minimum Operating Pressure: 7 psi (0.5 bar)
Rated to: 175 psi (12 bar) water working pressure.
Factory tested hydrostatically to 500 psi (34.5 bar).
Thread size: 3/4” NPT (20 mm BSPT)
Nominal K-factor: 8.0 U.S. (115 metric*) 
Glass-bulb fluid temperature rated to -65 °F (-55 °C)
* Metric K-factor measurement shown is in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Material Standards:
Sprinkler Body: Brass CW602N, UNS-C84400 or QM Brass
Deflector: Stainless Steel UNS S30400
Pip Cap Shell - Stainless Steel UNS-S44400
Pip Cap Disc - Stainless Steel UNS-S30100
Belleville Spring - Nickel Alloy
Pip Cap Seal - Polytetrafluoroethylene (PTFE)
Compression Screw: Brass CW612N, CW508L, UNS-C36000 or UNS-C26000
Shipping Cap: Polyethylene
Bulb: Glass, nominal 3 mm diameter
Ordering Information: (Refer to Table 1 and the current Viking List Price Book.)
4. INSTALLATION
Refer to appropriate NFPA, FM Global, and/or any other applicable installation standards.

NOTICE Risk of permanent damage.


Over-tightening the sprinkler can cause permanent damage.
> Tighten the sprinkler to a MAXIMUM torque of 20 ft-lbs. (27.1 N-m).

5. OPERATION
During fire conditions, when the temperature around the sprinkler reaches its operating temperature, the heat-sensitive liquid in the
glass bulb expands, causing the bulb to shatter, releasing the pip cap assembly. Water flowing through the sprinkler orifice strikes
the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking Sprinkler Model VK3521 is available through a network of domestic and international distributors. See The Viking Corporation
web site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
Form No. F_021316 20.11.17 Rev 20.2 Replaces Form No. F_021316 Rev 20.1
(Added max torque spec.)
Page 2 of 5

VK3521 QUICK RESPONSE


TECHNICAL DATA PENDENT SPRINKLER (K8.0)

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

TABLE 1: ORDERING INFORMATION


Instructions: Using the sprinkler base part number,
(1) add the suffix for the desired Finish
(2) add the suffix for the desired Temperature Rating.
Size 1: Finishes 2: Temperature Ratings
Sprinkler
Base Part NPT BSPT Max. Ambient Ceiling
No. Description Suffix1 Nominal Rating Bulb Color Suffix
Inch mm Temperature3
19925 3/4 -- Brass A
135 °F (57 °C) Orange 100 °F (38 °C) A
19937 -- 20 Chrome F
155 °F (68 °C) Red 100 °F (38 °C) B
White Polyester 4,6 M-/W
175 °F (79 °C) Yellow 150 °F (65 °C) D
Black Polyester 4,6 M-/B
200 °F (93 °C) Green 150 °F (65 °C) E
ENT 4,5,6 JN
286 °F (141 °C) Blue 225 °F (107 °C) G
Open -- -- Z
Example: 19925MB/W = VK3521 with White Polyester Finish and 155 °F (68 °C) Nominal temperature rating. This sprinkler is to be
installed into an area with a maximum ambient temperature of 100 °F (38 °C) meaning if the area will experience temperatures above
the maximum ambient rating, you shall use a higher temperature-rated sprinkler.
Accessories
Sprinkler Wrenches (see Figure 1):
A. Installer Wrench: Part No. 22055 (available since 2017).
B. Cabinet Wrench: Part No. 20901M/B (available since 2017).
C. Recessed Socket Wrench: Part No. 20951M/B2 (available since 2017).
D. Straight Wrench: Part No. 22940MB
Sprinkler Cabinet:
A. Up to 6 sprinklers: Part number 01724A (available since 1971).
B. 6-12 Sprinklers: Part number 01725A (available since 1971).
Footnotes
1. Where a dash (-) is shown in the Finish suffix designation, insert the desired Temperature Rating suffix. See example above.
2. Requires a 1/2” ratchet which is not available from Viking.
3. Based on NFPA 13, NFPA 13R, and NFPA 13D. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having
Jurisdiction. Refer to specific installation standards.
4. UL Listed as corrosion resistant.

5. FM Approved as corrosion resistant.

6. The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart. These tests cannot and
do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed
environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway.

7/16” (11 mm)


A B C D Nominal Pipe
Engagement

3/4” NPT
20 mm BSPT 2”
(51 mm)

Figure 1: Sprinkler Wrenches Figure 2: Sprinkler Dimensions

Form No. F_021316 20.11.17 Rev 20.2


Page 3 of 5

VK3521 QUICK RESPONSE


TECHNICAL DATA PENDENT SPRINKLER (K8.0)

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

APPROVAL CHART
Viking Quick Response Pendent Sprinkler
VK3521 K8.0 (115 metric)
Maximum 175 PSI (12 Bar) WWP
Thread Size Listings and Approvals2
Sprinkler Base
Part Number1 NPT BSPT
UL FM
Inch mm
19925 3/4 -- A1, B2X, B3Y A1, B2X, B3Y
19937 -- 20 A1, B2X, B3Y A1, B2X, B3Y
Approved Temperature Rating Codes:
A = 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141 °C)
B = 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)
Approved Finish Codes:
1 = Brass, Chrome, White Polyester 3,4
, Black Polyester 3,4, and ENT 4,5
2 = Brass, Chrome, White Polyester 3,4
, and Black Polyester 3,4
3 = ENT 4,5
Approved Escutcheon Codes:
X = Installed with Viking Recessed Escutcheons Models NP-1, NP-2, and NP-3, or Viking Standard Surface Mounted
Escutcheons
Y = Installed with Viking Model NP-1 Recessed Escutcheon OR Standard Surface Mounted Escutcheons
Footnotes
1 Base Part number is shown. For complete part number, refer to Viking’s current price schedule.
2 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
3 Other colors are available upon request with the same Listings and Approvals as the standard colors.
4 cULus Listed as corrosion resistant.
5 FM Approved as corrosion resistant.

DESIGN CRITERIA - UL

cULus Listing Requirements:


The Viking VK3521 Quick Response Pendent Sprinkler is cULus Listed as indicated in Approval Chart for installation in accordance
with the latest edition of NFPA 13 for standard spray sprinklers.
• Designed for use in Light and Ordinary occupancies.
• The sprinkler installation rules contained in NFPA 13 for standard spray Pendent sprinklers shall be followed.
IMPORTANT: Always refer to Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 for
general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest
edition of Viking Technical Data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and
also with the provisions of governmental codes, ordinances, and standards, whenever applicable.

DESIGN CRITERIA - FM

FM Approval Requirements:
The Viking VK3521 Quick Response Pendent Sprinkler is FM Approved as quick response Non-Storage Pendent sprinkler as
indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss
Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not
limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable
spacing, and deflector distance below the ceiling.
NOTE: The FM Installation guidelines may differ from UL and/or NFPA criteria.
IMPORTANT: Always refer to Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 for
general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest
edition of Viking Technical Data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and
also with the provisions of governmental codes, ordinances, and standards, whenever applicable.

Form No. F_021316 20.11.17 Rev 20.2


Page 4 of 5

VK3521 QUICK RESPONSE


TECHNICAL DATA PENDENT SPRINKLER (K8.0)

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

1. Install the escutcheon inner ring 2. Carefully slide the wrench** sideways 3. Install the sprinkler and escutcheon
onto the sprinkler threads. around the protective cap then push assembly into the pipe fitting. Be sure
upwards to engage with the sprinkler the escutcheon outer ring contacts
wrench flats. the surface of the finished ceiling.

Figure 3: Recessed Installation (with Recessed Socket Wrench)


**A 1/2” ratchet is required (not available from Viking).

1. Install the escutcheon inner ring 2. Carefully slide the wrench sideways
onto the sprinkler threads. around the protective cap then
push upwards to engage with the
sprinkler wrench flats.

3. Install the sprinkler and


escutcheon assembly into the pipe
fitting. Be sure the escutcheon
outer ring contacts the surface of
the finished ceiling.

Figure 4: Recessed Installation (with standard Installer’s Wrench)

Form No. F_021316 20.11.17 Rev 20.2


Page 5 of 5

VK3521 QUICK RESPONSE


TECHNICAL DATA PENDENT SPRINKLER (K8.0)

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058


Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

1. Install the escutcheon onto the 2. Carefully slide the wrench** sideways 3. Install the sprinkler and escutcheon
sprinkler threads. around the protective cap then push assembly into the pipe fitting. Be sure
upwards to engage with the sprinkler the escutcheon contacts the surface
wrench flats. of the finished ceiling.

Figure 5: Installation (with Straight Wrench)

2-1/8” (54 mm) 2-1/8” (54 mm)

Model NP-2 or NP-3


Model NP-1 Recessed Thread-On Recessed
Escutcheon Ceiling opening size: Escutcheon
Minimum: 2-5/16” (59 mm) (NP-3 Outer ring has a
Maximum: 2-1/2” (64 mm) larger diameter)

Min. 13/16” Min. 15/16”


(21 mm) (24 mm)
Max. 1-7/16” Max. 1-3/4”
(37 mm) (44 mm)

Ceiling opening size:


Minimum: 2-5/16” (59 mm)
Maximum: 2-1/2” (64 mm)

1-7/16”
(37 mm)

Standard Surface-Mounted Escutcheon


Figure 6: Installation Dimensions with Viking Escutcheons

Form No. F_021316 20.11.17 Rev 20.2 Replaces Form No. F_021316 Rev 20.1