The document provides product details for an AF40-30-11-13 100-250V50/60HZ-DC contactor. It is a 3 pole contactor that can control motors up to 18.5 kW at 400V AC or 30 hp at 480V, and switch power circuits up to 70A at 690V AC. It has a wide control voltage range of 100-250V at 50/60Hz or DC. The contactor has compact dimensions of 67mm width, 111mm depth and 125.5mm height.

Uploaded by

Mohammad Serour
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
177 views5 pages

1SBL347001R1311 Af40 30 11 13 100 250v50 60hz DC Contactor

The document provides product details for an AF40-30-11-13 100-250V50/60HZ-DC contactor. It is a 3 pole contactor that can control motors up to 18.5 kW at 400V AC or 30 hp at 480V, and switch power circuits up to 70A at 690V AC. It has a wide control voltage range of 100-250V at 50/60Hz or DC. The contactor has compact dimensions of 67mm width, 111mm depth and 125.5mm height.

Uploaded by

Mohammad Serour
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

PRODUCT-DETAILS

AF40-30-11-13
AF40-30-11-13 100-250V50/60HZ-DC
Contactor

General Information
Extended Product Type AF40-30-11-13
Product ID 1SBL347001R1311
EAN 3471523132139
Catalog Description AF40-30-11-13 100-250V50/60HZ-DC Contactor
The AF40-30-11-13 is a 3 pole - 690 V IEC or 600 UL contactor with pre-mounted
auxiliary contacts and screw terminals, controlling motors up to 18.5 kW / 400 V AC
(AC-3) or 30 hp / 480 V UL and switching power circuits up to 70 A (AC-1) or 60 A UL
general use. Thanks to the AF technology, the contactor has a wide control voltage
Long Description range (100-250 V 50/60 Hz and DC), managing large control voltage variations,
reducing panel energy consumptions and ensuring distinct operations in unstable
networks. Furthermore, surge protection is built-in, offering a compact solution. AF
contactors have a block type design, can be easily extended with add-on auxiliary
contact blocks and an additional wide range of accessories.

Ordering
Minimum Order Quantity 1 piece
Customs Tariff Number 85364900

Popular Downloads
Instructions and 1SBC101036M6801
Manuals
AF40-30-11-13 2

Dimensions
Product Net Width 67 mm
Product Net Depth / 111 mm
Length
Product Net Height 125.5 mm
Product Net Weight 0.99 kg

Technical
Number of Main 3
Contacts NO
Number of Main 0
Contacts NC
Number of Auxiliary 1
Contacts NO
Number of Auxiliary 1
Contacts NC
Rated Operational Auxiliary Circuit 690 V
Voltage Main Circuit 690 V
Rated Frequency (f) Auxiliary Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Conventional Free-air acc. to IEC 60947-4-1, Open Contactors q = 40 °C 105 A
Thermal Current (I th ) acc. to IEC 60947-5-1, q = 40 °C 16 A
Rated Operational (690 V) 40 °C 70
Current AC-1 (I e ) (690 V) 60 °C 60 A
(690 V) 70 °C 50
Rated Operational (415 V) 60 °C 40 A
Current AC-3 (I e ) (440 V) 60 °C 40 A
(500 V) 60 °C 35 A
(690 V) 60 °C 25 A
(380 / 400 V) 60 °C 40 A
(220 / 230 / 240 V) 60 °C 40 A
Rated Operational Power (400 V) 18.5 kW
AC-3 (P e ) (415 V) 22 kW
(440 V) 22 kW
(500 V) 22 kW
(690 V) 22 kW
(380 / 400 V) 18.5 kW
(220 / 230 / 240 V) 11 kW
Rated Operational (500 V) 2 A
Current AC-15 (I e ) (690 V) 2 A
(24 / 127 V) 6 A
(220 / 240 V) 4 A
(400 / 440 V) 3 A
Rated Short-time at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A
Withstand Current (I cw ) at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
for 0.1 s 140 A
for 1 s 100 A
Maximum Breaking cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A
Capacity cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Maximum Electrical (AC-1) 600 cycles per hour
Switching Frequency (AC-15) 1200 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 1200 cycles per hour
(DC-13) 900 cycles per hour
Rated Operational (24 V) 6 A / 144 W
Current DC-13 (I e ) (48 V) 2.8 A / 134 W
(72 V) 1 A / 72 W
(110 V) 0.55 A / 60 W
(125 V) 0.55 A / 69 W
(220 V) 0.27 A / 60 W
(250 V) 0.27 A / 68 W
(400 V) 0.15 A / 60 W
(500 V) 0.13 A / 65 W
AF40-30-11-13 3

(600 V) 0.1 A / 60 W
Rated Insulation Voltage acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 V
(U i ) acc. to UL/CSA 600 V
Rated Impulse 6 kV
Withstand Voltage (U imp
)
Maximum Mechanical 3600 cycles per hour
Switching Frequency
Rated Control Circuit 50 Hz 100 ... 250 V
Voltage (U c ) 50 Hz / 60 Hz 100 ... 250 V
60 Hz 100 ... 250 V
DC Operation 100 ... 250 V
Operate Time Between Coil De-energization and NC Contact Closing 19 ... 105 ms
Between Coil De-energization and NO Contact Opening 17 ... 100 ms
Between Coil Energization and NC Contact Opening 38 ... 95 ms
Between Coil Energization and NO Contact Closing 42 ... 100 ms
Connecting Capacity Flexible with Ferrule 1/2x 4 ... 35 mm²
Main Circuit Flexible with Insulated Ferrule 1/2x 4 ... 35 mm²
Rigid 1/2x 6 ... 3 5 mm²
Connecting Capacity Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Auxiliary Circuit Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 2.5 mm²
Connecting Capacity Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Control Circuit Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid 1/2x 1 ... 2.5 mm²
Wire Stripping Length Main Circuit 16 mm
Degree of Protection acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Terminal Type Screw Terminals

Technical UL/CSA
General Use Rating (600 V AC) 60 A
UL/CSA
Horsepower Rating (120 V AC) Single Phase 3 hp
UL/CSA (200 ... 208 V AC) Three Phase 10 hp
(220 ... 240 V AC) Three Phase 15 hp
(240 V AC) Single Phase 7-1/2 hp
(440 ... 480 V AC) Three Phase 30 hp
(550 ... 600 V AC) Three Phase 40 hp
Tightening Torque Auxiliary Circuit 11 IA
UL/CSA Control Circuit 11 IA
Main Circuit 35 IA

Environmental
Ambient Air Close to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C
Temperature Close to Contactor without Thermal O/L Relay -40 ... +70 °C
Close to Contactor for Storage -60 ... +80 °C
Climatic Withstand Category B according to IEC 60947-1 Annex Q
Maximum Operating 3000 m
Altitude Permissible
Resistance to Vibrations 5 ... 300 Hz 3 g closed position / 3 g open position
acc. to IEC 60068-2-6
Resistance to Shock acc. Closed, Shock Direction: A 25 K40
to IEC 60068-2-27 Closed, Shock Direction: B1 25 K40
Closed, Shock Direction: B2 15 K40
Closed, Shock Direction: C1 25 K40
Closed, Shock Direction: C2 25 K40
Open, Shock Direction: B1 5 K40
RoHS Status Following EU Directive 2011/65/EU
AF40-30-11-13 4

Certificates and Declarations (Document Number)


ABS Certificate ABS_15-GE1349500-PDA_90682247
BV Certificate BV_2634H36994A
CB Certificate CB_SE-96554
CCC Certificate CCC_2012010304589737
CCC_2015010304824714
CQC Certificate CQC2015010304824714
CQC2012010304589737
Declaration of 2020980304001256
Conformity - CCC 2020980304001074
Declaration of 1SBD250000U1000
Conformity - CE
DNV Certificate DNV-GL_TAE00001AF-3
DNV GL Certificate DNV-GL_TAE00001AF-3
EAC Certificate EAC_RU_FRME77B03447
Environmental 1SBD250168E1000
Information
GL Certificate DNV-GL_TAE00001AF-3
Instructions and 1SBC101036M6801
Manuals
KC Certificate KC_HW02016-15006C
LR Certificate LRS_1300087E1
RINA Certificate RINA_ELE084013XG
RMRS Certificate RMRS_1802705280
RoHS Information 1SBD250000U1000
UL Certificate UL_20130926-E312527_14_1
UL Listing Card UL_E312527

Container Information
Package Level 1 Units box 1 piece
Package Level 1 Width 150 mm
Package Level 1 Depth / 150 mm
Length
Package Level 1 Height 97 mm
Package Level 1 Gross 1.09 kg
Weight
Package Level 1 EAN 3471523132139
Package Level 2 Units box 10 piece
Package Level 2 Width 250 mm
Package Level 2 Depth / 300 mm
Length
Package Level 2 Height 300 mm
Package Level 2 Gross 10.9 kg
Weight
Package Level 3 Units 240 piece

Classifications
Object Classification Q
Code
ETIM 4 EC000066 - Magnet contactor, AC-switching
ETIM 5 EC000066 - Magnet contactor, AC-switching
ETIM 6 EC000066 - Power contactor, AC switching
ETIM 7 EC000066 - Power contactor, AC switching
eClass V11.0 : 27371003
UNSPSC 39121529
E-Number (Finland) 3707004
AF40-30-11-13 5