Product Selection Guide: T2 Series-60 & 100 Amps

This document provides a product selection guide for Universal Electric Corporation's T2 Series track busway systems, which are available in 60-amp and 100-amp versions. It includes an overview of the busway components, such as straight sections, elbows, tees, crosses, and various feed units. Product numbers and specifications are listed for each component. The guide also covers support and connection hardware accessories, color options, and services available from Universal Electric.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
345 views46 pages

Product Selection Guide: T2 Series-60 & 100 Amps

This document provides a product selection guide for Universal Electric Corporation's T2 Series track busway systems, which are available in 60-amp and 100-amp versions. It includes an overview of the busway components, such as straight sections, elbows, tees, crosses, and various feed units. Product numbers and specifications are listed for each component. The guide also covers support and connection hardware accessories, color options, and services available from Universal Electric.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 46

Product Selection Guide:

T2 Series- 60 & 100 Amps


T2 Series

INTRODUCTION & SPECS


Specs Introduction
This specification covers the electrical Universal Electric Corporation (UEC) is the leader in electrical power distribution in
characteristics and general requirements for the mission critical, commercial and light industrial industries with STARLINE Track
a track busway system, hereafter referred Busway. This system was designed to meet the rugged specification of the UL857,
to as (Track Busway). The system shall be Busway and Associated Fittings, with the flexible features of track lighting - and is
designed primarily for overhead distribution available in systems with 60 or 100 amps with isolated ground.
of electrical power. Supporting designated
work areas and equipment. Once installed It is the simple, versatile, fast and economical solution for supplying power to electrical
the Busway will provide a simple, versatile, loads and is unique because the busway can be instantly tapped at any location, with
fast and economic means of distributing a variety of plug-in units.
power. Loads fed from a variety of plug-in
units can be easily added or removed without The Product Selection Guide was developed to help the design engineer understand
shutting power down to the busway. and consider all of the options available with STARLINE Track Busway when
designing a system.
The Track Busway shall be designed and
manufactured to the following standards: This guide is all-inclusive; however, UEC excels at collaborating with design engineers
to provide solutions for any application. If you have a need that is not found in this
1. Underwriters Laboratories Standard, UL guide, please contact us at 1-800-245-6378 or email us at [email protected]. We
857 – The common UL, CSA, and ANCE will be happy to answer your questions over the telephone or schedule a visit with one
Standard for Busways that is derived from of our local representatives.
the fifth edition of CSA Standard C22.2 No.
27, the twelfth edition of UL 857, and the Also, if viewing this guide in print, please keep in mind that this is a working document.
second edition of NMX-J-148-1998-ANCE. UEC reseves the right to change information and descriptions of listed services and
products. The latest version of this guide is available for download at
downloads.uecorp.com/starline/busway/.
*All standards and certifications available
upon request

2.1 | StarlinePower.com
T2 Series

TABLE OF CONTENTS
SYSTEM LAYOUT DRAWING............................................................................................................................................2.3
POLARITY TIPS......................................................................................................................................................................2.4
LAYOUT TIPS..........................................................................................................................................................................2.5
COMPONENT RELATIONSHIP TIPS.............................................................................................................................2.6

60T2 Systems
STRAIGHT SECTIONS........................................................................................................................................................2.7
STRAIGHT SECTIONS: PRODUCT NUMBERS............................................................................................................2.8
ELBOW SECTIONS.............................................................................................................................................................2.9
ELBOW SECTIONS: PRODUCT NUMBERS..............................................................................................................2.10
TEE SECTIONS...................................................................................................................................................................2.11
TEE SECTIONS: PRODUCT NUMBERS....................................................................................................................2.12
CROSS SECTIONS...........................................................................................................................................................2.13
CROSS SECTIONS: PRODUCT NUMBERS.............................................................................................................2.14
END FEED UNITS...............................................................................................................................................................2.15
END FEED UNITS: PRODUCT NUMBERS.................................................................................................................2.16
ABOVE FEED UNITS.........................................................................................................................................................2.17
ABOVE FEED UNITS: PRODUCT NUMBERS.............................................................................................................2.18
END FEED CONNECTOR UNITS...................................................................................................................................2.19
END FEED CONNECTOR UNITS: PRODUCT NUMBERS.........................................................................................2.20
BELOW FEED UNITS........................................................................................................................................................2.21
BELOW FEED UNITS: PRODUCT NUMBERS............................................................................................................2.22
PENDANT FEED UNITS....................................................................................................................................................2.23
PENDANT FEED UNITS: PRODUCT NUMBERS........................................................................................................2.24

100T2 Systems
STRAIGHT SECTIONS.....................................................................................................................................................2.25
STRAIGHT SECTIONS: PRODUCT NUMBERS..........................................................................................................2.26
ELBOW SECTIONS...........................................................................................................................................................2.27
ELBOW SECTIONS: PRODUCT NUMBERS..............................................................................................................2.28
TEE SECTIONS...................................................................................................................................................................2.29
TEE SECTIONS: PRODUCT NUMBERS.....................................................................................................................2.30
CROSS SECTIONS...........................................................................................................................................................2.31
CROSS SECTIONS: PRODUCT NUMBERS.............................................................................................................2.32
END FEED UNITS...............................................................................................................................................................2.33
END FEED UNITS: PRODUCT NUMBERS.................................................................................................................2.34
ABOVE FEED UNITS.........................................................................................................................................................2.35
ABOVE FEED UNITS: PRODUCT NUMBERS.............................................................................................................2.36
BELOW FEED UNITS........................................................................................................................................................2.37
BELOW FEED UNITS: PRODUCT NUMBERS............................................................................................................2.38

RAL Colors............................................................................................................................................................................2.39
ACCESSORIES: SUPPORT HARDWARE..................................................................................................................2.40
ACCESSORIES: SUPPORT HARDWARE..................................................................................................................2.41
ACCESSORIES: CONNECTION HARDWARE.........................................................................................................2.42

SERVICES............................................................................................................................................................................2.43

2.2 | StarlinePower.com
T2 Series

SYSTEM LAYOUT DRAWING

End Cap

Connection Hardware

Straight Section

Tee

End Feed Unit Elbow

Plug-In Unit example:

For further information on plug-in


unit options, please visit the Plug-
In Units section

2.3 | StarlinePower.com
T2 Series

POLARITY TIPS

STARLINE utilizes a unique polarizing


method to prevent mismatched
components from being inadvertently
connected to each other. The system
is designed to prevent cross phasing
during installation.
Outlet boxes face this
It is particularly important to direction; away from the
understand this design concept polarizing stripe
prior to ordering and/or installing
some components.

For example, if the face direction of a Polarizing stripe


STARLINE plug-in unit is important in
your installation consider that they will
always face the conductor side.
Polarizing Stripe =
Plug-In Unit Front-Facing Direction =

End Cap

External-Left External Elbow


Tee Connector
(EL)

Internal-Right
Tee
(IR)

Internal Elbow
Connector

End
Cap End
Cap

2.4 | StarlinePower.com
T2 Series

SYSTEM LAYOUT TIPS

Power Feeds Busway Housing Sections


Determine location of power feeds Standard Busway lengths are available in 20, 10 and 5-foot increments. Although the
based on relation to power source, factory can cut individual STARLINE Track Busway sections to any length under 20
existing feeders and voltage drop feet, it is highly recommended to keep all layout runs in increments of 5 feet to simplify
concerns for longer runs. layout and installation. Custom lengths can be made but can increase lead time and
make layout and installation a bit more complex.
Support Hardware
Support hardware is spaced no more Busway Tees and Elbows Sections
than 10 ft apart. Refer to page 2.42 for Try to keep all runs as straight as possible as tees and elbows are added cost. Pay
support hardware details. Contact your close attention to polarity on the elbows. The polarity will need to match the adjacent
local Starline applications engineer for busway section(s) to be compatible.
any questions.
Length of Busway for a One Volt Drop in Line to Line Voltage:
Installation
Printed installation drawings are
supplied with each system shipment SYSTEM DISTRIBUTED VOLTAGE VOLTAGE
and they are also available for download DESIGNATION LOAD DROP @ 0.8 PF DROP @ 0.8 PF
online at http://downloads.uecorp.com/ Single Phase Three Phase
starline/busway/. CAD files of these 60T2 (standard) 60 amps 29 Ft. 51 Ft.
drawings are also available by contacting
your local Starline applications engineer. 100T2 (standard) 100 amps 42 Ft. 72 Ft.

2.5 | StarlinePower.com
T2 Series

COMPONENT RELATIONSHIP TIPS

When ordering material, it is important to understand the relationship between various


components.

Examples:

• No need to add extra Joint Kits for Elbows, Tees, or Crosses, as they are already
part of your housing count.

• If using an Above Feed, order a Joint Kit for each Feed.

• General support hardware rule to follow:

10 ft maximum spacing between supports and we recommend 10% more than the
required quantity to cover potential layout changes.

• Total Power Feeds and End Caps can be determined by counting the total number
of unconnected runs.

• Before specifying or ordering elbow or tee connectors, it is important to


understand polarity and the relationship to direction of outlets. Please refer to
pg. 2.4 Polarity Tips for more detail.

2.6 | StarlinePower.com
60T2 System

STRAIGHT SECTIONS
Product Description
Track Busway straight sections consist of
an extruded aluminum shell with insulated
copper conductor strips mounted on the two
opposite interior side walls. The aluminum
housing acts as a 100% ground path and
each straight has an open access slot over
its entire length for the insertion of turn-n-
lock plug-in units. The housing configuration
is 4 pole in a 300 Volt design. Track Busway
housing is connected together using in-line
connectors and housing couplers (found
L1 = Blue
under Accessories).
L2 = Black
L3 = Red
N = white or beige

MATERIAL: Extruded Aluminum

RATINGS: 100% Ground Path


1.79”
U.S: 60 Amp, 300 Volt

LENGTH: 5 Ft, 10 Ft, 20 Ft.;


or custom lengths between
2 - 20 Ft.
(N) (L2)
VOLTAGE DROP: distributed load
Single Phase 29 ft. (.8PF) 2.58”
(L1) (L3)
Three Phase 51 ft. (.8PF)

WEIGHT:
10 ft. 4 pole: 12.5 lbs
Four Pole

Housing Coupler:
placed over top of
connector to make a
mechanical connection

In-Line Connector:
placed in between
two pieces of busway
to make an electrical
connection

2.7 | StarlinePower.com
60T2 System

STRAIGHT SECTIONS: PRODUCT NUMBERS

U S 060 T2 C 4 S - 0200 C
1. 2. 3. 4. 5. 6. 7. 8. 9.
System Product Product Compat- Material Neutral/ Polarization Straight Busway
Type Frame ibility Ground Length Access
busbar

- STD0 **RAL (please see page 2.39)


10.
Paint
color

1. System (standard of measure) 10. Paint Color (allows painting of the busway housing)
U U.S. STD0 UEC Mill Finish RED0 Paint UEC Red
BLK0 Paint UEC Black BLU0 Paint UEC Blue
WHT0 Paint UEC White
2. Product Type (section component)
S Straight section

3. Product Frame (maximum amperage)


060 60 amps

4. Compatibility (frame compatibility)


T2 T2 systems

5. Material (busbar material)


C Copper

6. Neutral/Ground Busbar (size of neutral busbar and/or ground)


4 3 Phase plus Neutral

7. Polarization (orientation of section for mating purposes)


S Standard

8. Straight Length (length of section)


XXYY XX = feet, YY = inches

9. Busway Access (how plugs access the busway)


C Continuous

Examples:

US060T2C4S-1000C-STD0 = US, Straight section, 60 amps, T2, Copper conductor, 3 Phase plus neutral, Standard polarization- 10ft., Continuous access- standard mill
finish
US060T2C4S-0500C-P010 = US, Straight section, 60 amps, T2, Copper conductor, 3 phase plus neutral, Standard polarization- 5ft., Continuous
access- RAL 1001

2.8 | StarlinePower.com
60T2 System

ELBOW SECTIONS
Product Description
Elbow connectors are used for making a 90
degree turn in a 60 amp Busway run. Please
be aware of polarization issues before making
your final selection (refer to pg. 2.4 Polarity
Tips).

Elbows are electrically connected to sections


of 60 amp Busway by means of an in-line
connector. The connector is installed by
inserting in each end of the housing sections
to be joined. Hex head compression screws
are tightened to make a reliable connection.
Elbow connectors are polarized to prevent
phase mismatch. Elbow Connector

WEIGHT: .5 lbs

= Polarizing Stripe

Internal Elbow External Elbow

2.9 | StarlinePower.com
60T2 System

ELBOW SECTIONS: PRODUCT NUMBERS

U E 060 T2 C 4 S - IN
1. 2. 3. 4. 5. 6. 7. 8.
System Product Product Compat- Material Neutral/ Polarization Turning
Type Frame ibility Ground Direction
busbar

- STD0 **RAL (please see page 2.39)


9.
Paint
color

1. System (standard of measure) 9. Paint Color (allows painting of the busway housing)
U U.S. STD0 UEC Mill Finish RED0 Paint UEC Red
BLK0 Paint UEC Black BLU0 Paint UEC Blue
WHT0 Paint UEC White
2. Product Type (section component)
E Elbow section
**RAL system can also be used; reference page 2.39
3. Product Frame (maximum amperage)
060 60 amps

4. Compatibility (frame compatibility)


T2 T2 systems

5. Material (busbar material)


C Copper

6. Neutral/Ground Busbar (size of neutral busbar and/or ground)


4 3 Phase plus Neutral

7. Polarization (orientation of section for mating purposes)


S Standard

8. Turning Direction (direction of section polarizing stripe)


IN Internal EX External

Examples:

UE060T2C4S-IN-BLK0 = US, Elbow section, 60 amps, T2, Copper conductor, 3 Phase plus neutral, Standard polarization- Internal- painted black
UE060T2C4S-EX-STD0 = US, Elbow section, 60 amps, T2, Copper conductor, 3 phase plus neutral, Standard polarization- External- standard mill finish

2.10 | StarlinePower.com
60T2 System

TEE SECTIONS
Product Description
Similar to elbow connectors, tee connectors
are used for connecting branch housing
sections at 90 degrees to the main run.
Please be aware of polarization issues before
making your final selection (refer to pg. 2.4
Polarity Tips).

Tees are electrically connected to sections


of 60 amp Busway by means of an in-line
connector. The connector is installed by
inserting in each end of the housing sections
to be joined. Hex head compression screws In-line Connector = Polarizing Stripe
are tightened to make a reliable connection.
All in-line connectors are polarized to prevent
phase mismatch.

WEIGHT: 1 lb

External-Left External-Right
(EL) (ER)

Internal-Left Internal-Right
(IL) (IR)

2.11 | StarlinePower.com
60T2 Systems

TEE SECTIONS: PRODUCT NUMBERS

U T 060 T2 C 4 S - IR
1. 2. 3. 4. 5. 6. 7. 8.
System Product Product Compat- Material Neutral/ Polarization Turning
Type Frame ibility Ground Direction
busbar

- STD0 **RAL (please see page 2.39)


9.
Paint
color

1. System (standard of measure) 9. Paint Color (allows painting of the busway housing)
U U.S. STD0 UEC Mill Finish RED0 Paint UEC Red
BLK0 Paint UEC Black BLU0 Paint UEC Blue
WHT0 Paint UEC White
2. Product Type (section component)
T Tee section
**RAL system can also be used; reference page 2.39
3. Product Frame (maximum amperage)
060 60 amps

4. Compatibility (frame compatibility)


T2 T2 systems

5. Material (busbar material)


C Copper

6. Neutral/Ground Busbar (size of neutral busbar and/or ground)


4 3 Phase plus Neutral

7. Polarization (orientation of section for mating purposes)


S Standard R Reversed

8. Turning Direction (direction of section polarizing stripe)


IL Internal-Left EL External-Left
IR Internal-Right ER External-Right

Examples:

UT060T2C4S-IR-RED0 = US, Tee section, 60 amps, T2, Copper conductor, 3 phase plus neutral, Standard polarization- Internal-Right- painted red
UT060T2C4S-EL-STD0 = US, Tee section, 60 amps, T2, Copper conductor, 3 phase plus neutral, Standard polarization- External-Left- standard mill finish

2.12 | StarlinePower.com
60T2 System

CROSS SECTIONS
Product Description
Similar to tee connectors, crosses are
typically used for grid designs. Please be
aware of polarization issues before making
your final selection (refer to pg. 2.4 Polarity
Tips).

Crosses are electrically connected to


sections of 60 amp Busway by means
of an in-line connector. The connector is
installed by inserting in each end of the
housing sections to be joined. Hex head
compression screws are tightened to make a
reliable connection. All in-line connectors are
polarized to prevent phase mismatch.
Standard cross

= Polarizing Stripe

In-line Connector

2.13 | StarlinePower.com
60T2 Systems

CROSS SECTIONS: PRODUCT NUMBERS

U X 060 T2 C 4 S - ST
1. 2. 3. 4. 5. 6. 7. 8.
System Product Product Compat- Material Neutral/ Polarization Turning
Type Frame ibility Ground Direction
busbar

- STD0 **RAL (please see page 2.39)


9.
Paint
Color

1. System (standard of measure) 9. Paint Color (allows painting of the busway housing)
U U.S. STD0 UEC Mill Finish RED0 Paint UEC Red
BLK0 Paint UEC Black BLU0 Paint UEC Blue
WHT0 Paint UEC White
2. Product Type (section component)
X Cross section
**RAL system can also be used; reference page 2.39
3. Product Frame (maximum amperage)
060 60 amps

4. Compatibility (frame compatibility)


T2 T2 systems

5. Material (busbar material)


C Copper

6. Neutral/Ground Busbar (size of neutral busbar and/or ground)


4 3 Phase plus Neutral

7. Polarization (orientation of section for mating purposes)


S Standard

8. Turning Direction (direction of section polarizing stripe)


ST Standard

Examples:

UX060T2C4S-ST-RED0 = US, cross section, 60 amps, T2, Copper conductor, 3 Phase plus neutral, Standard polarization- Standard turning direction- painted red
UX060T2C4S-ST-STD0 = US, cross section, 60 amps, T2, Copper conductor, 3 phase plus neutral, Standard polarization- Standard turning direction- standard mill finish

2.14 | StarlinePower.com
60T2 Systems

END FEED UNITS


Product Description
With a built-in connector, the end feed units
for 60T2 systems consist of a steel junction
9.25”
box with removable side, a terminal block for
field connections and an in-line connector 3”
already terminated to one side of the terminal
block.

The unit is inserted into the Busway and held


in position via a bolted connection to the 4.5”
Busway.

WEIGHT: 3.5 lbs

Top View

Polarizing Stripe = LID

*Plug-in units face the standard


opposite side of the red orientation
triangle, or polarizing stripe

standard
orientation

LID

LID

reversed
orientation

reversed
orientation

LID

2.15 | StarlinePower.com
60T2 Systems

END FEED UNITS: PRODUCT NUMBERS

U F 060 T2 C 4 S - S L S N
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11.
System Product Product Compat- Material Neutral/ Polarization Lug/box Lid Accessories Accessories
Type Frame ibility Ground options orientation Package Location
busbar

- STD0 **RAL (please see page 2.39)


12.
Paint
Color

1. System (standard of measure) 12. Paint Color (allows painting of the busway housing)
U U.S. STD0 Paint UEC Silver RED0 Paint UEC Red
BLK0 Paint UEC Black BLU0 Paint UEC Blue
WHT0 Paint UEC White
2. Product Type (section component)
F End Feed
**RAL system can also be used; reference page 2.39
3. Product Frame (maximum amperage)
060 60 amps

4. Compatibility (frame compatibility)


T2 T2 systems

5. Material (busbar material)


C Copper

6. Neutral/Ground Busbar (size of neutral busbar and/or ground)


4 3 Phase plus Neutral

7. Polarization (orientation of section for mating purposes)


S Standard R Reversed

8. Lug/Box Options
S Standard lugs, standard box

9. Lid Orientation (viewed from the terminal, the side with


removable lid)
L Left R Right

10. Accessories Package (optional accessories for feed units)


S Standard

11. Accessories Location (viewed from the terminal, the side


with accessory)
N None (N/A)

Examples:
UF060T2C4R-SLSN-BLU0 = US, end Feed, 60 amps, T2, Copper conductor, 3 Phase plus neutral, Reversed polarization- Std lugs, Std box, Left lid orientation, standard accessory package, no
accessories location- painted blue

2.16 | StarlinePower.com
60T2 Systems

ABOVE FEED UNITS


Product Description
The above feed unit is used for supplying
power anywhere along the top of a Busway 4.25”
run. It consists of a two-foot section of 9.25”
Busway, and a junction box with a 60A rated
terminal block.

Two in-line connectors and housing couplers


(supplied separately) are used to connect
two adjacent busway sections.

WEIGHT: 2 - 5 lbs

2'

Internal View

2.17 | StarlinePower.com
60T2 Systems

ABOVE FEED UNITS: PRODUCT NUMBERS

U A 060 T2 C 4 S - S N S N - 0200 C 012


1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14.
System Product Product Compat- Material Neutral/ Polarization Lug/box Lid Accessories Accessories Straight Busway Feed
Type Frame ibility Ground options orientation Package Location Length Access Location
busbar

- STD0 **RAL (please see page 2.39)

15.
Paint
Color

1. System (standard of measure) 11. Accessories Location (viewed from the terminal, the side
U U.S. with accessory)
N None (N/A)
2. Product Type (section component)
A Above Feed 12. Straight Length (length of section)
0200 2 feet
3. Product Frame (maximum amperage)
060 60 amps 13. Busway Access (how plugs access the busway)
C Continuous
4. Compatibility (frame compatibility)
T2 T2 systems 14. Feed Location (location of the center of the top feed)
012 12 inches
5. Material (busbar material)
C Copper 15. Paint Color (allows painting of the busway housing)
STD0 Paint UEC Silver RED0 Paint UEC Red
6. Neutral/Ground Busbar (size of neutral busbar and/or ground) BLK0 Paint UEC Black BLU0 Paint UEC Blue
4 3 Phase plus Neutral WHT0 Paint UEC White

7. Polarization (orientation of section for mating purposes) **RAL system can also be used; reference page 2.39
S Standard R Reversed

8. Lug Options
S Standard lugs, standard box

9. Lid Orientation (viewed from the terminal, the side with


removable lid)
N None (N/A)

10. Accessories Package (optional accessories for feed units)


S Standard

Examples:
UA060T2C4S-SNSN-0200C012-BLK0 = US, Above feed, 60 amps, T2, Copper conductor, 3 phase plus neutral, Standard polarization- Std lugs, Std box, No lid orientation, Standard accessory
package, No accessory location- 2 ft., Continuous access, 12 inches- painted black

2.18 | StarlinePower.com
60T2 Systems

END FEED CONNECTOR UNITS


Product Description
This design of power feed has a built-
in connector and is used primarily in
applications where aesthetic appearance is
important- such as retail.
End Cap
Wire leads are preassembled to the
connector and eliminate the junction box on
the Busway.

Connector
24 in wire length is standard, but additional
lengths are available upon request.

WEIGHT: 2 lbs

2.19 | StarlinePower.com
60T2 Systems

END FEED CONNECTOR UNITS: PRODUCT NUMBERS

U C 060 T2 C 4 S - 024
1. 2. 3. 4. 5. 6. 7. 8.
System Product Product Compat- Material Neutral/ Polarization Wire
Type Frame ibility Ground Length
busbar

1. System (standard of measure)


U U.S.

2. Product Type (section component)


C Concealed feed

3. Product Frame (maximum amperage)


060 60 amps

4. Compatibility (frame compatibility)


T2 T2 systems

5. Material (busbar material)


C Copper

6. Neutral/Ground Busbar (size of neutral busbar and/or ground)


4 3 Phase plus Neutral

7. Polarization (orientation of section for mating purposes)


S Standard R Reversed

8. Wire Length (length of wire from the connector - in inches)


ZZZ ZZZ = inches (024 is standard)

Examples:
UC060T2C4S-024 = US, Concealed feed, 60 amps, T2, Copper conductor, 3 phase plus neutral, Standard polarization- 24 inches

2.20 | StarlinePower.com
60T2 Systems

BELOW FEED UNITS


Product Description
A Below Power Feed is designed to be
installed anywhere along the full-access
opening of a Busway run. Insert the Power
Feed connector into the Busway run where
desired and secure with a hanger bolt
(supplied). The Below Power Feed unit
must be completely installed in the selected
Busway housing before the adjacent housing
section can be installed. A terminal block
is provided in the box for field terminations.
Power supply cable is fed in from under the
unit.

WEIGHT: 4.8 lbs

2.21 | StarlinePower.com
60T2 Systems

BELOW FEED UNITS: PRODUCT NUMBERS

U B 060 T2 C 4 S - S R S N
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11.
System Product Product Compat- Material Neutral/ Polarization Lug/box Lid Accessories Accessories
Type Frame ibility Ground options orientation Package Location
busbar

- GAL0 **RAL (please see page 2.39)

15.
Paint
Color

1. System (standard of measure) 15. Paint Color (allows painting of the busway housing)
U U.S. GAL0 Galvanized
BLK0 Paint UEC Black RED0 Paint UEC Red
WHT0 Paint UEC White BLU0 Paint UEC Blue
2. Product Type (section component)
B Below Feed **RAL system can also be used; reference page 2.39

3. Product Frame (maximum amperage)


060 60 amps

4. Compatibility (frame compatibility)


T2 T2 systems

5. Material (busbar material)


C Copper

6. Neutral/Ground Busbar (size of neutral busbar and/or ground)


4 3Phase plus Neutral

7. Polarization (orientation of section for mating purposes)


S Standard R Reversed

8. Lug Options
S Standard lugs, standard box

9. Lid Orientation (viewed from the terminal, the side with meter)
R Right

10. Accessories Package (optional accessories for feed units)


S Standard

11. Accessories Location (viewed from the terminal, the side


with accessory)
N None (N/A)

Examples:
UB060T2C4S-SRSN-GAL0 = US, Below feed, 60 amps, T2, Copper conductor, 3Phase plus neutral, Standard polarization- Std lugs, Std box, Right lid orientation, Standard accessory package, No
accessory location- Galvanized

2.22 | StarlinePower.com
60T2 Systems

PENDANT FEED UNITS


Product Description
A Pendant Feed consists of a 1 ft. Busway
section with a 1 inch conduit size access
hole for access to connection leads inside
the Busway. A 1 inch conduit mounting
adapter is included.

12”

Hole used to access connection


leads with the Busway

2.23 | StarlinePower.com
60T2 Systems

PENDANT FEED UNITS: PRODUCT NUMBERS

U P 060 T2 C 4 S
1. 2. 3. 4. 5. 6. 7.
System Product Product Compat- Material Neutral/ Polarization
Type Frame ibility Ground
busbar

- STD0 **RAL (please see page 2.39)

8.
Paint
Color

1. System (standard of measure) 8. Paint Color (allows painting of the busway housing)
U U.S. STD0 UEC Mill Finish RED0 Paint UEC Red
BLK0 Paint UEC Black BLU0 Paint UEC Blue
2. Product Type (section component) WHT0 Paint UEC White
P Pendant Feed **RAL system can also be used; reference page 2.39

3. Product Frame (maximum amperage)


060 60 amps

4. Compatibility (frame compatibility)


T2 T2 systems

5. Material (busbar material)


C Copper

6. Neutral/Ground Busbar (size of neutral busbar and/or ground)


4 3 Phase plus Neutral

7. Polarization (orientation of section for mating purposes)


S Standard R Reversed

Examples:
UP060T2C4R-PD60 = US, Pendant feed, 60 amps, T2, Copper conductor, 3 Phase plus neutral, Reversed polarization- RAL 3036
UP060T2C4S-STD0 = US, Pendant feed, 60 amps, T2, Copper conductor, 3 Phase plus neutral, Standard polarization- standard mill finish

2.24 | StarlinePower.com
100T2 System

STRAIGHT SECTIONS
Product Description
Track Busway straight sections consist of
an extruded aluminum shell with insulated
copper conductor strips mounted on the two
opposite interior side walls. The aluminum
extrusion acts as a 100% ground path and
each straight has an open access slot over
its entire length for the insertion of turn-n-
lock plug-in units. The housing configuration
is 4 pole in a 600 Volt design. Track Busway
straights are connected together using in-line
connectors and housing couplers (found
under Accessories). L1 = Blue
L2 = Black
L3 = Red
N = white or beige
MATERIAL: Extruded Aluminum

RATINGS: 100% Ground Path


100 Amp, 600 Volt
1.79”
LENGTH: 5 Ft, 10 Ft, 20 Ft.;
or custom lengths between
2 - 20 Ft.

VOLTAGE DROP: distributed load
(N) (L2)
Single Phase 42 ft. (.85PF)
Three Phase 72 ft. (.85PF)
2.58”
(L1) (L3)
WEIGHT:
10 ft. (3m) 4 pole: 16 lbs

Four Pole

Housing Coupler:
placed over top of
connector to make a
mechanical connection

In-Line Connector:
placed in between
two pieces of busway
to make an electrical
connection

2.25 | StarlinePower.com
100T2 System

STRAIGHT SECTIONS: PRODUCT NUMBERS

U S 100 T2 C 4 S - 0200 C
1. 2. 3. 4. 5. 6. 7. 8. 9.
System Product Product Compat- Material Neutral/ Polarization Straight Busway
Type Frame ibility Ground Length Access
busbar

- STD0 **RAL (please see page 2.39)


10.
Paint
color

1. System (standard of measure) 10. Paint Color (allows painting of the busway housing)
U U.S. STD0 UEC Mill Finish RED0 Paint UEC Red
BLK0 Paint UEC Black BLU0 Paint UEC Blue
WHT0 Paint UEC White
2. Product Type (section component)
S Straight section
**RAL system can also be used; reference page 2.39
3. Product Frame (maximum amperage)
100 100 amps

4. Compatibility (frame compatibility)


T2 T2 systems

5. Material (busbar material)


C Copper

6. Neutral/Ground Busbar (size of neutral busbar and/or ground)


4 3 Phase plus Neutral

7. Polarization (orientation of section for mating purposes)


S Standard

8. Straight Length (length of section)


XXYY XX = feet, YY = inches (for U.S.)

9. Busway Access (how plugs access the busway)


C Continuous

Examples:

US100T2C4S-0206C-STD0 = US, Straight section, 100 amps, T2, Copper conductor, 3 Phase plus neutral, Standard polarization- 2ft. 6in., Continuous access- standard
mill finish
US100T2C4S-0500C-P010 = US, Straight section, 100 amps, T2, Copper conductor, 3 phase plus neutral, Standard polarization- 5ft., Continuous
access- RAL 1001

2.26 | StarlinePower.com
100T2 System

ELBOW SECTIONS
Product Description
Elbow connectors are used for making a 90
degree turn in a 100 amp compact Busway
run. Please be aware of polarization issues
before making your final selection (refer to
pg. 2.4 Polarity Tips).

Elbows are electrically connected to sections


of 100 amp Busway by means of an in-line
connector. The connector is installed by
inserting in each end of the housing sections
to be joined. Hex head compression screws
are tightened to make a reliable connection.
Elbow connectors are polarized to prevent
phase mismatch. Elbow Connector

WEIGHT: .5 lbs

= Polarizing Stripe

Internal Elbow External Elbow

2.27 | StarlinePower.com
100T2 System

ELBOW SECTIONS: PRODUCT NUMBERS

U E 100 T2 C 4 S - IN
1. 2. 3. 4. 5. 6. 7. 8.
System Product Product Compat- Material Neutral/ Polarization Turning
Type Frame ibility Ground Direction
busbar

- STD0 **RAL (please see page 2.39)


9.
Paint
color

1. System (standard of measure) 9. Paint Color (allows painting of the busway housing)
U U.S. STD0 UEC Mill Finish RED0 Paint UEC Red
BLK0 Paint UEC Black BLU0 Paint UEC Blue
WHT0 Paint UEC White
2. Product Type (section component)
E Elbow section
**RAL system can also be used; reference page 2.39
3. Product Frame (maximum amperage)
100 100 amps

4. Compatibility (frame compatibility)


T2 T2 systems

5. Material (busbar material)


C Copper

6. Neutral/Ground Busbar (size of neutral busbar and/or ground)


4 3 Phase plus Neutral

7. Polarization (orientation of section for mating purposes)


S Standard

8. Turning Direction (direction of section polarizing stripe)


IN Internal EX External

Examples:

UE100T2C4S-IN-BLK0 = US, Elbow section, 100 amps, T2, Copper conductor, 3 Phase plus neutral, Standard polarization- Internal- painted black
UE100T2C4S-EX-STD0 = US, Elbow section, 100 amps, T2, Copper conductor, 3 phase plus neutral, Standard polarization- External- standard mill finish

2.28 | StarlinePower.com
100T2 System

TEE SECTIONS
Product Description
Similar to elbow connectors, tee connectors
are used for connecting branch housing
sections at 90 degrees to the main run.
Please be aware of polarization issues before
making your final selection (refer to pg. 2.4
Polarity Tips).

Tees are electrically connected to sections


of 100 amp Busway by means of an in-line
connector. The connector is installed by
inserting in each end of the housing sections
to be joined. Hex head compression screws In-line Connector
are tightened to make a reliable connection.
All in-line connectors are polarized to prevent = Polarizing Stripe
phase mismatch.

WEIGHT: 1 lb

External-Left External-Right
(EL) (ER)

Internal-Left Internal-Right
(IL) (IR)

2.29 | StarlinePower.com
100T2 Systems

TEE SECTIONS: PRODUCT NUMBERS

U T 100 T2 C 4 S - IR
1. 2. 3. 4. 5. 6. 7. 8.
System Product Product Compat- Material Neutral/ Polarization Turning
Type Frame ibility Ground Direction
busbar

- STD0 **RAL (please see page 2.39)


9.
Paint
Color

1. System (standard of measure) 9. Paint Color (allows painting of the busway housing)
U U.S. STD0 UEC Mill Finish RED0 Paint UEC Red
BLK0 Paint UEC Black BLU0 Paint UEC Blue
WHT0 Paint UEC White
2. Product Type (section component)
T Tee section
**RAL system can also be used; reference page 2.39
3. Product Frame (maximum amperage)
100 100 amps

4. Compatibility (frame compatibility)


T2 T2 systems

5. Material (busbar material)


C Copper

6. Neutral/Ground Busbar (size of neutral busbar and/or ground)


4 3 Phase plus Neutral

7. Polarization (orientation of section for mating purposes)


S Standard R Reversed

8. Turning Direction (direction of section polarizing stripe)


IL Internal-Left EL External-Left
IR Internal-Right ER External-Right

Examples:

UT100T2C4S-IR-RED0 = US, Tee section, 100 amps, T2, Copper conductor, 3 phase plus neutral, Standard polarization- Internal-Right- painted red
UT100T2C4S-EL-STD0 = US, Tee section, 100 amps, T2, Copper conductor, 3 phase plus neutral, Standard polarization- External-Left- standard mill finish

2.30 | StarlinePower.com
100T2 System

CROSS SECTIONS
Product Description
Similar to tee connectors, crosses are
typically used for grid designs. Please be
aware of polarization issues before making
your final selection (refer to pg. 2.4 Polarity
Tips).

Crosses are electrically connected to


sections of 100 amp Busway by means
of an in-line connector. The connector is
installed by inserting in each end of the
housing sections to be joined. Hex head
compression screws are tightened to make a
reliable connection. All in-line connectors are
polarized to prevent phase mismatch.

Standard cross

= Polarizing Stripe

In-line Connector

2.31 | StarlinePower.com
100T2 Systems

CROSS SECTIONS: PRODUCT NUMBERS

U X 100 T2 C 4 S - ST
1. 2. 3. 4. 5. 6. 7. 8.
System Product Product Compat- Material Neutral/ Polarization Turning
Type Frame ibility Ground Direction
busbar

- STD0 **RAL (please see page 2.39)


9.
Paint
color

1. System (standard of measure) 9. Paint Color (allows painting of the busway housing)
U U.S. STD0 UEC Mill Finish RED0 Paint UEC Red
BLK0 Paint UEC Black BLU0 Paint UEC Blue
WHT0 Paint UEC White
2. Product Type (section component)
X Cross section
**RAL system can also be used; reference page 2.39
3. Product Frame (maximum amperage)
100 100 amps

4. Compatibility (frame compatibility)


T2 T2 systems

5. Material (busbar material)


C Copper

6. Neutral/Ground Busbar (size of neutral busbar and/or ground)


4 3 Phase plus Neutral

7. Polarization (orientation of section for mating purposes)


S Standard

8. Turning Direction (direction of section polarizing stripe)


ST Standard

Examples:

UX100T2C4S-ST-RED0 = US, cross section, 100 amps, T2, Copper conductor, 3 phase plus neutral, Standard polarization- Standard turning direction- painted red
UX100T2C4S-ST-STD0 = US, cross section, 100 amps, T2, Copper conductor, 3 phase plus neutral, Standard polarization- Standard turning direction- standard mill finish

2.32 | StarlinePower.com
100T2 Systems

END FEED UNITS


Product Description
With a built-in connector, the end feed units
for 100T2 systems consist of a steel junction 9.25”
box with removable side, a terminal block for
3”
field connections and an in-line connector
already terminated to one side of the terminal
block.

The unit is inserted into the Busway and held


4.5”
in position via a bolted connection to the
Busway.

WEIGHT: 3.5 lbs

Top View

Polarizing Stripe = LID

*Plug-in units face the standard


opposite side of the red orientation
triangle, or polarizing stripe

standard
orientation

LID

LID

reversed
orientation

reversed
orientation

LID

2.33 | StarlinePower.com
100T2 Systems

END FEED UNITS: PRODUCT NUMBERS

U F 100 T2 C 4 S - S L S N
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11.
System Product Product Compat- Material Neutral/ Polarization Lug/box Lid Accessories Accessories
Type Frame ibility Ground options orientation Package Location
busbar

- STD0 **RAL (please see page 2.39)


12.
Paint
Color

1. System (standard of measure) 12. Paint Color (allows painting of the busway housing)
U U.S. STD0 Paint UEC Silver RED0 Paint UEC Red
BLK0 Paint UEC Black BLU0 Paint UEC Blue
WHT0 Paint UEC White
2. Product Type (section component)
F End Feed
**RAL system can also be used; reference page 2.39
3. Product Frame (maximum amperage)
100 100 amps

4. Compatibility (frame compatibility)


T2 T2 systems

5. Material (busbar material)


C Copper

6. Neutral/Ground Busbar (size of neutral busbar and/or ground)


4 3Phase plus Neutral

7. Polarization (orientation of section for mating purposes)


S Standard R Reversed

8. Lug/Box Options
S Standard lugs, standard box

9. Lid Orientation (viewed from the terminal, the side with


removable lid)
L Left R Right

10. Accessories Package (optional accessories for feed units)


S Standard

11. Accessories Location (viewed from the terminal, the side


with accessory)
N None (N/A)

Examples:
UF100T2C4R-SLSN-BLU0 = US, end Feed, 100 amps, T2, Copper conductor, 3 phase plus neutral, Reversed polarization- Std lugs, Std box, Left lid orientation, standard accessory package, no
accessories location- painted blue

2.34 | StarlinePower.com
100T2 System

ABOVE FEED UNITS


Product Description
The above feed unit is used for supplying
power anywhere along the top of a Busway
6.5”
run. It consists of a two-foot section of
12.5”
Busway, and a junction box with a 100A rated
terminal block.

Two in-line connectors and housing couplers


(supplied separately) are used to connect 3.5”
two adjacent busway sections.

WEIGHT: 5 lb

24”

Internal View

2.35 | StarlinePower.com
100T2 Systems

ABOVE FEED UNITS: PRODUCT NUMBERS

U A 100 T2 C 4 S - S N S N - 0200 C 012


1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14.
System Product Product Compat- Material Neutral/ Polarization Lug/box Lid Accessories Accessories Straight Busway Feed
Type Frame ibility Ground options orientation Package Location Length Access Location
busbar

- STD0 **RAL (please see page 2.39)

15.
Paint
Color

1. System (standard of measure) 12. Straight Length (length of section)


U U.S. 0200 2 feet

2. Product Type (section component) 13. Busway Access (how plugs access the busway)
A Above Feed C Continuous

3. Product Frame (maximum amperage) 14. Feed Location (location of the center of the top feed)
100 100 amps 012 12 inches

4. Compatibility (frame compatibility) 15. Paint Color (allows painting of the busway housing)
T2 T2 systems STD0 Paint UEC Silver RED0 Paint UEC Red
BLK0 Paint UEC Black BLU0 Paint UEC Blue
5. Material (busbar material) WHT0 Paint UEC White
C Copper
**RAL system can also be used; reference page 2.39
6. Neutral/Ground Busbar (size of neutral busbar and/or ground)
4 3 Phase plus Neutral

7. Polarization (orientation of section for mating purposes)


S Standard R Reversed

8. Lug Options
S Standard lugs, standard box

9. Lid Orientation (viewed from the terminal, the side with meter)
N None (N/A)

10. Accessories Package (optional accessories for feed units)


S Standard

11. Accessories Location (viewed from the terminal, the side


with accessory)
N None (N/A)

Examples:
UA100T2C4S-SNSN-0200C012-BLK0 = US, Above feed, 100 amps, T2, Copper conductor, 3 phase plus neutral, Standard polarization- Std lugs, Std box, No lid orientation, Standard accessory
package, No accessory location- 2 ft., Continuous access, 12 inches- painted black

2.36 | StarlinePower.com
100T2 Systems

BELOW FEED UNITS


Product Description
A Below Power Feed is designed to be
installed anywhere along the full-access
opening of a Busway run. Insert the Power
Feed connector into the Busway run where
desired and secure with a hanger bolt
(supplied). The Below Power Feed unit
must be completely installed in the selected
Busway housing before the adjacent housing
section can be installed. A terminal block
is provided in the box for field terminations.
Power supply cable is fed in from under the
unit.

WEIGHT: 4.8 lbs

2.37 | StarlinePower.com
100T2 Systems

BELOW FEED UNITS: PRODUCT NUMBERS

U B 100 T2 C 4 S - S R S N
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11.
System Product Product Compat- Material Neutral/ Polarization Lug/box Lid Accessories Accessories
Type Frame ibility Ground options orientation Package Location
busbar

- GAL0 **RAL (please see page 2.39)

12.
Paint
Color

1. System (standard of measure) 12. Paint Color (allows painting of the busway housing)
U U.S. GAL0 Galvanized
BLK0 Paint UEC Black RED0 Paint UEC Red
WHT0 Paint UEC White BLU0 Paint UEC Blue
2. Product Type (section component)
B Below Feed **RAL system can also be used; reference page 2.39

3. Product Frame (maximum amperage)


100 100 amps

4. Compatibility (frame compatibility)


T2 T2 systems

5. Material (busbar material)


C Copper

6. Neutral/Ground Busbar (size of neutral busbar and/or ground)


4 3 Phase plus Neutral

7. Polarization (orientation of section for mating purposes)


S Standard R Reversed

8. Lug Options
S Standard lugs, standard box

9. Lid Orientation (viewed from the terminal, the side with meter)
R Right

10. Accessories Package (optional accessories for feed units)


S Standard

11. Accessories Location (viewed from the terminal, the side


with accessory)
N None (N/A)

Examples:
UB100T2C4R-SRSN-WHT0 = US, Below feed, 100 amps, T2, Copper conductor, 3 phase plus neutral, Reversed polarization- Std lugs, Std box, Right lid orientation, Standard accessory package,
No accessory location- painted white

2.38 | StarlinePower.com
T2 Series

RAL Colors

1st Character 2nd Character 3rd Character 4th Character

P Paint 0 100 0 0 0 0
1 101 1 1
2 102 2 2
3 103 3 3
4 200 4 4
5 201 5 5
A 300 6 6
B 301 7 7
C 302 8 8
D 303 9 9
E 400
F 401
G 500
H 501
J 502
K 600
Example:
L 601
M 602 P B 2 0 = Paint RAL 3012
N 603
P 700
Q 701
R 702
S 703
T 704
U 800
V 801
W 802
X 900
Y 901
Z 902

2.39 | StarlinePower.com
T2 Series

ACCESSORIES: SUPPORT HARDWARE

Threaded Rod Part Number 3/8” rod


coupler
For mounting to 3/8 - 16 threaded rod. Can URHB-3
be inserted anywhere along the top full-
Available in plain zinc
access slot of busway. Hanger support is
or black (-BLK)
required every 10 ft maximum.
Weight
.3 lb

Part Number
Standard UTHB-3 (3/8”)
For mounting to strut or other flat surfaces. UTHB-1/4 (1/4”) 3/8” or 1/4”
Twist-in design allows inserting anywhere
Stud
along the top full-access slot on the busway. Available in plain zinc
Hanger support is required every 10 ft or black (-BLK)
maximum.
Weight
.2 lb

Weight Hook Part Number


Can be used as a hanger to suspend the UWHRT2
Busway from chains or cables. Can also be
Available in plain zinc
used to hang loads of up to 50 lbs under
the Busway, such as light fixtures, tools and Weight
balancers. .2 lb

2.40 | StarlinePower.com
T2 Series

ACCESSORIES: SUPPORT HARDWARE

Surface Mount Part Number


For mounting to a surface. Comes with a 3/8 UMCT2-S (surface)
Available in all standard and RAL colors
inch hole.

T-Bar Suspended Ceiling Part Number


For mounting to an inverted T-bar. The UTHB-4
clip locks onto T-bar and the Busway is
Available in plain zinc
connected to the stud on the clip. T-bar is
mounted with surface clip.
Weight
.1 lb

Recessed Mount Part Number


Recessed mount brackets are used when URMT2
installing Busway that is recessed into a
Available in plain zinc
suspended ceiling.

Weight
*Hanger bolt must be ordered separately
.1 lb

Cable Part Number


For mounting to a 1/16 in. or 3/32 in. aircraft UACH-1 (1/16” cable)
cable with easy grip clamp assembly. Cable UACH-2 (3/32” cable)
is not included. Hanger support is every 10 ft.
Available in plain zinc
maximum.

Weight
.2 lb

2.41 | StarlinePower.com
T2 Series

ACCESSORIES: CONNECTION HARDWARE

Joint Kit
For the connection of adjacent busway Part Number
sections. Each kit is comprised of an in-line UJKT2-4
connector and housing coupler.
Available in all standard and RAL colors
In-Line Connector: sections of Busway are
joined electrically by means of an in-line
connector. All in-line bus connectors are
polarized to prevent phase mismatch.
Housing Coupler: sections of Busway are
joined mechanically by means of a housing
coupler. One is required per connection
point.

In-Line Connector Part Number


The connector is installed by inserting it UBCT2-4
into each end of the housing sections to be
joined. Hex head compression screws are
tightened to make a reliable connection.

Housing Coupler Part Number


Housing couplers make the mechanical UHCT2
connection between sections of Busway.
Available in all standard and RAL colors 6”

1.83”
End Cap Part Number
For covering the end of 60T2 or 100T2 UECT2
busway.
Available in all standard and RAL colors
2.44”

Weight:
.2 lb

Optional Closure Strip Part Number


Made of white, rigid PVC, the closure strip UCST2
is used to close the continuous access slot
of the Busway. It may be used for aesthetic Available in black & white
purposes, for keeping dust and dirt from
entering the Busway or as an added safety Maximum Cut Length: 20 ft
measure. It is easily cut to length in the field
to be installed around plug-in units.

2.42 | StarlinePower.com
T2 Series

SERVICES

Universal Global Services offers a With over 30 years of experience in the busway market, Starline has the knowledge
comprehensive suite of services from and expertise to ensure that your Track Busway system is functioning at a best-in-
startup and system certification through class level.
on-going support contracts and
extended warranty programs. To We are currently offering the following services:
ensure that your Busway system is
installed properly you can trust Starline’s Startup and System Certification
team of factory certified technicians to Certified technicians inspect and validate that the installation meets factory standards,
perform services throughout the long life ensuring ongoing reliability and compliance with facility safety requirements. Upon
of your Starline Track Busway system. successful completion of system startup, Starline’s standard one (1) year
Our complete line of services include: manufacturer’s warranty will be automatically extended for two (2) years.

• Load Bank Testing and Equipment • Double the length of the standard factory warranty
Rentals • Ensure all joint and feed connections are properly installed with continuity testing
• Meter Services • Ensure proper installation of all plug-in units
• Startup and System Certification • Validate that system will perform to your specified requirements
• Engineering Studies • Full certification report delivered electronically at conclusion of service
• On-Site Installation Support
• On-Site Product Training
• Extended Warranty and Enhanced Engineering Studies
Service Plans Understanding the dangers and implementing a safety program is imperative to
maintaining a safe work environment. Our professional engineers will conduct
Contact your Starline Representative comprehensive facility electrical studies and recommend corrective actions,
today to add services to your Track confirming your systems reliability and compliance with government and safety
Busway order, or download the detailed requirements.
Statement of Work documents at
http://downloads.uecorp.com/services. On-Site Installation Support
On-site installation support begins by scheduling a site trip during your system
installation. All work is performed by certified technicians- including review of
installation best practices prior to the job, visual inspection of safe system installation,
contractor installation oversight, and inspection and verification of functionality after
rework.

On-Site Product Training


Certified technicians will provide a comprehensive training course curriculum that
meets our high factory system standards, ensuring ongoing reliability of the system
while also emphasizing operational safety. This course curriculum takes place in both
a classroom and on-site with equipment.

2.43 | StarlinePower.com
T2 Series

SERVICES (cont'd)

Extended Warranty and Enhanced Service Plans


Ensure that your equipment investment is always covered. Select from an extended
factory warranty or one of our many Enhanced Service Plans to meet your
organizational requirements.

Silver Gold
Choice of Extended Warranty or Extended Platinum
1, 2, 1, 2,
Enhanced Silver, Gold or Platinum 1, 2, 3, 4 2, 3, 4
3, 4 3, 4
Service Plans years years
years years
Repair or replacement of defective parts throughout life of
X X X X
service agreement
24/7 technical support hotline X X X X
One (1) service site visit per year X
Two (2) service site visits per year X X
Visual inspection of meters X X X
Visual inspection of all joints for visible gaps X X X
Update firmware and verify all Starline CPM products X X X
Includes travel and expenses X X X
Thermal imaging of all plug-in units X X
Thermal imaging of all Busway joints X X
Thermal imaging of all end feed units X X
Detailed and fully executed thermography report X X
Online portal to view test reports and documentation X X
Spare parts inventory management program X

2.44 | StarlinePower.com
168 Georgetown Rd. Canonsburg, PA 15317 800-245-6378 +1 724-597-7800 www.StarlinePower.com [email protected]

Universal Electric Corporation, manufacturer of STARLINE Track Busway, has


been a global leader in power distribution since 1924. The company’s focus on
innovation continues to pave the way for safer, more flexible and reliable electrical
power distribution systems. Other STARLINE products include the Critical Power
Monitor (CPM), which works in conjunction with STARLINE Track Busway to
improve energy efficiency; Plug-In Raceway, the flexible, wall-mounted power
distribution system; and DC Solutions, the revolutionary 380V direct current
alternative for data centers.

REV 2

While every effort has been made to ensure the accuracy of all information, Universal Electric
Corporation does not accept liability for any errors or omissions and reserves the right to
change information and descriptions of listed services and products.

Most STARLINE systems and most standard components are UL, CE or ETL listed.