ELSTR01D Pdvsa

This document is a data sheet for designing and manufacturing liquid-immersed power transformers ranging from 500 kVA to 10,000 kVA with high voltages up to 34.5 kV. It includes specifications for the system parameters and windings, impedance, bushing locations and connections, insulating liquid and preservation system, testing requirements, documentation formats, and efficiency considerations. Site conditions, ratings, accessories, alarms and monitoring, and special motor requirements are also noted.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
94 views1 page

ELSTR01D Pdvsa

This document is a data sheet for designing and manufacturing liquid-immersed power transformers ranging from 500 kVA to 10,000 kVA with high voltages up to 34.5 kV. It includes specifications for the system parameters and windings, impedance, bushing locations and connections, insulating liquid and preservation system, testing requirements, documentation formats, and efficiency considerations. Site conditions, ratings, accessories, alarms and monitoring, and special motor requirements are also noted.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 1

PDVSA N-276 Sep.

02
Data Sheet for Design and Manufacture of Liquid-Immersed Power Transformers
of 500 kVA through 10,000 kVA up to 34.5 kV High Voltage Winding

Client       Engineering Org.       Spec. No.      


Project Title       Location       Date      
Project Location       Contract No       Equip. No.      
Proj. No.       Specifier Name       Tele. No.      
P.O. No.      
Refer to Specification No. ELSTR01 For General Requirements
Applicable State & Local Codes:      

Data Provided By  Buyer  Bidder With Proposal  Seller After Order


Site Conditions: Accessories:
Altitude       Ft Seismic Zone      
Current Transformers (per Section 5.7.2)
Ambient Temperature: Max      C Min      C
Other unusual conditions:      
H.V. Quantity       Ratio       Acc.Class      
Rating : L.V. Quantity       Ratio       Acc.Class      
OA Rating KVA (as per Section 5.1.2) Quantity Ratio
      Neutral             Acc.Class      
Other Dissolved Gas Monitor (as per Section 5.7.4)
Sudden Pressure Relay (as per Section 5.7.5)
System parameters and Windings: Alarm/Auxiliary Relay Control Voltage       Volts
High Voltage       kV       Phase       Hertz
Delta Wye Insulating Liquid and Preservation System (per Section 6):
Solidly Grounded Resistance Grounded Ungrounded Mineral Oil (Type II as per ASTM D3487-88) (as per Section 6.1.2)
Copper Other       Other       (as per Section 6.1.3)
Low Voltage       kV       Phase       Hertz Sealed Tank System with Purge Nozzle and Shutoff Valve
Delta Wye Inert Gas Pressure System (as per Section 6.2.2)
Solidly Grounded Resistance Grounded Ungrounded
Copper Other       Special Requirements:
Transformer will supply Single Large Motor as Follows:
Impedance: Standard (as per Section 5.1.11) Other       HP       Voltage       Full Load       Amps
Bushing Location and Connection Method: Locked Rotor       Amps Acceleration Time       Seconds
High Voltage Line Top Mounted Air Terminal Chamber Other      
Flanged Throat Other  Test as listed in this Practice Witnessed Not Witnessed
Witnessed
     
High Voltage Neutral Temp Rise Lightning Impulse Temp Switching Impulse
 Switching
Impulse
 Lightning
Impulse
 Switching
Top Mounted Air Terminal Chamber Impulse
Flanged Throat Other       Front of Wave Radio Influence Voltage
Low Voltage Line Top Mounted Air Terminal Chamber Audible Sound Level Mechanical Pressure Test
Flanged Throat Other       Other      
Low Voltage Neutral Top Mounted Air Terminal Chamber
Flanged Throat Other       Documentation:
 Electronic Document Format .dxf Other      
Space Heaters in Air Terminal Chambers: Seller to provide:
Thermostats Required Not Required      no. of copies of all documentation plus
     no. of copies of the operating manuals.
Cooling Fans:
Voltage       Volts Remote Contact (as per Section 5.5.11) Efficiency Considerations (per Section 5.2):
Fan Failure Alarm Required (as per Section 5.7.3) Seller Shall Optimize Efficiency Based on:
Other       Average Load: %     Other %    
Load (Copper) Losses: US$ / kw:      
Alarm and Monitoring: Core (Iron) Losses: US$ / kw:      
Voltage       Volts
Other Requirements:
     
     
     

Page 1 of 1