EE6702-PSG - Unit-III Apparatus Protection
EE6702-PSG - Unit-III Apparatus Protection
APPARATUS PROTECTION
CURRENT TRANSFORMERS
• Current Transformers (CT) are used to reduce the heavy
current flowing in an element of a power system to low values
that are suitable for relay operation
• Current rating of a protective relay is usually 1A or 5A. Besides
reducing the current level, the CT also isolates the relay circuit
from the primary circuit (high voltage power circuit)
• Requirements of CTs used for Protection:
• A CT used for instrumentation (measurement) is required to
be accurate over the normal working range of currents,
whereas the CT used for protection is required to give a
correct ratio upto several times rated primary current
N1 N2
38
TRANSFORMER PROTECTION
• OPERATION:
• O and R are the operating and restraining coils of the relay
• Connections are made in such a way that under normal conditions
or in of case of external faults NO current flows through the
operating coil of the relay, consequently, the relay does not operate
• External Fault:
• if a external fault occurs on phase “C”, then there is an over current
in the Phase-C. This current is supplied through two of the lines IA –
IC and IC – IB on the side of the transformer
• Similarly due to connections of CT secondary windings on the Y
side of transformer, two pilot wires (Ic – Ib and Ia - Ic) carry the fault
current, with the result that current circulates in two of the %
differential relay units and there is NO current in the spill path
(operating coil). Thus the scheme remains stable.
58
TRANSFORMER PROTECTION
• Core-balance protection suffers from drawback that it cannot
provide protection against overloads. If a fault or leakage
occurs between phases, core-balance relay will not operate.
• In combined leakage and over-load protection (Fig.), two
overload relays and one leakage or earth relay are connected.
• Earth relay has low current setting and operates under earth
or leakage faults only. Overload relays have high current
setting and are arranged to operate against faults between
phases.
• Trip contacts of overload relays and earth-fault relay are
connected in parallel. with energising of either overload
relay or earth relay, the circuit breaker will be tripped.
73
GENERATOR PROTECTION
• It is used for the protection of generators above 1 MW. It protects
against winding faults. (phase to phase and phase to ground faults)
• For an external fault condition, the currents sent by the CTs on both
sides of the stator winding cancel each other and there is no spill
current in the operating coil, therefore the relay does not operate
• For an internal fault, operating coil carries sum of the currents sent
by both CTs and therefore it operates and trips the circuit breaker.
• The percentage differential protection does not respond to external
faults and overloads. It provides complete protection against phase
to phase faults. It provides protection against ground faults to
about 80 to 85 % of the generator stator windings.
s1 s2
77
GENERATOR PROTECTION
• Here setting of earth-fault relay is reduced without impairing
stability.
• In this scheme two elements are arranged for phase fault
protection and the third for earth fault protection only.
• Two phase elements (A and C) together with a balancing resistor
(BR) are connected in star and earth relay (ER) is connected
between this star point and neutral pilot wire.
• Star-connected circuit is symmetrical as regards impedance and any
symmetrical spill current due to high through phase-fault will cancel
at relay star point and will not flow through earth fault relay
• It is possible with this scheme of protection to operate with a
sensitive earth fault relay and still maintain a high degree of
stability
• This sensitive operation of earth fault relay enables low setting
which provides protection to a greater % of stator windings.
UNIT-III EE6702 Protection and Switchgear 78
GENERATOR PROTECTION
• Operation:
• If earth fault occurs on any one phase, out-of-balance secondary
current in CT’s in that phase, will flow through the earth relay and
via pilot wires S1 and S2 to the neutral of the CTs. This will cause
operation of earth fault relay only.
• If a fault occurs between two phases, the out-of-balance currents
will circulate round the two CT secondaries via any two of the coils
(pair A & BR or C & BR) without passing through the earth relay.
Therefore only the phase-fault relays will operate
• For stator faults, tripping of CB to isolate faulty generator is not
sufficient to prevent further damage as generator will still continue
to supply power to fault until its field excitation is suppressed
• Therefore, percentage differential relays initiate an auxiliary relay
which in turn trips the main and field circuit breaker, shuts down
the prime mover and operates an alarm.
107
GENERATOR PROTECTION
114
MOTOR PROTECTION
• An induction motor draws a very large starting current of the order
of 6 to 8 times the full-load current if started direct-on-line.
• Amplitude of the starting current may be comparable to fault
current. an over-current relay must be able to discriminate
between these two currents
• Hence, coordination between the starting characteristic of the
motor and the over-current relay is required.
• Fig. shows starting current superimposed on the thermal capability
curve of the motor, and the characteristic of an over-current relay
• It can be seen from fig. that OC relay characteristic must be above
starting characteristics but below thermal characteristics of motor.
• This will ensure that the protective relay does not operate during
starting of the motor but will positively operate when the load
exceeds the motor's thermal capability.
143
MOTOR PROTECTION
• A synchronous motor may pull out of step due to severe
overload or due to reduction in supply voltage.
• Such a condition may be detected by a relay which responds
to change in power factor that occurs when there is pole
slipping
• One such typical circuit is shown in Fig. The voltage between
two phases is compared with the current in the third phase;
an attracted armature relay energized from a full-wave
rectifier bridge is differentially connected and is in the
operated state so long as the motor is in synchronism (step)
• A nonlinear resistor protects the rectifiers and extends the
operating range of the relay.
166
BUSBAR PROTECTION
• It is possible to design a station so that faults that develop are
mostly earth-faults.
• This can be achieved by providing earthed metal barrier
(Fault Bus) surrounding each conductor throughout its entire
length in the bus structure and connected to conductor
through insulator
• With this arrangement, every fault that might occur must
involve a connection between a conductor and an earthed
metal part.
• By directing flow of earth-fault current, it is possible to detect
the faults and determine their location. This type of
protection is known as fault bus protection