A Digital Assessment Technique of Transformer Winding Oscillations
A Digital Assessment Technique of Transformer Winding Oscillations
Keywords: HV transformer, equivalent circuit, winding response, transfer function, digital recording, signal processing
__________________________________________________________________________________________________________
Prof. dr hab. inz. Ryszard Malewski*. Lowicka 53 m 14, 02 535 Warszawa, Poland. E-mail: [email protected]
Transformer winding design at a modest repair facility A series resistor inserted in such circuit represents a
damping caused by the copper loss in the conductors,
The transient voltage distribution along the winding is
increased by skin and proximity effects. All these
usually calculated by specialized programs. Such programs
parameters have to be determined from the proposed
are based on a practical experience accumulated for
winding drawing.
decades of transformer design by the leading transformer
manufacturers of an established reputation. Needless to say In addition, an insulation dielectric loss has also a
that these programs are considered proprietary, as they certain contribution to the damping, and it can be simulated
provide the competitive edge in the nowadays worldwide by a high ohmic resistor parallel to the ground capacitance.
open competition. As a further refinement, the series resistance frequency
dependence, and the core permeability influence on self, as
To design a transformer a modest repair facility has to
well as mutual inductances should also be taken into
ask an established manufacturer for a design and
account.
manufacturing technology license. Alternatively, an in-
house expertise can be developed, based on the experience Validation of the winding equivalent circuit
acquired during repairs of different transformer types and To validate the simulation, a low voltage impulse is
makes. The second way is often preferred, considering a applied to the winding, and the resulting transient voltage is
high cost of the license fee, and other imposed limitations. digitally recorded on each double-disc of the untanked
Besides, the design of transformers rated at a medium winding. The winding transfer function is then derived from
power and voltage level has already been mastered, and these measurements using the signal processing. The
does not require the state of the art design tools. In the case transfer function of the simulated circuit is then compared
of ENERGOSERWIS, an assistance has been provided by to the transfer function obtained from measurements. The
the experts from a Polish transformer design school equivalent circuit is then corrected by subsequent iterations
established around the large, State owned transformer until a satisfactory agreement is achieved. At this moment, a
works ELTA, some thirty years ago. With the changing dielectric stress is determined on the insulating system
economic situation this school has been partly elements, which can be adjusted to ensure an adequate
dispersed, but the skilled engineers are still available as safety margin.
consultants. Nevertheless, the proposed winding An example of a typical winding simulation
calculation have to be checked by measurements. A HV winding of 25 MVA, 115kV±15%/16.5 kV, 3 phase
Equivalent circuit of transformer windings transformer has been taken as an example. The HV winding
The transient voltage distribution along the winding is is composed of 32 double discs, with a few interleaved
calculated using an equivalent circuit composed of lumped discs installed at the upper and lower sections. Each double-
elements: the series capacitance of each coil, its ground disc was simulated by one segment of the digital model.
capacitance and capacitance to adjacent windings, an The equivalent circuit was quickly assembled using a circuit
inductance and mutual inductance to near by coils. analysis program “Micro-Cap” [22], since the elements
were chosen and positioned by simple ‘mouse clicking’.
Fig. 1. An equivalent circuit of the examined HV winding. Each double-disc is characterized by: K- series capacitance, C-
ground and nearby winding capacitance, L-selfinductance, and M-mutual inductance to five neighbor coils. A variable
frequency and an impulse voltage source was used for different analyses. The series resistance R was selected to fit the
measured waveforms.
Calculation of equivalent circuit elements Chowdhuri [25], and an excellent, though somewhat sarcastic
A calculation of the circuit components represents the most discussion of his paper by Jayaram emphasized an
difficult part of the project. It has to be done at two stages. At importance of this effect. A formula for the capacitance of a
first the model simulates the untanked winding, such as double-disc coil stabilized by the shield wire is given, and
examined with a low voltage impulse. At the second stage, checked experimentaly by Poulin [26].
the oil impregnated winding is simulated, taking into account A self inductance of the winding was obtained from its short-
the paper-oil insulation dielectric constant, and also an effect circuit impedance, at the first approximation. A fundamental
of the regulation winding installed on the HV coil. work of Rabins [27] was consulted, however complexity of
The following assumptions have been made: his formulae precluded their direct use. An additional study
• The magnetic core can be represented by a grounded, metal by Lech [28] provided algorithms for numerical calculations.
sheet cylinder. An analytic formula for inductance of air-core disc coils,
• The winding resistance is constant within the analysis derived by Lyle from Maxwell equations, was published by
frequency range. Wirgau [29]. Fergestad & Henriksen [16] presented a self and
• The magnetic coupling of five adjacent double-disc coils is mutual inductance calculation of the disc coils, supported by
the same over the whole winding height. experimental results.
• The low voltage and regulation windings can be At first, the calculated self inductance did not follow the
represented by a metal sheet cylinder. measured value. Then, a correction was introduced by fitting
A validity of the last assumption was checked by the calculated resonant frequencies to the measured ones. The
measurements taken with the short circuited secondary mutual inductance was calculated with a satisfactory
winding nested inside the HV coil. accuracy.
At first, the winding resistance was calculated using skin
The series capacitance of a double-disc coil has been derived
effect formulae, but the proximity of adjacent wires must be
from the energy stored between the adjacent turns. A voltage
the controlling factor. The ‘Micro-Cap” program allows for
distribution proportional to the turn number was assumed,
simulation of a frequency dependent resistance, but then the
and the resulting turn to turn voltage was calculated.
long calculation time of becomes objectionable. Finally, the
Formulae for calculation of a simple and interleaved double-
resistance was adjusted to get a realistic damping of the
disc coil were derived by Degeneff [23]. These expressions
winding higher order resonances, but then the first resonance
are also given in a book authored by Hastermann, Mosiñski
Q-factor is too low. This, however, has little effect on the
and Maliszewski [24]. A mutual capacitance between
simulated waveforms.
neighbor coils was calculated by
Fig. 2. Transfer functions of the simulated winding. The double-disc number is marked on each graph.
3
The simulated winding transfer function was calculated by frequency spectrum of the standard lightning impulse, and
“Micro-Cap” for each double-disc, and is shown in Fig. 2. of transients generated by the transmission system.
These curves were combined to a three-dimensional graph, High frequency models have also been developed for
which reveals the frequency and space distribution of studies of internal oscillations within a double-disc [30, 31,
winding natural resonances, as shown in Fig. 3. 32]. However, the nanosecond front time transients, and a
few megahetz resonances are not addressed here.
Measurement of the winding response to a low voltage
impulse
The transient voltage was recorded on each double-disc
using a high resolution (12 bit) digital oscilloscope,
operating at 10 MHz sampling, and equipped with an
optically isolated probe [33]. Such probe is needed for the
disc to disc voltage measurement, since the grounded
terminal of an ordinary probe affects the examined disc
potential. A set of the transient voltage measured on each
double-disc are presented in Fig. 5.
Although the transient voltage distribution measured in the
examined winding looks similar to the simulated
distribution shown in Fig. 4, but such comparison of the
waveshapes is merely qualitative. The frequency domain
transfer functions can be compared quantitatively, since the
Fig. 3. The examined winding transfer function plotted resonant frequencies can be measured. A difference
against frequency and space. An exaggerated Q-factor between the measured and simulated resonant frequency
of the first resonance is caused by the assumed reflects the simulation accuracy.
constant resistance value.
Once the winding resonant frequencies have been derived, a
transient voltage can be calculated at each coil, for any
impulse form applied at the input. A steep front impulse has
been used as an example, and the winding response is
shown in Fig. 4.
4
Fig. 6. Transfer function derived from transient voltage measured at each double-disc of the winding.
A transfer function of each double-disc was then calculated manufacturing and repair facilities. A low voltage impulse
as a quotient of the recorded waveform spectrum and the source, a high resolution digital oscilloscope, and a
spectrum of the applied impulse. The whole winding commercial circuit analysis program are needed to develop,
transfer function is shown in Fig. 6. A three-dimensional and to verify the transformer winding model. The winding
graph is shown in Fig. 7 design can be then optimized, without compromising the
insulation dielectric strength.
The transfer function derived from the transient voltage
measured at each double-disc is a tool of many uses. For
instance, a stress on the winding insulation subject to the
front chopped impulse test can be calculated, if such
impulse is convoluted with the winding transfer function.
A calculated transient voltage across an oil duct, or a
creep stress along a spacer-oil interface is needed to make
the field plot, and to calculate the insulation safety margin.
As an extension of this study, a dielectric stress induced on
the winding insulation by the test lightning impulse can be
compared to the stress caused by system generated
overvoltages [35].
Conclusions
• The transient voltage distribution in the transformer
windings can be calculated using a commercially
available circuit analysis program, and verified by low
Fig. 7. The examined winding transfer function calculated voltage measurements on an untanked winding.
from the transients measured on each double-disc. • A low voltage impulse generator, a high resolution
An accuracy of the “Micro-Cap” simulation can be assessed digital oscilloscope and a signal processing software.
by a comparison of the equivalent circuit transfer function are required to derive the winding transfer function
(shown in Fig. 2 and 3) to the actual winding transfer from the measured transients.
function derived from measurements. • A comparison of the measured and simulated transfer
Discussion function allows for iterative corrections of the model,
The main objective of this paper to present an easily until a satisfactory accuracy is achieved.
accessible technique of the transient stress calculation in a • The winding transfer function is a tool of many uses. In
transformer winding insulation. A more refined model, addition to the model verification, a transient voltage
which takes into account a capacitive coupling between distribution can be calculated for any waveform
neighbor coils, a frequency dependent winding resistance, applied to the input terminal, such as a front chopped
an effect of the magnetic permeability of the transformer impulse, or a system generated switching overvoltage.
core, etc., can be worked out, and a more accurate References
representation of the winding transfer function can be 1. Wagner, K.W., “Das Eindringen einer
achieved. However, the presented technique is not intended elektromagnetischen Welle in eine Spule mit
as a substitute for the specialized programs. This simple Windungskapacität”, Elektrotechnik und
procedure can be used by modest transformer Maschinenbau, Vol. 33, No. 8, 1915, p. 89.
5
2. Abetti, P.A., “Survey and Classification of Published 19. vanNuys, R., “Interleaved HV Transformer Windings”
Data on the Surge Performance of Transformers....”, IEEE Trans., Vol. PAS-97, 1978, p. 1946.
AIEE Trans. Part III, Vol. 77, 1959, p. 1403. 20. Miki, A., Hosoya, T., Okuyama, K., “A Calculation
3. Abetti,. P.A., “Bibliography on the Surge Performance Method for Impulse Voltage ..... in the Windings.”,
of Transformers....”, AIEE Trans. Part III, Vol. 77, IEEE Trans. Vol. PAS-98, No. 3, 1978, p.90.
1958, p. 1150 21. US Patent No. 2 453 552, November, 1948
4. Blume, L.F., Boyajian, A., “Abnormal voltages within 22. “Micro-Cap IV”, Spectrum Software, Sunnyvale,
transformers”, AIEE Transactions, Vol. 38, 1919, p. 577 California.
5. Bewley, L.V., “Traveling Waves on Transmission 23. Degeneff, R., “Simplified Formulas to Calculate
Systems”, New York, 1933. Equivalent Series Capacitance...”, GE-Tech. Inform.
6. Pirenne, J., “Théorie génerale des phénomenes No. 75PTD017, 1976, Pittsfield, Mass.
oscillatoires dans des enroulements des 24. Hastermann, Z., Mosiñski, F., Maliszewski, A.,
transformateurs”, RGE, Vol. 47, No. 19, 1940. “Dielectric Strength of Power transformers”, WNT,
7. Rüdenberg, R., “Electromagnetic Waves in Warsaw, 1983, (in Polish).
Transformer Coils Treated by Maxwell’s Equations”, 25. Chowdhuri, P., “Calculation of Series Capacitance for
J. Applied Physics, Vol. 12, March, 1941, p. 219. Transient Analysis of Windings”, IEEE Trans. Vol.
8. Chadwick, A.T., Ferguson, J.M., Ryder, D.H., Stearn, PWRD-2, No. 1, 1987, p. 133.
G.F., “Design of Power Transformers to Withstand 26. DelVecchio, R.M., Poulin, B., Ahuja, R., “Calculation
Surge Due to Lightning with Special Reference to a and Measurement of Winding Disc Capacitances with
New Type of Winding”, IEE Proc. Part II, Vol. 97, Wound-in Shields”, IEEE transactions, Vol. PWRD-
1950, p. 737. 13, No. 2, 1998, p. 503.
9. Abetti, P.A., Maginniss, F.J., “Natural Frequencies of 27. Rabins, L., “Transformer Reactance Calculation with
Coils and Windings Determined by Equivalent Digital Computer”, AIEE Trans. Vol. 75, Part I, 1956,
Circuits”, AIEE Trans. Vol. PAS, Part III, June, 1953, p. 261.
p. 495. 28. Lech, W., “Impulse Overvoltage Calculation in
10. McWhirter, J.H., Fahrnkopf, C.D., Steele, J.H., Transformers using Digital Computer”, Postêpy TWN,
“Determination of Impulse Stresses within Vol. 4, PWN, Warsaw, 1956, (in Polish).
Transformer Windings by Computer”, AIEE Trans. 29. Wirgau, K. A., “Inductance Calculation of Air-Core
Vol. 75, Part III, 1956, p. 1267. Disc Winding”, IEEE Trans. Vol. PAS-95, No. 1,
11. Schleich, A., “Behaviour of Partly Interleaved Jan./Feb., 1976, p. 394.
Transformer Windings Subject to Impulse Voltages”, 30. Cornick, K., Filliat, B., Kieny, C., Müller, W.,
Bulletin Oerlikon, No. 389/390. 1961, p. 4. “Distribution of Very fast Transient Overvoltages in
12. Pedersen, A., “On the Response of Interleaved Transformer Windings”, CIGRE, paper 12-204, 1992
Transformer Windings to Surge Voltages”, AIEE 31. Müller, W., Stein, W., “Behavior of HV Transformer
Trans. Vol. 82, Part III, 1963, p. 349. Windings on Steep-Fronted Input Waves of
13. Stein G.M., ”A Study of the Initial Surge Distribution Nanosecond Duration”, Siemens Power Engineering,
in Concentric Transformer Windings”, IEEE Trans. V 1983, No. 6, p. 259.
Vol. PAS-83, Sept. 1964, p. 877. 32. Teranishi, T., Ikeda, M., Honda, M., Yanari, T., “Local
14. Heller, B., Veverka, A., “Surge Phenomena in Voltage Oscillation in Interleaved Transformer
Electrical Machines”, Iliffe Books, London, 1968. Windings”, IEEE Trans. Vol. PAS-100, No. 2, 1981,
15. Jayaram, B, N., “The Equivalent Series Capacitance of p. 873.
a Single Disc Coil in a Transformer Winding”, ETZ-A, 33. Malewski, R., Franchek, M. A., McWhirter, J.H.,
1973, p. 547. “Experimental Validation of A Computer Model
16. Fergestad, P.J., Henriksen, T., “Inductances for the Simulating An Impulse Voltage Distribution in HV
Calculation of Transient Oscillations in a Transformer Windings”, IEEE Trans. Vol. PWRD-9,
Transformers”, IEEE Trans. Vol. PAS-93, March - No. 4, 1994, p. 1789.
April, 1974, p. 500. 34. Malewski, R., et al. "Checking Electromagnetic
17. Margolis, H.B., et al. “Experience with Part Winding Compatibility of A HV Impulse Measuring Circuit
Resonance in EHV Auto-Transformers; Diagnosis and with Coherence Function", ERA Seminar of HV
Corrective Measures”, IEEE Trans. Vol. PAS- ,94, Measurements, Arnhem, Oct. 1994.
1975, p. 1298. 35. Vailles, Ch., Malewski, R., Dai-Do, X., Aubin, J.,
18. Degeneff, R.C., “A General Method for Determining “Measurements of Dielectric Stress in EHV
Resonances in Transformer Windings”, IEEE Transformer Insulation”, IEEE Trans. Vol. PWRD-13,
Transactions, Vol. PAS-96, No. 2, 1977, p. 423. No. 2, 1998, p. 1757.