High Capacity Gas Chlorinator: MODEL 2101
High Capacity Gas Chlorinator: MODEL 2101
MODEL 2101
HIGH CAPACITY
GAS CHLORINATOR
1.88
CONTENTS GUIDE MODEL 2101 48
1 each Model A-2821 Vacuum Regulator with 1 NPT
MODEL 2107
HIGH CAPACITY
AUTOMATIC
SWITCHOVER
GAS CHLORINATOR
The principal use of the REGAL Gas Chlorinator is to chlorinate ADDITIONAL FEATURES
water, wastewater and industrial process water with gas chlorine. • System Back-up – Each cylinder’s chlorinator has its own vacuum regulating
The simple, efficient design has made REGAL Gas Chlorinators diaphragm and safety/inlet valve insuring that chlorination can be continued if service
the industry standard. Built with heavy duty corrosion resistant should be required on either chlorinator.
parts, REGAL Chlorinators provide safe, long-lasting service. • Corrosion-resistant, Factory-adjusted Detent Mechanism – Detent does not require
any field adjustment assuring that cylinder switchover will occur at the proper time,
The REGAL Model 2107 Automatic Switchover Gas Chlorinators are
and that all available gas in supply cylinder will be used.
totally vacuum-operated chlorination systems which are designed to
• In-Use/Stand-by Indication – Prominent indicator on face quickly tells which is the
automatically switch the chlorine feed from an empty chlorine source
stand-by cylinder and which cylinder is in use.
to a full chlorine source. It is also designed to provide system-backup.
• Pre-tested/Pre-set – The entire REGAL 2107 Gas Chlorinator is tested as a system at
Should a problem develop with either vacuum regulator, chlorination
the factory and no field adjustment or calibration is required to place it into operation.
can be continued. The Chlorinators are of the vacuum operated solution
feed type, designed for mounting directly on a chlorine manifold CAPACITIES
header valve. The switchover chlorinators are self-actuating, eliminating Dual scale metering tubes with maximum capacities of 1000 and 2000 pounds per 24
the need for a separate switchover module. A separate chlorine gas hours of chlorine gas with corresponding metric scales of 20 and 40 kilograms per hour.
flowmeter and rate control valve panel may be located wherever it is The minimum feed rate is 1/20th of the maximum for each metering tube.
most convenient for the operator and connected between the vacuum
regulator junction at the pressure relief (vent) valve, and the ejector, FLOW RATE ADJUSTMENT
by means of safe vacuum piping. The ejector assembly contains a back Manual adjustment is by means of a flow rate control valve located at the top of the
flow check valve. Chlorine gas flow rate is regulated by a spring- flow meter/rate valve panel. Flow rate is then regulated by a special spring-loaded,
opposed diaphragm regulator which is also the automatic safety shut- diaphragm-operated valve in the vacuum regulator. The system is automatic. It will
off valve. Should vacuum be interrupted for any reason anywhere in turn off and on as the ejector water supply is turned off and on and will return to the
the system the safety shut-off/inlet valve immediately closes, shutting preset flow rate.
off the chlorine supply from the pressurized chlorine source. A pressure
relief valve designed to “vent” the system also provides a central EJECTOR REQUIREMENTS
interconnection point for the vacuum piping. Model 2107 Gas Chlorinators are tested to give the best operation in the system
being treated. Generally, the amount of water (GPM) required to operate the ejector
FEATURES depends upon the chlorine flow rate, the ejector back pressure, and the ejector water
• Fewer parts, simpler design for less down time, easier maintenance supply pressure which is available. In all cases, the minimum pressure differential and
and lower costs, year after year. water flow for your installation should be determined prior to installation and start up.
• Materials that stand up to ultraviolet degradation and chlorine OPERATION
attack…wet or dry. The vacuum regulator is clamped on the header valves of chlorine cylinder or ton
• Limited Warranty for the life of the chlorinator on vital parts… container manifolds.The vacuum line is connected from each vacuum regulator unit to
diaphragm and inlet spring against corrosion. the wall mounted, pressure relief (vent) valve, and a single vacuum line connects the
• Combined O-ring/diaphragm sealing of the front and back body outlet of the pressure relief valve to a wall mounted, flow meter/rate valve panel. The
parts helps prevent air leaks into the system and eliminates the need ejector assembly is either wall mounted or supported by rigid pipe, and is connected
for special tightening tools. to the flow meter/rate valve panel with a single vacuum line.
• Inlet safety valve "capsule" allows easy removal with minimal
disassembly for inspection or cleaning with no special tools.
OPERATION (continued)
Water, under pressure is forced through the ejector REGAL MODEL 2107
HIGH CAPACITY AUTOMATIC SWITCHOVER GAS CHLORINATORS
nozzle which creates a strong vacuum in the ejector
SERIES 2000
body. This pulls gas into the ejector through a special VACUUM REGULATOR
CHLORINE GAS MANIFOLD
back-flow check valve and then into the nozzle outlet. (PRESSURE) (Optional)
The gas mixes with the ejector water and is discharged REMOTE METER PANEL ASSEMBLY
through the solution piping into the water being treated. FLEXIBLE
DRIP
LEG
CONNECTORS HEATER
The ejector vacuum is transmitted through the vacuum
A/C POWER
line to the rate valve and the flow meter; then through SOURCE
the connector on the pressure relief (vent) valve and on 1" VACUUM PIPING