Plant Layout With Brief Process Information and Fire and Risk Analysis of Power Plant
Plant Layout With Brief Process Information and Fire and Risk Analysis of Power Plant
ON
STUDY OF POWER PLANT LAYOUT
WITH BRIEF PROCESS
INFORMATION AND FIRE RISK
ANALYSIS
I also thank Mr. Golam Mowla for providing study material and
books from the Library, and the class mates who helps me a lot in the
making of the project.
CHANDAN MONDAL
3rd
SEMESTER
Roll: DSSPE/IS
(P)/S3
No:0015
Student of Diploma in Industrial
safety
(2019-
2021)
DURGAPUR SOCIETY FOR
SAFETY &
PROFESSIONAL
EDUCATION
INDEX
SL. NO Description
01 Acknowledgement
02 Introduction
03 Thermal Power Plant
04 Layout of Power Plant
05 Brief description of plant process
06 Hazard identification risk & risk reduction strategies
07 Short Definition
08 Classification of Fire
09 Maintenance of Extinguisher
10 Fixed Fire Fighting system
11 Automatic fire fighting system
12 B.A Set
13 U.N Classification
14 Fire Alarm System
15 Determining fire hazard
16 Checklist of fire prevention
17 On-site emergency plan
18 Conclusion
THERMAL POWER PLANT
A generating station which converts heat energy of coal combustion into electrical energy is
known as a steam power station.
A steam power station basically works on the Rankine cycle. Steam is produced in the boiler
by utilizing the heat of coal combustion. The steam is then expended in the prime mover and
is condensed in a condenser to be a fed into the boiler again. The steam turbine drives the
alternator which converts mechanical energy of the turbine into the electrical energy. The
type of power station is suitable where coal and water are available in abundance and a large
amount of electric power is to be generated.
The above diagram is the lay out of a simplified thermal power plant and the below is also
diagram of a thermal power plant.
The above diagram shows the simplest arrangement of coal fired (Thermal) power plant.
Main parts of the plant are
1. Coal conveyor 2. Stoker 3. Pulverize 4. Boiler 5. Coal ash 6. Air preheated 7. Electrostatic
precipitator 8. Smoke stack 9. Turbine 10. Condenser 11. Transformers 12. Cooling towers
13. Generator 14. High - voltage power lines
Types of Pulverizes
Ball and Tube Mill Ball mill is a pulverize that consists of a horizontal rotating cylinder, up
to three diameters in length, containing a charge of tumbling or cascading steel balls,
pebbles, or rods.
Tube mill is a revolving cylinder of up to five diameters in length used for fine pulverization
of ore, rock, and other such materials; the material, mixed with water, is fed into the chamber
from one end, and passes out the other end as slime.
Boiler: Now that pulverized Coal is put in boiler furnace. Boiler is an enclosed vessel in
which water is heated and circulated until the water is turned in to steam at the required
pressure.
Coal is burned inside the combustion chamber of boiler. The products of combustion are
nothing but gases. These gases which are at high temperature vaporize the water inside the
boiler to steam. Sometimes this steam is further heated in a super heater as higher the steam
pressure and temperature the greater efficiency the engine will have in converting the heat in
steam in to mechanical work. This steam at high pressure and temperature is used directly as
a heating medium, or as the working fluid in a prime mover to convert thermal energy to
mechanical work, which in turn may be converted to electrical energy. Although other fluids
are sometimes used for these purposes, water is by far the most common because of its
economy and suitable thermodynamic characteristics.
Classification of Boilers
Water tube boilers: In these boilers water is inside the tubes and hot gases are
outside the tubes. They consists of drums and Tubes. They may contain any number of
drums (you can see 2 drums in fig).Feed water enters the boiler to one drum (here it is drum
below the boiler).This water circulates through the tubes connected external to drums. Hot
gases which surround these tubes will convert the water in tubes in to steam. This steam is
passed through tubes and collected at the top of the drum since it is of light weight. So the
drums store steam and water (upper drum). The entire steam is collected in one drum and it is
taken out from there (see in layout fig). As the movement of water in the water tubes is high,
so rate of heat transfer also becomes high resulting in greater efficiency. They produce high
pressure, easily accessible and can respond quickly to changes in steam demand. These are
also classified as vertical, horizontal and inclined tube depending on the arrangement of the
tubes. These are of less weight and less liable to explosion. Large heating surfaces can be
obtained by use of large number of tubes. We can attain pressure as high as 125 kg/sq cm and
temperature from 315 to 575 centigrade.
Super heater: Most of the modern boilers are having super heater and reheated
arrangement. Super heater is a component of a steam-generating unit in which steam, after it
has left the boiler drum, is heated above its saturation temperature. The amount of superheat
added to the steam is influenced by the location, arrangement, and amount of super heater
surface installed, as well as the rating of the boiler. The super heater may consist of one or
more stages of tube banks arranged to effectively transfer heat from the products of
combustion. Super heaters are classified as convection, radiant or combination of these.
Re-heater: Some of the heat of superheated steam is used to rotate the turbine where it
loses some of its energy. Re heater is also steam boiler component in which heat is added to
this intermediate-pressure steam, which has given up some of its energy in expansion
through the high-pressure turbine. The steam after reheating is used to rotate the second
steam turbine (see Layout fig) where the heat is converted to mechanical energy. This
mechanical energy is used to run the alternator, which is coupled to turbine, there by
generating electrical energy.
Cooling Towers: The condensate (water) formed in the condenser after condensation is
initially at high temperature. This hot water is passed to cooling towers. It is a tower- or
building-like device in which atmospheric air (the heat receiver) circulates in direct or
indirect contact with warmer water (the heat source) and the water is thereby cooled (see
illustration). A cooling tower may serve as the heat sink in a conventional thermodynamic
process, such as refrigeration or steam power generation, and when it is convenient or
desirable to make final heat rejection to atmospheric air. Water, acting as the heat-transfer
fluid, gives up heat to atmospheric air, and thus cooled, is re-circulated through the system,
affording economical operation of the process.
Two basic types of cooling towers are commonly used. One transfers the heat from warmer
water to cooler air mainly by an evaporation heat-transfer process and is known as the
evaporative or wet cooling tower.
Evaporative cooling towers are classified according to the means employed for producing air
circulation through them: atmospheric, natural draft, and mechanical draft. The other
transfers the heat from warmer water to cooler air by a sensible heat-transfer process and is
known as the non-evaporative or dry cooling towers.
Non-evaporative cooling towers are classified as air-cooled condensers and as air-cooled heat
exchangers, and are further classified by the means used for producing air circulation
through them. These two basic types are sometimes combined, with the two cooling
processes generally used in parallel or separately, and are then known as wet-dry cooling
towers.
Economizer: Flue gases coming out of the boiler carry lot of heat. Function of
economizer is to recover some of the heat from the heat carried away in the flue gases up the
chimney and utilize for heating the feed water to the boiler. It is placed in the passage of flue
gases in between the exit from the boiler and the entry to the chimney. The use of
economizer results in saving in coal consumption, increase in steaming rate and high boiler
efficiency but needs extra investment and increase in maintenance costs and floor area
required for the plant. This is used in all modern plants. In this large number of small
diameter thin walled tubes are placed between two headers. Feed water enters the tube
through one header and leaves through the other. The flue gases flow outside the tubes
usually in counter flow.
Air pre-heater: The remaining heat of flue gases is utilized by air pre-heater. It is a
device used in steam boilers to transfer heat from the flue gases to the combustion air before
the air enters the furnace. Also known as air heater; air-heating system. It is not shown in the
lay out. But it is kept at a place nearby where the air enters in to the boiler.
The purpose of the air pre-heater is to recover the heat from the flue gas from the boiler to
improve boiler efficiency by burning warm air which increases combustion efficiency, and
reducing useful heat lost from the flue. As a consequence, the gases are also sent to the
chimney or stack at a lower temperature, allowing simplified design of the ducting and stack.
It also allows control over the temperature of gases leaving the stack (to meet emissions
regulations, for example).After extracting heat flue gases are passed to electrostatic
precipitator.
Electrostatic precipitator: It is a device which removes dust or other finely divided
particles from flue gases by charging the particles inductively with an electric field, then
attracting them to highly charged collector plates. Also known as precipitator. The process
depends on two steps. In the first step the suspension passes through an electric discharge
(corona discharge) area where ionization of the gas occurs. The ions produced collide with
the suspended particles and confer on them an electric charge. The charged particles drift
toward an electrode of opposite sign and are deposited on the electrode where their electric
charge is neutralized. The phenomenon would be more correctly designated as electrode
position from the gas phase.
The use of electrostatic precipitators has become common in numerous industrial
applications. Among the advantages of the electrostatic precipitator are its ability to handle
large volumes of gas, at elevated temperatures if necessary, with a reasonably small pressure
drop, and the removal of particles in the micrometer range. Some of the usual applications
are: (1) removal of dirt from flue gases in steam plants; (2) cleaning of air to remove fungi
and bacteria in establishments producing antibiotics and other drugs, and in operating rooms;
(3) cleaning of air in ventilation and air conditioning systems; (4) removal of oil mists in
machine shops and acid mists in chemical process plants; (5) cleaning of blast furnace gases;
(6) recovery of valuable materials such as oxides of copper, lead, and tin; and (7) separation
of retile from zirconium sand.
Smoke Stack: A chimney is a system for venting hot flue gases or smoke from a boiler,
stove, furnace or fireplace to the outside atmosphere. They are typically almost vertical to
ensure that the hot gases flow smoothly, drawing air into the combustion through the
chimney effect (also known as the stack effect). The space inside a chimney is called a flue.
Chimneys may be found in buildings, steam locomotives and ships. In the US, the term
smokestack (colloquially, stack) is also used when referring to locomotive chimneys. The
term funnel is generally used for ship chimneys and sometimes used to refer to locomotive
chimneys. Chimneys are tall to increase their draw of air for combustion and to disperse
pollutants in the flue gases over a greater area so as to reduce the pollutant concentrations in
compliance with regulatory or other limits.
What is FIRE?
FIRE is a chemical combustion reaction with evaluation of heat or light.
Fire Tetrahedron
• Basic components of a fire are:
– fuel
– source of ignition
– oxygen
– process of combustion
• Commonly referred to as the "fire tetrahedron"
Stage / Phase of fire
1. Incipient Stage. - A) Invisible Smoke. B) Smoke.
2. Smothering Stage.
3. Flame.
4. Heat.
5. Hazard (if heat cannot be control).
Classification of Fire
Fire is a chemical reaction involving the rapid oxidation or burning of a fuel. It needs four
elements to occur as illustrated below in the tetrahedron. This is described by the following
illustration:
The first component of the tetrahedron is fuel. Fuel can be any combustible material such as:
solid (such as wood, paper, or cloth), liquid (such as gasoline) or gas (such as acetylene or
propane). Solids and liquids generally convert to gases or vapours before they will burn.
Another component of the tetrahedron is oxygen. Fire only needs an atmosphere with at least
16% oxygen.
Heat is also a component of the tetrahedron. Heat is the energy necessary to increase the
temperature of the fuel source to a point in which sufficient vapours are emitted for ignition
to
occur.
The final side of the tetrahedron represents a chemical chain. When these components are
brought together in the proper conditions and preparations, fire will develop. Take away any
one of these elements, and the fire cannot exist or will be extinguished if it was already
burning.
Fires are classified into four groups according to sources of fuel: Class A, B, C, and D based
on the type of fuel source. Table 1 below describes the classifications of fire which can be
used in making hazard assessment.
Extinguishing Agent
A material used to control/terminate a fire by cooling the material in the combustion process,
obstructing the supply of oxygen to the combustion process, or chemically inhibiting the
combusting process.
A – Aim the nozzle low Aim the nozzle or the outlet towards the base of the fire. Some hose
assemblies are clipped to the body of the extinguisher, and then release the hose and point.
S – Squeeze the handle, lever
Squeeze the handle, lever to release the extinguishing agent.
In some cases valves are present. Before approaching the fire try a short burst.
S – Sweep from side to side at the base of the fire until it is out. After fire is doused,
watch for the smoldering hot spots and possible re-flash. Put off the fire completely.
Method of Extinguishment
1. Cooling
2. Smothering
3. Starvation
Safety Precautions for Maintenance of Extinguisher
While opening any extinguisher.
(a)Ensure that there is no residential pressure in any hose or nozzle.
(b)Unscrew the cap or valve assembly slowly for 2 or 3 turns to allow any residential
pressure to escape via the vent hole.
(c)Do not depend on pressure gage (Stored pressure type) to verify the pressure.
(d)If pressure is not released after unscrewing the cap then do not unscrew it further - sudden
release of pressure may eject parts, cap assembly or the contents of the extinguisher.
(e)The valves of co2 extinguisher /gas cartridge extinguisher should not be attempted to be
removed.
(f)Dry powder extinguisher should be opened only in the driest condition & for minimum
time to minimize the effect of moisture on it. Moisture cause caking of the powder.
(g)Mixing of different types of powder should be avoided as it may cause chemical making.
(h)All sealing component should be cleaned & properly lubricated to prevent leakage after
recharge.
(i)Never connect a stored pressure extinguisher to be charged directly to the high pressure
source.
(j)Storage of recharge material for long periods should be avoided.
Selection of Location
1. To be placed in conspicuous position & shell be readily accessible for immediate use.
2. As near as possible to exits or stairs with out hindering the escape routes.
3. Not to travel more than 15m from the site of fire to reach the extinguisher.
4. If special risk is contained in a confined space ,extinguisher to be installed outside that
space.
5. Wall mounted extinguisher – bottom 1m above ground level.
6. Necessary to construct suitable cover/shade to protect extinguisher.
7. Extinguisher should not be placed in the open from excessive heat & cold as well as from
corrosive environment.
1. Dry Riser.
2. Wet Riser.
3. Dry cum Wet Riser.
4. Yard Hydrant.
5. Automatic Water Sprinkler.
6. Water Spray Projector.
7. City Fire Fighting Water Supply.
DRY RISER
Dry riser are suitable in some buildings not more than 61mts.in height, where prompt fire
brigade help is available and where fire brigade is located within a distance of 8km.from the
building and has easy access thereto unimpeded by railway level crossing and traffic
congestion. A satisfactory supply of water shall always be available through the town mains
or a ground/underground tank. Dry riser shall be installed only in consultation with the
appropriate authority and their approval of the scheme.
Design Parameter
1. Each riser serves area not more than 930 sq.mt.
2. Riser should be located at easily approachable location.
3. Riser should be of 100mm internal dia. For buildings having ht. up to 46mts. And
150mm for buildings having ht. between 46mts. To 61mts.
4. Fire brigade breaching connection with instantaneous male inlet 2*65mm.for each
100mm.dia.riser and 4*65mm.for each150mm.dia.riser.
5. Fire brigade inlet are fixed on an external wall at 1mt.above ground level, stand
within
12mts.of distance from riser.
6. Inlet are enclosed in a wall box with wired glass front marked as “FIRE BRIGADE
DRY MAIN INLET”.
7. A 65mm. instantaneous female outlet should be provided at 1mts.height from floor
level on each floor.
8. The outlet must meet the requirement at the local Fire authority and Fire Brigade.
9. An air release valve is fitted at the top of each riser to release compressed air during
pumping operation.
10.Each dry riser must be electrically earthed by a direct earth
connection.
Water is a cheapest and readily and naturally available means of fire extinguishing. It has
four times more thermal conductivity then air. With the help of automatic sprinkler system in
less quantity of water more area can be extinguished. In this process water is sprayed in fine
droplets. In this process the surrounding space is filled with fine droplet. Due to this percent
of oxygen in the surrounding area goes down and temperature also goes down. This two
aspect help in extinguishing the fire. Thus automatic water sprinkler system gives a facility
to discharge water automatically in sufficient density to extinguish the fire.
This type of system is used, where temperature of water , inside the piping network, is
maintained above freezing point of water. In this system the piping network is fully charged
with water at required pressure. As soon as sprinkler heads actuate, discharge of water start
in form of spray.
Alarm check valve and water flow detector are installed in the system to actuate local and
remote alarms.
B.A Set
i) Atmospheric Type
(ii) Self Contained type
(a)Closed Circuit (b) Open Circuit
E.g. Proto, Salvos. E.g. Drager.
Respiration
Breathing or respiration is a spontaneous action performed by the human body some 15-30
times every minute. When at rest the body requirement are comparatively low and air is
sucked into & out of the lungs by breathing a rate 15-18 times/minute. When more energy is
exerted either through work excitement, the breathing rate is increased. i.e. 30 times/minute.
At rest ,about 30 inch3(1/2 it apox) air are normally inhaled at each breath & about the same
quality is exhaled – this amount is known as Tidal Air. By taking a deep breath a further 120
inch3 may be taken in making a total of 150 inch3 – this is known as Inspiratory Rescue.
On subsequent deep exhalation this may be increased by further 100 inch3 called the
Expiratory Rescue volume and the total exhalation as about 250 inch³. Thus the total exhaled
is known as the Vital Capacity & varies with different people.
U N Classification
Colour Coding
Class 2 - Gases
2.1 Flammable Gases Red.
2.2 Non-flammable Gases Green.
2.3 Poison/Toxic Gases White.
Class 4 - Solids
4.1 Flammable Solids White
4.2 Spontaneously Combustible Material Red
4.3 Materials these are dangerous when wet Blue
Types of signals
Fire alarm system may provide 3 types of signals – Alarm, Supervisory & Trouble.
A supervisory signal indicates that action is needed in connection with the operation of other
fire protection systems those are monitored by fire-alarm system.
Basics
Fire-alarm systems are classified according to the function. They are expected to perform.
The basic components of each system are –
1. A system Control unit.
2. A primary or main power supply.
3. A secondary or stand – by power supply.
4. one or more initiating device circuit or signalling line circuit.
5. One or more fire alarm notification appliance circuit.
6. Many system also have an off – premises connection by means of an auxiliary fire alarm
system.
Circuit
Fire alarm system have 3 basic types of circuit
1. Initiating Device Circuit (IDC).
2. Notification Appliance Circuit (NAC).
3. Signalling Line Circuit (SLC).
Many fire-alarm system control units have more than one initiating device circuit so that
the fire location can be indicated on an enunciator panel by floor, wing, subsection, or room.
The enunciator can be built into the control unit or located in a lobby,
maintenance area, telephone switchboard room or some other location easily accessible to
fire service personnel.
DETERMINING FIRE HAZARDS
This section consists of two steps: first, identifying the existing fire hazards in the workplace
and, second, taking action to resolve them. The inspection checklist, in Appendix A,
provides a guide for precise fire-safe practices that must be followed. The location of these
major fire hazards are denoted in Appendix C. Also included in Appendix C is a listing of
the personnel responsible for the maintenance of the equipment and systems installed to
prevent or control fires.
Material hazards shall be identified, as evident on the specific Material Safety Data Sheets
(MSDS), and label on containers as soon as they arrive in the workplace. The
identification system shall also include incorporation into the company’s hazard
communication program.
OXYGEN-ENERGIZED ATMOSPHERES
Oxygen-enriched atmospheres involve operating rooms and anesthesia machines, oxygen
tents as used by ambulances, fire and police or rescue squads; hospitals and laboratory
supply systems; cutting and welding. If practical, non-flammable anesthetic agents will be
used. To prevent dangerous adiabatic heating of flammable anesthetic gases, the cylinder
valves will be opened very slowly to allow the gradual introduction of the high pressure gas
downstream from the cylinder valve. This will permit a slow build up of pressure and hence
temperature. An aid to the identification of hazards associated with medical agents and gases
in NFPA 704, Standard Systems for the Identification of the Fire Hazards of Materials.
INDUSTRIAL TRUCKS
The type of industrial truck being used shall be approved for use within any building storing
hazardous materials. All re-fueling operations shall be conducted outside and away from
storage of flammable materials. Areas that are used for maintenance and battery charging of
electrical trucks should be separated from storage areas.
ORDINARY COMBUSTIBLE
• Wooden pallets will not be stacked over 6 feet tall. If feasible, extra pallets will be stored
outside or in separate buildings to reduce the risk of fire hazards.
• Piles of combustible materials shall be stored away from buildings and located apart from
each other sufficiently to allow firefighting efforts to control an existing fire.
FLAMMABLE MATERIALS
• Bulk quantities of flammable liquids shall be stored outdoors and away from buildings.
Smaller quantities are subsequently brought into a mixing room where they are prepared for
use. The mixing room shall be located next to an outside wall equipped with explosion relief
vents. The room shall also have sufficient mechanical ventilation to prevent the accumulation
of flammable vapor concentration in the explosive range.
• Small quantities (limited to amount necessary to perform an operation for one working
shift)
of flammable liquids shall be stored in, and also dispensed from, approved safety containers
equipped with vapor-tight, self-closing caps, screens or covers.
• Flammable liquids shall be stored away from sources that can produce sparks.
• Flammable liquids shall only be used in areas having adequate and, if feasible, positive
ventilation. If the liquid is highly hazardous, the liquid shall only be used in areas with a
local exhaust ventilation.
• Flammable liquids shall never be transferred from one container to another by applying air
pressure to the original container. Pressurizing such containers may cause them to rupture,
creating a serious flammable liquid spill.
• When dangerous liquids are being handled, a warning sign will be posted near the
operation, notifying other employees and giving warning that open flames are hazardous and
are to be kept away.
• The storage and usage areas will include fire-resistive separations, automatic sprinklers,
special ventilation, explosion-relief valves, separation of incompatible materials, and the
separation of flammable materials from other materials.
The automatic sprinkler system, if applicable, will adhere to NFPA 13, Standard for the
Installation of Sprinkler Systems. The sprinkler system and components will be electrically
supervised to ensure reliable operation. This includes gate valve tamper switches with a local
alarm at a constantly attended site when the valve is closed. If a single water supply is
provided be a connection to the city mains, a low pressure monitor is included. If pressure
tanks are the primary source of water, air pressure, water level, and temperature shall be
supervised. If fire pumps are provided to boost system pressure, supervision will monitor
loss of pump power, pump running indication, low system pressure, and low pump suction
pressure.
In hospitals, every patient sleeping room will be provided with an outside window or door
that can be opened from the inside; this will allow venting of products of combustion if there
is a fire. A specially designed smoke control system can be a substitute for an outside
window.
Portable fire extinguishers are placed in a building. Fire extinguishers must be kept fully
charged and in their designated places. The extinguishers will not be obstructed or obscured
from view. A map indicating the locations of all fire extinguishers for this company is
located in Appendix E. The fire extinguishers will also be inspected at least monthly, to
make sure that they are in their designated places, have not been tampered with or actuated,
and are not corroded or otherwise impaired. Attached inspection tags shall be initialed /dated
each month.
The location of all hydrants, hose houses, portable fire extinguishers, or other fire protective
equipment should be properly marked with arrows and signs painted on the pavement.
TRAINING
All employees shall be instructed on the locations and proper use of fire extinguishers in
their work areas. Employees shall also be instructed as to how to operate the building’s fire
alarm system, and be familiar with evacuation routes. The training of all employees shall
include the locations and types of materials and/or processes which pose potential fire
hazards. The training program shall also emphasize the following:
1. Use and disposal of smoking materials
2. The importance of electrical safety
3. Proper use of electrical appliances and equipment
4. Unplugging heat-producing equipment and appliances at the end of each work day
5. Correct storage of combustible and flammable materials
6. Safe handling of compressed gases and flammable liquids (where appropriate) Ongoing
training shall include regularly scheduled fire drills. Training documentation shall be place in
Appendix D.
ELECTRICAL EQUIMENT
_ No makeshift wiring.
_ Fuse and control boxes clean and closed.
_ Extension cords serviceable.
_ Circuits properly fused or otherwise protected.
_ Motors and tools free of dirt and grease.
_ Equipment approved for use in hazardous areas (if required).
_ Lights clear of combustible materials.
_ Safest cleaning solvents used.
FRICTION
_ Machinery properly lubricated.
_ Machinery properly adjusted and/or aligned.
SPECIAL FIRE-HAZARD MATERIALS
_ Storage of special flammable isolated.
_ Non-metal stock free of tramp metal.
OPEN FLAMES
_ Kept away from spray rooms and booths.
_ Portable torches clear of flammable surfaces.
_ No gas leaks.
PORTABLE HEATERS
_ set up with ample horizontal and overhead clearances.
_ safely mounted on non-combustible surfaces.
_ Secured against tipping or upset.
_ Use of steel drums prohibited.
_ Combustibles removed or covered.
_ Not used as rubbish burners.
HOT SURFACES
_ hot pipes clear of combustible materials.
_ Soldering irons kept off combustible surfaces.
_ ample containers available and serviceable.
_ Ashes in metal containers.
SPONTANEOUS IGNITION
_ Flammable waste material in closed, metal containers.
_ piled material, dry, and well ventilated.
_ Flammable waste material containers emptied frequently.
_ Trash receptacle emptied daily.
STATIC ELECTRICITY
_ Flammable liquid dispensing vessels grounded and bonded.
_ Proper humidity maintained.
_ Moving machinery grounded.
HOUSEKEEPING
_ No accumulation of rubbish.
_ Premises free of unnecessary combustible materials.
_ Safe storage of flammables.
_ No leaks or dripping of flammables and floor free of spills.
_ Passageways clear of obstacles.
_ Fire doors unblocked and operating freely.
_ Automatic sprinklers unobstructed.
FIRE PROTECTION
_ Proper type of fire extinguisher.
_ extinguishing system in working order.
_ Fire extinguisher in proper location.
_ Service date current.
_ Access to fire extinguishers unobstructed.
_ Personnel trained in use of equipment.
_ Access to fire extinguishers clearly marked.
_ Personnel exits unobstructed and maintained.
_ Fire protection equipment turned on.
(1) Alarm raiser (2) incident controller (3) Main controller (4) Emergency team
including engineers and experts (5) Fire fighting team (6) Gas control team (7) First –
aid and health care team (8) Ambulance & evacuation team (9) safety officer (10)
Security officer.
Names, designation, telephone number of above persons are to be displayed on main
notice board. Their function at time of emergency are to be laid down.