Fire Safety 3b
Fire Safety 3b
GROUP 3
Atrium : A large-volume space created by a floor opening or series of floor openings connecting two or
more stories that is covered at the top of the series of openings and is used for purposes other than an
enclosed stairway; lifts hoist-way; an escalator opening; or as a utility shaft used for plumbing,
electrical, air conditioning, or communications facilities.
Automatic Fire Detection and Alarm System : A system comprising components and sub-systems
required for automatically detecting smoke, heat or fire initiating an alarm and other actions as
appropriate. This system also includes manually operated electronic fire alarm (MOEFA) system.
Combustible Material : A material which either burns itself or adds heat to a fire, when tested for no
combustibility in accordance with accepted standard.
Evacuation Lift : Lift that can be used, during an emergency, for self-evacuation.
Exit Access : That portion of a means of egress that leads to an exit (for example, doorways, staircase
lobby, ramps, Veranda, corridor or passageway leading to an exit).
Exit Discharge : The component of a means of egress between the termination of an exit and a
public way.
Firefighting Shaft (Fire Tower) : An enclosed shaft having protected area of 120 min fire resistance
rating comprising protected lobby, staircase and fireman lift, connected directly to exit discharge or
through exit passageway with 120 min fire resistant wall at the level of exit discharge to exit
discharge. These shall also serve the purpose of exit requirement/ strategy for the occupants.
Fire Load : Calorific energy, of the whole contents contained in a space, including the facings of the
walls, partitions, floors and ceilings.
Fireman's Lift : A lift or a group of lifts invariably associated with all the features and requirements
of a fire-fighting shaft. Such lifts are installed to enable fire services personnel to reach different
floors with minimum delay, and shall meet the additional features as required in accordance with
this Part. This lift also serves the purpose of meeting the requirement of evacuation lift for assisted
evacuation.
Fire Resistance Rating : The time that a material or construction will withstand the standard fire
exposure as determined by fire test done in accordance with the standard methods of fire tests of
materials/ structures as per the accepted standard [
Fire Separation : The distance in meter, measured from the external wall of the building concerned
to the external wall of any other building on the site, or from other site, or from the opposite side of
street or other public space for the purpose of preventing fire.
Fire Stop : A fire resistant material, or construction, having a fire resistance rating of not less than
the fire separating elements, installed in concealed spaces or between structural elements of a
building to prevent the spread/propagation of fire and smoke through walls, ceilings and the like as
per the laid down criteria.
Fire Wall or Fire Separating Wall : A fire resistance rated wall having fire protected openings,
which restricts the spread of fire and extends continuously from the foundation to the roof (and
through the roof at least 1m above the roof in case of combustible roof), with sufficient structural
stability under fire conditions to allow collapse of construction on one side or either side without
collapse of the wall.
•Lift Lobby - A space from which people directly enter a lift car(s) and into which people directly enter
•upon exiting a lift car(s).
•Means of Egress - A continuous way of travel from any point in a building or structure to a public
•way, consisting of three separate and distinct parts, that is, exit access, exit and exit discharge.
•Means of Escape - A way out of a building or structure that does not conform to the strict definition
•of ‘means of egress’ but does provide an alternate way out.
•Pressurization - The establishment of a pressure difference across a barrier to protect exit, stairway,
•lobby, exit passageway or room of a building from smoke penetration.
•Refuge Area - An area within the building for a temporary use during egress. It generally serves as a
•staging area which is protected from the effect of fire and smoke.
•Roof Exits - A means of escape on to the roof of a building, where the roof has access to it from the
•ground through alternative stair case or adjacent building.
•Smoke Barrier - A continuous membrane, or a membrane, where such membrane is designed and
•constructed to restrict the movement of smoke.
•Smoke Compartment - A space within a building enclosed by smoke barriers on all sides.
•Travel Distance - The distance to be travelled from any point in a building to a protected exit or
•external escape route or final exit measured along the line of travel.
•Ventilation - Supply of outside air into, or the removal of inside air from an enclosed space.
•Hydrant System - A distribution system having a network of piping installed underground/above ground
around and/or through inside of a building with internal and/or external hydrants fitted with landing valves
at regular intervals according to the occupancy.
•Automatic Sprinkler System - A system of water pipes fitted with sprinkler heads at suitable intervals
•and heights and designed to actuate automatically, control and extinguish a fire by the discharge of water.
•Automatic Water Spray Systems - A special fixed pipe system connected to a reliable source of fire
•protection water supply and equipped with water spray nozzles for specific water discharge and distribution
•over the surface or area to be protected.
•Foam Protection System - Firefighting systems where foam is made by mechanically mixing air with a
•solution consisting of fresh water to which a foaming agent (liquid concentrate) has been added. Firefighting
•foam is a stable aggregation of small bubbles of density lower than oil or water, and shows tenacious qualities
•for covering horizontal surfaces.
•Fire Zone No. 1 - This shall comprise areas having residential (Group A), educational
•(Group B), institutional (Group C), assembly (Group D), small business (Subdivision E-1)
•and mercantile (Group F) buildings, or areas which are under development for such occupancies.
•Fire Zone No. 2 - This shall comprise business (Subdivisions E-2 to E-5) and
•industrial buildings (Subdivisions G-1 and G-2), except high hazard industrial buildings
•(Subdivision G-3) or areas which are under development for such occupancies.
•Fire Zone No. 3 - This shall comprise areas having high hazard industrial buildings
•(Subdivision G-3), storage buildings (Group H) and buildings for hazardous uses (Group J) or areas which are
under development for such occupancies.
•Unless otherwise specified, lifts, escalators, moving walks and revolving doors shall not be
•considered as exits and shall not constitute any part of the required exit.
•Every exit, exit passageway and exit discharge shall be continuously maintained free of all obstructions
•or impediments to full use in the case of fire or other emergency.
•Every building having human occupancy shall be provided with exits sufficient to permit safe egress
•of occupants, in case of fire or other emergency.
•In every building or structure, exits shall comply with the minimum requirements of this Part, except
•those not accessible for general public use.
•No building shall be so altered as to reduce the number, width or protection of exits to less than that
•required
•For non-naturally ventilated areas, fire doors with 120 min fire resistance rating shall be provided and
•particularly at the entrance to lift lobby and stair well
• Exits shall be so arranged that they may be reached without passing through another occupied unit/passage
in others control, if they pose challenge or restriction in means of egress.
• At least half of the required exit stairs from upper floors (rounded to the next higher number) shall
discharge directly to the exterior or through exit passageways.
• Unless otherwise specified, all the exits and exit passagewaysto exit discharge shall have a clear ceiling
height of at least 2.4 m. However, the height of exit door shall be at least 2.0 m.
• he capacity of the means of egress required from any storey of the building shall not be reduced
along the path of egress travel until arrival to the exit discharge.
• The lifts, escalators, moving walks, turnstiles and revolving doors shall not be considered in
determining the required capacity of means of egress for the individual floor(s) or the building.
• Suitable means shall be provided so that all access controlled exit doors, turnstiles, boom barriers
and othersuch exits shall automatically operate to open mode during emergencies like fire, smoke, acts of
terrorism, etc, so that people can safely and quickly egress into safe areas outside.
Exits shall be placed as remote from each other as possible and shall be arranged to provide direct access in
separate directions from any point in the area served.
DOORS
Access controlled doors . Access controlled doors and electromagnetic doors shall fall under this
category. These shall meet the following requirements:
1) Doors shall have fire rating as per the requirements at the location of installation.
2) Activation of the building automatic sprinkler or fire detection system, if provided, shall
automatically unlock the doors in the direction of egress, and the doors shall remain unlocked
until the
automatic sprinkler system or fire-alarm system has been manually reset.
3) Loss of power to the part of the access control system that locks the doors shall automatically
unlock the doors in the direction of egress.
4) A manual release device shall be provided in the readily accessible vicinity of the egress door
with a signage .PUSH TO EXIT. and when the same is operated, it shall result in direct interruption
of power to the lock, independent of the acces control system electronics.
In the case of buildings where there is a central corridor, which is part of exit access, the doors
of rooms (except for rooms having assembly occupancy) shall open inwards to permit smooth
flow of traffic in the corridor.
STAIRCASE
All exit staircases shall discharge, at the level of exit discharge, to the exit discharge, either,
a) directly, or
b) through an exit passageway, or
c) through a large lobby.
The minimum width of tread without nosing shall be250 mm for staircase of residential buildings.
This shall be minimum 300 mm for assembly, hotels, educational, institutional, business and other
buildings.
The treads shall be constructed and maintained in a manner to prevent slipping. The maximum
height of riser shall be 150 mm as per our requirements. The number of risers shall be limited to 12
per flight.
Source: NBC 2016
INTERNAL STAIRCASES
The internal staircases may be constructed with an external wall, or otherwise, and shall comply with the
following:
a) Internal stairs shall be constructed of non- combustible materials throughout, and shall have fire resistant
rating of minimum 120 min.
d) No flue chimney, electromechanical equipment, air conditioning units, gas piping or electrical panels
shall be allowed in the stairway.
e) Not withstanding the detailed provision for exits, the following minimum width shall be provided for
staircases for respective occupancies:
A handrail shall be provided on one side of the staircase of width less than 1 500 mm, and on both sides of
the staircase of width 1500 mm and more.
The minimum headroom in a passage under the landing of a staircase and under
the staircase shall be 2.2 m.
Access to exit staircase shall be through a fire door of a minimum 120 min fire resistance rating.
No living space, store or other fire risk shall open directly into staircases.
The exit (including staircases) shall be continuous from refuge floors or terrace level, as applicable, to the
level of exit discharge. No electrical shafts/air conditioning ducts or gas pipes, etc, shall pass through or open
in the staircases.
8) Beams/columns and other building features shall not reduce the head room/width of the staircase.
All external stairs shall be directly connected to the ground. Entrance to the external stairs
shall be separate and remote from the internal staircase.
The external stairs shall be constructed of non- combustible materials, and any doorway
leading to it shall have minimum 120 min fire resistance.
No external staircase, shall be inclined at an angle greater than 45° from the horizontal.
External stairs shall have straight flight not less than 1500 mm wide.
Handrails, to be provided on both sides, shall be of a height not less than 1 000 mm and not
exceeding 1200 mm. There shall be provisions of balusters with maximum gap of 150 mm.
The use of spiral staircase shall be limited to low occupant load and to a building not
exceeding 9 m in height. A spiral staircase shall be not less than 1 500 mm in diameter and
shall be designed to give adequate headroom.
Ramps shall have landings located at the top, at the bottom, and at
doors opening onto the ramp.
Every landing shall be not less than 1 500 mm long in the direction of
travel.
Where the ramp is not part of an accessible route, the ramp landings
shall not be required to exceed 1250 mm in the direction of travel,
provided that the ramp has a straight run.
Source: NBC 2016
Handrails shall be provided on all ramps on both sides.
PRESSURIZATION
Pressurization is a method adopted for protecting the exits from ingress of smoke, especially in high-
rise buildings. In pressurization, air is injected into the staircases, lobbies, etc, as applicable, to raise their
pressure slightly above the pressure in adjacent parts of the building. As a result, ingress of smoke or toxic
gases into the exits will be prevented. The pressurization of staircases and lift lobbies shall be adopted as
given in the table.
• Lift shafts shall have a vent at the top of area not less than 0.2 sq m.
• Lift motor room shall be located preferably on top of the shaft and separated from the
shaft by the floor of the room.
• The number of lifts in one lift bank shall not exceed four.
• For buildings 15.0 m. and above in height, collapsible gates shall not be permitted
• Exit from the lift lobby, if located in the core of the building, shall be through a self-
closing fire smoke check door of one-hour fire resistance.
• Suitable arrangements such as providing slope in the floor of the lift lobby shall be
made to prevent water used during fire fighting, etc at any landing from entering the
lift shafts.
Provision of helipad
• All high-rise buildings of height 200 m. and above shall have provision for a Helipad
as per clause no 5.5.8 of the Bye-Laws.
• Service duct shall be enclosed by walls and door, if any, of 2 hours fire rating.
• If ducts are larger than 10 sq m. the floor should seal them, but provide suitable opening
for the pipes to pass through, with the gaps sealed.
• A vent opening at the top of the service shaft shall be provided between one-fourth and
one-half of the area of the shaft.
• Refuge chutes shall have an outlet at least of wall of non-combustible material with fire
resistance of not less than two hours.
• They shall not be located within the staircase enclosure or service shafts or air-
conditioning shafts.
• Refuge chutes shall not be provided in staircase walls and A/C shafts etc
• The basement shall be partitioned and in no case compartment shall be more than 500 sq m. and less
than 50 sq m. area except parking. Each compartment shall have ventilation standards as laid down in
Bye-Laws separately and independently. The partition shall be made in consultation with Chief Fire
Officer.
• The first basement (immediately below ground level) can be used for services/parking/other permissible
services. Lower basement, if provided, shall exclusively be used for car parking only.
For all buildings with a height of 15 m and above and Group Housing with a height of 30m and above, there
shall be a control room on the entrance floor of the building with communication system (suitable public
address system) to all floors and facilities for receiving the message from different floors. Details of all floor
plans along with the details of firefighting equipment and installations shall be maintained in the fire control
room. The fire control room shall also have facilities to detect the fire on any floor through indicator board
connections; fire detection and alarm systems on all floors. The fire staff in-charge of the fire control room
shall be responsible for the maintenance of the various services and firefighting equipment and installations in
co-ordination with security, electrical and civil staff of the building.
a) These shall be located in air ducts and return air ducts/passages at the following points:
i) At the fire separation wall.
ii) Where ducts/passages enter the central vertical shaft.
iii) Where the ducts pass through floors.
iv) At the inlet of supply air duct and the return air duct of each compartment on every floor.
b) The dampers shall operate automatically and shall simultaneously switch off the air- handling
fans. Manual operation facilities shall also be provided.
Note: For blowers, where extraction system and dust accumulators are used, dampers shall be
provided.
c) Fire/smoke dampers (for smoke extraction shafts) for building more than 24 m. in height.
For apartment houses in non-ventilated lobbies/corridor operated by detection system and
manual control sprinkler system.
For other buildings on operation of smoke/heat detection system and manual control/sprinkler
system.
d) Automatic fire dampers shall be so arranged so as to close by gravity in the direction of air
movement and to remain tightly closed on operation of a fusible link.
•Fire escapes shall not be taken into account in calculating the evacuation time of a building.
•Entrance to fire escape shall be separate and remote from the internal staircase.
•The route to fire escape shall be free of obstructions at all times, except a doorway leading to the fire escape
which shall have the required fire resistance.
•Fire escapes stairs shall have straight flight not less than 75cm wide with 25 cm treads and risers not more
than 19 cm. The number of risers shall be limited to 16 per flight.
•The use of spiral staircase shall be limited to low occupant load and to a building of height 9 m unless they
are connected to platforms, such as balconies and terraces to allow escapes to pause.
•A spiral fire escape shall be not less than 150cm in diameter and shall be designed to give adequate head
room.
Source: NBC 2016
RAMPS
•Ramps with a slope of not more than 1 in 10 may be substituted for and shall comply with all the
applicable requirements of required stairway as to enclosure, capacity and limiting dimensions.,
Large slopes shall be provided for special uses but in no case greater than 1 in 8. For all slopes
exceeding 1 in 10 and where the use is such as to involve danger of slipping, the ramp shall be surfaced
with approved non-slipping material.
•Ramps shall lead directly to outside open space at ground level or courtyards or safe place.
•For building above 24 m in height, access to ramps from any floor of the building shall be through
smoke stop door.
•In case of more than one main staircase of the building inter-connected by a
corridor or other enclosed space, there shall be atleast one smoke stop door across
the corridor or enclosed space between the doors in the enclosing walls of any two
staircases.
•Refuge Area-For all buildings exceeding 15 m in height, refuge area shall be provided as follows :
for floors above 15 m and upto 24 m -one refuge area on the floor immediately above 18m.
for floors above 24 m and upto 36 m-one refuge area on the floor immediately above 24m.
for floors above 36 m-one refuge area per every five floors above 36m
• Refuge area shall be provided on the external walls as cantilever projections or in any other manner
(which will not be covered in FAR) with a minimum area of 15 sq mtr. And to be calculated based on
the population on each floor at the rate of 1 sq.m. per person.
•All the floors shall be accessible for 24 hours by the lifts. The lifts provided in the
buildings shall not be considered as a means of escape in case of emergency.
•Grounding switch at ground floor level to enable the fire service to ground the lift
in case of an emergency shall also be provided.
•The lift machine room shall be separate and no other machinery shall be installed
there in.
Buildings shall be planned, designed and constructed to ensure fire safety and this shall be done in
accordance with para IV Fire Protection of national Building code of India, unless otherwise specified
in these bye-laws. In the case of buildings (identified in Bye-laws No. 6.2.4.1), the building schemes
shall also be cleared by the Chief Fire Officer, Delhi Fire Service.
The additional Provisions related to fire protection of buildings more than 15 m is height and
buildings identified in Bye-law No. 6.2.4.1, shall be as given in Appendix-K
GENERAL REQUIREMENT
In addition to the provisions of part IV Fire Protection of National Building Code of India, the Chief
Fire Officer, Delhi Fire Service may insist on suitable provisions in the buildings from fire safety and
fire fighting point of view depending on the occupancy and height of buildings.
•The internal enclosing walls of staircase shall be of brick or R.C.C. construction having fire resistance of
not less than two hours. All enclosed staircases shall have access through self-closing doors of at least
half-hour fire resistance- These shall be single swing doors opening in the direction of the escape. The
door shall be fitted with check action door closers.
• The staircase enclosure on external wall of the building shall be ventilated to atmosphere at each
landing.
• Permanent vent at the top equal to 5% of the cross sectional area of the enclosure and openable sashes'
at each floor level with area equal to 15% of the cross sectional area of the enclosure of external wall shall
be provided. The roof of the shaft shall be at least lm above the surrounding roof. There shall be no
glazing or glass bricks in any internal enclosing wall of a staircase. 1f the staircase is in the core of the
building and cannot be ventilated at each landing, a positive pressure of 5-mm. w.g. by an electrically
operated blower/blowers shall be maintained.
• The mechanism for pressurizing the staircase shaft shall be so installed that the same shall operate
automatically and also with manual operation facilities, when the automatic fire alarm (See Bye-law No.
K. 11) operates.
• The walls enclosing lift shafts shall have a fire resistance of not less than two hours. Shafts shall
have permanent vents at the top not less than 1 800 sq. mm. in clear area. Lift motor rooms
preferably be sited at the top of the shaft and shall be separated from lift shafts by the enclosing
wall of the shaft or by the floor of the motor rooms.
• Landing doors in lift enclosures shall open in the ventilated or pressurized corridor/lobby and
shall have fire resistance of not less than one hour.
• The number of lifts in one lift bank shall not exceed four. Shaft for fire lift in a lift bank shall be
separated from each other by a brick masonry or RCC wall of fire resistance of not less than two
hours.
•If the lift shaft and lift lobby are in the core of the building a positive pressure of not less than 2.5
mm and not more than 3 mm. w.g. by an electrically operated blower shall be maintained in the lift
lobby and positive pressure of not less than 5 mm w.g. shall be maintained in the lift shaft. The
mechanism for pressurising the lift shaft and lift lobby shall be so installed that they shall operate
automatically when the automatic fire alarm operates. The mechanism shall have facilities to
operate manually.
• Exit from the lift lobby shall be through a self-closing smoke stop door of half-hour fire
resistance.
• The lift machine room shall be separate and no other machinery shall be installed therein.
• Lifts shall not normally communicate, with the basement. However, one of the lifts may be
permitted to reach the basement levels provided the lift lobby at each basement level is
pressurized and separated from the rest of the basement areas, by smoke actuated fire
resisting door of two hours fire resistance.
•Each basement shall be separately ventilated. Vents with cross sectional area (aggregate) not less than
2.5% of the floor area spread evenly round the perimeter of the basement shall be provided in the form
of grills or breakable stall-boards light or payment light or by way of shafts.
•The staircase of basements shall be of enclosed type having fire resistance of not less than two hours
and shall be situated at the periphery of the basement and shall communicate with basement through a
lobby provided with fire resisting self-closing doors of half-hour fire resistance. If the travel distance
exceeds 18.50m additional staircases at proper places shall be provided.
SERVICE DUCTS
•Service ducts for electrical conduits, cables etc.shall be enclosed by walls having a fire resistance of not
less than two hours. Doors for inspection or access shall also have a fire resistance of not less than two
hours.
•If the. Cross-sectional area exceeds 1 sq. m. it shall be sealed where it passes a floor by carrying the floor
through the duct. The floor within the duct shall be pierced for any service pipe or ventilation trunk and
shall fit as closely as possible around any such pipe or trunk.
•Hoppers to refuse chutes shall be situated in well ventilated positions and the chutes shall
be continued upwards with an outlet above roof level and with an enclosure wall of non-
combustible material with fire resistance of not less than two hours. The hoppers shall not
be located within the staircase enclosure.
• Inspection panel and hopper (charging station) opening shall be fitted with tight fitting
metal doors, covers, having a fire resistance of not less than one hour.
• Refuse chutes shall not be provided in staircase walls, air-conditioning shafts, etc. K-6.4
Refuse chambers shall have walls and floors of roofs constructed of non-combustible and
impervious material and shall have a fire resistance of not less than two hours. They shall be
located at a safe distance from exit routes.
•The lift shall have a floor area of not less than l.5 sq.m. It shall have loading capacity of not less than 500
kg. (8 persons lift) with automatic closing doors.
•The electric supply shall be on a separate service from electric supply mains in a building and cables run
in route safe from fire, that is, within the lift shaft. In case of failure of normal electric supply it shall
automatically trip over to alternate supply.
•The operation of a fire lift is a simple toggle or two button switch situated in a glass fronted box adjacent
to the lift at the entrance level. When the switch is on, landing call-points will become inoperative and the
lift will be on car control only. When the switch is off, the lift will return to normal working. This lift can
be used by the occupants in normal times.
•The words "FIRE LIFT" shall be conspicuously displayed in fluorescent paint on the lift landing doors at
each floor level.
•For buildings above 15 m in height collapsible gates shall not be permitted for lifts and shall have solid
doors with fire resistance of 2 hours.
Source: NBC 2016
THANKYOU
QUIZ
Ques.1) Fire resistance of a building depends on?
b) Integrity (E)
c) Insulation(I)
a) 15 m
b) 7 m
c) 12 m
d) 10 m
a) 15 m
Ques.4) The travel distance in case of dead-end shall be?
a) 7.5 m
b) 10.5 m
c) 15 m
d) 9 m
a) 7.5 m
Ques.5) The staircase of basement shall be of enclosed type having fire
resistance of not less than
a) 2 hours
b) 1.5 hours
c) 2.5 hours
d) 1 hour
a) 2 hours
Ques.6) A Fire Fighting shaft is an enclosed shaft having protected area of _____ fire resistance
rating comprising protected lobby, staircase and fireman lift, connected directly to exit
discharge or through exit passageway.
a) 120 mins
b) 100 mins
c) 140 mins
b) Adjacent to lift
a) 2.4 sq. mt
b) 1.4 sq. mt
a) 0.2
b) 0.4
c) 0.6
a) 0.2
Ques.10) Maximum number of lifts in one lift bank shall be :
a) 2
b) 4
c) 6
b) 4
Ques.11) Refuge chutes shall not be provided in
a) Staircase walls
b) A/C shafts
a) Fire compartment
b) Water Compartment
c) Smoke Compartment
c) Electricity Compartment
c) Smoke Compartment
Ques.13) For non-naturally ventilated areas, what should be the fire
resistance rating of the fire exit doors?
a) 180 mins
b) 150 mins
c) 120 mins
c) 90 mins
c) 120 mins
Ques.14) What is the continuous way of travel from any point in a building or structure to a public
way, consisting of three separate and distinct parts, that is, exit access, exit and exit discharge.
a) Means of escape
b) Means of egress
c) Emergency exit
a) 40m
b) 50m
c) 35m
d) 45m
d) 45m
Ques.17) Any changes in travel direction in ramp shall be preceded by landings of size?
a) 1.5m X 1.5 m
b) 1.2m X 1.2 m
c) 2.0m X 2.0m
a) 1:8
b) 1:15
c) 1:12
a) 1500 mm wide
b) 1250 mm wide
c) 1350mm wide
a) 2000 mm
b) 2100 mm
c) 1850mm