FIELD JEDDAH TEST No: HEA-160-P-05

COORDINATES (X,Y) 545063.715 2340958.312 Test Type (Pullout/Lateral) Pullout


THEORTICAL DEPTH (m): 2.55 PROFILE: HEA-160
REAL DEPTH (m): 2.55 DESIGN LOAD (kg): 2743.02
HEIGHT OF APPLIED LOAD (m): 1.70 DESIGN LOAD (N): 26909
TYPE OF FOUNDATION Direct Ramming TIME PILE DRIVING: 87
VERTICAL
PERCENTAJE OF THEORICAL REAL PERCENTAJE HOLDING TIME
COMMENTS APPLIED LOAD (N) DISPLACEMENT
LOAD LOAD (N) OF LOAD (min)
(mm)
0% 0 0.0 0% 0.0 0.00
25% 6727 6727.4 25% 5 0.39
50% 13455 13454.7 50% 5 0.44
75% 20182 20182.1 75% 5 0.85
100% 26909 26919.3 100% 5 1.52
30% 8073 8070.9 30% 5 1.39
0% 0 245.2 1% 1.22
50% 13455 13454.7 50% 5 1.32
100% 26909 26919.3 100% 5 1.73
125% 33636 33646.6 125% 5 2.52
150% 40364 40374.0 150% 5 3.58
175% 47091 47101.3 175% 5 6.12
200% 53818 53750.2 200% 5 7.60
220% 59200 59212.6 220% 5 9.27
250% 67273 67293.2 250% 5 14.57
300%

250%

200%
Load Percentaje

Loading 100%
150%
Unloading
Loading 200%
100%

50%

0%
0.00 2.00 4.00 6.00 8.00 10.00 12.00 14.00 16.00
Displacement (mm)

Post Inclination N-S: 0.2 Post Inclination E-W: 0.5