Model: C1760 D5e Frequency: 50 HZ Fuel Type: Diesel: Generator Set Data Sheet
Model: C1760 D5e Frequency: 50 HZ Fuel Type: Diesel: Generator Set Data Sheet
Standby Prime
Fuel consumption kVA (kW) kVA (kW)
Ratings 1760 (1408) 1600 (1280)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
US gph 31.7 55.9 80.0 104 29.8 51.9 74.1 96.3
L/hr 120 212 303 395 113 197 281 365
Fuel flow
Maximum fuel flow, L/hr 1630
Maximum fuel inlet restriction, mm Hg 203
Maximum fuel inlet temperature, °C 70
power.cummins.com
©2019 Cummins Inc. | DS49-CPGK (09/19)
Air Standby rating Prime rating
Combustion air, m3/min 139 125
Maximum air cleaner restriction, kPa 6.2
Exhaust
Exhaust gas flow at set rated load, m3/min 320 295
Exhaust gas temperature, °C 477 452
Maximum exhaust back pressure, kPa 6.7
Genset outline
Open set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.
power.cummins.com
©2019 Cummins Inc. | DS49-CPGK (09/19)
Alternator data
Connection Temp rise ºC Duty Alternator Voltage
Wye, 3-phase 163 / 125 S/P PI734D 400 – 416 V
Wye, 3-phase 105* P PI734E 400 – 416 V
Ratings definitions
Emergency Standby Limited-Time Running Prime Power (PRP): Base Load (Continuous)
Power (ESP): Power (LTP): Power (COP):
Applicable for supplying Applicable for supplying Applicable for supplying Applicable for supplying
power to varying electrical power to a constant power to varying electrical power continuously to a
load for the duration of electrical load for limited load for unlimited hours. constant electrical load for
power interruption of a hours. Limited Time Prime Power (PRP) is in unlimited hours. Continuous
reliable utility source. Running Power (LTP) is in accordance with ISO 8528. Power (COP) is in
Emergency Standby Power accordance with ISO 8528. Ten percent overload accordance with ISO 8528,
(ESP) is in accordance with capability is available in ISO 3046, AS 2789,
ISO 8528. Fuel stop power accordance with ISO 3046, DIN 6271 and BS 5514.
in accordance with AS 2789, DIN 6271 and
ISO 3046, AS 2789, BS 5514.
DIN 6271 and BS 5514.
©2019 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
DS49-CPGK (09/19)