Programming Guide - Power Factor Conroller: 1. Features
Programming Guide - Power Factor Conroller: 1. Features
2. CONNECTION DIAGRAM
UP To edit the value/system type up-ward in edit To scroll pages in upward direction and view different
mode and scroll through the parameters. parameters.
DOWN To edit the value/system type down-ward in To scroll pages in upward direction and view different
edit mode and scroll through the parameters. parameters.
Page 1 of 5 PG/iPFC/V2/0114
7 Press RIGHT key to accept selected system type stabilizes
Page 2 of 5 PG/iPFC/V2/0114
33 Press RIGHT key to set 1000.C1
the Capacitor VAR value for First digit blinking can be edited using
C1 UP/DOWN key.
34 Press RIGHT key to accept the 1000.C1 Range: 500VAR to 9999MVAR
edited value for first digit. Second digit blinking, can be edited
using UP/DOWN key. Press RIGHT key
to accept the edited value. Continue
the same method till fourth digit.
35 Press RIGHT key 1000.C1 Eg: To set 11.00KVAR
Decimal point blinking. Can be set at Set first four digits (1100) as explained
appropriate location using UP/DOWN above press UP/DOWN key to place
key. Ascertain the correct scale decimal point at appropriate location. Use
(Kilo/Mega) is selected. Kilo/Mega is UP/DOWN KEY. Letter K/M will indicate the
placed on the right hand side of the Kilo/Mega.
display as K/M. Press RIGHT key to
accept the edited value.
36 Press DOWN key 1000.C2 Capacitor VAR value for C2
Follow the procedure as described in
steps 32 to 34.
37 Press DOWN key 1000.C3 Capacitor VAR value for C3
Follow the procedure as described in
steps 32 to 34.
38 Press DOWN key 1000.C4 Capacitor VAR value for C4
Follow the procedure as described in
steps 32 to 34.
39 Press DOWN key 1000.C5 Capacitor VAR value for C5
Follow the procedure as described in
steps 32 to 34.
40 Press DOWN key 1000.C6 Capacitor VAR value for C6
Follow the procedure as described in
steps 32 to 34.
41 Press DOWN key 1000.C7 Capacitor VAR value for C7
Follow the procedure as described in
steps 32 to 34.
42 Press DOWN key 1000.C8 Capacitor VAR value for C8
Follow the procedure as described in
steps 32 to 34.
43 Press DOWN key 1000.C9 Capacitor VAR value for C9
Follow the procedure as described in
steps 32 to 34.
44 Press DOWN key 1000.C10 Capacitor VAR value for C10
Follow the procedure as described in
steps 32 to 34.
45 Press DOWN key 1000.C11 Capacitor VAR value for C11
Follow the procedure as described in
steps 32 to 34.
46 Press DOWN key 1000.C12 Capacitor VAR value for C12
Follow the procedure as described in
steps 32 to 34.
47 Press DOWN key dISA.An. 1st Analog input parameter
51 Press DOWN key xxxx bA (baud rate).Communication Defines the baud rate. Option :
speed. (9600 -default/factory set) 1200,2400, 4800, 9600, 19.20k
52 Press DOWN key EUEn.PA (Parity check) Internal communication error check
EUEn (even)/odd(odd)/no(no parity)
Comment: Can change the option using
UP & DOWN keys.
53 Press DOWN key 1.000dE (Device ID) Defines the (ID) communications
identification number. Option: 1-247
54 Press DOWN key Reverse lock (blocks energy accumulation
no rE in case the CT polarity reverse.
Option : NO/YES
Page 3 of 5 PG/iPFC/V2/0114
55 Press DOWN key Range:1000 -9999. Password user Caution : If password other than the
definable. default or user defined is used, meter will
reject programming.
CAUTION: Password can only be reset
and recalibrated at factory.
56 Press DOWN key 0.400St Starting current value to be displayed in
the meter
Range: (0.2 to 10 % of full scale)
57 Press DOWN key S A V E “Y” blinking. If “n”(no) is selected then Meter enters
into RUN mode without memorizing any
58 Press RIGHT key to store the Display returns to Run mode. edited Values in the setup
changes done
Once the required parameter is programmed press the DOWN key continuously till it reaches SAVE page directly.
4.1 The List of parameters can be configured and the range is given below
Sl.No. Parameter Default setup Range
1 Connection mode(ELEMNT) STAR STAR/ DELTA
2 PT Primary (PT.Prı) 415.0 100V- 999kV
3 PT Secondary (PT SEC) 415.0 50V - 550V
4 CT Primary (CT.Prı) 5.000 0.5A - 99kA
5 CT SECondary (CT SEC) 5.000 0.5A - 6A
6 VA selection (UA.SLEC) Arith (Arithmetic) Arith (Arithmetic) / Vector/ Vec.H (vector harmonics)
7 No.of Relays (nr) 12.000 1-12
8 Control type (C.t) Auto Auto/Manual
9 PF lag(Lg) 0.980 0.800 to 0.999
10 PF lead(Ld) 0.980 0.800 to 0.999
11 Switch ON time(on) 20.00 4 to 99 seconds
12 Switch OFF time(oF) 20.00 4 to 99 seconds
13 Discharge time(t.d) 50.00 4 to 99 seconds
14 Average Time(t.A) 15.00 2 to 200 seconds
15 Over voltage(o.u) 498.0 48 to 999KV
16 Under voltage(uu) 48.00 48 to 999KV
17 Over current(o.A) 6.000 0.050 to 6A
18 Under current(u.A) 0.200 0.050 to 6A
19 Over Harmonics(O.H) 20.00 1 to 100%
20 Alarm delay (A.d) 3.000 3 to 99 seconds
21 Capacitance(C1) 1000.0 500 VAR to 9999 MVAR (default 1000 VAR = 1 kVAR)
22 Capacitance(C2) 1000.0 500 VAR to 9999 MVAR
23 Capacitance(C3) 1000.0 500 VAR to 9999 MVAR
Page 4 of 5 PG/iPFC/V2/0114
41 Password (PASud) 1000 1000 to 9999
42 StArt.A (starting current) 0.400 0.2 to 10 %
7. Manual Mode:
Press UP and DOWN Keys together, and 'CLEAr' (Clear) is shown on the display. Enter the Password (default password is 1000.
Set up and clear has the same password) and it will display “CLr.I”. Press DOWN Key and meter displays “Manual”. Once
manual selected it will display C1 OFF or C1.On (depends on whether the capacitor is ON or OFF). Press RIGHT key to make it
ON or OFF. Continue this for other no. of relays programmed. Once the required no. of relays are switched ON or OFF display will
prompt to “CLEAr.”or Manual . When display prompts to CLEAr press DOWN key and ‘n’ will display and Press the RIGHT key
to come out.
8. LED Indications:
LED status Meaning LED Meaning
status
KILO – ON Kilo C3 – ON Capacitor Bank 3 ON / Relay 3 ON status
MEGA – ON Mega C4 – ON Capacitor Bank 4 ON / Relay 4 ON status
KILO & MEGA – ON Giga C5 – ON Capacitor Bank 5 ON / Relay 5 ON status
KILO & MEGA – OFF Direct reading C6 – ON Capacitor Bank 6 ON / Relay 6 ON status
Minus (-) ON Lag/Minus C7 – ON Capacitor Bank 7 ON / Relay 7 ON status
Minus (-) OFF Lead/Plus C8 – ON Capacitor Bank 8 ON / Relay 8 ON status
COM – ON Communication ON C9 – ON Capacitor Bank 9 ON / Relay 9 ON status
– ON Alarm relay ON C10 – ON Capacitor Bank 10 ON / Relay 10 ON status
C1 – ON Capacitor Bank 1 ON / Relay 1 ON status C11 – ON Capacitor Bank 11 ON / Relay 11 ON status
C2 – ON Capacitor Bank 2 ON / Relay 2 ON status C12 – ON Capacitor Bank 12 ON / Relay 12 ON status
9. Display of Parameters:
DISPLAY Meaning DISPLAY Meaning DISPLAY Meaning
Average Power Factor Frequency VAr B Phase
Page 5 of 5 PG/iPFC/V2/0114