Air Circuit Breakers For The 21st Century: Catalogue No.'00-P55E

This document summarizes an air circuit breaker that provides compact size and operational capability for switchboards. Some key points: 1. The breaker has the world's smallest depth, saving space in switchboards by eliminating intermediate conductors between isolating and fixed main contacts. 2. Standard models are available with ratings from 800 to 4000 amps. Connection options include vertical, horizontal, and front terminals to suit most installations. 3. An optional operation panel allows remote monitoring and control of up to eight breakers, displaying data in real time from up to 50 meters away.

Uploaded by

Asif Shah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
71 views4 pages

Air Circuit Breakers For The 21st Century: Catalogue No.'00-P55E

This document summarizes an air circuit breaker that provides compact size and operational capability for switchboards. Some key points: 1. The breaker has the world's smallest depth, saving space in switchboards by eliminating intermediate conductors between isolating and fixed main contacts. 2. Standard models are available with ratings from 800 to 4000 amps. Connection options include vertical, horizontal, and front terminals to suit most installations. 3. An optional operation panel allows remote monitoring and control of up to eight breakers, displaying data in real time from up to 50 meters away.

Uploaded by

Asif Shah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Ensuring Service, Maintaining Quality

Catalogue No.’00-P55E

Air Circuit Breakers for the 21st Century


The ultimate in compactness and operational capability

Will suit the Switchboard with Minimum Depth

H: 460
Saved space

D: 345

W: 354 W: 460

800-2000A 2500-3200A

úThe dimensions of TemPower2 series ACBs are identical


except for the width.
The panel cutout size is the same for all types of this series,
which makes it easy to arrange the ACBs in switchboards.
Direct connections of the isolating main contacts to the hinges
of the fixed main contacts eliminate the need for intermediate úACBs with front connections are available off-the-shelf. Front
conductors, implementing ACBs having the world's smallest connections are especially suitable for smaller-depth switch-
depth and resulting in space saving in switchboards. boards.

Standard Range
TYPE AR208S AR212S AR216S AR220S AR325S AR332S AR440S
AMPERE RATING(A) 800 1250 1600 2000 2500 3200 4000
NUMBER OF POLES 3, 4
AC RATED INSULATION VOLTAGE [Ui](V. 50/60Hz) AC1000V
RATED OPERATIONAL VOLTAGE [Ue](V. 50/60Hz) 690 690 690 690 690 690 690
RATED CURRENT (max) [In](A) IEC 800 1250 1600 2000 2500 3200 4000

AC RATED BREAKING CAP. [kA sym rms]/MAKING CAP. [kA peak]


IEC AC 690V 50/105 65/143 75/165

440V 65/143 85/187 100/220

RATED SHORT TIME WITHSTAND 1s 65 85 100


CURRENT[Icw][kA rms] 3s 50 65 75

RATED IMPULSE WITHSTAND VOLTAGE [Uimp](kV) 12

LATCHING CURRENT (kA) 65 100

TOTAL BREAKING TIME (s) 0.03

CLOSING OPERATION TIME 0.08

W 354/439 460/580 631/801

DRAW-OUT TYPE 3P/4P(mm) H 460/460

D 345/345 375/375
Increased accessibility from the front Full selectivity achieved

It enhances ease of installation, operation, and maintenance. The rated breaking capacity, the rated short-time withstand
current, and the rated latching current are identical.
As the breaking capacity is not lowered even if the ACB is
Connection to the main circuit furnished with the short time-delay trip function only, full
(for front connections) Replacement of internal parts
(Removing the front cover enables
selectivity is achieved.
replacement of internal parts.)

AR208S 800A AR325S 2500A AR440S 4000A


Connection to the control circuit AR212S 1250A AR332S 3200A
Type and rated current
AR216S 1600A
AR220S 2000A
Rated breaking current (at AC440V)
Manual operation With INST trip function
With ST delay trip function 65kA 85kA 100kA
(Without INST trip/MCR functions)

Rated short-time withstand current (for 1 sec.)


Breaker fixing bolt (optinal) Rated latching current

Draw-out operation

Terminal Configurations
to suit most installations

Three(3) types of main circuit terminal arrangements are


Operation panel available for centralized
available: vertical terminals, horizontal terminals, and front
indication and control connections. Different types of terminal arrangements can
be specified for the line and load sides.

£Horizontal terminals £Vertical terminals £Front connections

No extra arc space required,


vertical stacking permitted
The operation panel, an integrated monitoring and control
tool, has functions and capabilities of watt-hour meters, Little arc gas is discharged No extra
arc space
wattmeters, voltmeters, ammeters, switches, and indicators, during interrupting operation required
allowing the operator to remotely monitor and control up to and no extra arc space on the
eight ACBs via serial communications. top of the ACB is required.
Two large LED monitors on the panel can read two kinds of A stack-together arrangement
data simultaneously in real time. of the ACBs will minimize the
The operation panel can be installed up to 50 m away from height of the switchboard.
the ACBs.
RMS sensing over-current release (OCR)

The TemPower RMS sensing over-current release provides a wide range of protection functions and capabilities within three
different relays.
°Optimum protective coordination
AGR-L Industrial & transformer protection
In addition to the standard L- and S-characteristics, the R-characteristic is available in
AGR-R Standard Inverse, Very Inverse and five types of characteristics: I0.02t, It, I2t, I3t, and I4t.
Extremely Inverse curve Using the TemPower 2 series allows optimum protective coordination with upstream or
AGR-S Generator protection type downstream circuit breakers and loads.
°Reverse power trip function (The first-ever feature for ACBs)
The OCR for generator protection has a reverse power trip function, negating the need
for installation and wiring work for external reverse power relays.
°2-stage pre-trip alarm function
This function can be used to adjust feeding to loads according to their essentiality.
°N-phase protection function
The N-phase protection function prevents the neutral conductor from sustaining dam-
age or burnout due to the possible large current.
°Ground fault trip function
Inverse curve or definite curve can be selected.
°Earth leakage trip function
°Adjustable under-voltage trip function
°Data measuring and output function
This function measures phase currents, line voltages (or phase voltages), electric
power, and electric energy, and outputs them in the form of analog values ranging
from 4 to 20 mA dc.
°Communication function
This function supports the LONTALK protocol and enables transmission of data including
line voltage, phase current, electric power, and electric energy via LONWORKS net-
works.
Standard type LCD indication type °Contact temperature monitoring function

LONWORKS and LONTALK are registered trademarks of Echelon Corporation

OVERSEAS NETWORK
TERASAKI (EUROPE) LTD.
80 Beardmore Way, Clydebank Industrial Estate, Clydebank, Glasgow, G81 4HT. SCOTLAND (U. K.)
Telephone : 44-141-941-1940 / Fax : 44-141-952-9246 / E-mail : [email protected] / http://www.terasaki.com/

TERASAKI ITALIA s.r.l.


Via Campania 4/6, 20090 Segrate, Milano, ITALY
Telephone : 39-02-2137574 / Fax : 39-02-26922931 / E-mail : [email protected] / http://www.terasaki.it/

TERASAKI ESPAÑA, S.A.U.


Roma, s/n, 08400 Granollers, Barcelona, SPAIN
Telephone : 34-93-879-60-50 / Fax : 34-93-870-39-05
E-mail : [email protected] / http://www.terasaki.es/

TERASAKI CIRCUIT BREAKERS (S) PTE. LTD.


227 UBI Avenue 4, Singapore 408815, SINGAPORE
Telephone : 65-744-9752 / Fax : 65-748-7592 / E-mail : [email protected]

TERASAKI ELECTRIC (M) SDN. BHD.


Lot 3, Jalan 16/13D, 40000 Shah Alam, Selangor Darul Ehsan, MALAYSIA
Telephone : 60-3-549-3820 / Fax : 60-3-549-3960 / E-mail : [email protected]

TERASAKI DO BRASIL LTDA.


Rua Cordovil, 259-Parada De Lucas, 21250-450 Rio De Janeiro-R. J., BRAZIL
Telephone : 55-21-481-1259 / Fax : 55-21-481-0935 / E-mail : [email protected]

TERASAKI ELECTRIC (CHINA) LIMITED


72 Pacific Industrial Park, Xingtang Zengcheng, Guangzhou 511340, CHINA
Telephone : 86-20-8270-8556 / Fax : 86-20-8270-8586 / E-mail : [email protected]

Head Office : 7-2-10 Hannancho, Abenoku, Osaka, JAPAN


Circuit Breaker Division : 7-2-10 Kamihigashi, Hiranoku, Osaka, JAPAN
Telephone : 81-6-6791-9323 / Fax : 81-6-6791-9274
E-mail : [email protected] / http://www.terasaki.co.jp/

AUG.’00-10.0K Pamphlet No. ’00-P55E


The contents of this publication may be subject to change without notice.
Recycled paper used for environmental protection.