Air Circuit Breakers For The 21st Century: Catalogue No.'00-P55E
Air Circuit Breakers For The 21st Century: Catalogue No.'00-P55E
Catalogue No.’00-P55E
H: 460
Saved space
D: 345
W: 354 W: 460
800-2000A 2500-3200A
Standard Range
TYPE AR208S AR212S AR216S AR220S AR325S AR332S AR440S
AMPERE RATING(A) 800 1250 1600 2000 2500 3200 4000
NUMBER OF POLES 3, 4
AC RATED INSULATION VOLTAGE [Ui](V. 50/60Hz) AC1000V
RATED OPERATIONAL VOLTAGE [Ue](V. 50/60Hz) 690 690 690 690 690 690 690
RATED CURRENT (max) [In](A) IEC 800 1250 1600 2000 2500 3200 4000
D 345/345 375/375
Increased accessibility from the front Full selectivity achieved
It enhances ease of installation, operation, and maintenance. The rated breaking capacity, the rated short-time withstand
current, and the rated latching current are identical.
As the breaking capacity is not lowered even if the ACB is
Connection to the main circuit furnished with the short time-delay trip function only, full
(for front connections) Replacement of internal parts
(Removing the front cover enables
selectivity is achieved.
replacement of internal parts.)
Draw-out operation
Terminal Configurations
to suit most installations
The TemPower RMS sensing over-current release provides a wide range of protection functions and capabilities within three
different relays.
°Optimum protective coordination
AGR-L Industrial & transformer protection
In addition to the standard L- and S-characteristics, the R-characteristic is available in
AGR-R Standard Inverse, Very Inverse and five types of characteristics: I0.02t, It, I2t, I3t, and I4t.
Extremely Inverse curve Using the TemPower 2 series allows optimum protective coordination with upstream or
AGR-S Generator protection type downstream circuit breakers and loads.
°Reverse power trip function (The first-ever feature for ACBs)
The OCR for generator protection has a reverse power trip function, negating the need
for installation and wiring work for external reverse power relays.
°2-stage pre-trip alarm function
This function can be used to adjust feeding to loads according to their essentiality.
°N-phase protection function
The N-phase protection function prevents the neutral conductor from sustaining dam-
age or burnout due to the possible large current.
°Ground fault trip function
Inverse curve or definite curve can be selected.
°Earth leakage trip function
°Adjustable under-voltage trip function
°Data measuring and output function
This function measures phase currents, line voltages (or phase voltages), electric
power, and electric energy, and outputs them in the form of analog values ranging
from 4 to 20 mA dc.
°Communication function
This function supports the LONTALK protocol and enables transmission of data including
line voltage, phase current, electric power, and electric energy via LONWORKS net-
works.
Standard type LCD indication type °Contact temperature monitoring function