Defining Size and Location of Capacitor in Electrical System
Defining Size and Location of Capacitor in Electrical System
System (1)
http://electrical- engineering- portal.com/defining- siz e- and- location- of- capacitor- in- electrical- system- 1 March 4, 2013
jiguparmar
Content
Type of Capacitor Bank as per Its Application:
1. Star-Solidly Grounded
2. Star-Ungrounded
3. Delta-connected Banks
1. Parallel Connection
2. Series Connection
The reactive power supplied by the fixed capacitor bank is constant irrespective of any
variations in the power factor and the load of the receivers. These capacitor banks are
switched on either manually (circuit breaker / switch) or semi automatically by a remote-
controlled contactor.
This arrangement uses one or more capacitor to provide a constant level of compensation.
These capacitors are applied at the terminals of inductive loads (mainly motors), at bus bars.
Disadvantages:
Application:
Go to Content ↑
These capacitor banks are made up of a combination of capacitor steps (step = capacitor +
contactor) connected in parallel. Switching on and off of all or part of the capacitor bank is
controlled by an integrated power factor controller.
The equipment is applied at points in an installation where the active-power or reactive power
variations are relatively large, for example:
Where the kvar rating of the capacitors is less than, or equal to 15% of the supply transformer
rating, a fixed value of compensation is appropriate.
Control is usually provided by contactors. For compensation of highly fluctuating loads, fast
and highly repetitive connection of capacitors is necessary, and static switches must be used.
Go to Content ↑
Automatic Power Factor correction equipment is divided into three major categories:
Advantages:
Application:
Automatic bank Best for variable loads, prevents Higher equipment cost
over voltages, low installation cost
Go to Content ↑
Application:
2. Heavy-duty
Application:
Application:
Go to Content ↑
For HT capacitors the minimum ratings that are practical are as follows:
11 KV 200 Kvar
22 KV 400 Kvar
33 KV 600 Kvar
Unit sizes lower than above is not practical and economical to manufacture.
When capacitors are connected directly across motors it must be ensured that the rated
current of the capacitor bank should not exceed 90% of the no-load current of the motor to
avoid self-excitation of the motor and also over compensation.
Precaution must be taken to ensure the live parts of the equipment to be compensated should
not be handled for 10 minutes (in case of HT equipment) after disconnection of supply.
Crane motors or like, where the motors can be rotated by mechanical load and motors with
electrical braking systems, should never be compensated by capacitors directly across motor
terminals.
For direct compensation across transformers the capacitor rating should not exceed 90 %
of the no-load KVA of the motor.
Go to Content ↑
For selection of Capacitor we have to calculate Total Non-Liner Load like: UPS, Rectifier,
Arc/Induction Furnace, AC/DC Drives, Computer, CFL Blubs, and CNC Machines.
Calculation of Non liner Load, Example: Transformer Rating 1MVA,Non Liner Load
100KVA
% of non Liner Load = (Non Liner Load/Transformer Capacity) x100 = (100/1000)
x100=10%.
According to Non Linear Load Select Capacitor as per Following Table.
Standard Duty
Above 30%
Go to Content ↑
Configuration of Capacitor
Power factor correction capacitor banks can be configured in the following ways:
Go to Content ↑
1. Star-Solidly Grounded
Initial cost of the bank may be lower since the neutral does not have to be insulated from
ground.
Capacitor switch recovery voltages are reduced
High inrush currents may occur in the station ground system.
The grounded-Star arrangement provides a low-impedance fault path which may require
revision to the existing system ground protection scheme.
Typically not applied to ungrounded systems. When applied to resistance-grounded
systems, difficulty in coordination between capacitor fuses and upstream ground
protection relays (consider coordination of 40 A fuses with a 400 A grounded system).
Application: Typical for smaller installations (since auxiliary equipment is not required)
Go to Content ↑
2. Star-Ungrounded
Industrial and commercial capacitor banks are normally connected ungrounded Star, with
paralleled units to make up the total kvar.
It is recommended that a minimum of 4 paralleled units to be applied to limit the over voltage
on the remaining units when one is removed from the circuit.
If only one unit is needed to make the total kvar, the units in the other phases will not be
overloaded if it fails.
In industrial or commercial power systems the capacitors are not grounded for a variety of
reasons. Industrial systems are often resistance grounded. A grounded Star connection on
the capacitor bank would provide a path for zero sequence currents and the possibility of a
false operation of ground fault relays.
Also, the protective relay scheme would be sensitive to system line-to-ground voltage
Unbalance, which could also result in false relay tripping.
Go to Content ↑
3. Delta-connected Banks
Delta-connected banks are generally used only at distributions voltages and are configured
with a Single series group of capacitors rated at line-to-line voltage. With only one series
group of units no overvoltage occurs across the remaining capacitor units from the isolation of
a faulted capacitor unit.
Therefore, unbalance detection is not required for protection and they are not treated further
in this paper.
Go to Content ↑
This is the most popular method of connection. The capacitor is connected in parallel to the
unit. The voltage rating of the capacitor is usually the same as or a little higher than the system
voltage.
Go to Content ↑
Series Connection
This method of connection is not much common. Even though the voltage regulation is much
high in this method,
One is that because of the series connection, in a short circuit condition the capacitor should
be able to withstand the high current. The other is that due to the series connection due to the
inductivity of the line there can be a resonance occurring at a certain capacitive value.
This will lead to very low impedance and may cause very high currents to flow through the
lines.
Go to Content ↑