Ike Electric Pvt. LTD.: System Fault Level Calculation M/S Tneb
Ike Electric Pvt. LTD.: System Fault Level Calculation M/S Tneb
18.75 MVA , 15MW , 984 A synchronous speed = 1500rpm , p.f 0.8 lag ,
voltage 11kV +-10% , reactance Xd” – 26% = 0.26
CALCULATION AS FOLLOWS:
Calculation
= 72.115 MVA
Page 1
= 2.2186 %
= 6001.38
= 0.02666 %
= 11.25 %
= 23.17 MVA
Above 37 KW non VFD motor load as per electrical load list No. TNEB-WIL-IKE-A11.
2) Total kW = 111 kW
Page 2
3) Therefore kVA at 0.8 p.f lag & Efficiency 0.9 = 154 kVA
= 154 x 5 kVA
= 770 kVA
= 0.770 MVA
= 30.11 MVA
= 41.89 KA
C) Fault MVA at 11kV Bus considering Base kV 0.433V = 1.6 x 100 / (ZB)
= 244.91 MVA
Page 3
Fault current on 11kV Bus = 244.91 / ( √3 x 11 )
= 12.85 kA
Zs = 0.0266 %
Zg = 2.2186 %
ZA = Zs + Zgt =0.9266
11kV Bus
Page 4
ZB = ZA l l Zg
0.6533
11kV Bus
Zdt = 6.25 %
0.415 kV Bus
M
MOTOR
M
Project : 15MW COGEN POWER PLANT ARIGNAR
ANNA,TNEB.
DOC No. :TNEB-WIL-
IKE-A94
DATE : 21 - 4 - 2011
Reactance
M
Zeq = ZB + Zdt
m
M MOTOR
transformer Impedance
Zs = System Impedance
Zgt = Generator
m
m Page 5