Biosafety Level 3 (BSL-3) Laboratory Design Standards: January 2020
Biosafety Level 3 (BSL-3) Laboratory Design Standards: January 2020
Design Standards
January 2020
CC Noncommercial License
This manual is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License. When reusing the content
under this license, please provide (1) attribution to “Environment, Health & Safety at the University of California, Office of the
President”; (2) the following copyright notice: © The Regents of the University of California; and (3) if feasible, a hyperlink to where
the original source material appears.
Introduction
The University of California (UC) is home to some of the world’s most advanced and pioneering
biomedical science and clinical research. Consistently ranked among the leaders in the field of
Infectious Disease research, the UC is often called upon to provide critical expertise in response to
worldwide public health crises. Infectious Disease research involving highly pathogenic and primarily
aerosol transmissible agents (i.e., Risk Group 3 agents) has the potential to present significant risk
to individuals, the community, and the environment. The ability to safely conduct these research
activities is largely dependent upon the highly engineered Biosafety Level 3 (BSL-3) laboratory, the
highest-level containment facilities currently operated by the UC. The primary objective of these
laboratories is to provide the best possible physical containment of Risk Group 3 agents. Hence, the
design and engineering of these laboratories must be maintained at the highest attainable
standards.
Several authorities have published standards for the design of BSL-3 laboratories. Development of
the UC Biosafety Level 3 Design Standards has incorporated input from several of these sources,
including the following:
• CDC Biosafety in Microbiological and Biomedical Laboratories (BMBL), 5th Edition, 2009
• NIH Design Requirements Manual for Biomedical Laboratories and Animal Research
Facilities (DRM), 2019
• NIH Guidelines for Research Involving Recombinant or Synthetic Nucleic Acid Molecules
(NIH Guidelines), 2016
• National Institutes of Health Biosafety Level 3 Laboratory Certification Requirements,
2006
• Industry Standards and Best Practices
The information presented in these Standards addresses facility design and engineering systems for
BSL-3 containment laboratories and incorporates additional design elements to assist campuses in
conducting facility risk assessments. It is important to note that an effective BSL-3 program is not
only reliant upon the facility and engineering, but also operation and maintenance (O&M) protocols,
robust training programs, administrative controls, and standard operating procedures (SOPs).
Application
The BSL-3 Laboratory Design Standards represent the UC requirements for constructing BSL-3
laboratories. These Standards need to be referenced and used by UC design teams including
For the purposes of these Design Standards, major renovations/retrofits are defined as any of the
following: 1. Changes to fixed primary containment equipment (e.g. ducted BSCs or any other
devices connected to the BSL-3 exhaust system); 2. Changes to major HVAC systems/components
(e.g. exhaust fans, air handling units, airflow control valves, isolation dampers, Building Management
Systems / Building Automation Systems (BMS/BAS), ductwork, etc.); 3. Changes to floorplans or
structural components of the secondary containment boundaries (e.g. walls, ceilings, or attached
fixtures); 4. Any other changes to the facility that could impact overall safety, operations, or
ventilation system performance. This Standard is applicable to the specific retrofit and not meant to
apply to the entire facility. As plans to renovate specific features of an existing facility evolve, it is
important to address any identified issues that may affect the safe operations of a BSL-3 laboratory,
potentially presenting a risk to the UC community or the environment. These Standards have been
approved by the UC systemwide High Containment Laboratory Oversight Committee (HCLOC), and
shall be incorporated or referenced in Campus Building Standards.
Note: Facilities required to comply with the Federal Select Agent Program and/or Dual Use
Research of Concern may have additional biosafety or biosecurity design features beyond these UC
Standards. In addition to the UC Standards, campuses must reference and comply with the
applicable Federal regulatory standards when designing Federal Select Agent or Dual Use Research
high-containment facilities.
Campus Involvement
At the onset of a new BSL-3 laboratory or existing laboratory renovation design project, it is
important to consider the involvement of specific campus experts. Consultation with these key
campus members may provide insight into critical design flaws that may affect specific aspects of
the laboratory’s functionality. These contributions could prove to be exceptionally cost-effective in
Deviations
Campuses must comply with the UC Biosafety Level 3 Design Standards and Best Practices should
be considered when appropriate. When justified by a documented risk assessment, a deviation may
be considered. A campus seeking a deviation approval must first complete the UC BSL3 Design
Standards Deviation Request Form, Appendix I. The completed form and requested
documentation shall be presented to the campus High Containment Laboratory Oversight Group
(HCLOG) for approval. With campus HCLOG approval, the deviation request will be presented to
the UC systemwide HCLOC, for final approval.
BSL-3 Architectural.............................................................................................................................. 2
General ............................................................................................................................................... 2
Anterooms .......................................................................................................................................... 4
Doors .................................................................................................................................................. 5
Windows ............................................................................................................................................. 6
Floors.................................................................................................................................................. 7
Base ................................................................................................................................................... 7
Walls ................................................................................................................................................... 7
Ceilings ............................................................................................................................................... 8
Finishes .............................................................................................................................................. 9
Furniture ...........................................................................................................................................10
Sealing ..............................................................................................................................................11
Electrical .............................................................................................................................................27
Plumbing .............................................................................................................................................38
Vacuum Line.....................................................................................................................................39
Sinks .................................................................................................................................................40
Shower .............................................................................................................................................41
Drains ...............................................................................................................................................41
Traps ................................................................................................................................................42
Telecom ............................................................................................................................................47
Security.............................................................................................................................................47
Signage ............................................................................................................................................49
Seismic .............................................................................................................................................51
Safety ...............................................................................................................................................53
Decontamination ..............................................................................................................................55
Autoclaves ........................................................................................................................................59
Centrifuge .........................................................................................................................................61
CC Noncommercial License
This manual is licensed under a Creative Commons Attribution-NonCommercial 4.0 International License. When reusing the content
under this license, please provide (1) attribution to “Environment, Health & Safety at the University of California, Office of the
President”; (2) the following copyright notice: © The Regents of the University of California; and (3) if feasible, a hyperlink to where
the original source material appears.
The BMBL is published jointly by the U.S. Department of Health and Human Services, the
Centers for Disease Control and the National Institutes of Health. The document describes
Biological risk assessment, lab practices, safety equipment, and facilities requirements required
for designing and operating laboratories at Biosafety Levels (BSL) 1 through 4. Although not a
code, certification of BSL facilities is dependent on following the recommendations in this
document.
• National Institutes of Health Biosafety Level 3 Laboratory Certification Requirements, July 2006
https://www.orf.od.nih.gov/PoliciesAndGuidelines/Bioenvironmental/Documents/BSL-3
CertificationGuidelinesFINAL_508.pdf
• NIH Guidelines for Research Involving Recombinant or Synthetic Nucleic Acid Molecules (NIH
Guidelines), 2016
• University of California Environment, Health & Safety (EH&S) Laboratory Safety Design Guide,
Second Edition, September 2007
New UC BSL-3 laboratories and designated Access to the BSL-3 laboratory and work N/A
retrofits must be reviewed for compliance with activities conducted in the facility must be
applicable provisions of the American with evaluated on a case-by-case basis to
Disabilities Act (ADA) and related codes and determine appropriate accommodations
regulations. and accessibility. Work with the
appropriate units on campus to determine
specific ADA design requirements and
compliance with Title 24 California
Building Code Chapter 11 Accessibility.
Design the laboratory to be easily cleaned and Smooth walls, floors, and ceilings with N/A
decontaminated. 1, 2, 3, 4 finish that is resistant to repeated
chemical decontamination.
Keep the BSL‐3 laboratory separate from un‐ N/A Consider locating the facility on an
secured high traffic areas. 5, 6, 7 upper floor. Consider location of
BSL‐3 laboratories in relation to
other zones such as BSL‐2 support
laboratories, offices and break
rooms, elevators, loading docks,
etc. for effects on laboratory
pressurization and airflow.
Provide dedicated anteroom to include space Dedicated anteroom is accessed through N/A
for personal protective equipment (PPE) and self-closing doors that should be
waste. Doors are self-closing. 8, 9, 10, 11, 12 physically interlocked with over‐ride for
emergency use.
Sealed penetrations (through partitions, walls, Sealed penetrations should be visible for N/A
floors and ceilings) are required. 17, 18, 19, 20 ease of inspection and verification.
Primary containment devices must be placed Primary containment equipment such as Consider Appendix A of the DRM
in such a way as to minimize impact of room BSCs, shall be placed in the room so that and Appendix A of the BMBL for
airflow on function/containment. This must be containment is not impacted by supply exact distances from features and
determined in conjunction with the High diffusers, exhaust grilles, doors, traffic for placement in a space.
Containment Laboratory Director (HCLD). 21, 22, flow, or other equipment.
23, 24
Containment Barrier
Standard Explanation Best Design Practice
Construct BSL‐3 containment barrier with steel Frame partition assemblies shall include N/A
studs, sheet rock and appropriate backing gypsum board that is selected and
material. 26, 27 detailed to be appropriately impact,
moisture and water resistant. Standard
gypsum board is not acceptable. Light-
gauge steel studs used for partition
framing shall be 18-gauge minimum
thickness.
Anterooms
Standard Explanation Best Design Practice
Anterooms must be appropriately sized for Provide anteroom large enough to allow Anteroom should also include space
program requirements based on risk for a change bench, storage shelves for for a logbook and wall calendar. If
assessment and considerations for future clean PPE, laundry receptacle and waste the anteroom will be the main
expansion of research focus. Anterooms must container. entryway for equipment, size
be sized to meet local Fire Code requirements. appropriately for largest piece of
equipment, including door sizes.
Doors must have door locks access controls Electronic lock systems shall be linked to Consider including biometric or PIN
that allows for fast and efficient removal of restricted remote access management devices for locks on doors access
access clearance, such as card keys. Hard software. Adhere to any local/UC policy control based on risk assessment.
key access must be off master and provided (UCOP IS-3 policy)
as a backup to electronic lock systems.
Electronic locks must fail secure with a bypass
for egress. 33, 34, 35
Door must be welded steel or fiberglass Wooden doors and frames are not Provide 42 in. single leaf doors.
constructed of sufficiently durable material permitted.
(e.g.: stainless steel, FRP, or epoxy-painted
welded steel) with welded steel frames, and
large enough for passage of equipment. 39
Door sweeps must be provided for pest Broom sweeps, no rubber sweeps. N/A
control, but must be adjustable to facilitate
inward airflow movement. 41, 42
Vision panels must be in all interior doors Vision panels in exterior doors should be N/A
Access to the laboratory must be through two Egress only doors may be single door N/A
interlocked doors; provide interlock over‐ride configuration. No hardware on outside of
for emergency use. 46, 47, 48 the door.
Door swing direction must be determined in N/A Doors should swing in the direction
discussion with EH&S and Fire Marshal. 49 of airflow (clean to dirty).
Doors serving locations that require directional Airflow through undercut doors allows for N/A
airflow shall be configured to allow for containment airflow and plays a role in
sufficient air movement at the undercut to establishing operating pressure
achieve proper operation without excessive differential between spaces, which
pull or closure pressure.52 requires verification of height and airflow
to ensure proper cascading pressurization
control of the facility.
Windows
Standard Explanation Best Design Practice
All windows must be appropriately sealed and N/A Windows on perimeter walls or
non‐operable. 53, 54, 55, 56, 57 doors should be considered only
after a security assessment.
Window frames must be fully welded and N/A If windows are located on perimeter
sealed. 58 walls, they should be appropriately
• Provide laminated and tempered glass at glazed, as described in the DRM.
all windows
Floors of mechanical rooms and interstitial N/A Floors of mechanical rooms and
levels located above biocontainment areas interstitial levels located directly
shall be designed to prevent leaks. above biocontainment areas should
Penetrations through the floor shall be be marked to indicate the location of
protected by raised curbs or sleeves. 70, 71 rooms and utility distribution below
where possible.
Base
Standard Explanation Best Design Practice
Walls
Standard Explanation Best Design Practice
Walls shall be durable, monolithic, and N/A Corner guards and bumper rails
resistant to chemicals and disinfectants. Walls should be provided to protect wall
shall be sealed to the base, ceiling, surface in high traffic/impact areas.
doorframes, cover plates, and all other
Ceilings
Standard Explanation Best Design Practice
Finish monolithic ceiling with a durable Ceilings shall be monolithic, seamless N/A
moisture resistant substrate such as epoxy construction. Ceiling systems shall be
paint that is resistant to all chemical and designed to resist damage from deflection
cleaning agents that may be used. 79, 80, 81, 82, 83 caused by differential air pressure surges
that may occur during HVAC fan-failure
testing. Ceiling material and support
systems shall be designed to be moisture
and sag resistant.
• Ceilings shall be durable and resistant
to moisture, wash-downs and
pressurization. Ceilings shall be
monolithic, seal to the walls, and with
sealed access panel, lights, diffusers,
and other ceiling-mounted devices.
Epoxy painted gypsum board or
panelized composite systems are
standard. Gypsum board shall not be
standard wall board, but must be
specified and detailed to be
appropriately moisture and sag
resistant. Acoustical tile celling
systems are not acceptable.
Access Panels
Standard Explanation Best Design Practice
Minimize access panels. Any access panels N/A Locate access panels outside the
must be gasketed and latched to allow for BSL‐3 suite.
room decontamination. Access panels must be
piano type hinged. 85, 86
Finishes
Standard Explanation Best Design Practice
The interior finishes of a BSL-3 shall form a N/A BSL-3 wall and ceiling finishes,
durable, monolithic, impermeable enclosure. unless factory finished, should have
Mock-ups of all finishes shall be provided for high performance reinforced multi-
review and approval, and as a basis for coat resinous paint finish (reinforced
acceptance of the final installation. The mock- epoxy paint or equivalent). Paint
ups shall be constructed in the same applicators should be Society for
conditions, and using the same materials and Protective Coatings (SSPC) Coating
techniques as the final installation. The mock- Application Specialist (CAS Level II)
ups shall include all typical conditions, Certified, and should be trained and
including sealants, transitions between approved by the paint manufacturer.
materials, inside and outside corners. 87, 88, 89 All high performance resinous paint
applications should be inspected by
an independent third party Coating
Inspector Program (CIP) level 3
certified inspector.
Furniture
Standard Explanation Best Design Practice
Spaces between benches, cabinets and Fixed millwork, casework, and N/A
equipment must be accessible for cleaning. 91, countertops shall either be sealed to walls
92
and floors or positioned with sufficient
spacing to facilitate cleaning and minimize
harborage of pests.
Bench tops must be impervious to water and N/A Bench tops should be epoxy,
resistant to heat, organic solvents acids, stainless steel, or phenolic resin.
alkalis, and other chemicals. 60, 61, 62, 93, 94
Chairs must be covered with non‐porous N/A Consider ergonomic needs when
chemical and decontaminant resistant choosing chairs. Adhere to any
material. 95, 96 local/UC policy.
Sealing
Standard Explanation Best Design Practice
A BSL-3 environment must have a The air change rate will be determined by N/A
minimum of 6 air changes per hour.3, 4 the largest of the following; internal heat
gain (cooling load), exhausted equipment
(fume hood, glove-box, etc.), or minimum
according to this standard.
A BSL‐3 environment must have Having supply/exhaust interlock will Consider redundancy by providing
supply/exhaust fan interlock. 5, 6, 7, 8 prevent/ minimize airflow reversal in case both Software and Hardware
of exhaust fan(s) failure and Interlocks
prevent/minimize laboratory from going too
deep negative during supply fan(s) failure.
The A/E shall utilize the latest edition of Adherence to the latest version of energy N/A
the following energy codes and codes will ensure compliance with local,
standards to design the exterior state and federal requirements.
envelope and select HVAC systems, • Include local and UC standards
domestic water heating, electrical
distribution and illuminating systems ‐
ASHRAE Standard 90.1, Energy Policy
Act 2005, and International Energy
Conservation Code. 11
Provide a ducted dedicated, single pass BSL-3 exhaust ductwork shall not be Dedicated ventilation system
exhaust ventilation system. The exhaust shared with non-BSL-3 spaces. (supply and exhaust) will allow a
fan system shall be redundant (N+1 faster response of the
minimum) and provide directional management system by being
airflow, from least hazardous area to able to isolate BSL-3 facility
most potentially hazardous. 12, 13, 14, 15, 16 without affecting the rest of the
• The laboratory exhaust air must not building.
re‐circulate to any other area of the
building. 30, 31, 32, 33
Under normal operations, system shall Maintaining directional airflow from low N/A
provide directional airflow and shall be hazard to high hazard will minimize cross-
exhausted to outside. 17, 18, 19, 20 contamination of spaces. Air shall not be
recirculated.
A N+1 redundancy is required for High- The air-handling unit must provide enough A dedicated air handing system is
Containment laboratory rooms. capacity for future upgrades. Capacity of highly recommended. Consider
Capacity and size of the make‐up air the cooling system shall include the designs with multiple fans,
system serving containment program cooling demand plus an allowance isolation dampers and controls
devices/equipment shall correspond to for future expansion of internal heat gain maybe designed to satisfy the
100% of the programmed containment requirements as defined by the campus N+1 requirements.
devices/equipment plus future capacity personnel.
as defined by the campus personnel. Considerations should be made
21, 22 for design of the HVAC system
with regard to constant volume or
variable volume.
Provide 100% outdoor air supplied to Providing outside air will minimize cross- Provide dedicated supply (air
the BSL-3 laboratory that is then contamination between spaces. handling unit and ductwork).
exhausted directly. 23
Provide digital monitor or analog Pressure monitor must allow laboratory N/A
magnehelic gauge at each door leading personnel to verify that laboratory is under
to a new pressure zone. 24, 25, 26 negative pressure.
Provide audible and visual alarms to Local alarms shall notify laboratory Alarm should report to Facilities
notify personnel of air flow disruption. 27, personnel of issues with the facility. personnel and Building
28
Management System (BMS) after
the appropriate alarm delay set
point.
A BSL-3 environment shall have air Having a differential pressure of -0.05 N/A
pressure differential of -.05” in.w.g. at in.w.g. provides the containment of
each barrier door and laboratory.29 pathogens in the case of a release outside
the BSC
Exhaust air must be HEPA filtered. The HEPA filter sterilizes the air before it is N/A
Laboratory building exhaust air should discharged into the environment
be dispersed away from occupied areas • Consider other regulatory requirements
and from building air intake locations. when volatile chemicals and
34, 35, 43, 44, 45 radioactive materials will be used in B2
cabinets.
Exhaust air systems shall be arranged N+1 configuration provides redundancy in N/A
with single fans or multiple manifolded the system in case of a failure.
fans designed to achieve N+1
redundancy and maintain the exhaust
air system fully operational, at all times.
Each fan shall be designed to be
capable of being fully isolated while the
overall system remains fully
operational. 37, 42
Provide a dedicated exhaust system Class III BSC are commonly used for N/A
with double HEPA filters in series for a aerosol procedures involving biological
Class III BSC. 38 materials with hazardous chemicals or
radioactive materials.
HEPA filter housings shall have gas‐ This allows for HEPA filter housing N/A
tight isolation dampers, decontamination before any repairs and/or
decontamination ports, and/or bag‐ maintenance is required.
in/bag‐out (with appropriate • Isolation dampers, decontamination
decontamination procedures) capability. ports and bag in-bag out should be
46, 47 located in areas that are easily
accessible with enough room for
maintenance/filter change-outs.
• HEPA filter housing shall be welded
stainless steel construction.
• Each HEPA filter shall be capable of in
situ decontamination and full face filter
scanning.
The HEPA filter housing shall allow for HEPA filters must be checked for leaks on N/A
leak testing of each filter and assembly. an annual basis.
48, 49, 50
All electrical penetrations shall be Sealed penetrations are required for N/A
sealed airtight internally at the decontamination and directional airflow
containment boundary. 1 , 2, 3, 4 • J box is sealed and in wet areas
• Refer to NIH DRM for areas to be consider using an outlet cover
sealed and sealant type.
Electrical faceplates and devices shall BSL-3 laboratories must be able to be Utilize stainless steel cover plates
be able to withstand routine area decontaminated without affecting for switches and receptacles in
decontamination, as well as, after spills, the electrical components rooms that will utilize vaporized
splashes, or other potential paraformaldehyde or chlorine
contamination. 5, 6, 7, 8, 9 dioxide gaseous decontamination
protocols.
• Use of foam and rubber shall be
• Based on decontamination
minimized.
methods, consider providing
• Wall‐mounted electrical receptacles
electric relays for control of
and switches and ceiling‐mounted
power outlets for disinfecting
receptacles shall be hinged, self‐
agent generation equipment,
closing, weatherproof and stainless
mixing equipment, and
steel SS‐316 with rounded edge
neutralizing agent generation
cover plates with neoprene closed‐
equipment (if required by
cell gasket material for all wall
disinfecting agent), to be
devices.
controlled from outside the
room(s). Provide power to de‐
humidification equipment if
required by disinfection agent
protocol.
Conduits for all systems - Conduit Threaded rigid conduit with sealed N/A
applications in BSL-3 facilities are as penetrations at containment barrier
follows: 10, 11 provides a long term and durable
• Conduit type: use rigid galvanized pathway that meets the airtight
steel (RGS) conduit with threaded
BSL-3 facilities - All components of the BSL-3 laboratories shall have Emergency Generator - Provide a
HVAC system (supply and exhaust), emergency power for critical local generator dedicated to the
alarms, emergency lighting and components. facility to provide
laboratory outlets for essential emergency/standby power.
equipment (Biological Safety Cabinets, Consider providing 100%
freezers, autoclave, etc.) shall be on a generator backup.
backup power system. 12, 13, 14, 15
• All BSL-3 equipment and controls
on backup power shall be supplied
backup power through a closed
transition transfer switch. BAS
controllers and BSCs shall have
uninterruptible power supply (UPS)
with a run time of at least 120
seconds
• UPS shall be installed such that it is
easy to monitor and replace on a
regular basis. Backup power to the
laboratory and associated systems
shall be on dedicated circuits from
the generator.
• All HVAC equipment must be
capable of auto-restart after a power
failure.
Provide emergency power for the Emergency Power shall connect the As determined per program basis,
following essential equipment: 16, 17 following loads to the standby electrical recommend connecting the
1. HVAC systems: following loads to the standby
The emergency power system shall be Emergency electrical service size shall N/A
designed to meet applicable codes and be adequate to meet the current and
standards. 18, 19, 20 future emergency electrical demand,
and applicable codes and standards
Life safety loads shall be wired Life Safety Loads may include all or N/A
separately from normal powered, legally some of the following:
required and optional standby loads. 21 • Emergency egress lighting
• Egress signage
• Communications systems (including
PA systems
• Fire alarm and mass notification
systems
• Self-contained battery-powered
lighting at generator set location
• Fire-suppression systems (fire
pumps, jockey pumps,
compressors, valves, etc.)
Provide UPS power to all alarms and A central UPS system or a number of N/A
electronic key access systems. During local UPSs may be required to backup
the design phase, review with facility all building wide low voltage systems
user’s additional equipment that may that are essential for containment
require UPS power backup. 22, 23, 24 operation, safe shutdown of the facility
• Biological Safety Cabinets, and for critical BSL-3 specific loads.
refrigerators and freezers should be
J boxes shall be cast and/or sealed Provide cast boxes with external Consider double gang J boxes
airtight. 25, 26, 27 mounting provisions, external hub, and • Type and Depth: All boxes
gasketed device cover plates should be double gang type;
• Sealing: Provide a 25 mm (1 in.) the box depth should be at
barrier of silicone caulk around the least the next larger than
wire within a device box hub. minimum size required per
Provide a continuous bead of caulk code.
between the device box and the
adjacent surface. Provide a
continuous bead of caulk around
the device cover plate and the
adjacent surface.
Panel boards must be located outside Electrical equipment that requires N/A
the contained space. Circuit breakers service shall not be installed within a
must be labeled. 28 containment area.
The electrical equipment shall mirror the The separate distribution panels shall N/A
N+1 configuration of the critical be powered from separate transfer
Provide labeled shut-off valves to utilities To maintain the integrity of the Access to shut-off valves should
servicing the BSL-3 area(s) and locate containment envelope there should be no be restricted to trained individuals
them outside the containment barrier. 1, 2 access panels in the BSL‐3 laboratory. whenever possible.
Laboratory Mechanical, Electrical, • Labels should be
Plumbing (MEP) items that may need understandable to trained
maintenance shall be outside the individuals, but not
containment zone. compromise security.
Cylinder gases shall be piped from N/A Provide a locked closet for
adjacent rooms outside the BSL‐3 suite, 3 cylinder gases.
Do not provide compressed air to the The use of compressed air increases the N/A
BSL‐3 suite. 8, 9 risk of aerosolizing microorganisms.
Inhalation of infectious aerosols is the
primary route of laboratory acquired
infections.
Water Distribution
Standard Explanation Best Design Practice
The water distribution system shall be Pipe mains shall be designed to achieve N/A
designed to provide the required flow and the maximum calculated flow rate and to
pressure for the most hydraulically provide a 20% allowance for future
demanding fixture/equipment. System expansion.
must comply with local regulations and
industry standards. 11, 12, 13
Vacuum Line
Standard Explanation Best Design Practice
Provide easily replaceable HEPA filters N/A Installed central vacuum systems
where vacuum lines connect to BSCs. 17, should be dedicated to the BSL-3
18, 19, 20, 21, 22
laboratory, should not serve other
• HEPA filters on the vacuum lines areas, and should be located in
must be easily replaceable and close proximity to the
appropriately decontaminated prior to containment space. Central
Sinks
Standard Explanation Best Design Practice
Provide hands‐free hand wash sink with Provide additional sinks as required by N/A
electrically operated valves at each zone risk assessment.
within the BSL‐3 laboratory. 28, 29 • Risk assessment of agents and
laboratory procedures may
recommend additional sinks in an
effort to minimize exposures.
Faucets must be designed such that the N/A Faucets within containment
splash is minimized during handwashing should have atmospheric vacuum
and other procedures. 30 breaker and laminar flow, non-
aerating, non-splash outlet.
Flow rates shall be at least 1.8 gal/min. 31 Laboratory sinks are not regulated by Suggest that Calgreen kitchen
CalGreen (California code) or LEED. UC sink requirement be adopted:
Sustainability policy calls for water use 1.8 GPM normal maximum with
reduction in facilities. Adopting this intermittent maximum of 2.2
Shower
Standard Explanation Best Design Practice
Shower out requirements are based on A shower out requirement will be based When not required, consideration
risk assessment. 33, 34, 35, 36, 37 on risk assessment. If required, pass‐ should be given to the future
• Hand‐held showers shall not be through design shower should be addition of showers with regards
utilized except where specifically considered to allow traffic in one direction to laboratory design layout and
required for barrier‐free compliance only. Dirty clothing/PPE shall not plumbing demands.
and shall include a vacuum breaker. contaminate the clean area.
• Hand held fixtures must have a
vacuum breaker and a mount.
• Consider EDS for shower out if
required by risk assessment.
Fixtures requiring potable supply direct Backflow device shall be Reduced N/A
from the domestic potable water system Pressure Principle type for highest risk
(e.g., emergency eyewash, showers, and level noted in the California Plumbing
toilet room/shower fixtures located in Code Table 603.2
containment) shall be isolated from other
functions with an ASSE 1013 backflow
preventer. 38, 39
Drains
Standard Explanation Best Design Practice
Floor sinks provided for receiving the N/A Floor drains/floor sinks should be
condensate from the sterilizer chamber avoided in containment.
shall be on the clean side of the autoclave
bioseal. 41, 42
Drains pipes must be resistant to liquid N/A Metal pipes should be avoided in
decontaminant used in the facility. areas where decontaminated
liquid waste will be disposed.
Traps
Standard Explanation Best Design Practice
Exposed conduit, piping or pathways are Any material exposed in the BSL-3 N/A
to be resistant to decontamination laboratory shall be resistant to
chemicals and easily cleaned behind, if decontamination methods.
surface mounted.
Provision for landline telephone must be Landline makes communication with Provide an intercom or hands‐
made available. dispatch easier free telephone in each room,
including anteroom 1
• System must be connected
to a location that has
personnel available for
emergency response at all
times work is being
performed in a BSL‐3
laboratory.
Provide a method for electronic transfer of Electronic transfer method eliminates N/A
information to outside of containment the practice of transferring documents
(e.g.: scanner, fax, iPad, etc.). 2 from the BSL-3 to areas outside of
containment.
Security
Standard Explanation Best Design Practice
Anteroom doors must be self-closing and Self-closing doors are required to both N/A
interlocked. Interlocked doors must have maintain the pressure differential and
an emergency override. 3, 4, the security of the space. Locks are
required to prevent unauthorized
access to the containment facility.
Signage
Standard Explanation Best Design Practice
Enhanced facility requirements shall be In some cases, risk assessment may N/A
determined by risk assessment study. call for facility designs that exceed
Enhancements may be required for those recommended in the BMBL
facility and security based on Select BSL‐3 guidelines. This may be due to
Agent Requirements. Example includes the agents and/or volumes in use, the
shower-out capabilities for projects experimental procedures or other
involving work with Highly Pathogenic guidelines that may be followed. The
Avian Influenza. 8, 9, 10 enhancements noted have all been
noted in other parts of this document
and may be required to further protect
the users and environment, to better
be able to decontaminate the facility
or to provide better security.
• Laboratory effluent
decontamination
The BSL‐3 facility design, operational BSL‐3 facilities are some of the most N/A
parameters, and procedures must be complicated facilities to design,
verified and documented prior to construct and operate. The complex
operation. Facilities must be re‐verified systems must be thoroughly
and documented at least annually. 11 documented and facilities personnel
should be trained to maintaining the
various systems.
Seismic
Standard Explanation Best Design Practice
All tall (over 42 inches) and/or heavy This is to prevent damage of N/A
equipment must be provided with seismic equipment in the event of an
restraints designed to withstand shaking earthquake.
equivalent to 7.0 on the Richter scale. 14
Tall and/or movable cabinets must be Penetrations made to the containment N/A
seismically anchored. Anchor points that envelop need to be sealed to maintain
penetrate the containment barrier must be proper directions airflow.
properly sealed.
Provide adequate storage for safety Readily available safety equipment will N/A
equipment and supplies in the BSL‐3 facilitate response in an emergency.
suite, including biological and chemical
spill kits. 1
Provide mounted type ABC fire Provide type ABC fire extinguisher at Provide in gasket, recessed
extinguisher at contained side of contained side of anteroom door. Risk cabinet.
anteroom door. Risk assessment and assessment and Fire Marshal
Fire Marshal requirements shall requirements shall determine need for
determine need for additional fire additional fire extinguishers.
extinguishers. The maximum travel
distance to an extinguisher shall be 15
m (50 ft.). For open labs, the fire
extinguisher shall be located as closely
as possible to the exit access doors.7, 8
Provide space in anteroom for storage N/A Considerations for privacy and
of clean PPE. Provide areas for laundry changing areas should be made
and/or waste bin for disposal of dirty
PPE as necessary. Provide space and
outlets for PAPR charging station and
adequate space for donning/doffing
procedures.
Provide local audible and visual alarms N/A Consider also reporting alarm to
for the following: 11 PI, facilities or campus
• Fire hazard security/police, as appropriate for
• HVAC failure a given alarm condition.
• Differential pressure at any door out • Freezer and incubator alarms
Decontamination
Standard Explanation Best Design Practice
Rooms shall be capable of being The facility should be capable of being Consider placement of
sealed for protocols that require fully sealed for decontamination decontamination ports that are
gaseous and/or vapor decontamination. purposes. accessible from the outside of the
17, 18, 19
facility.
Decontamination corridor
integrated into the design for
Liquid effluent from BSL-3 autoclaves Based on risk assessment, liquid from N/A
may be discharged to sanitary sewer or the BSL-3 autoclave may need to be
reclaimed as appropriate. 20 treated prior to disposal to municipal
sewer.
Air evacuated from the autoclave Provide HEPA filter at the autoclave N/A
chamber prior to decontamination cycle vacuum system to minimize release of
shall be considered potentially infectious material during purging phase.
contaminated and requires HEPA
filtration or other validated method.
Class II Biological Safety Cabinets must Primary containment is required for N/A
meet the NSF/ANSI 49 standard. 21, 22, manipulations of infectious materials
23
Biosafety Cabinets
Minimum Standards Explanation Best Design Practice
BSCs must meet the NSF/ANSI 49 Locate BSCs to minimize air current BSCs should be placed according
standard. Include space for seismic effects of passing traffic and door to the NIH DRM Appendix A.
bracing. 18, 19, 20 openings. Adhere to any UC ergonomics
policies.
• Perform a risk assessment to
determine if the BSCs can be
safely exhausted back into the
room or if they require a
thimble or hard connection.
Hard ducted cabinets (B1 or
B2) cannot be installed
without consultation with
EH&S.
For labs that will be performing aerosol Aerosol challenges shall be conducted N/A
challenges, consideration must be given within a class III biological safety cabinet,
to Class III BSC with enhancements (e.g.: other primary containment device, or
double door sterilizer or dunk tank) or other approved inhalation - exposure
other primary containment devices. Work system capable of withstanding rigorous
with HCLD and EH&S for risk assessment decontamination by disinfectants required
of specific aerosol challenges. 21, 22, 23 by the program.
• Provide HEPA filtration for supply and
exhaust of Class III BSCs.
Flow Cytometry
Minimum Standards Explanation Best Design Practice
Centrifuge
Minimum Standards Explanation Best Design Practice
As part of the review process, the HCLOC Chair will select a subcommittee of five designated
reviewers. One member shall be an HCLOG chair from a location other than the submitting campus,
one member shall be the HCLD from the submitting campus, and the remaining three members will
be chosen by the HCLOC Chair or Vice Chair. The subcommittee will strive to provide the submitting
campus a decision within 10 working days of receiving all the necessary information.
Please note financial restrictions do not outweigh safety requirements. Requests for deviations
cannot be based solely on financial constraint.
Campus:
High Containment Lab Director:
Campus BSL3 Building Location Details (see request for relevant documentation below):
Principle Investigator(s):
Date: Click or tap to enter a date.
UC BSL3 Design Standard – provide the standard section or sections you are seeking to deviate
from
Section:
Number:
State the standard:
Proposed research
Personnel