Manual BLT
Manual BLT
temporarily, all the landing doors should be closed,the doors that can’t be closed
WARNING
Before check, confirm the main power of elevator and the lighting has been off state.
Cut off the corresponding air switch in control cabinet of elevator.
WARNING
During the following process of check, any problem happened
should be checked and solved carefully, confirming no influence
on equipment and people!
Push the key Enter,it will enter the main interface of main controller:
The followings are the corresponding explanation of the lower left/right corner :
Automatic(AUTO)
Test(TEST)
Fire control(FIRE)
Seism(SEISM)
Driver (MANUAL)
Fulload(FULLY)
Overload(OVER)
Lightload(LIGHT)
Self-learning(LEARNING)
Services JAB(LOCK)
The followings are the corresponding explanation of the lower right corner:
Open door (open)
Close door (close)
(2).Menu
In the main interface,push the Enter key, it will enter the selection of mode of
main menu,for example:
In the menu:the first digit figure indicates the main menu,the second digit figure
indicates the corresponding submenu below the main menu.
At this time,push “↑” and“↓”key to choose main menu item, Esc key will exit
from the selection of main menu and return to main interface,Enter key will enter
the selection of submenu item.
(3) The setting of powerup(report parameters refer to Elevator Report Parameters
Instruction of MPK 708C System )
Main controller has 10 main menus totally,push“↑”、“↓”key to alter options of
main menu. After the option is confirmed, push Enter key to enter the submenu of
this menu. The operation after entering submenu is the same as that at main menu.
In the editing pattern,push“↑”、“↓”key to alter parameter value. After the
parameter value is confirmed, push Enter key to reserve parameter value. Esckey
are quitted modification. The defaults have been set up initially for all the
parameters in controller before ex-works. But some parameters must be set anew
according to the position on site.
Main menu:
Configuration (CONFIG)
Time setting(TIME)
Setting of station(landing)(STATION)
Call menu(CALL)
Input and output(IO)
Door (DOOR)
Error history(ERROR HISTORY)
Password(PASSWORD)
Pulse monitor(PULSE MONITOR)
Input select(INPUT SELECT)
The following descripts the function and setting of some menus.
A. Configuration of menu(CONFIG)
Push Enter key,it will enter the submenu of CONFIG menu:
ADDRESS:The scope for selection is 0-15. It is mainly used for setting the
address of elevators during the paralleling ,group control or remote monitoring of
elevators(when two elevators are in parallel, only one is set as 1, the other can be
set as 2).
CONNECT: OFF-LINE is the normal working mode of elevator;ON-LINE is
the automatic calling working mode.
SPEED : Select the speed output of main controller , select V<1.5m/S ,
microprocessor only output one speed signal V1; if V>1.6m/s,microprocessor
will output two speed signals V1,V2;if V>2.0m/s,microprocessor will output
three speed signals V1,V2,V3.(The speed value that needs outputting on site has
nothing to do with rated speed.)
FLOOR DISPLAY:Set the display mode of each floor,push key ENTER to enter
the following interface:
When the display mode is modified,only to push key ENTER,the modifying
cursor “>” sign will arise,then use “↑”,“↓”key to modify its value. After the
modification is finished, push Ente key to reserve the modified result and push Esc
key to exit from the modification state.
All the displayable string list as follows:
0~64, A~Z,-1~-9,1A, 2A, 1B,2B, 1S, 2S, A1, A2, A3, B1, B2, B3, E1, E2, F1, G1,
G2, UB, DB, PB, LG, L1, L2, M1, M2, P1, P2, P3, S1, S2, S3, SS, RC, 5A, 8A,
3A, RG, PH, JP, NJ, GH, MP, GF, π, TZ, NF, SB, 3B, P4, P5, B4, B5, UG
DATE:Set up the current system date.
TIME:Set up the current system time.
LEARNING:Set up the self-learning function.
MANUAL DOOR:Set closing door state under the driver state. OFF mode:need
to push button for long time to close door; ON mode:Close the door by inching.
MANUAL DIRECTION:Set if driver state external call can stop the elevator or
not。OFF mode:external call can’t stop the elevator; ON mode:External call can
stop the elevator.
CONVERIVE SELECT: SIEI is SIEI inverter, MICICINTROL is MICO inverter.
DIFERFLOOR: Duplex parallel with differfloors and numbers of differfloors in
bottom are set together for two elevators. The default is 00. Set the value is 1 or 2.
This parameter is altered in the condition of repairing.
SOFTWARE VERSION: V 0.0. It display system software version.
PULSES PR: 00128 Run curve displays resolution ratio.
B. Time setting menu(TIME)
STOP:Direction/ enable release time, the default is 3.5s.
START:Unused, the default is 0.
BRAKE: Unused.
DOOR OPEN: Set the time of opening door, the default is 2.1s.
DOOR CLOSE: Set the time of closing door automatically. The default is 5s.
OPEN PROTECT:Set time of opening door protection.when opening door limit
cannot reak off because of fault,this protection time value can be set ,door
machine will stop opening door so that the danger of door machine being damaged
for long time’s Power ON can be prevented, the default is 8s.
CLOSE PROTECT:Set the time of closing door protection. When door lock or
closing door limit can’t be connected or break off because of fault,set this
protection time value so that door machine stops closing door,and opening door
anew, the default is 8s.
RINGING:Under the driver state,set the sounding time of buzzer when there is
external call signal, the default is 1s.
GONG: The endurance period of arrival gong signal, the default is 1s.
SPEED STOP: The parking protection, the default is 0.9s.
FLOOR PROTECT: The single floor protection time, the default is13s.
TIME1: The safety edge is always running, the ring time of buzzer, the default is
10s
TIME2:The eliminator of runtime, the default is 60s.(It bases on the setting of
concrete elevator operation.
TIME3:1) Stand-by.
RUN TIMES: Record the times of elevator operation.
C. Setting of Base Station (Station).
BASE:Set the main stop and locking elevator landing of paralleled elevator. The
floor value of this main stop should be set as per absolute floor.
FIRE HOUSE:Set elevator in a fire-fighting state, the value in accordant with
setting of floor when it returns to the base station.
HIGHEST:This value is acquired through self-learning. It doesn’t need setting.
WAIT(1):When the paralleling of elevator is set, it waits on that floor at other
times.
WAIT(2):Stand-by.
REPLY STATION:Set the responding storeys.
SAFEEDGE: Unused
CONTROL MODE: Control mode menu, set by binary system, input
corresponding decimal numeral, initialization is 00.
00: Chinese mode, the elevator shall not be running continuely afer returning to
base station when standby power supply is used.
16: Chinese mode, the elevator shall be running continuely afer returning to base
station when standby power supply is used.
01: Russian mode, the elevator shall be not running continuely afer returning to
base station when standby power supply is used.
17: Russian mode, the elevator shall be running continuely afer returning to base
station when standby power supply is used.
Content above is the option for main controller menu. Set several menus after
power on (refered in the front), continue to describe corresponding menu setting in
the following chapter.
4.7. Confirmation of safety circuit:
After main controller is powered on,confirmation of commissioning of safety circuit
is conducted. When car top inspection is on the ‘inspection’,the safty circuit
commissioning is conducted,confirm the following conditions:
a. The phasesequence of three phase input power source is correct. The indicator light
of phase sequence relay will shine.
b. Machine room 5SB5, pit 5SB6, car top 5SB3 emergency stop don’t act.
c. The other safety circuits don’t act.
When the above conditions are met,safety circuit will run.At the same time,in the
main controller menu option(IO),open the input (I)dot-monitor page layout.when
3.3 is highly bright, safety circuit is valid.
If normal display is not correct or there is error display , the following
commissioning can only be conducted until the error is treated in time.
4.8. Confirm the normal working state of inverter after power-up:
(1) Keyboard sign
Inverter keyboard is composed of LCD monitor, 7 indicator lights and function keys.
The state of inverter’s driving signal can be judged by indicator light, its contens are
as follows:
Name Color Function
-Torque Yellow The inverter output torque is minus.
+Torque Yellow The inverter output torque is positive.
ALARM Red Inverter fault
ENABLE Green Inverter enable
Zero speed Yellow The rotation speed of motor is zero.
Limit Yellow The inverter is under the current limiting .
Activate the function of option 2 of the key
Shift Yellow
press.
Note: For the concrete operation instruction of inverter, see the 《SIEI inverter
operation instruction》
(2).The powerup display is normal.
R: 0 S: 0
MONITOR
Or after push key SHIFT, push key HOME,the above page layout will arise。The
above page layout is the inverter’s page layout of monitoring.
4.9. Initial setting of parameters of inverter:
A.Monitor
Function:Monitor the operation parameter of inverter
The list of the main contents monitored:
Monitor:
Name Content Unit /Note
Output current Output current A
Output power Output power KW/KVA
Norm Speed Running speed rpm
I/O status:
Name Content Unit /note
E:enable
DI 1, 2:direction
Input state
7654321E 4, 5, 6:speed
In accordance with drawing.
0:running contactor
1:braking contactor
DO 3210 Output state
2:Inverter failure
In accordance with drawing.
Input
Content Description
point
0.0 Inspection /normal Close is in normal running condition
0.1 Slow/up Close is effective
0.2 Slow/down Close is effective
0.3 Running inspection OFF when running, ON when stops.
0.4 Inverter malfunction ON indicates that the inverter is running normally.
0.5 Brake test ON when running
0.6 Brake arm test ON when switch off
0.7 Earthquake ON when earthquake happens
1.0 Power failure ON indicates the running of power failure emergency
emergency test
1.1 Back-up power ON indicates the running of back-up power
1.2 Fire detection ON when fire happens
1.3 Motor overheated ON indicates that it is running normally.
detection
1.4 Back-up
1.5 Lock elevator ON when it is locked
1.6 Door zone It is closed at door zone.
1.7 Firefighter It is closed during fire control.
2.0 Limit/ up Signal cut-off during upper limit
2.1 Limit/ down Signal cut-off during lower limit
2.2 V3/up Signal cut-off when speed V3 is at the up speed
changing point
2.3 V3/down Signal cut-off when speed V3 is at the down speed
changing point
2.4 V2/up Signal cut-off when speed V2 is at the up speed
changing point
2.5 V2/down Signal cut-off when speed V2 is at the down speed
changing point
2.6 V1/up Signal cut-off when speed V1 is at the up speed
changing point
2.7 V1/down Signal cut-off when speed V1 is at the down speed
changing point
3.0 Speed test It is ON when the elevator running speed <0.3m/s
3.1 Landing door 110VAC inspects landing door lock
3.2 Car door 110VAC inspects car door lock.
3.3 Safety circuit 110VAC inspect safety circuit.
Note: The input point is effective in low potential (Observe from the display screen: high brightness)
5.3 The adjustment of emergency electromotion
(1) Commissioning procedure:
a. Close main supply, reset the switch of control cabinet emergency stop, ensure the inverter in the control
cabinet is electrified, and the display is operating. The main controller is in the status of TEST.
b. Car top inspect operation is in normal condition.
c .Ensure the input conditions of above list is avaliable,main controller I/O menu can be monitored.
d. The inspection speed Vn of inverter is set to 300mm/s when delivery from factory.
e. Push upward, downard button in controller cabinet, the door should close automatically.
(2) If input conditions are not available, conduct commissioning corresponding to collateral drawings and
find out the malfunction point. If there is concerned malfunction alarm, consult inverter malfunction
or main controller malfunction, and solve the problems in time.
(3) Notice for TEST running:
A. When elevator external safety circuit: speed limit switch 5SQ1, upper terminal landing switch 5SQ2,
lower terminal landing switch 5SQ4, car buffer switch 5SQ6, counterweight buffer switch 5SQ7,
safety gear switch 5SQ8 is running, the TEST running can be used.
B. Before operating, make sure that the car door is closed completely and nobody is in the shaft.
C. TEST running can only be carried out by the professional adjustment and maintenance people
qualified by BLT ELEVATOR COMPANY. Others are forbidden to carry out these functions
privately.
(4) The treatment of malfunction in TEST running:
During TEST running, the commissioning engineer can monitor the current pulse count menu
CURRENT in PULSE MONITOR menu. If the impulse value doesn’t change, checks the frequency
division output of inverter; if E9 Tach Direction Error appears, exchange phase A, phase B.
5.4 Commissioning procedures for car top inspection
After normal running TEST in machine room, inspection works on car top can be carried out on the
premise of confirming safety. Before car top inspection is carried out, the working line of car top
inspection should be confirmed right. All buttons act normally including car top emergency-stop
safety switch.
During the operation process of car top inspection, main controller displays TEST.
When car top inspection is operating, the machine room emergency electromotion is invalid.
If up and down buttons on car top inspection is different from elevator running direction, the working
line of car top inspection direction shall be checked. The change of direction instruction toward
inverter and other changes in control cabinet are not allowed.
If the door of elevator is open, it shall be closed automatically after pressing up and down button on
car top.
Notice for car top inspection:
Press ‘control’ and ‘direction’ button simultaneously when inspection running is operating. Release
‘direction’ button first to stop, and release ‘control’ button 2 seconds later. Thus, the elevator will
stops slowly, or else the safety circuit will be cut off after the ‘control’ button is released, and the
elevator will stop immediatedly, which result in ‘electric arc’ when contactor is off, and it will
damage the contactor if it is serious.
Professional on the car top shall be careful from time to time!
6. Technical Manual& Electric Instruction for BLT Door Operator Controller
6.1 Introduction 2
Operation panel
Mounting hole 2-¢5
Control terminator
Relay output terminator
2. Operation panel:
Operation panel is used to operate door controller manually so as to open/close door and set various kinds
of parameters.
Note: Do not connect the output terminator (U, V, W) to input AC power supply.
4. Control terminator:
Control terminator is an external signal input of door controller, which is used to connect control signal of
door opening/closing, and also the signal of speed change switch and limit switch.
Note: Signal common point (terminator NO. 8) is connected to inner power of door controller, and do not
set earthed.
5. Relay output terminator:
Contact specification: 230V AC 0.3A, 30V DC 0.3A
(ohmic load)
Mechanical life: Over 100 million times
Electric life: Over 100 thousand times
The status of relay output terminator is varies
synchronously with the status of door running, the original
state is NC. When the door is at the arrival position of
OPEN or CLOSE, corresponding NC contact of relay will
Output terminals Output terminals be opened.
of OPEN arrival of CLOSE
relay arrival relay
Name NC COM. NO
contact contact
Output terminals of B2 C2 A2
OPEN arrival relay
Output terminals of B3 C3 A3
CLOSE arrival relay
6. Earth terminal:
To avoid an electric shock, the ground terminal must connect with the grounding line of input AC
power.
7. The parameter settings and instructions of door open/close running status:
The running status of door opening/closing is determined by corresponding speed curve parameters.
There are 3 speed curves: one is open curve, one is close curve, and another one is slow close curve.
Every speed curve is composed of 6 speed segments, and the status of door running could be changed if
you set the parameters of the 6 speed segments.
operator controller
Parameter setting & changing
method:
1. The parameter shoud be set when Press the MODE
button four
elevator stops. times to display
‘P01’
2. After the setting is finished, press
“mode” button to enter into
Press the ▲(up) button twice
“operation preparation completely”, to display‘P03’
and display “000”, orelse, the door Press the SET button to
display P03 data
controller is not going to run.
3. The set data will still be saved after Press the ▲(up) button to change
the data into 60
power off.
4. There is an example for parameter Press the SET button to confirm
which is setting on the right side: the data
Press the MODE button to change into
Change the data of P03 from‘50’to ‘operation preparation
completely’state
‘60’.
7.1 Open speed curve and instructions of relevant parameter settings:
7.1.1 Open speed curve:
7.3.2 The instruction of related parameters for slow close speed curve:
Open operation: Press the ▲ button once, and next press the RUN button once,then the running of door
operator will be unidirectional.
Close operation: Press the ▼ button once, and next press the RUN button once,then the running of
door operator will be unidirectional.
* Notice: Parameter ‘P08’‘P09’ have to be recovered to factory default before door operator gets back to
normal running.
9 The treatment of abnormal situation:
9.1 The reset of unexpected tripping:
If abnormal tripping occurs when door operator works in normal condition, press “STOP” button to
reset the door operator controller.
9.2 The malfunction code and treatment are displayed when abnormal tripping occurs:
10 Standard specifications:
1. Schematic plan:
Door motor
Door controller
Bistable switch
Door motor
3. Bistable switch:
3.1 Four bistable switches are taken to detect the moving position of door on door operator and they are:
“Open limit” “Open speed change” “Close limit” “Close speed change”. These four signals are connected
to elevator door controller directly. The functions of the 4 switches are descripted as follows:
3.2 In addition, another bistable switch is installed to detect the 1/3 position of opening door, which signal
wire is connected to the elevator main controller directly.
4. Car door lock switch:
AZ051 slave door switch is applied on car door lock switch, and the car door lock switch is connected to
safety circuit in series. AZ051 is a switch with the characteristics of double contact, absolute break
contactor, and also a separated contact component. It is used in elevator door and plays a role of
safeguard.
Glass fiber reinforced thermoplastic ,
Shell
self-extinction
Cover Transparent thermoplastic
Fixation 2 ×M4,circular aperture
Rated insulated
500VAC
voltage
Constant current 4A
Rated working
2A (230VAC),1A(200VDC)
current
Contact type Pressure frictional contact
silver-copper contact of spring-strip
Door interlock switch Contact
structure
Wiring M4 screw,automatic clamp
Structure Accord with EN81-1/2 standard
Protective grade IP20
5. Wiring socket:
9 cores wiring socket: Type AMP1-480707, the contents of wiring are as follows:
Socket
aperture Wire NO. Connecting position Function description
NO.
1 114 L Input power supply AC L
line of door controller
2 115 N Input power supply AC N
line of door controller
3 601 Output terminator of door Open arrival output signal
controller B2
4 602 Output terminator of door Close arrival output signal
controller B3
5 614 Control terminator of door OPEN command input signal
controller 1
6 615 Control terminator of door CLOSE command input
controller 2 signal
7 0V Output terminator of door Door controller output signal
controller C2, C3 COM
8 616 Control terminator of door Door controller input signal
controller 8 COM
9 617 Control terminator of door Door nudging input signal
controller 5
P01 0.5 P19 0 P37 1 P55 0 P73 3 D11 55 D29 1.5 D47 0.5
P02 0.5 P20 0 P38 0 P56 1 P74 0 D12 25 D30 1.3 D48 0.35
P03 50 P21 0 P39 0 P57 0 P75 0 D13 5 D31 0.5 D49 0.5
P04 0 P22 0 P40 1 P58 5 P76 0 D14 1.5 D32 1.1 D50 0.3
P05 20 P23 0 P41 0 P59 10 P77 1 D15 2.5 D33 1 D51 3
P06 2 P24 0 P42 0 P60 50 P78 100 D16 16 D34 0.5 D52 2
P07 3.6 P25 0.1 P43 27 P61 1.2 P79 0 D17 23 D35 1.5 D53 0
P08 2 P26 0 P44 0 P62 1.2 D00 0 D18 20 D36 0.8 D54 3
P09 4 P27 1 P45 10 P63 0 D01 655 D19 8 D37 0.5 D55 8
P10 0 P28 0.5 P46 0 P64 50 D02 0 D20 4 D38 1.1 D56 8
P11 0.5 P29 250 P47 0 P65 70 D03 5 D21 1 D39 1.5 D58 8
P12 0 P30 0 P48 7 P66 5 D04 15 D22 3 D40 0.5 D59 2.5
P13 0 P31 3 P49 4 P67 100 D05 40 D23 16 D41 0.5 D60 0.5
P14 50 P32 0 P50 5 P68 200 D06 70 D24 19 D42 0 D61 1.5
P15 50 P33 140 P51 6 P69 0 D07 95 D25 16 D43 2.5 D62 0.8
P16 1 P34 10 P52 512 P70 0 D08 100 D26 9 D44 2.5 D63 1.1
P17 1 P35 1 P53 0 P71 0 D09 95 D27 2.5 D45 0.5 D65 1.5
P18 0 P36 96 P54 1 P72 3 D10 80 D28 1 D46 1
7 Self-learning running
7.1 During self-learning running commissioning, first you have to confirm the settings of the following
parameters are right:
The selection of speed parameters are based on landing height and rated running speed of elevator:
SPEED:
When elevator rated speed V<1.5m/s, the microcomputer will output one speed signal V1 only.
When elevator rated speed V>1.6m/s, the microcomputer will output two speed signals V1, V2.
When elevator rated speed V>2.0m/s, the microcomputer will output three speed signals V1, V2, V3.
The corresponding running speed of inverter should be set according to the collateral drawings.
When operating elevator shaft self-learning, the running speed is set as inspection speed Vn (It is set as
350mm/s usually).
7.2 After the above parameters are confirmed right, the following signal connetion also need to be
inspected.
(1) The installation position of speed changing switch and limit switch.
a) The position of installation is shown as the following table 1 and 2:
If the system is set as V1=800mm/s; V2=200mm/s; V3=1750mm/s, then the braking distance should be
set as SV1=1.16m; SV2=2.16m; SV3=3.65m.
1750 3650±30
2000 4600±30
Magnet
Guide rail
This installation distance is the distance for speed changing when the elevator runs at different speed. This
distance value is recorded by main controller througth shaft self-learning. During elevator commissioning,
the switch of speed change should be installed correctly according to standard documents.
b) Confirm the shaft signal action:
Monitor the signal action in the IO menu of main controller:
When the car runs in the middle of the shaft, all the speed change switches are effective. At this moment:
Up run, input point 2.2, 2.4, 2.6 disconnect orderly;
Down run, input point 2.3, 2.5, 2.7 disconnect orderly;
(If there are only two speeds, do not use 2.2, 2.3)
7.3 Start self-learning running: After the above steps are performed, the self-learning running could be
started.
Start self-learning running by menu CONFIG/LEARNING ON.
During running, every door zone signal and the distance of speed change is recorded by main controller.
Self-learning running could be interrupted by Inspection/Test manually or system malfunction.
7.4 Renewal self-learning: When any change occcurs in the door zone inspection of shaft or the position
of speed change switch is changed, an effective self-learning must be performed.
8 Debugging operation
8.1 On-site inspection and confirmation
(1) The inspection and confirmation of machine assembling
A. The elevator pit components are installed in good condition. If hydraulic buffer has been used, confirm
the buffer oil is enough as requested; the pit should be dry.
B. There is no barrier in the shaft which can influence the running of the elevator.
C. The landing door is installed in good condition.
D. Good sealing between landing door upright and door opening.
E. The installation of guide rail has been approved qualified.
F. The installation of steel rope is correct and tight.
G. The installation and fixing of all sorts of switches.
H. The tension sheave of speed governor steel rope has been installed correctly.
I. The installation of car is complete, consolidate and tighten.
J. The traveling cable has been installed and fixed in good condition.
K. The positioning of machine room components comply with the national standards.
L. The fixing of main machine complies with the requirements of factory installation, and the main
machine beam should be fixed and sealed (concealed work) good.
M. If it is equipped with gear traction machine, confirm the oil in reduction gearbox is enough.
N. Confirm the encoder on the main machine is fixed firmly.
O. The positioning of speed governor is satisfied the national standards.
P. The wire duct is laid in order, and they should be connected by copper sheet and yellow green wire.
Q. The installation and positioning of control cabinet is in order.
R. The machine room and shaft should be kept clean.
S. The leveling sensor flashboard in every floor of shaft should be installed correctly.
T. The car door operator is installed correctly.
A. The wiring of door operator should be correct; the wiring of infrared curtain should be correct.
B. The wiring of car top leveling sensor should be correct, and ensure the installation dimension is correct
and firm.
C. Every safety switch in the shaft could act effectively.
D. The installation position of upper and lower inspection switches in the shaft should be correct, and the
action of switch is effective.
E. The wiring of interphone is correct, and ensures the call is normal.
F. The wiring of arrival gong is correct. (Skip this step if there is no arrival gong)
G. The wiring of external calling box is reliable and correct.
H. The wiring of car lighting and fan is correct.
Note: The installation position of shaft speed change switch (the distance of speed change for various
elevator speeds) should comply with the stipulated distance strictly in the system standards. During
the debugging, after comfirm the installation position of hardware strictly, the position of speed
change switch will not be changed after shaft self-learning, which is to keep the hardware speed
change distance in accordance with the software.
(2) The comfirmation of inverter parameter
Confirm the corresponding speed setting value of inverter, and again, the relevant running parameters.
8.3 Machine room test running
After the above parameter settings are confirmed, the calling debugging in the machine room could be
started.
The calling running should be performed under the CALL menu:
(1) Operate the elevator in V3, V2, V1 speed respectively, that is, distance between floors for calling shall
be operated ≥ 9m, 6m.
(2) During calling running, check the status of door switch, any problems that appears should be solved
immediately.
8.4 Normal operation debugging
After the above debugging is complete, you can ride in the elevator and adjust the comfort.
(1) The comfort adjustment
A. The adjustment of acceleration and deceleration (menu: Travel/ Ramp profile)
The running curve of BLT elevator has been adjusted when delivery from factory, and usually, it is no
need to adjust.
In general: The vibration occurs frequently during accelerating, and this is extremely important for
passenger’s comfort feeling. And this will result in parts dumping or vibrating in drive system, what’s
more, many mechanical parts will suffer from heavy weight. Not everyone has the same feeling towards
vibration; it is related to people’s age, physique, and mental state.
B. The start adjustment
Due to the lack of special advance torque facility, the phenomenon of sliding to the bearing side may
occur when the elevator is starting. Adjust the Sdp P/I value for starting could solve this problem.
C. Vertical vibration during running
Mechanical reasons may lead to vertical vibration, and you can solve the problem by adjusting the
parameters in inverter.
High-frequemcy vertical vibration could be adjusted so that the elevator will keep stable during
high-speed running. If the wave drifting sense appears during high-speed running, adjust Sdp P/I.
Note: The Sdp P is increasing gradually, which can speed up the system dynamic response. But, if it is too
large, the traction machine may become unstable; the Sdp I is increasing gradually, but, if it is too large,
the traction machine may become unstable.
(2) The adjustment of creep distance
Install the decelerating switch according to the requirements of “7 Shaft self-learning” in this manual so
that appropriate creep distance is obtained. If the switch position is not correct, please adjust it again.
8.5 The adjustment of leveling precision
(1) The measurement of floor horizon deviation
The car should be stopped at the leveling position while installing door zone plate, so that the elevator can
level precisely and accelerate the process of debugging. (Please see the previous instructions)
When adjusting leveling for MPK708C system, firstly, adjusts and stops the elevator on the same position
of upward and downward door zone when it runs upward and downward to the landing by the previous
debugging.
(2) Adjust the V0 value, and achieve the leveling position. (Usually, V0=115~119mm/s)
8.6 The setting of external calling board
1) There is an 8-bit DIP switch on the external calling board, and NO.8 is the terminal resistor. When this
external calling board is at the lower landing, the NO.8 is ON and the other landings are OFF.
2)Based on the binary coding 1248 in turn, the other 7 bits from low to high should be dialed according to
the absolute landings. For instance, NO.5 landing, DIP switch 1st bit, 3rd bit is ON.
3) For elevator with opposite door, if the two doors need to be opened and closed solely, the 7 th bit stands
for the external calling signal of 2# door.
8.7 The settings of running time limit
The running time eliminator of the electromotor should act ≤ the lower value of the following two time
values:
①45s;
②The overall travel time of elevator adds 10s. If the overall travel time is less than 10s, the minimum
value is 20s. After the electromotor running time is determined, set the running time limit protection in
TIME/TIME2 of MPK708C main controller menu.
9-Function confirmation
Confirm other functions work normally:
1. Confirm the normal situation for lighting in car and fan switch (whether the relay is cut
off)
As no operation signal within 300s, the car lighting and fan will be automotically
closed and restarted as re-operating.
2. Confirm the normal condition for driver’s functional switch.
In the car, turn on the driver’s switch and the displayer on the main controller appears
the state of MANUAL mode.
Driver’s functions include: as the elevator is operated by the driver, the corresponding
indicator light in the car is on if there is an external call signal; but as for limited
calling, driver can select the corresponding floor in the car;
At driver state,as for the setting of door, see the menu CONFIG chapter 4
3. Confirm the normal situation of the functional switch for full load/bypass switch.
As 100% load in the car, the functional switch for full load/ bypass switch (with full
load indication) come into operation. (“FULLY” display on major controller).
The functions for full load/ bypass switch are: no response to the external call as full
load, only for the car call.
4. Confirm the normal situation for special functions:
In the car, turn on the special switch and make it come into operation.
Special function is: when using the special functions, the elevator will keep the signal,
but will not response to the external call signal, that is limited calling. Arbitrary calls
are for special person in the car.”
5. Confirm the normal situation for fire control functions:
As testing the fire control function, the test can be carried out within the machine room
so as to make the input point for fire control be effective. At the moment, the panel of
major controller displays FIRE STATE.
Fire control function is: as operating the fire control function, the operating elevator
will stop at the nearest parking floor, then return to the designated fire exit landing and
automatically open the door. As the fire fighter enters the elevator after the calling, the
elevator will run to the rquired floor for task implementation. As the fire fighter
operates elevator, the door can be set hand-operation or automatic closing after calling.
The menu can be set as follows.
6. Confirm the normal situation for overload function:
When there is 115% load in the car, the overload switch (with overload indication)
comes to operation and the panel of major controller displays “Over” state.
Overload function is: the overload signal is detected when elevator stops. The
elevator will stop operating as it is overloaded.
10-Asynchronism Motor Adjustment
Asynchronism motor self-adjustment (Do motor self-adjustment on site according to
the following commissioning procedure)
10.1 Asynchronism motor adjustment
1. Power off and make 478 and 519 be in short circuit.
2. Power on and contactor 4KM1 on output side pulls in.
3. Set the following parameters according to the motor nameplate.
Open the menu of STARTUP/Startup config/Enter Setup Mode As.Then set the
corresponding parameters of MOTOR DADA or Drive DATA. At the same time,
4KM2 pulls in.
4. Make ENA and 24V be in short circuit.
5. Open the menu of STARTUP/Startup config/Enter Setup Mode As/ autotune.
Push the complete still autotune button.
6. Self-learning is beginning and it may carry on for about 5 minutes.
7. When the operation board of inverter displays “End”, self learning ends up.
8. During exiting menu, operate Load setup at the path of menus/Startup and choose
YES-ENTER.
9. Save the parameters of self -learning at the path of menus/Startup/SaveConfig.
10. After self-learning, power off and renew the connecting wire of inverter and
contactor.
10.2 Synchronism motor adjustment procedure
A Synchronism motor current adjustment
1. Power off and make 478 and 519 be in short circuit.
2. Power on and contactor 4KM1 and 4KM2 on output side pull in.
3. Set the following parameters according to the motor nameplate.
Open the menu of STARTUP/Startup config/Enter Setup Mode Br
(synchronism).Then set the corresponding parameters of MOTOR DADA or Drive
DATA. At the same time, 4KM2 pulls in.
4. Make ENA and 24V be in short circuit.
5. Open the menu of STARTUP/Startup config/Enter Setup Mode As. Push the
CurrReg autotune button.
6. Self-learning is beginning and it may carry on about for 5 minutes.
7. When the operation board of inverter displays “End”, self learning ends up.
8. During exiting menu, operate Load setup at the path of menus/Startup and choose
YES-ENTER.
9. Save the parameters of self -learning at the path of menus/Startup/SaveConfig.
B Synchronism motor magnetic field adjustment
1. Power off and make 478 and 519 be in short circuit, and make 118 and 475 be in
short circuit.
2. Make the Enable (12 port) and +24V (19 port) of inverter be in short circuit.
Connect 220VAC terminal (Wire number is 111,115) of transformer with
contactor coil respectively. As picture 1 shows:
3. Power on and contactor 4KM1 and 4KM2 on output side pull in.
4. Enter inverter Service menu and input password (28622)
5. Open the Service/Brushless menu, press Autophasing Still button.
6. Make inverter ENA, FWD, V0 signal and 24VDC be in short circuit, there is
magnetic field self-learning pace on operation panel. When the pace is 100%,
self-learning of magnetic field has finished.
7. Save the parameters of self -learning at the path of menus/Startup/SaveConfig.
8. Record value of SinCos/Res pos and SinCos/Res off at the menu
Service/Brushless. Repeat the learning function of magnetic field position for
several times in order to confirm that the value of magnetic degree is right. Each
learning result should be similar or same.
9. After self-learning, power off and renew the connecting wire of inverter and
contactor.
11- Adjustment of Floor Station
The running of elevator is 2 floors 2 stations, start the following self-learning
adjustment process: (other adjustment methods are the same)
1) Make V1 upper speed changing signal (12.6) be in short-circuit.
2) Make the elevator get across the upper landing leveling plate and strike the upper
limit, then stop.
3) If the elevator strikes the upper limit without getting across the upper landing
leveling plate, self-learning of well is failure. So it need move the limit switch up
by 100mm or move leveling plate down properly in order to meet 2) requirement.
4) Start self-learning of well.
5) Renew the connection of V1 upper speed changing signal(12.6) and leveling plate
position.
The specific adjustment method is as follows:
11.1. Firstly, make sure the following parameters have been set.
According to the height of floor and the rated speed of elevator to ensure the
parameter of Speed:
SPEED:rated speed,when V<1.5m/S, computer only outputs one speed signal V1.
Running speed is the inspection speed Vn(usually is 300mm/s)during elevator
self-learning .
11.2. After setting above parameters, check the connection of following signals.
(1)The installation location of the speed changing switch and limit switch .
A. The drawing of installation location:
Refer to standard document to install speed changing switch properly; the
adjustment method is the same as chapter 7.
B. Make sure that signal action of well is right:
Check the sigal action on IO menu of main controller.
When elevator is running in the middle of well, the speed changing signal is
valid:
a)Run up, input point 2.6 is off;
b)Run down, input point 2.7 is off.
2.0 Limit /up Upper limitation, signal cut-off
2.1 Limit /down lower limitation, signal cut-off
2.6 V1(lower speed)/up V1 speed, up speed changing, signal cut-off
2.7 V1(lower speed)/down V1 speed, down speed changing, signal cut-off
2) Set parameters
Set parameters in menu CONFIG:
ADDRESS: one elevator is 1#, the other one is 2#
12.2 Differfloor parallel elevator:
(1) Connection on site
Connecting wire of main controller is the same as Standard parallel elevators
adjustment method.
(2) Set parameters:
Set in menu CONFIG :Modify the parameters on the state of inspection. Turn off
power after modification in order to take effect.
a)ADDRESS:The elevator which has basement is 1#, the other one is 2#.
When they are under group control, the address No. of elevator which has basement
is odd number address, the address No. of elevator which does not have basement is
even number address.
b)DIFERFLOOR: Default value(00)
Differfloor parallel; set number of the lower terminal
differfloor landing for both elevators at the same time. The setting value is 1 or 2.
(3) Set DIP switch (for example)
Set the DIP switch of landing call display board, the DIP switch of differfloor
display board is set as the absolute landing of both elevators.
Such as:
1# stop is:1,2,3,4…10
2# stop is:-1,1,2,3,4…10
So:
1# DIP switch of landing call display board is: 2,3,4…11;
2# DIP switch of landing call display board is the standard setting:1,2,3,4,…11
DIFFERFLOOR: Set 1.
13- Pre-opening/ releveling function
13.1 The installation manual of leveling switch
The installation drawing of leveling switch ( it suits for releveling function) is drawing1:
Drawing 1
Note:If there is only pre-opening function, this operation is not needed.
Installation requirement:
1. When elevator is leveling, the horizontal center of 4SQ4 is as high as the center of door zone
leveling plate;
2. 16SQ2 and 16SQ3 distribute equidistantly to center of 4SQ4;
3. Adjust the distance between door zone leveling top edge and bottom edge of 16SQ2 to be 5~10 ㎜;
4. Adjust the distance between door zone leveling bottom edge and top edge of 16SQ3 to be 5~10 ㎜;
5. The vertical center lines of 16SQ2, 4SQ4 and 16SQ3 coincide.
13.2 The action order of releveling
When elevator stops normally, only 4SQ4 door zone switch is blocked by magnet vane of door zone.
When elevator stops, 16SQ2 or 16SQ3 is blocked by magnet vane of door zone because of some reason,
the elevator will run at releveling speed in the opposite direction until the blocked switch is away from the
block; And only when 4SQ4 door zone switch is blocked by magnet vane of door zone, should the
elevator stop running immediately. Keep leveling error of elevator rational by fine-adjustment of
releveling speed.
13.3 The setting of main controller:
2. Opening time:
=24= TIME
DOOR OPEN: It suits for pre-opening function;
0000.2 /S On the premise that there is no E2 door interlock fault,
this time is set as short as possible.
3. PM card monitoring:
=AA= INPUT SELECT
PMCARD:
ON
4. Pre-opening:
=A9= INPUT SELECT
PRE-OPEN:
ON
5. Releveling:
=A8= INPUT SELECT
RE-LEVELING:
ON
Picture:simple weighing device(If there is any change, the appearance takes real
products as standard.)
(2) Put the weight equivalent to 90% rated load into car evenly by installation personnel
outside landing, then the installation personnel in pit adjust the position of full-load switch
7SQ1 and make it contact with the press plate at car bottom, and the switch acts. At this time,
calling box outside landing displays “FULL LOAD”, namely, the full-load switch has been
adjusted well.
(3) Put the weight equivalent to 100% rated load into car evenly by installation personnel
outside landing, then the installation personnel in pit adjust the position of over-load switch
4SQ1 and make it contact with press plate at car bottom, but the switch does not act. At this
time, one installation person outside landing comes into car and the switch acts. Meanwhile,
operation panel displays “OVER LOAD” and buzzer buzzs continuously. After the
installation personnel go out of car, “OVER LOAD” will disappear and the buzzer will stop
buzzing, namely, over-load switch has been adjusted well.
(4) After adjusting over-load switch and full-load switch well, the installation personnel outside
landing move the weight out of car and close landing door.
(5) Renew the emergency stop switches on car roof and in pit.
(6) The installation personnel on car roof make the elevator run to leveling position of the
second floor at inspection speed, then stop the elevator and press emergency stop buttons on
car roof.
(7) Open landing door on the first floor by installation personnel outside landing and the
people in pit get out. Close the landing door.
(8) The installation personnel on car roof renews the emergency stop button on car roof and
leaves car roof. Renew elevator’s running to be normal.
(9) Install half-load switch on the elevator which has power failure emergency function. Put
50% rated load in car when adjusting, the adjustment method is the same as above
mentioned.
15. MPK708C electric system’s factory parameter
15.1 MPK708C main controller’s factory parameter(Y standard for single unit, and others shall be
dealt with according to the construction.)
15.1.4 CALL(40)
No. Sub Menu Content Facotry Default
41 UP CALL
42 DOWN CALL
43 CAR CALL
15.1.5 I/O (50) Output/input monitor manu
No. Sub Menu Content Facotry Default
INPUT(A,B,0.0-3.3)
51
Input of main controller
OUT(0.0-2.5)
52
Output of main controller
X01-X08
53 The mode of internal option
board
A00-A13
PM709 the signal input
54
X34,X35
The main controller output
B00-B06
55
PM709 the signal output
00: Chinese mode, no sub-lock detecting function; As standby power is used, the elevator shall not
run after returns to the base landing.
16: Chinese mode, no sub-lock detecting function; As standby power is used, the elevator could
continue to run after returns to the base landing.
03: Chinese mode, sub-lock detection function; As standby power is used, the elevator shall not run
after returns to the base landing.
19: Chinese mode, sub-lock detection function; As standby power is used, the elevator could
continue to run after returns to the base landing.
01: Russian mode, as standby power is used, the elevator shall not run after returns to the base
landing.
17: Russian mode, as standby power is used, the elevator could continue to run after returns to the
base landing.
No. Sub Menu Content Facotry Default
RE-LEVELING Default OFF Y
A8
ON: has
PRE-OPEN Default OFF Y
A9
ON: has
PMCARD Default OFF
AA ON has the function of pre-open
and relevel.
0: a single door operator for a Y
single operation box
1: Two operation boxes for double
door operator or single door
AB OPEN-METHOD: operator. Two door operators shall
act at the same time.
2: Two operation boxes for double
door operator. Door operators
control respectively.
REPAIR OPEN: Unused, the open door button
AC could not make the door open
during inspection.
GROUP CONTROL OFF: has not Y
AD
ON: has
MONITOR OFF: has not Y
AE
ON: has
ARRIVE LAMP OFF: has not Y
AF
ON: has
0: Cancel this function Y
>0: If the number of error open is
more than set value, the function of
AG ERROR OPEN TIMES
automatic door close will stop. If
the door press button is pressed,
the door will try to close again.
TIME4 Default 0s Y
The time it keeps the
same direction after the
AH cut off of the speed
signal during the
setting of inspection
operation
FORCE CLOSE OFF: has not Y
AI
ON: has
AJ TEST TIME Standby
CLOSE LAMP The time it takes to close the car
AK light without call.
Default 03(minute)
Parameter
No. Parameter name Parameter value Unit
No.
37 Spd 0 ref thr 3726 Synchronous 1, Asynchronous 5 rpm
38 Spd 0 ref delay 3727 500 ms
39 Spd 0 speed thr 3724 Synchronous 1, Asynchronous 5 rpm
40 Spd 0 spd delay 3725 500 ms
SGP tran21 h
41 3706 95%
thr
42 SGP tran32 I thr 3707 0.5%
SGP tran21
43 3708 0.5%
band
SGP tran32
44 3709 0.1%
band
45 DO 0 src 4065 RUN cont mon
46 DO 1 src 4066 BRAKE cont mon
47 DO 2 src 4067 Drive OK
48 DO 3 src 4068 Compare 1 output
49 Dig Enable src 156 Dig pad 15
50 Tcurr lim sel 1190 T lim sym var
51 Tcurr lim sel 1195 Pad15
52 Pad0 9100 62
53 Pad1 9101 4000
54 Pad3 9103 32767
55 Cmp 1 inp 0 src 6049 Norm Speed
56 Cmp 1 inp 1 6042 1000
57 Cmp 1 function 6044 |I0| < |I1|
58 Cmp 2 inp 0 src 6064 Speed ref
59 Cmp 2 inp 1 src 6065 Norm Speed
60 Cmp 2 function 6059 I0 == I1
61 Cmp 2 window 6060 3276
62 Cmp 2 delay 6061 2 s
63 EF src 9075 Dig pad 5
64 EF hold off 9600 2000 ms
15.3 The set of CT inverter’s factory parameter
15.3.1 Inverter functional parameter
15.3.3.2 Sychronous
No. Parameter Parameter name BLT factory default
(This
parameter is
applicable to
all kinds of CT
inverters)
1 Pr1.06 Motor maximum speed (rpm) Motor rated speed
2 Pr5.07 Motor rated current (A) Sychronous traction machine’s
name plate
3 Pr5.08 Motor rated speed(rpm) Sychronous traction machine’s
name plate
4 Pr5.09 Motor rated voltage (V) Sychronous traction machine’s
name plate
5 Pr5.11 Motor rated number of poles Synchronous 20
15.3.4 Mechanical parameter of elevator
No. Parameter (This Parameter name BLT factory default
parameter is applicable
to all kinds of CT
inverters)
1 Pr19.27 Denominator of reduction Traction machine’s name
ratio plate (Set for asychronous
traction machine)
2 Pr19.29 Diameter of traction Traction machine’s name
sheave (mm) plate
3 Pr19.30 Numerator of reduction Traction machine’s name
ratio plate (Set for asychronous
traction machine)
4 Pr20.10 Roping Asychronous 1; Synchronous
2
7 Pr18.16 Vr(mm/s) 10
8 Pr18.29 Elevator rated rotating Motor rated speed
speed (rpm)
9 Pr18.30 Elevator rated speed Elevator rated speed
(mm/s)
15.3.6 Parameter of curve
No. Parameter (This Parameter name BLT factory default
parameter is
applicable to all kinds
of CT inverters)
1 Pr19.17 Start optimized jerk(mm/s3) 10
2 Pr19.14 Start jerk(mm/s3) 600
3 Pr0.03 Acceleration rate (m/s2) 0.600
4 Pr19.15 Running jerk(mm/s3) 600
Figure:
14. E14:
Fault content: Count error, that the error between the floor at which the elevator is and the
pulse value exceeds the speed changing distance at terminal landings.
Cause of fault: Elevator does not stop at levelling position. This alarm may be caused by the
fault of E2,E4,or E9.
Remedies: Autotune again if the fault happens again and again after the adjustment of leveling
or speed changing switches at terminal landings. Check if there are E2,E4,E9,
E18 in the fault record and find the reason.
Fault display and recovery: The fault will not be displayed by the landing indicator, recorded
by the main controller. The elevator will return to down
terminal landing at a single speed after leveling.
15. E15 :
Fault content: Pulse count is not consistent with inductor count.
Cause of fault: Door zone switch error, poor installation.
The wiring of door zone switch is not correct.
Check if there are faults of E9 or E14, when the pulse signal is abnormal.
Remedies: Check door zone switch and replace it if there is any damage.
Check wiring.
Check pulse count, referring to the related fault code.
Fault display and recovery: The fault will not be displayed by the landing indicator, and
recorded by the main controller. There is no need to stop the
elevator.
17. E17 :
Fault content: Landing door opens in an abnormal condition.
The lock of landing door is not open after the lock of car door has been closed
for more than 2 seconds.
Cause of fault: The switch of door lock is damaged or wiring is not correct.
Door operator is not adjusted properly.
Remedies: Replace switch and check wiring.
Check the installation dimension of door operator.
Fault display and recovery: The fault can be displayed by the landing indicator, and recorded by
the main controller.
18. E18 :
Fault content: After elevator starts (in 1.5s), the input point of inverter could not be detected.
Cause of fault: Inverter is damaged or parameter setting is wrong.
The wire or terminal is loose.
The main contactor (4KM1, 4KM2) can not release well during service.
Remedies: Check inverter and parameter.
Check wiring and terminals.
The main contactor (4KM1, 4KM2) can not release well during service. Check if
there is a momentary break of the safety circuit or door lock.
Keep pit dry.
Fault display and recovery: The fault can be displayed by the landing indicator, and recorded by
the main controller. The elevator will level at the nearest floor and
could not start again, which could be rectified after an inspection
operation is applied or power supply is cut off.
19. E19 :
Fault content: The monitoring point of inverter brake is not open; elevator cannot restart.
Cause of fault: Inverter is damaged or parameter setting is wrong.
Input point of controller is damaged.
Remedies: Check inverter and parameter.
Replace controller.
Fault display and recovery: The fault can be displayed by the landing indicator, recorded by the
main controller, and removed by the open of monitoring point.
20. E20 :
Fault content: Floor record is not consistent with the forced changing switch. Switch is off
while elevator is not at terminal landings.
Cause of fault: The speed changing switch is damaged.
Speed changing magnet is not installed properly.
Wrong action of door zone switch
Remedies: Replace switch
Adjust the position of magnet, with a horizontal distance of 6±1mm between magnet
and switch.
Replace door zone switch.
Fault display and recovery: The fault will not be displayed by the landing indicator, and
recorded by the main controller.
21. E21 :
Fault content: The brake switch does not switch off (main machine), and elevator can not
restart.
Cause of fault: Brake detection switch damage or wiring fault.
The fault of brake adjusting
Remedies: Replace switch, check wiring.
Readjust the arm of brake.
Fault display and recovery: The fault can be displayed by the landing indicator, recorded by the
main controller and removed by the release of brake switch.
22. E22 :
Fault content: Floor record is not consistent with the forced changing switch. Switch is not off
while elevator is at terminal landings.
Cause of fault: Speed changing switch is damaged.
The installation of speed changing magnet is not correct.
Remedies: Replace switch, check wiring.
Adjust the position of magnet, with a horizontal distance of 6±1mm between
magnet and switch.
Fault display and recovery: The fault will not be displayed by the landing indicator, and
recorded by the main controller.
23. E23 :
Fault content: The button has jammed for more than 30 seconds.
Cause of fault: The button of landing call has jammed.
Remedies: Check the button of landing call and change it if it is damaged.
Fault display and recovery: The fault will not be displayed by the landing indicator, and
recorded by the main controller.
24. E24 :
Fault content: The main controller will record the fault E24 when the door lock was open for
over 3s, but door closing limit switch has not been switched off. Landing call and
car call display E24 at the same time and open the door in reverse. If there is no
door operator of No.2, a blank shall be left for the input point for 2# door
operator’s door closing limit.
Cause of fault: The bistable switch for limiting the door operator close is damaged.
The closing limit switch of door operator is not adjusted well.
Remedies: Check switches and replace the bad ones.
Adjust the position of switch.
Fault display and recovery: The fault can be displayed by the landing indicator, recorded by the
main controller and removed if elevator is restored to inspection
operation, door lock is open for over 2 seconds, or the limit switch
of door closing is switched off.
25. E25 :
Fault content: Cannot detect the input of safety door zone (I3.4), with the function of door
pre-opening.
Cause of fault: Wire is connected loosely or in a wrong way.
Security module is damaged.
Remedies: Check the wiring.
Check the security module(SM01-001)
Fault display and recovery: The fault can be displayed by the landing indicator, recorded by the
main controller and removed after the signal recovery.
26. E26 :
Fault content: PM709 for car top board has a communication fault (When parameter INPUT
SELECT/PMCARD=ON)
Cause of fault: The interruption of transmission lines
Control board or PM709 board is damaged.
Remedies: Check communication circuit to eliminate interference.
Replace control board.
Fault display and recovery: The fault can be displayed by the landing indicator, recorded by the
main controller and removed after the communication recovery.
27. E27:
Fault content: Cannot detect the input of security contact (I3.5), with the function of door
pre-opening.
Cause of fault: The wire is loose or connected wrong.
Door zone signal fault
Security module(SM01-001)fault
Remedies: Check wiring.
Check the action of door zone switch and the installation of it.
Check security module(SM01-001)
Fault display and recovery: The fault can be displayed by the landing indicator, recorded by the
main controller and removed after the signal recovery.
28. E28:
Fault content: Cannot detect the input of speed testing point (I3.0), with the function of door
pre-opening.
Cause of fault: The fault of inverter parameter or the damage of unit
Relay (3KA4) is damaged.
Remedies: Check the parameter of inverter and the signal of speed monitoring.
Check the relay (3KA4) and its wiring.
Fault display and recovery: The fault can be displayed by the landing indicator, recorded by the
main controller and removed after the signal recovery.
30. E30:
Fault content: If the trap door is opened in the Russian mode, the elevator cannot start.
Inspection reset is need after the trap door is closed.
Cause of fault: Trap door switch is damaged or there is problem in wiring.
One forgets to reset after manual operation.
Remedies: Check the wiring and replace the switch.
Inspection reset
Fault display and recovery: The fault can be displayed by the landing indicator, and recorded by
the main controller. This fault can be only removed by setting the
elevator in an inspection operation.
31. E31:
Fault content: Signal adhesion of leveling switch. The leveling signal had no response after
running signal has been sent for 3s.
Cause of fault: The depth that the leveling plate inserts into the leveling switch is inadequate,
leading to false switch action.
Leveling switch is damaged.
Wiring fault with a short-circuit
Remedies: The leveling plate shall insert into the 2/3 of the switch at least. Please read
“Electric Installation Manual”
Replace the switch.
Check the circuit.
Fault display and recovery: The fault can be displayed by the landing indicator, recorded by the
main controller, and removed after the elevator is changed into an
inspection operation.
32. E32:
Fault content: Motor is overheating. The door keeps open.
Cause of fault: Motor overheating
Detection switch failure or circuit failure
Remedies: Contact the manufacturer if this happens.
Fault display and recovery: The fault will not be displayed by the landing indicator, recorded by
the main controller and removed after motor cooling.
33. E33:
Fault content: Electric weighing device has a fault in communication. The door keeps open.
Cause of fault: Communication wiring fault or communication interference
Weighing device is damaged.
Remedies: Check the wiring.
Replace the weighing device.
Fault display and recovery: The fault will not be displayed by the landing indicator, recorded by
the main controller, and removed after communication recovery.
16.2 The fault record of SIEI inverter is adequate. In the commissioning, the fault alarmed shall be
removed in time. The fault records are as follows: (Note: Refer to the corresponding instruction
when other kinds of inverters are used on site.)