Inspection and Test Plan: Installation of Fire Alarm System

The document outlines an inspection and test plan for the installation of a fire alarm system, including material delivery and storage, panel installation, device installation, device testing, and ancillary equipment installation. It specifies acceptance criteria and required documentation for each activity, as well as the roles and required attendance of different parties for inspections. Sign-off is required from the contractor and sub-contractor to verify inspections and that work meets specifications.

Uploaded by

Binu Sulochanan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (4 votes)
4K views

Inspection and Test Plan: Installation of Fire Alarm System

The document outlines an inspection and test plan for the installation of a fire alarm system, including material delivery and storage, panel installation, device installation, device testing, and ancillary equipment installation. It specifies acceptance criteria and required documentation for each activity, as well as the roles and required attendance of different parties for inspections. Sign-off is required from the contractor and sub-contractor to verify inspections and that work meets specifications.

Uploaded by

Binu Sulochanan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

INSPECTION AND TEST PLAN

Client: Project: Document no.: Revision:

Project Reference: Discipline: ELECTRICAL

Contractor:
Description: INSTALLATION OF FIRE ALARM SYSTEM Page 1 of 3
Specification & Reference Parties Inspection Role
S. No. Activity Acceptance Criteria Frequency Verifying Documents
Document

Approved Method Statement:


Material Delivery, Upon receipt of
01 Manufacturer’s Instruction a) Delivery Note H W W
Handling and Storage consignment
FFE/DPL/KFIP/E-MS-01

Approved Approved Material Submittals:


Fire Alarm Coordination drawing.
Approved Method Statement:
02 Panel Installation Approved Every installation a) Inspection Request H W W
Fire Alarm Shop drawing FFE/DPL/KFIP/E-MS-01

NFPA 72 As per Manufacturer’s Instruction

Approved Material Submittals:


Approved
Fire Alarm Coordination drawing. Approved Method Statement:
Cable & Devices
03 Approved FFE/DPL/KFIP/E-MS-01 Every installation a) Inspection Request H W W
Installation
Fire Alarm Shop drawing
As per Manufacturer’s Instruction
NFPA 72

Remarks:

Sub-Contractor’s Personnel: (Name, Sign & Date) Contractor’s Personnel: (Name, Sign & Date)

W - Witness point: Attendance at site is expected, H - Hold point: Attendance at site is mandatory and S- Surveillance: Random attendance & or visual R - Review: Documents to be reviewed, no signature
signature is required on check sheet or IR, but if The signature is required on the check sheet or IR at the time of inspection at site. required on the documents (R may be addition to
Engineer is not present to sign at the time, follow on the inspection in order to release for Following activity. any of the other action codes.)
work shall proceed and related documents (s) signed Work shall proceed & considered approved if employer’s
later. personnel do not show up for more than 30 minutes from
scheduled inspection time and the related document(s)
shall be signed later.
INSPECTION AND TEST PLAN
Client: Project: Document no.: Revision:

Project Reference: Discipline: ELECTRICAL

Contractor:
Description: INSTALLATION OF FIRE ALARM SYSTEM Page 2 of 3
Specification & Reference Parties Inspection Role
S. No. Activity Acceptance Criteria Frequency Verifying Documents
Document

Approved Approved Method Statement:


a) Inspection Request
Fire Alarm Coordination drawing.
After completion of
Fire alarm system Device Approved FFE/DPL/KFIP/E-MS-01
04 Fire Alarm system b) Device Test report H H H
test Fire Alarm Shop drawing
installation. (Carried out by Sub
As per approved specialist
Contractor)
NFPA 72 procedure(Sub Contractor)

Approved
Fire Alarm Coordination drawing.
Approved Material Submittals:
Approved
05 Ancillary Equipment Approved Method Statement: Every installation a) Inspection Request H W W
Fire Alarm Shop drawing
FFE/DPL/KFIP/E-MS-01
NFPA 72

Remarks:

Sub-Contractor’s Personnel: (Name, Sign & Date) Contractor’s Personnel: (Name, Sign & Date)

W - Witness point: Attendance at site is expected, H - Hold point: Attendance at site is mandatory and S- Surveillance: Random attendance & or visual R - Review: Documents to be reviewed, no signature
signature is required on check sheet or IR, but if The signature is required on the check sheet or IR at the time of inspection at site. required on the documents (R may be addition to
Engineer is not present to sign at the time, follow on the inspection in order to release for Following activity. any of the other action codes.)
work shall proceed and related documents (s) signed Work shall proceed & considered approved if employer’s
later. personnel do not show up for more than 30 minutes from
scheduled inspection time and the related document(s)
shall be signed later.
INSPECTION AND TEST PLAN
Client: Project: Document no.: Revision:

Project Reference: Discipline: ELECTRICAL

Contractor:
Description: INSTALLATION OF FIRE ALARM SYSTEM Page 3 of 3
Specification & Reference Parties Inspection Role
S. No. Activity Acceptance Criteria Frequency Verifying Documents
Document

Approved
Fire Alarm Coordination drawing. Approved Method Statement: a) Inspection Request
After completion of
Pre-checks and Visual
06 Approved FFE/DPL/KFIP/E-MS-01 As Fire Alarm system b) Pre-Checklist & Visual H H W
Inspection
Fire Alarm Shop drawing per approved specialist installation. Inspection form (Carried
NFPA 72 procedure(Sub Contractor) out by Subcontractor)

Approved Approved Method Statement:


Fire Alarm Coordination drawing. a) Inspection Request
FFE/DPL/KFIP/E-MS-01
During the integrity
07 Integrity Test Approved b) Pre-Checklist & Visual H H H
Test
Fire Alarm Shop drawing As per approved specialist Inspection form (Carried
procedure(Sub Contractor) out by Subcontractor)
NFPA 72

Remarks:

Sub-Contractor’s Personnel: (Name, Sign & Date) Contractor’s Personnel: (Name, Sign & Date)

W - Witness point: Attendance at site is expected, H - Hold point: Attendance at site is mandatory and S- Surveillance: Random attendance & or visual R - Review: Documents to be reviewed, no signature
signature is required on check sheet or IR, but if The signature is required on the check sheet or IR at the time of inspection at site. required on the documents (R may be addition to
Engineer is not present to sign at the time, follow on the inspection in order to release for Following activity. any of the other action codes.)
work shall proceed and related documents (s) signed Work shall proceed & considered approved if employer’s
later. personnel do not show up for more than 30 minutes from
scheduled inspection time and the related document(s)
shall be signed later.