MSC-3 Driver Instruction Manual
MSC-3 Driver Instruction Manual
Instruction Manual
MSC-3 User’s Manual
ZENER TECHNOLOGY AND QUALITY ASSURANCE
Since 1978 Zener Electric has supplied many thousands of AC drives to industry. These drives have
been installed into numerous applications resulting in a wealth of in house experience. The Zener MSC-3
AC variable speed controller is the culmination of this experience, modern technology and industrial
application requirements. The Zener Quality Assurance program ensures that every MSC-3
manufactured has proven to operate correctly in the production test bay before dispatch.
MSC-3 PRODUCT WARRANTY
Zener Electric warranty the MSC-3 against defective workmanship and materials for a period of 24
months from the date of dispatch. Such defects will be rectified free of charge for both labour and
material, at Zener Electric’s premises subject to:
1. Zener Electric's customer raising an order upon Zener for service and/or repairs, subject to a
warranty claim. The order is to state particulars of the model and serial number, the date of
original purchase and invoice/delivery docket number.
2. All damage resulting from incorrect installation or use other than in accordance with the
instruction manuals issued by Zener Electric is excluded from this warranty.
3. The Warranty being rendered invalid if the product is misused or if any unauthorised alteration,
modification or substitution of any part of the product be made or the serial number of the
product is defaced or altered.
4. The cost of transportation (both ways) is to be met by the owner if it's necessary to return the
product, or any part of it, to Zener Electric’s premises.
5. A charge being accepted by the owner for travelling time and expenses incurred in connection
with warranty service at the user's site as requested by the owner.
6. If the product was not purchased from Zener Electric directly, then a warranty claim must be
lodged with the original supplier in the first instance. Repairs will not be effected by Zener
Electric unless approved by the original supplier. Goods not of our own manufacture
incorporated in our supply or sold by us, carry their maker's warranty only.
7. Goods returned for claim under warranty will be accepted on the condition that should the claim
be rejected then all costs, including inspection, will be charged to the customer's account.
8. Zener Electric is not liable for any consequential loss.
SAFETY
Your MSC-3 must be applied, installed and operated in a safe manner. It is the responsibility of the user
to ensure compliance with all regulations and practices covering the installation and wiring of your MSC-
3. The instruction manual should be completely read and understood before attempting to connect or
operate the MSC-3. Only skilled personnel should install this equipment.
Contents
WARNING...........................................................................................................................................................3
RECEIVING.........................................................................................................................................................3
SOFTWARE ........................................................................................................................................................3
MSC-3 MECHANICAL INSTALLATION DIAGRAM ...............................................................................................4
3 PHASE MSC-3 ELECTRICAL INSTALLATION DIAGRAM. ................................................................................7
SINGLE PHASE MSC-3 ELECTRICAL INSTALLATION .......................................................................................8
INDUSTRIAL TERMINALS TYPICAL CONNECTION DIAGRAM – CONFIG 1 ......................................................9
HVAC TERMINALS TYPICAL CONNECTION DIAGRAM – CONFIG 3...............................................................10
QUICK SETUP FOR CONFIG 1.........................................................................................................................11
QUICK SETUP FOR CONFIG 3.........................................................................................................................13
QUICK SETUP FOR CONFIG 4.........................................................................................................................15
MSC-3 START UP .............................................................................................................................................17
MSC-3 RUN MODE ...........................................................................................................................................17
MSC-3 MENU MODE.........................................................................................................................................19
CONTROL CONSOLE MENU ............................................................................................................................19
A00 DISPLAY ....................................................................................................................................................19
A01 RUN VARIABLE...............................................................................................................................19
A02 RUN SCALE ....................................................................................................................................19
A03 RUN UNITS .....................................................................................................................................19
A04 MENU PROTECT ............................................................................................................................20
A05 SET CTL DEFS................................................................................................................................20
B00 MOTOR......................................................................................................................................................20
B01 MOTOR VOLTS...............................................................................................................................20
B02 MOTOR AMPS ................................................................................................................................20
B03 MOTOR HZ .....................................................................................................................................20
B04 MOTOR RPM ..................................................................................................................................20
C00 PERFORMANCE........................................................................................................................................21
C01 MIN HZ............................................................................................................................................21
C02 MAX HZ...........................................................................................................................................21
C03 RAMP ...................................................................................................................................21
C04 ACCEL TIME ........................................................................................................................22
C05 DECEL TIME ........................................................................................................................22
C06 S TIME .................................................................................................................................22
C07 FLUX PLUS %.................................................................................................................................22
C08 HI SPD FLUX+ ................................................................................................................................22
C09 SLIP COMP.....................................................................................................................................23
C11 AUDIBLE FREQ ..............................................................................................................................23
D00 PROTECTION............................................................................................................................................24
D01 CURRENT LIM ................................................................................................................................24
D02 I2T ...................................................................................................................................................24
2
D02 I T ........................................................................................................................................24
2
D03 I T ZERO HZ ........................................................................................................................24
D04 I2T CNR HZ...........................................................................................................................25
D05 REVERSE .......................................................................................................................................25
D08 DC INPUT .......................................................................................................................................25
E00 STOP/START .............................................................................................................................................25
E01 STOPPING ......................................................................................................................................25
E06 DYNAMIC BRK ................................................................................................................................25
E07 AUTO RESTART .............................................................................................................................26
E08 A/RS ALLOWED..............................................................................................................................26
E09 A/R CLR TIME .................................................................................................................................26
E10 RESET BY PF .................................................................................................................................26
F00 REFERENCES ...........................................................................................................................................27
F01 REMOTE .........................................................................................................................................27
F02 LOCAL.............................................................................................................................................27
F03 ESO.................................................................................................................................................27
F04 JOGFWD.........................................................................................................................................27
F05 JOGREV..........................................................................................................................................27
SPEED REFERENCES......................................................................................................................................28
R00 AN1.................................................................................................................................................28
MSC3 ANALOG INPUT SCALING .....................................................................................................................28
R01 REF AT 0% .....................................................................................................................................29
R02 REF AT 100%..................................................................................................................................29
R03 PRESET..........................................................................................................................................29
R04 MOTORIZD POT .............................................................................................................................29
R07 CONSOLE REF ...............................................................................................................................29
IM00092A Page 1
MSC-3 User’s Manual
G00 INPUT/OUTPUT ........................................................................................................................................ 30
STANDARD TERMINAL CONFIGURATIONS.................................................................................................... 30
G02 CONFIG 1 INDUSTRIAL ................................................................................................................. 30
G03 CONFIG 2 VSC2000....................................................................................................................... 31
G04 CONFIG 3 HVAC............................................................................................................................ 31
G05 CONFIG 4 ...................................................................................................................................... 31
G06 CONFIG 5 ...................................................................................................................................... 31
G07 CONFIG 6 ...................................................................................................................................... 32
G08 CONFIG 7 ...................................................................................................................................... 32
G09 CONFIG 8 ...................................................................................................................................... 32
G10 ENABLE/RESET............................................................................................................................. 32
G11 DIG IN1 .......................................................................................................................................... 33
G12 DIG IN2 .......................................................................................................................................... 33
G13 DIG IN3 .......................................................................................................................................... 33
G14 DIG IN4 .......................................................................................................................................... 33
CONTROL TERMINAL FUNCTIONS ........................................................................................... 34
G15 RELAY1.......................................................................................................................................... 36
G16 RELAY2.......................................................................................................................................... 36
RELAY OUTPUT FUNCTIONS .................................................................................................... 36
DISPLAY MESSAGES ...................................................................................................................................... 37
MSC-3 TROUBLE SHOOTING GUIDE.............................................................................................................. 38
YOUR MSC-3 SETUP NOTES .......................................................................................................................... 41
MSC-3 SPECIFICATIONS................................................................................................................................. 42
MSC-3 OUTPUT CURRENT SPECIFICATIONS ................................................................................................ 44
APPENDIX A - MSC-3 CHARACTER SET......................................................................................................... 45
Page 2 IM00092A
MSC-3 User’s Manual
Warning
Please note the following:
Your MSC-3 must be applied, installed and operated in a safe manner in accordance with all local rules
and regulations.
The MSC-3 is intended for use only in fixed wiring applications. It is not intended for use on a flexible
supply cable.
The MSC-3 contains a substantial EMC line filter and as a result it is unsuitable for use on earth leakage
protected circuits.
The MSC-3 contains capacitors that take greater than one minute to discharge below 50Vdc. The voltage
across these capacitors should be measured before any work is carried out inside the enclosure.
The MSC-3 contains high energy circuits that may be hazardous. Do not operate the MSC-3 with the
door or enclosure open.
Receiving
Inspect the MSC-3 for any shipping damage. If any damage is found, report it to the carrier immediately.
Access the inside of the controller and visually check for any damage.
Do not attempt to operate the MSC-3 if any obvious damage exists.
After the initial inspection, the MSC-3 can be repacked and stored in a clean, dry location until it is
required for use. DO NOT store this equipment in an area where the ambient temperature will fall below
-20°C (-4°F) or rise above 70°C (158°F). DO NOT store this equipment in areas of high condensation or
corrosive atmosphere. Proper storage is necessary to ensure satisfactory controller start up and
performance.
Software
This manual applies to MSC-3 software revision 1.38. The software revision is displayed briefly at power
up.
IM00092A Page 3
MSC-3 User’s Manual
E
Chassis A IP30 / NEMA1
F D A
B C
Page 4 IM00092A
MSC-3 User’s Manual
Chassis B
IM00092A Page 5
MSC-3 User’s Manual
Chassis C
Dimensions
mm inch
A 715 28.1
B 470 18.5
C 290 11.4
D 620 24.4
E 330 13.0
F 667 26.7
Dimensions for the IP 30
and IP66 chassis’ are
identical.
Drive Weights
Drive kg lbs
x55 42 92
x82 44 97
x109 46 101
x140 50 110
DC Bus Choke weighs
20kg (44lbs) on top of
above weights.
600V drives must have a
bus choke
Page 6 IM00092A
MSC-3 User’s Manual
IMPORTANT
MSC-3 1. Either fuses or a circuit breaker
Three Phase Input should be connected as shown. Fast
semiconductor fuses are not required.
2. UL compliant installations must use
UL listed fuses as per the table below.
3. Cable sizes should be selected
L1 L2 L3 E M1 M2 M3 according to local wiring rules using
the currents given in the table below.
4. For complete motor thermal
protection microtherms or thermistors
should be installed in the motor
winding.
5. For compliance with EMC standards,
the motor wiring and ground
conductor must be enclosed in a
continuous metallic sheath or conduit,
which has good contact to both the
motor and inverter chassis. The
3 Phase Supply sheath should contain only the wiring
L1 L2 L3
from one inverter and its associated
DC Supply motor cables. No other conductors
+ - may be included.
IM00092A Page 7
MSC-3 User’s Manual
0%
0% Speed 100%
Page 8 IM00092A
MSC-3 User’s Manual
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
O C No Power
O C Power On and
Stop/
Run Stopped
Reset
C O Power On and
Drive running
RL1 - Run
Local Remote 1k to 10k ohm
potentiometer No Power O C
Power On and O C
not tripped
Optional
Power On, C O
8 9 10 11 12 Drive Tripped
Optional Output Disable
RL2 - Trip
Single direction
2 wire control
+ -
1 2 3 4 5 6
Input reference source
For 4-20mA signals
SW1 0..5V the analog input
Stop/ “REF AT 0%”
SW1 0..10V
Reset should be set to
SW1 -25%. See Speed
0..20mA
4..20mA References section
Start
for details
Remote
Local
IM00092A Page 9
MSC-3 User’s Manual
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
O C No Power
O C Power On and
Tripped
Stop Run C O Power On, Drive
Enabled and not
tripped
RL1 - Proof
1k to 10k ohm
Essential potentiometer
Services Override No Power O C
Local Remote 8 9 10 11 12 Power On and O C
not operating in
ESO mode
Power On and, C O
Optional ESO operating
+ -
RL2 - ESO
Optional Output Disable
Optional Wiring
If selection between local
Essential Services and remote is not required,
Override place a link between Local / Remote
terminals 1 and 5. In “local” the MSC-3
If the output disable is not is controlled from the
Power up start up required place link between front panel console.
with ESO terminals 1 and 6. In “remote”, the
MSC-3 is controlled
from the terminal
strip.
Page 10 IM00092A
MSC-3 User’s Manual
Stop/
Reset
Stop/
3 Wire Reset Run 2 Wire
Start Control Control
OR OR
Local/Remote Selection
+5V D1 D2 D3 D4 EN
1 2 3 4 5 6
Local Remote
IM00092A Page 11
MSC-3 User’s Manual
STEP 3. Choose your speed reference and connect it as shown.
External External
Potentiometer Reference
SCN +5V IN+ IN- COM SCN +5V IN+ IN- COM
8 9 10 11 12 8 9 10 11 12
OR
+ -
SW1 0..5V
1k to 10k ohm
potentiometer SW1 0..10V
OR OR
To use either the Preset Speed or the Console Reference select REMOTE from the REFERENCES menu.
Use the arrows to display the options. Press Enter when the one you require is displayed.
Set SW1 as shown. If a 4 to 20mA reference is to be used, select REMOTE from the REFERENCES menu. AN1
should be displayed. Press Enter. Set the REF AT 0% to –25%. Press Enter.
STEP 4. Setup your motor parameters in the MOTOR menu using the motor nameplate information.
STEP 5. From the PERFORMANCE menu setup your MIN and MAX speeds and your RAMP times.
STEP 6. From the PROTECTION menu setup your current limit and I2t currents.
Page 12 IM00092A
MSC-3 User’s Manual
+5V D1 D2 D3 D4 EN +5V D1 D2 D3 D4 EN
1 2 3 4 5 6 1 2 3 4 5 6
OR
Stop
Stop Run
Start
ESO
ESO
OR OR
+5V D1 D2 D3 D4 EN
+5V D1 D2 D3 D4 EN
1 2 3 4 5 6
1 2 3 4 5 6
Hand
Off
Auto
ESO
ESO
IM00092A Page 13
MSC-3 User’s Manual
External External
Potentiometer Reference
SCN +5V IN+ IN- COM SCN +5V IN+ IN- COM
8 9 10 11 12 8 9 10 11 12
OR
+ -
OR OR
To use either the Preset Speed or the Console Reference select REMOTE from the REFERENCES menu. Use
the arrows to display the options. Press Enter when the one you require is displayed.
Set SW1 as shown. If a 4 to 20mA reference is to be used, select REMOTE from the REFERENCES menu.
AN1should be displayed. Press Enter. Set the REF AT 0% to
-25%. Press Enter.
STEP 4. From the INPUT/OUTPUT menu select Terminal CFG. Use the up and down arrows until
CONFIG 3 is displayed. Press ENTER. Now connect the wire to terminal 6.
STEP 5. Setup your motor parameters in the MOTOR menu using the motor nameplate information.
STEP 6. From the PERFORMANCE menu setup your MIN and MAX speeds and your RAMP times.
STEP 7. From the PROTECTION menu setup your current limit and I2t currents.
Page 14 IM00092A
MSC-3 User’s Manual
.
STEP 2. Choose your control method from one of the following. Connect your control wiring as shown. Do not
connect the wire into terminal 6 yet.
+5V D1 D2 D3 D4 EN
+5V D1 D2 D3 D4 EN
1 2 3 4 5 6
1 2 3 4 5 6 OR
OR
Local Remote
Reverse
External External
Potentiometer Reference
MSC-3 Control Board MSC-3 Control Board
SCN +5V IN+ IN- COM SCN +5V IN+ IN- COM
8 9 10 11 12 8 9 10 11 12
OR
+ -
OR
OR
To use either the Preset Speed or the Console Reference select REMOTE from the REFERENCES
menu. Use the arrows to display the options. Press Enter when the one you require is displayed.
IM00092A Page 15
MSC-3 User’s Manual
Set SW1 as shown. If a 4 to 20mA reference is to be used select REMOTE from the REFERENCES
menu. AN1should be displayed. Press Enter. Set the REF AT 0% to -25%. Press Enter.
STEP 4. From the INPUT/OUTPUT menu select Terminal CFG. Use the up and down arrows until
CONFIG 4 is displayed. Press ENTER. Connect the wire to terminal 6 now.
STEP 5. Setup your motor parameters in the MOTOR menu using the motor nameplate information.
STEP 6. From the PERFORMANCE menu setup your MIN and MAX speeds and your RAMP times.
STEP 7. From the PROTECTION menu setup your current limit and I2t currents.
STEP 8. From the PROTECTION menu enable the REVERSE direction.
Page 16 IM00092A
MSC-3 User’s Manual
MSC-3 Start up
Connect the input and motor wiring in accordance with the Electrical Installation Diagram. Select the
terminal configuration you require from the table on page 30. Connect the control wiring according to the
appropriate Control Wiring Diagram or follow a quick setup. The MSC-3 is now ready to run. Before
applying power ensure that rotation of the motor shaft will not cause injury or damage.
After applying power it is recommended that you at least go through the MOTOR, PERFORMANCE and
the INPUT/OUTPUT menus to set up the MSC-3 before running the motor to prevent any unexpected
motor operation. The MSC-3 is supplied with a link between the En terminal and the +5V terminal which
is all that is required to run the MSC-3 from the console. A connection between these two terminals must
always be made for the motor to run.
The five pushbuttons and display form a console through which drive features and settings are altered to
suit the application. When the MSC-3 is first powered up, the start banner is displayed for approximately
2 seconds. An example of the start banner is shown below. It displays the drive size, software version
and the temperature of the MSC-3 hardware. While the banner is displayed the internal fan is switched
on to verify its operation. If the fan is not required it will then be turned off.
R11
V1.38 23°C
25.0 Hz
50.0 FWD
The example shows that the desired output speed is 50 Hz and the motor is rotating at 25 Hz in the
forward direction as indicated by the status.
To start the drive, select a direction by pressing either of the run buttons: p FWD or qREV button. Use
the p FWD button to increase the speed reference and the q REV button to decrease it. The motor
should rotate up to the desired speed. If it does not, refer to the Trouble Shooting Guide at the end of this
manual.
If the motor shaft spins in the wrong direction remove the input power, wait for the MSC-3 to discharge
and swap any two motor phase wires. Re-apply input power and select a direction by pressing p FWD or
q REV.
IM00092A Page 17
MSC-3 User’s Manual
Operation and access to the Run Mode and Menu Mode is done with the console push buttons. The
action of each push button changes with the mode of operation and the state of the drive. The following
table describes how the console push buttons affect the drive control.
Page 18 IM00092A
MSC-3 User’s Manual
A00 DISPLAY
This menu allows selection of run variables and in the case of output frequency adjustment of its display
format and units. It also provides a restore factory defaults function.
A01 RUN VARIABLE
A single run variable is selected from this menu for display on the run screen.
• V01 Hz Output frequency
• V02 rpm Motor speed
• V03 % Load Relative motor load
• V04 Amps Drive output current
• V05 Volts DC DC link voltage
• V06 kW Drive output power
• V07 Volts AC Drive output voltage
• V08 °C Power circuit temperature (Celsius)
• V09 °F Power circuit temperature
(Fahrenheit)
• V10 I2t used Motor thermal overload level
IM00092A Page 19
MSC-3 User’s Manual
A04 Menu Protect
The feature protects the entire menu mode with a code so that settings and configurations are protected
from unauthorized changes. After you enable this feature, return to the Run Screen. The next time
anyone presses ESC to enter the Menu mode the following message will appear:
Use the up and down buttons to adjust the code value to the number 1470. Press Enter to accept. If
entered correctly, the familiar menu mode will be displayed. If the correct code is not entered you are
returned back to the run screen.
A05 SET CTL DEFS
This menu allows the factory default parameters to be reinstalled. The MSC-3 must be disabled before
you can restore the defaults. Pressing the Enter button will cause the message A06 CHECK WIRING
to be displayed. This is intended as a warning and an opportunity to confirm that terminal wiring is suited
to the default settings, otherwise unexpected drive operation may result.
Pressing the ENTER button again will cause the defaults to be loaded.
B00 MOTOR
This menu allows you to enter motor nameplate information. Press the Enter button to view and modify
Motor Volts, Motor Amps, Motor Hz and Motor rpm.
B01 MOTOR VOLTS
Default value: 230, 240, 415, 460 or 575 V (depends on model)
Range: 200..900 V
Use the up or down push buttons to adjust this setting to the motor nameplate voltage. Press Enter when
finished and the motor nameplate current is displayed or ESC to abort the adjustment
B02 MOTOR AMPS
Default value: drive nominal current
Range: 18 to 137% of drive overload current listed in the MSC-3 Output Current Specifications
table on page 44.
Use the up or down push buttons to adjust this setting to the motor nameplate current in amps. Press
Enter when finished and the motor frequency is displayed or ESC to abort the adjustment.
Entering the Nameplate Current of your motor determines the operation points for the Flux Plus and Slip
Comp features. This setting is not used to limit the output current of the MSC-3. Refer to D01 CURRENT
LIMIT for that particular feature.
B03 MOTOR Hz
Default value: 50 or 60 Hz
Range: 30..200 Hz
Use the up or down push buttons to adjust this setting to the motor nameplate frequency (Hz). Press
Enter when finished or ESC to abort the adjustment. This setting does not affect the minimum or the
maximum frequency output of the MSC-3. Refer to C01 MIN Hz and C02 MAX Hz for those features.
B04 MOTOR RPM
Default value: 1465 or 1765 rpm
Range: 500..60 times the Motor Hz entered previously, in rpm
Use the up or down push buttons to adjust this setting to the motor nameplate speed (rpm). 60 times the
Motor Hz is the two pole speed for an unloaded motor. Press Enter when finished or ESC to abort the
adjustment.
Page 20 IM00092A
MSC-3 User’s Manual
C00 PERFORMANCE
This section allows you to set the motor performance characteristics.
C01 MIN Hz
Default value: 0 Hz
Range: 0 to 195Hz
This sets the frequency that the MSC-3 will run when given a run signal. The value is entered in Hz.
There must be a difference of at least 5Hz between the MIN Hz and the MAX Hz setting. For example, if
MAX Hz is set to 45Hz, then the largest allowed value for MIN Hz is 40Hz. Use the up or down push
buttons to adjust the MIN Hz value, press Enter to accept the value or press ESC to abort the
adjustment. It is possible to use the full span of the analog input to adjust the speed reference through
the remaining reduced speed range. For example: Max Hz = 50Hz and Min Hz = 20Hz, the analog input
“R01 Ref at 0%” should be set to 40%. Zero at the analog input will produce a reference of 20Hz. Full
span at the input will produce a reference of 50Hz.
C02 MAX Hz
Default value: 50 or 60Hz (depends on model)
Range: 5Hz to 200Hz
This sets the frequency that the drive will run with the speed reference at maximum. There must be a
difference of at least 5Hz between the MIN Hz and the MAX Hz setting. This value is scaled by the Run
Scale value and so is always entered in user defined units. Use the up or down push buttons to adjust the
MAX Hz value, press Enter to accept the value or press ESC to abort the adjustment.
C03 Ramp
The MSC-3 has a programmable Ramp with adjustable acceleration, deceleration and S-curve rates.
Individual settings are provided for the linear and curved portions of the ramp.
Frequency
Acceleration Rate
Adjusting the linear
setting changes the
slope of this line
S- curve same
at both ends of
linear ramp
0 time
S time S time
Ramp time with S time set to 0.01
When the motor accelerates, the ACCEL TIME and S TIME settings are used. When the motor
decelerates, the DECEL TIME and S TIME settings are used. Press Enter to adjust these parameters.
NOTE: Alterations to any ramp parameter is not permitted while the drive is operating in ESO mode,
(see page 35 for more information on ESO)
IM00092A Page 21
MSC-3 User’s Manual
C06 S TIME
Default value: 0.01 sec
Range: 0.01 to 40.00 sec
The S TIME is the time taken for the motor to reach the limit of acceleration (as set by the rated speed
and the ACCEL TIME or DECEL TIME). Using the S TIME ensures smooth speed increases and
decreases. The longer the S TIME, the smoother the speed transition.
The S TIME will extend the ramp time as set by the ACCEL and DECEL TIME. The ramp time is now
roughly equal to the S TIME plus ACCEL TIME or DECEL TIME.
C07 Flux plus %
Default value: 25%
Range: 0 to 150% of adjustment range
The MSC-3 uses a sensorless flux vector control algorithm to control the motor operation. This control
algorithm provides independent control of motor flux throughout the speed range and is highly robust
against motor parameter changes. It uses the motor nameplate parameters entered in the B00 MOTOR
menu as the basis for its calculations to produce the correct flux in the motor. For a motor to produce full
torque it must have the correct flux applied to it. This is particularly critical at low speed. Flux Plus
adjusts the motor flux estimate to provide additional control where specific adjustments to the motor
torque response are required.
This feature enables an adjustment in the flux vector algorithm that can increase motor flux to produce
more torque for the same motor current. The amount of extra torque produced will vary from motor to
motor depending on motor size, efficiency and the operating speed.
Increase the value to produce more torque. This should be done in small steps to ensure the drive does
not go into Current Limit. If the drive does go into current limit decrease the Flux Plus value slightly.
This is the maximum torque that the motor can produce.
Use the up or down buttons for the adjustment. Press Enter when adjusted or ESC to abort adjustment.
C08 Hi Spd Flux+
Available Choices: H00 ENABLE
H01 DISABLE (default)
When this is disabled the flux plus decreases with increasing speed. This allows more efficient operation
of the MSC-3 on loads that have a high starting torque but do not require any extra torque during normal
operation. If your load requires high torque throughout the entire speed range Enable Hi Spd Flux+.
Press Enter to view the setting. Use the up or down push button to enable or disable Hi Spd Flux+. Press
Enter to accept the new setting or ESC to abandon.
Page 22 IM00092A
MSC-3 User’s Manual
C09 SLIP COMP
Default value: 0%
Range: 0 to 150% of slip speed
Motor slip is the difference between the shaft speed and the frequency applied to the motor (synchronous
speed) and is dependent on load. Slip Comp can provide compensation for this varying slip to produce
constant shaft speed under varying loads. The MSC-3 estimates the slip of the motor using the
parameters entered in the MOTOR parameters menu and the motor load. A value of 100% will make the
shaft speed equal the synchronous speed. Flux Plus may be used in conjunction with Slip Comp to
provide increase output torque at low speeds. Press Enter then use the up and down buttons to adjust
the amount of SLIP COMP. When adjusted, press Enter to accept the new setting or ESC to abort the
adjustment.
C11 AUDIBLE FREQ
Available Choices: C12 2kHz
C13 4kHz
C14 8kHz
C15 16kHz
C16 Auto select (default)
This value sets the maximum frequency that the drive uses in the creation of its PWM output voltage.
This frequency is noticeable as an audible sound that the motor makes. Usually higher settings produce
less audible noise but increase the switching losses which produces more heat in the drive. For most
efficient operation select 2 kHz. Press Enter then use the up or down buttons to choose the AUDIBLE
FREQ. Press Enter when finished to accept the choice or ESC to abort.
IM00092A Page 23
MSC-3 User’s Manual
D00 PROTECTION
This section lets you set the motor protection features.
D01 CURRENT LIM
Default value: drive overload current.
Range: 18 to100% of Drive Overload Current listed in MSC-3 Output Current Specifications
table on page 44, entered in amps.
This sets the maximum output current of the MSC-3. If excessive load is applied to the motor, the drive
will only apply this amount of current to the motor until the overload condition is removed. Current
limiting is achieved by reducing the speed of the motor. The Current Limit value cannot be set higher
than the maximum output current for the drive.
Press Enter then use the up or down buttons to adjust the CURRENT LIM. Press Enter when finished to
accept the adjustment or ESC to abort.
D02 I2t
The I2t feature estimates the heating of the motor according to the motor load. When the estimated
heating exceeds I2t setting, the drive will trip on I2t. For a motor running at 110% of its I2t current this will
take approximately two minutes. The time to trip will shorten the further the motor current exceeds the I2t
value.
If power is removed from the drive after an I2t trip, the motor should be allowed to cool down before the
inverter is restarted. Motors running highly loaded at low speeds should have external cooling and an
external motor thermal sensing device such as microtherms or thermistors for protection.
The I2t feature has the ability to set the trip threshold as a function of output frequency. This allows the I2t
to protect motors that have reduced cooling at low speeds because they are not externally cooled. The
diagram below is an example of the I2t trip threshold profile.
2 2
I t used D02 I t %
2
I t trip threshold
2
D03 I t zero Hz %
2
D04 I t cnr Hz
Hz
2
I t speed profile
2
D02 I t
Default value: drive nominal current
Range: 18% to 100% of drive Overload Current listed in MSC-3 Output Current Specifications
table on page 44, entered in amps.
This sets the upper limit of I2t and is entered in amps. This is equivalent to the usual I2t setting. Use the
up and down push buttons to adjust the D02 I2t value and press Enter to accept the value or ESC to
abandon changes.
D03 I2t zero Hz
Default value: drive nominal current
Range: 18% to 100% of drive Overload Current listed in MSC-3 Output Current Specifications
table on page 44, entered in amps.
Page 24 IM00092A
MSC-3 User’s Manual
This sets the trip threshold when the speed is zero (e.g. DC HOLD). This value cannot be set higher than
the D02 I2t value set above. Use the up and down push buttons to adjust the D03 I2t zero Hz value and
press Enter to accept the value or ESC to abandon changes.
D05 Reverse
Available Choices: H00 ENABLE
H01 DISABLE (default)
The MSC-3 is shipped with its reverse direction disabled to prevent damage to mechanical devices or
hazardous equipment operation caused by the motor running backwards. Press Enter to view the setting.
Use the up or down push button to enable or disable Reverse. Press Enter to accept the new setting or
ESC to abandon.
D08 DC INPUT
Available Choices: H00 ENABLE
H01 DISABLE (default)
This feature allows the MSC-3 to operate from a DC Input Supply. The DC Supply voltage should be at
least 1.414 times higher than the motor voltage. Press Enter to view the setting. Use the up or down
push button to enable or disable DC Input. Press Enter to accept the new setting or ESC to abandon.
E00 STOP/START
This section sets the motor stopping and starting modes.
E01 STOPPING
Available Choices: E02 RAMP TO STOP (default)
E03 COAST
This controls the operation of the MSC-3 when any stop signal is given.
RAMP TO STOP means that the MSC-3 will continue to control the motor in order to bring it to a stop in
the time set by the DECEL TIME and S TIME.
COAST means that the MSC-3 will stop controlling the motor and allow it to coast to a stop, just as if the
power supply had been disconnected.
E06 DYNAMIC BRK
Available Choices: H00 ENABLE
H01 DISABLE (default)
Dynamic Braking provides the means for dissipating the motor regenerative energy into an external
resistor. This may be required when the MSC-3 experiences regenerative currents from an overhauling
load or a high inertia load that is required to decelerate rapidly. Dynamic Braking requires the dynamic
braking option to be connected to the MSC-3. Please see the dynamic braking instruction manual for
resistor sizing and dynamic braking application information.
Use the up or down buttons to select either Enable or Disable. Press Enter to accept the selection or
ESC to abort.
IM00092A Page 25
MSC-3 User’s Manual
E07 AUTO RESTART
Auto Restart allows the MSC-3 to automatically attempt to restart after a trip occurs. If the MSC-3 trips it
will wait 10 seconds then attempt to clear the fault. If it is unsuccessful it will keep trying every ten
seconds. It will do this the number of times specified in A/Rs ALLOWED. If the fault is cleared and the
drive runs without tripping for the A/R CLR TIME the number of auto restarts attempted will start counting
from 1 again. If the trip is cleared by any other means the fault count will start from 1 again.
Note: Alteration to any of the Auto Restart parameters is not permitted while the MSC-3 is operating in
ESO mode.
E08 A/Rs ALLOWED
Default value: 0
Range: 0 to 15 restarts
This number indicates how many times the MSC-3 will attempt to restart after a trip. For the motor to run
after the trip is cleared, the drive must be given a valid run command. Select 0 restarts in order to de-
activate Auto Restart.
Use the up or down buttons to adjust A/Rs ALLOWED. Press Enter to accept the adjustment or ESC to
abort.
E09 A/R CLR TIME
Default value: 20 min
Range: 0.1 to 20 min
If the MSC-3 operates for the A/R CLR TIME without any trips occurring the number of restarts is reset to
the value of A/Rs ALLOWED. Set the A/R CLR TIME to 0.1min for infinite auto restarts.
Use the up or down buttons to adjust A/R CLR TIME. Press Enter to accept the adjustment or ESC to
abort.
E10 Reset by PF
Available Choices: H00 ENABLE
H01 DISABLE (default)
Enabling this facility allows the MSC-3 to reset all trips when a momentary power failure occurs. This
feature is useful in power-up start applications because trips may be cleared without any extra switch
logic by turning the power off and straight back on again without waiting for the drive to completely power
down.
Use the up or down buttons to select either Enable or Disable. Press Enter to accept the selection or
ESC to abort.
Page 26 IM00092A
MSC-3 User’s Manual
F00 REFERENCES
This lets you set the speed references for all the MSC-3 operating modes. Various options may allow the
connection of a different speed source from those listed for the standard MSC-3. When these options are
fitted the extra input options will appear where the word “Options” appears in the lists below. More preset
speeds or a second analog input are examples of this.
For more information on the different drive operating modes see the Control Terminal Functions on Page
34
F01 REMOTE
Default value: Analog Input 1
Other Choices: Preset
Motorized Pot
Console Ref
Options
When the drive is operating in remote mode it will take its speed reference from this source. Use the up and down
push buttons to select a reference and press Enter to accept the selection or ESC to abandon.
F02 LOCAL
Default value: Console Ref
Other Choices: Analog Input 1
Preset
Motorized Pot
Options
When the drive is operating in local mode it will take its speed reference from this source. Use the up
and down push buttons to select a reference and press Enter to accept the selection or ESC to abandon.
F03 ESO
Default value: Preset
Other Choices: Analog Input 1
Motorized Pot
Console Ref
Options
When the drive is operating in ESO mode it will take its speed reference from this source. Use the up
and down push buttons to select a reference and press Enter to accept the selection or ESC to abandon.
If Reverse operation is required in ESO enter the desired speed as a negative value.
F04 JOGFWD
Default value: Preset
Other Choices: Analog Input 1
Motorized Pot
Console Ref
Options
When the drive is running in JOGFWD it will take its speed reference from this source. Use the up and
down push buttons to select a reference and press Enter to accept the selection or ESC to abandon.
F05 JOGREV
Default value: Preset
Other Choices: Analog Input 1
Motorized Pot
Console Ref
Options
IM00092A Page 27
MSC-3 User’s Manual
When the drive is running in JOGREV it will take its speed reference from this source. Use the up and
down push buttons to select a reference and press Enter to accept the selection or ESC to abandon.
Speed References
R00 AN1
When the Analog Input is selected as a speed reference for any of the different operating modes, two
parameters need to be checked. The MSC-3 will let you do this every time the analog input is selected
as a reference. They are R01 REF AT 0% and R02 REF AT 100%. Use the up or down buttons to
change the values (if required). Press enter to accept the value or ESC to abort.
highspeed − lowspeed
max speed
m=
highinput − lowinput
highspeed
REFAT 0% = ( − m * highinput ) *100
max speed
REFAT100% = 100 * m * inputrange + REFAT 0%
Examples:
Standard 4-20mA Bipolar Input
At 4mA input we want 0Hz and at 20mA At 1V input we want 40Hz in reverse and
input we want 50Hz, maximum speed at 4V input we want 30Hz in forward,
50Hz using the 0-20mA input range. maximum speed 40Hz using the 0-5V
input range.
50 − 0 30 + 40
m = 50 = 0.0625 m = 40 = 0.583
20 − 4 4 −1
50 30
REFAT 0% = ( − 0.0625 * 20) * 100 = −25 REFAT 0% = ( − 0.583 * 4) * 100 = −158
50 40
REFAT100% = 100 * 0.0625 * 20 − 25 = 100 REFAT100% = 100 * 0.583 * 5 − 158 = 133
Page 28 IM00092A
MSC-3 User’s Manual
R01 REF AT 0%
Default value: 0%
Range: - 1000% to 1000%
This value specifies what the reference will be when 0% of the input signal is present at the analog input
terminals. For a 4 to 20mA input signal, R01 REF AT 0% must be set to –25%.
R02 REF AT 100%
Default value: 100%
Range: -1000 to 1000% of input span
This value specifies what the reference will be when 100% of the input signal present at the analog input
terminals.
R03 PRESET
Default value: 60%
Range: -100% to 100% of CO2 MAX Hz
If PRESET is chosen as the speed source you must enter the preset speed value. Use the up or down
buttons to adjust the preset speed. The preset speed is entered in % of CO2 MAX Hz. Press Enter to
accept the speed value or press ESC to abort.
IM00092A Page 29
MSC-3 User’s Manual
G00 INPUT/OUTPUT
There are two ways to assign terminal strip functions in the MSC-3.
The user can choose a standard terminal configuration from the standard list.
The user can create a custom terminal configuration.
The simplest way to set a terminal configuration is to choose from one of the standard terminal
configurations tabulated below. From the console menu press enter. Use the up arrow and down arrow
buttons to move through the list of standard terminal configurations CONFIG 1 - CONFIG 8. When you
have chosen a configuration press the enter button. Selecting one of these loads the terminals with the
listed functions. The MSC-3 does not remember which configuration was selected but remembers
the individual terminal functions. It does this so that you can then modify any of the terminals to suit
your specific application. This also means that every time you go to the G01 Terminal CFG menu, the
first option displayed is G02 CONFIG 1. To see the terminal configuration you must look at each terminal
individually.
Note: The MSC-3 must be disabled to select another terminal configuration.
Remember if you make a mistake press the escape button twice. This will take you out of the menu
mode and move you into the run mode.
Page 30 IM00092A
MSC-3 User’s Manual
G03 CONFIG 2 VSC2000
D1 D2 D3 D4 EN RL1 RL2
Terminal.
2 3 4 5 6 13,14,15 16,17,18
FWD & REV &
Function RESET ~STOP ENABLE RUN TRIP
LATCH LATCH
1. The MSC-3 only runs in remote. The remote reference can be set to any available option.
2. AN1 is the default speed reference.
3. To run the drive in reverse the Reverse Direction must be enabled.
G04 CONFIG 3 HVAC
D1 D2 D3 D4 EN RL1 RL2
Terminal.
2 3 4 5 6 13,14,15 16,17,18
FWD & ENABLE
Function ~STOP ESO REMOTE PROOF ESO
LATCH / RESET
IM00092A Page 31
MSC-3 User’s Manual
G07 CONFIG 6
D1 D2 D3 D4 EN RL1 RL2
Terminal.
2 3 4 5 6 13,14,15 16,17,18
ENABLE
Function FWD REV JOGFWD JOGREV RUN TRIP
/ RESET
1. Sets the REMOTE speed reference to the Motorized Potentiometer. The UP and DOWN buttons on
the console operate in parallel to the Up and Down terminals. They will change the value of the
motorized pot but will not start the motor.
2. Sets the LOCAL speed reference to the CONSOLE REF. The console then behaves as normal.
3. To change either of the above references, go to A35 DIG IN 4 in the menu and select an alternate
after you have selected this terminal configuration.
4. FWD input is non latching.
G10 Enable/Reset
Available Choices: H00 ENABLE
H01 DISABLE (Default)
This sets the operation of the Enable terminal between being purely an enable terminal and also being
able to reset a trip condition. When set to ENABLED, applying a positive edge to the ENABLE input will
attempt to reset a trip condition. When this feature is set to DISABLED the ENABLE input cannot reset
the MSC-3 after a trip.
Use the up and down push buttons to select ENABLED or DISABLED. Press Enter to accept the setting
or Esc to abort.
Page 32 IM00092A
MSC-3 User’s Manual
IM00092A Page 33
MSC-3 User’s Manual
Control Terminal Functions
Function Description Parameters
I00 A momentary contact closure on this input will start the motor
FWD&LATCH in the forward direction.
When the input is removed the motor continues to run in the None
forward direction (latching). It requires an I02 STOP function
to be assigned in order to break the latch and stop the motor.
I01 REV& A momentary contact closure on this input will start the motor
LATCH in the reverse direction.
When the input is removed the motor continues to run in the
reverse direction (latching). It requires I02 STOP function to None
be assigned in order to break the latch and stop the motor.
The reverse direction must be enabled for the motor to run
backwards.
I02 ~STOP This input is required to be held for the motor to run. If it is
opened any latched input is cleared and the motor will stop
running. None
This is used with FWD&LATCH and REV&LATCH to stop the
motor.
I03 FWD While this input is held the motor will run in the forward
direction. When the input is removed the motor will stop
running (non latching).
The I03FWD function disregards the state of the I02 ~ STOP
input and the drive will not stop while I03 FWD input is None
present and the Enable input is wired to +5V.
Both I03 FWD & I04 REV inputs must be wired to +5 to
activate bipolar operation.
I04 REV While this input is held the motor will run in the reverse
direction. When the input is removed the motor will stop
running (non latching).
The I04 REV function disregards the state of the I02 ~ STOP
input and the drive will not stop while I04 REV input is None
present and the Enable input is wired to +5V.
Both I03 FWD & I04 REV inputs must be wired to +5 to
activate bipolar operation.
IO5 UP Increases the motorised pot reference. None
I06 DOWN Decreases the motorised pot reference.
For the UP and Down terminals to have an effect the
None
motorised pot must be selected as a speed source. They
also require other terminals to stop and start the motor.
I07 RESET Will attempt to reset a trip condition. None
Page 34 IM00092A
MSC-3 User’s Manual
IM00092A Page 35
MSC-3 User’s Manual
G15 RELAY1
G16 RELAY2
These two menu items permit an individual function assignment to each relay output. Pressing enter on
these menu items presents a list of output functions with the currently assigned function being presented
first.
Some relay functions require a value to be set. When these functions are selected the chance to set the
value will follow with the current value displayed first.
Use the up and down push buttons to move through the list, press Enter to select the new function or Esc
to abort.
Relay Output Functions
Function Indication when energised Parameters
O00 RUN Indicates that the drive is running in either forward or reverse. none
O01 TRIP Indicates the presence of a trip that has stopped the output of
the drive none
O02 ESO Indicates that the MSC-3 is in the essential services mode. none
O03 PROOF Indicates that the MSC-3 is enabled and not tripped. none
O04 ZERO SPEED Indicates that the MSC-3 is at zero speed. none
O05 AT SPEED Indicates that the motor speed is equal to the reference speed. none
O06 UNDER Indicates that the motor speed is below the entered value. % of CO2
SPEED % MAX Hz
O07 OVER SPEED Indicates that the motor speed is above the entered value. % of CO2
% MAX Hz
O08 ON The relay is energized. none
O09 OFF The relay is de-energised. none
O10 A/R FAIL Indicates that the drive could not auto restart as all restarts have
been exhausted. none
O11 FWD Indicates that the motor is running in the forward direction. none
O12 REV Indicates that the motor is running in the reverse direction. none
O13 ENABLED Indicates that the MSC-3 is enabled. none
2
O14 I2t TRIP Indicates that the I t motor overload feature has activated. none
O15 OVER TEMP Indicates that the MSC-3 is too hot for safe operation. none
Page 36 IM00092A
MSC-3 User’s Manual
Display Messages
The MSC-3 displays a variety of messages on the second line of its display to indicate the drive status.
These messages may be divided into two types, trip messages and run messages.
The MSC-3 will protect itself under a variety of fault conditions. When one of these conditions is
experienced the MSC-3 will trip, shut down the motor output and display one of the following messages.
The message will be displayed until the fault is cleared and a reset signal is applied.
The following messages indicate the current operating condition of the MSC-3.
IM00092A Page 37
MSC-3 User’s Manual
Page 38 IM00092A
MSC-3 User’s Manual
IM00092A Page 39
MSC-3 User’s Manual
Page 40 IM00092A
MSC-3 User’s Manual
IM00092A Page 41
MSC-3 User’s Manual
MSC-3 Specifications
Input Supply Voltage 4 to 20mA range
Common mode range
MSC-3R 380 to 480Vac, 3Ø ± 25Vdc to AN COM
MSC-3J 440 to 600Vac, 3Ø Relay Outputs
MSC-3L 208 to 240Vac, 3Ø 2 Form C Outputs (Single pole change over
All these voltages have a tolerance of –15% to +10% contacts)
Contact Rating (Resistive load)
Input Frequency
5A@250Vac
48 to 62Hz 5A@30Vdc
Contact Rating (Inductive load)
Output Voltage 2A@ 250Vac
MSC-3R 0 to 480Vac, 3Ø 2A@30Vdc
MSC-3J 0 to 600Vac, 3Ø User Parameters
MSC-3L 0 to 240Vac, 3Ø
The output voltage cannot be higher than the input Motor Voltage 200 to 900V
voltage The output voltage cannot exceed the input voltage
Motor Current
Output Frequency 20 to 150% of max. continuous current
Motor Frequency 30 to 200Hz
Range: 0 to 200Hz
Resolution: 0.1% Motor Speed
Linearity: 0.2% of maximum frequency 500 to 60 x Motor Frequency in rpm
Minimum Frequency 0 TO 195HZ
Enclosure Rating Maximum Frequency 5 to 200Hz
Acceleration time 0.5 TO 600S
IP30 (NEMA 1) 0.5 TO 600S
Deceleration time
IP66 (NEMA 4)
S time 0.01 to 40s
Environmental Rating Flux Plus 0 to 150%
Slip Comp
Storage Temperature:
0 to 150% of slip speed
-20 to +70º C -4 to 158º F
Operating Temperature: DC Hold
0 to 40º C 32 to 104º F 0 to 50% of drive rated current
0 to 50º C † 32 to 122º C † Audible 2 to 16kHz
Dependent on load current Frequency
Relative Humidity: 5 to 95% Current Limit
Non condensing 20 to 110% of max cont current
Altitude: 0 to 1000m I 2t 20 to 110% of max cont current
0 to 3281 feet I2t Zero Hz
20 to 100% of max cont
Standards Compliance current
Models marked with this symbol 2
I t cnr Hz 2 to 200Hz
comply with the Australian EMC
Framework requirements Drive Stopping
Ramp to stop
Coast to stop
UL 508C Dynamic Braking
Auto Restart
Local Controls
Number of restarts
Up, Down, Enter, Escape, Stop/Reset 0 to 20
Reset time:
Terminal Strip 0.1 to 20 minutes
Digital Inputs References
+5V and DIG COM Analog Input
5Vdc supply, Console Reference
40mA max current Preset
D1 to D4 and EN Digital Inputs Motorized Potentiometer
Logic High 3 to 5Vdc The following functions can be enabled or disabled:
Logic Low 0 to 2Vdc
Analog Input Menu Protect
Vref and AN COM Reverse Direction
+5Vdc Supply High Speed Flux Plus
5mA max current DC Input
IN+ and IN-
Differential Input Dynamic Braking
0 to 5V range Reset by Power Failure
0 to 10V range Power Failure Ride Through
0 to 20mA range
Page 42 IM00092A
MSC-3 User’s Manual
Model Max. Supply Max. Fuse Fuse Max. Wire Size Max. Tightening
Short Circuit Size Class Torque
Rating
(Amps rms
Symmetrical)
240V
MSC-3L3 18,000A , 240V 20 J 10 A.W.G (6mm2) 15.6 in.lb (1.76 Nm)
MSC-3L5 18,000A , 240V 20 J 10 A.W.G (6mm2) 15.6 in.lb (1.76 Nm)
MSC-3L7 18,000A , 240V 20 J 10 A.W.G (6mm2) 15.6 in.lb (1.76 Nm)
MSC-3L11 18,000A , 240V 20 J 10 A.W.G (6mm2) 15.6 in.lb (1.76 Nm)
MSC-3L15 18,000A , 240V 60 T 6 A.W.G (16mm2) 16 in.lb (1.8 Nm)
MSC-3L20 18,000A , 240V 60 T 6 A.W.G (16mm2) 16 in.lb (1.8 Nm)
MSC-3L23 18,000A , 240V 60 T 6 A.W.G (16mm2) 16 in.lb (1.8 Nm)
MSC-3L30 18,000A , 240V 60 T 6 A.W.G (16mm2) 16 in.lb (1.8 Nm)
MSC-3L40 18,000A , 240V 60 T 6 A.W.G (16mm2) 16 in.lb (1.8 Nm)
MSC-3L55 † 18,000A , 240V 200 T 2/0 A.W.G. (70mm2) 120 in.lb (13.6Nm)
MSC-3L82 † 18,000A , 240V 200 T 2/0 A.W.G. (70mm2) 120 in.lb (13.6Nm)
MSC-3L109 † 18,000A , 240V 200 T 2/0 A.W.G. (70mm2) 120 in.lb (13.6Nm)
MSC-3L140 † 18,000A , 240V 200 T 2/0 A.W.G. (70mm2) 120 in.lb (13.6Nm)
480V
MSC-3R3 18,000A , 480V 20 J 10 A.W.G (6mm2) 15.6 in.lb (1.76 Nm)
MSC-3R5 18,000A , 480V 20 J 10 A.W.G (6mm2) 15.6 in.lb (1.76 Nm)
MSC-3R7 18,000A , 480V 20 J 10 A.W.G (6mm2) 15.6 in.lb (1.76 Nm)
MSC-3R11 18,000A , 480V 20 J 10 A.W.G (6mm2) 15.6 in.lb (1.76 Nm)
MSC-3R15 18,000A , 480V 60 T 6 A.W.G (16mm2) 16 in.lb (1.8 Nm)
MSC-3R20 18,000A , 480V 60 T 6 A.W.G (16mm2) 16 in.lb (1.8 Nm)
MSC-3R23 18,000A , 480V 60 T 6 A.W.G (16mm2) 16 in.lb (1.8 Nm)
MSC-3R30 18,000A , 480V 60 T 6 A.W.G (16mm2) 16 in.lb (1.8 Nm)
MSC-3R40 18,000A , 480V 60 T 6 A.W.G (16mm2) 16 in.lb (1.8 Nm)
MSC-3R55 † 18,000A , 480V 200 T 2/0 A.W.G. (70mm2) 120 in.lb (13.6Nm)
MSC-3R82 † 18,000A , 480V 200 T 2/0 A.W.G. (70mm2) 120 in.lb (13.6Nm)
MSC-3R109 † 18,000A , 480V 200 T 2/0 A.W.G. (70mm2) 120 in.lb (13.6Nm)
MSC-3R140 † 18,000A , 480V 200 T 2/0 A.W.G. (70mm2) 120 in.lb (13.6Nm)
600V
MSC-3J3 18,000A , 600V 20 J 10 A.W.G (6mm2) 15.6 in.lb (1.76 Nm)
MSC-3J5 18,000A , 600V 20 J 10 A.W.G (6mm2) 15.6 in.lb (1.76 Nm)
MSC-3J7 18,000A , 600V 20 J 10 A.W.G (6mm2) 15.6 in.lb (1.76 Nm)
MSC-3J11 18,000A , 600V 20 J 10 A.W.G (6mm2) 15.6 in.lb (1.76 Nm)
2
MSC-3J15 18,000A , 600V 60 T 6 A.W.G (16mm ) 16 in.lb (1.8 Nm)
MSC-3J20 18,000A , 600V 60 T 6 A.W.G (16mm2) 16 in.lb (1.8 Nm)
MSC-3J23 18,000A , 600V 60 T 6 A.W.G (16mm 2) 16 in.lb (1.8 Nm)
MSC-3J30 18,000A , 600V 60 T 6 A.W.G (16mm2) 16 in.lb (1.8 Nm)
2
MSC-3J40 18,000A , 600V 60 T 6 A.W.G (16mm ) 16 in.lb (1.8 Nm)
MSC-3J55 † 18,000A , 600V 200 T 2/0 A.W.G. (70mm2) 120 in.lb (13.6Nm)
MSC-3J82 † 18,000A , 600V 200 T 2/0 A.W.G. (70mm2) 120 in.lb (13.6Nm)
MSC-3J109 † 18,000A , 600V 200 T 2/0 A.W.G. (70mm2) 120 in.lb (13.6Nm)
MSC-3J140 † 18,000A , 600V 200 T 2/0 A.W.G. (70mm2) 120 in.lb (13.6Nm)
• Inverse-time circuit breakers can be used provided that the let-through energy (I2t) and peak let
through current (Ip) is less than that of the maximum fuse rating specified.
• Use Copper Conductors Only.
MSC-3 Specifications
DC Supply Voltage Output Voltage
MSC-3R 400 to 680Vdc † MSC-3R 0 to 480Vac, 3Ø
MSC-3J 550 to 850Vdc † MSC-3J 0 to 600Vac, 3Ø
MSC-3L 200 to 340Vdc † MSC-3L 0 to 240Vac, 3Ø
All these voltages have a tolerance of The output voltage cannot be higher than the input
-15% to +10% voltage divided by 1.414
† Rating not included in UL listing.
IM00092A Page 43
MSC-3 Users Manual
These currents apply to all ranges MSC-3 independent of the input voltage.
• 60 Second Rating
Page 44 IM00092A
MSC-3 User’s Manual
IM00092A Page 45
Australian ZENER ELECTRIC PTY LIMITED
Manufacturers
ACN 001 595 428
DELIVERY ADDRESS POSTAL ADDRESS
366 Horsley Road P.O. Box 4462 Tel: +61-2 - 9795 3600
MILPERRA MILPERRA DC Fax: +61-2 - 9795 3611
NSW 2214 NSW 1891 Email: [email protected]
AUSTRALIA AUSTRALIA
http://www.zener.net
© Zener Electric Pty Limited 2001
IM00092A
23 November 2001