Wind Design For Rooftop Solar Panels Based On ASCE 7-16 Input Data & Design Summary
Wind Design For Rooftop Solar Panels Based On ASCE 7-16 Input Data & Design Summary
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Wind Design for Rooftop Solar Panels Based on ASCE 7-16
Array location
To North dN = 50 ft, (15.24 m)
To South dS = 10 ft, (3.05 m)
To West dW = 80 ft, (24.38 m)
To East dE = 30 ft, (9.14 m) Solar Panel Net (toward & away) LRFD Pressure
North-West corner 1 = 34.4 psf, ( 1648 N/m2)
Effective wind area for structural element being designed North-East corner 2 = 47.4 psf, ( 2268 N/m2)
A = 3.13 ft2 ( 0.29 m2) South-West corner 3 = 47.4 psf, ( 2268 N/m2)
South-East corner 4 = 56.0 psf, ( 2680 N/m2)
ANALYSIS
Velocity pressure
qh = 0.00256 Kh Kzt Kd Ke V2 = 18.43 psf
where: qh = velocity pressure at mean roof height, h. (Eq. 26.10-1 page 268)
Kh = velocity pressure exposure coefficient evaluated at height, h, (Tab. 26.10-1, pg 268) = 0.70
Kd = wind directionality factor. (Tab. 26.6-1, for building, page 266) = 0.85
h = mean roof height = 20.00 ft
Ke = ground elevation factor. (1.0 per Sec. 26.9, page 268)