Flow Switch
Flow Switch
GR
Materials Rg 5 nickelled, 1.4310, CW614N nickelled,
medium-contact NBR, hard ferrite
Non-medium- PA, PVC
contact materials
Weight see table "Dimensions and weights"
Installation Standard: horizontal inwards flow; switching
location head not recommended underneath; other
installation positions are possible; the
installation position affects the switching
point and range.
Ranges
Details in the table correspond to horizontal inwards flow with
decreasing flow rate.
brown blue
optionally, normally closed
no. 0.214
(not all adjustment
ranges are
possible, brown blue
please enquire)
Switching voltage max. 230 V AC
Switching current max. 1 A
Switching max. 50 VA
capacity
Protection class 1 - PE connection
Ingress protection IP 65
Electrical cable 1.8 m
connection
pi-ho_fkv-ff-gr_e V1.02-04 1
Handling and operation Ordering code
● Include straight calming section of 5 x DN in inlet and outlet 1. 2. 3. 4. 5.
● If the media are dirty, install a filter FF - G R
(use magnetic filter for ferritic components).
● It must be ensured that the values given for voltage, current, =Option
and power are not exceeded.
● When switched on, a load must be connected in series. 1. Nominal width
The electrical details apply to ohmic loads. 008 DN 8 - G 1/4
Capacitive, inductive and lamp loads must be operated using a 010 DN 10 - G 3/8
protective circuit. 015 DN 15 - G 1/2
020 DN 20 - G 3/4
025 DN 25 - G 1
032 DN 32 - G 11/4
040 DN 40 - G 11/2
050 DN 50 - G 2
2. Process connection
G female thread
3. Connection material
R red bronze
4. Switching point H2O can be set as
desired between
009 0.4 - 9 l/min
010 0.4 - 10 l/min
012 0.4 - 12 l/min
025 0.6 - 25 l/min
040 1.5 - 40 l/min
060 2.0 - 60 l/min
090 3.0 - 90 l/min
150 5.0 - 150 l/min
5. Wiring
S 'normally open', no. 0.212
'normally closed', no. 0.214
O
(please enquire about range)
Options
● Adjustment for oil or gas
● Special values
Ordering information
● Specify direction of flow, medium, and switching point.
● For oils, state viscosity, temperature and designation
(e.g. ISO VG 68) (enquire about range).
● For gases, state pressure (relative or absolute), temperature
and medium (e.g. air) (enquire about range).
2 pi-ho_fkv-ff-gr_e V1.02-04