Multi Storey Timber Frame Building
Multi Storey Timber Frame Building
‘MULTI-STOREY
TIMBER-FRAME
BUILDING’
modelling the racking stiffness of timber-frame
shear-walls
Version 23-04-2012
Tunis Hoekstra
[email protected]
+31(0)638819574
‘Multi-storey timber frame building’ – literature review 23-04-2012
Introduction
This report presents a literature review concerning stiffness- and force-distribution issues and modelling aspects
of timber-frame buildings. This review is a part of the MSc thesis ‘Multi-storey timber-frame building’. The aim of
the project is explained first. Secondly, the aspects governing the shear-wall behaviour are discussed. Thereafter
experimental test-data is presented, which will be used in the next phases of the master’s thesis. The report on
the results of the literature review will be finished with a chapter concerning modelling and analysis of the
timber-frame structure. A reference list of the consulted sources is included in the last part of the report.
Table of contents
Introduction .................................................................................................................................................................. 2
Table of contents .......................................................................................................................................................... 2
1 Aim of the literature review .................................................................................................................................... 3
1.1 Problem definition ........................................................................................................................................3
1.2 Position of the literature review within in the project .................................................................................3
1.3 Intended thesis results ..................................................................................................................................3
2 Effects on structural behaviour as found in literature ............................................................................................ 6
2.1 Shear-wall level .............................................................................................................................................6
2.2 Fastener and hold-down level.....................................................................................................................23
3 Experimental results .............................................................................................................................................. 27
3.1 Full-scale shear-wall tests ...........................................................................................................................27
3.2 Full-scale shear-wall tests with opening .....................................................................................................32
3.3 Sheeting-to-timber fastener tests ...............................................................................................................34
3.4 Hold-down anchorage tests ........................................................................................................................37
3.5 Compression perpendicular to grain tests ..................................................................................................39
4 Issues concerning the modelling approach and code directives........................................................................... 40
4.1 Modelling aspects .......................................................................................................................................40
4.2 Eurocode 5 methods for strength verification ............................................................................................44
4.3 NEN-EN 594 Racking test method ...............................................................................................................44
5 References ............................................................................................................................................................. 46
page 2 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
page 3 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
Test-data of:
Literature
· fasteners
review
· hold-down anchorage Eurocode 5:
· shear-walls · joint slip modulus Kser
· perforated shear-walls (with
opening)
A
shear modulus G for modelling framework modelling approach
approach with equivalent plate can also be derived analytical
model
shear-walls using equivalent shear parameter k for a braced stiffness value for
modulus G in a plate modelling framework modelling approach perforated shear-walls
wall behaviour
B
· Determined racking stiffness
values from test-data
· Results of analytical methods
(methods found in literature)
Evaluation: If match is proven, between racking- stiffness determined from tests on perforated walls, and racking
Results
stiffness derived by modeling perforated walls (using plate model & parameter G), the results could consist of:
· Modeling suggestion: plate model with G and / or braced framework model with parameter k or k’!
· Equivalent stiffness values G , k and/or k’ : for a certain range of shearwall geometries and configurations (a certain
sheeting material & fastener)
figure 1: Intended plan of approach for the remaining part of the project.
page 4 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
k!
G
F! u!
G
! #
!" =
$
Comparison between stiffness value derived by modelling and analysis, and stiffness
determined from test-data
page 5 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
2.1Shear-wall level
2.1.1 Force distribution in the shear-wall sheeting
2.1.2 Influence of fasteners on the stiffness of shear-wall panels
2.1.3 Influence of hold-down characteristics on the stiffness of shear-wall panels
2.1.4 Influence of aspect ratio (h/b) on the stiffness of shear-wall panels
2.1.5 Influence of number of shear-wall panels on the stiffness of shear-wall diaphragms
2.1.6 Influence of asymmetric sheeting on the stiffness of shear-wall panels
2.1.7 Influence of openings (perforation) on the stiffness of shear-wall panels
2.1.8 Diaphragm action of floors
2.2Fastener and hold-down level
2.2.1 Fasteners
2.2.2 Hold-down anchors
The timber-frame wall is a building element which can be part of the stabilizing structure. In such a case the
timber-frame shear-wall has a load-bearing function, not only for the purpose of transferring vertical loads, but
also for the transfer of the horizontal forces which act on the building. In case of wind for example, the horizontal
wind-load is transferred to the timber-frame shear-wall by diaphragm action of the floors. The racking force on
the shear-wall is divided over the wall length, this results in a distributed load on top of the wall. This distributed
load will be transferred to the foundation or substructure by the shear-wall.
The shear-wall itself is a composite element. A timber-frame wall consists of timber frame elements, connections,
wood-based or gypsum-based panels, and fasteners: screw, nail or staple. The shear-wall is able to transfer the
racking forces thanks to the sheeting which acts as a brace to the timber framing elements. The shear-force on
top of the wall-element is transferred to the sheeting by means of fasteners which are located along the
perimeter of the sheeting.
page 6 / 49
‘Multi-storey timber frame building’ – literature review timber framing / top rail 23-04-2012
height h = ± 2600 mm
hold-down
timber framing / bottom rail
(b) CR
(a) Fp /2 (c)
Fp
Fp
Fp CR CR
Fp
Fp /2
CR CR = center of rotation of stud / rail
figure 4: Forces from the fasteners on the sheeting of a fully anchored timber-frame shear-wall (h/b = 2). (a): elastic
force distribution, (b): plastic force distribution according to the lower bound method as adopted in the Eurocode 5,
(c): plastic force distribution according to the upper bound method. (Källsner & Girhammar, 2009)
In figure 4 (a), a force distribution according to a linear elastic model is shown. In a linear elastic model, the
sheeting-to-timber joints have linear elastic load-slip characteristics up to failure. The joint stiffness is
independent of force direction and grain orientation of the sheeting and timber framing elements. As can be seen
from the figure, the load on the fasteners is of different magnitude for each position. From comparison with
page 7 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
experimental testing can be concluded that the elastic model generally will lead to a underestimation of the
shear-wall capacity. Nevertheless, the horizontal displacement of the wall calculated according to the linear
elastic model agreed very well with the results of full-scale shear-wall tests.
In figure 4 (c) a plastic force distribution is shown, based on the plastic upper bound method. Each of the five
timber members rotates around its own centre of rotation. Sheeting-to-timber joints are completely plastic, the
properties are independent of the force direction and grain orientation of the sheet and timber members. The
loads on the fasteners are of the same magnitude, because the fasteners have plastic characteristics. By
experimental testing, the use of this method turned out to result in an overestimation of the racking capacity of
the shear wall.
In figure 4 (b), a force distribution is shown according to a lower bound plastic model. In this model, a pure shear
flow along the perimeter of the wall is assumed, on the condition of force and moment equilibrium. The force on
each fastener is at most equal to the plastic capacity of the fastener. The framing members, the timber framing
elements, are considered to be completely flexible. Therefore, the force distribution will become parallel with the
framing members. This in contrast with models mentioned in (a) and (c). Model (b) turned out to correspond very
well with experimental testing, giving values for the racking capacity lower than, or equal to the exact value
obtained by testing. Besides this, the method is suitable for, and very useful to, hand calculation. This may have
been the reason to include the plastic lower bound method in Eurocode 5. The method is based on a static
theorem, while the upper bound method (c) was based on a kinematic theorem. In a kinematic theorem, a
geometrically possible pattern of deformation is assumed. By means of the principle of virtual work, the internal
work of all the fasteners is made equal to the work of the external forces. Therefore, the centre of rotation (CR) of
the timber frame elements is shown in figure 4 (c).
As a consequence of the fastener forces on the sheet, a force distribution in the sheet will develop as shown in
the figure below. The force distribution in the sheeting will be visible when the buckling mode of the timber-
frame shear-wall is observed. In case of buckling, the compressive stress in the sheeting was too high, and caused
the sheeting to deform out of plane. Due to the remaining tensile forces in the diagonal, the sheeting can
maintain its function partly.
tension
compression
figure 6: Example of buckling in case of a thin plate / sheet, without intermediate stud. Test set-up
for experimental verification. (Kessel & Sandauw-Wietfeldt, 2004)
page 8 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
‘For the horizontal stability of wood framed buildings, diaphragm action in the walls is of crucial
importance. The structural behavior and capacity of wall diaphragms are primarily dependent on
the sheathing-to-timber joints. (….) Considering the presence of a lateral load F at the top of the
shear walls, the timber frame must be regarded as unstable, and unable to counteract external
force, which is only resisted by the sheathing and metal fasteners. Apart from the possibility to
uplift of the shear wall, the total lateral displacement is function of fastener slip and shear
distortion of the sheathing (which is usually relatively small and often neglected). Also the global
lateral strength capacity of shear diaphragm is often determined by the resistance of the local joint
between timber frame and sheathing panel (…).’ (Conte et al., 2011)
In the figure below, the separate contributions to the horizontal deformation of a shear-wall element made of
two shear-wall panels are compared. The racking deformation of a timber-frame shear-wall consists of: (a) slip of
the fasteners, (b) strain in the hold-down anchorage, (c) shear deformation of the sheeting, and (d) slip between
the bottom rail and substructure. The remaining issues are considered to be insignificant.
(c) (a)
(b) (d)
figure 7: Separate contributions to the total horizontal racking deformation of the timber-
frame shear-wall. (Conte et al., 2011)
Parameters, which can be varied to influence the effect of the fasteners on the shear-wall behaviour, are:
· choice of fastener type: screw, nail, staple,
· choice of fastener properties: diameter Ø, and length
· spacing of the fasteners (s) along the edges of a panel, being the distance between individual fasteners
page 9 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
The fastener properties themselves are influenced by the thickness and density of the board material, and the
density of the framing timber. What choices can be made to influence the fastener characteristics and what the
influence is of these choices will be explained in §2.2 (page 23).
When doing a racking test, the aplication of sufficient amount of anchorage, can be equivalent with applying a
vertical load. It is also possible to do racking tests by loading the panel with a diagonal load. These three options
are all equivalent if no uplift occurs. In figure 9 is shown what type of force distribution will occur in case of
sufficient anchorage, and what type of force distribution will develop when no hold-down or, insufficient
anchorage is applied. These differences have an enormous influence on the performance of the wall, and on the
utilization of material.
Fi,v,E
d!
s
fasteners 2s
hold-down
Fi,t,Ed!
Fi,c,Ed!
bi!
figure 8: Timber-frame shear-wall panel with fastener figure 9: Forces on fasteners exerted by the sheeting: (L) in
spacing (s). case of sufficient hold-down capacity, (R) in case of
insufficient hold-down capacity.
As can be seen from the right hand side of figure 9, the tensile forces caused by the horizontal force (Fi,v,Ed) have
to be transferred trough the plate to the fasteners in the bottom rail, because of the lack of tie-down anchorage
or vertical load. Due to this disadvantageous force distribution, the fasteners in the bottom rail are loaded
perpendicular to the edge of the panel, and perpendicular to the grain of the bottom rail. This will cause a very
bad failure mode, which is reason for brittle behaviour of the wall panel.
Often no-hold down is applied in the test set-up. Sometimes the argumentation is that it is not common practice
to provide the hold-down anchorage, or, from the viewpoint of costs, an engineered solution is not preferred
because hold-downs are very costly. Except for the cases where the vertical permanent load can prevent tensile
forces to develop, it may be clear that effective utilization of materials only can be reached when structures are
equipped with hold-down devices. (See figure 10 & figure 11 on the next page.)
page 10 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
The effect described above is also found in several tests. Among others, Dolan and Heine did experimental testing
to get more insight into the effect of hold-down anchorage on shear-wall behaviour. They conclude the following.
Failure modes for walls with no overturning restraint were obviously different. For all three walls the typical
failure mode was the tension end stud seperating from the bottom rail and the sheeting unzipping from the
bottom rail (Dolan & Heine, 1997).
figure 10: Unzipping of sheeting from the bottom rail figure 11: Lack of anchorage / vertical load causing the
(Ni et al., 2010) fasteners to tear through the sheeting edge. (Salenikovich,
2000)
page 11 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
From tests on walls with a length in the range of 0,6 until 3,6 m in plan of the building, was found, that walls of
1,2 m and longer tend to develop the same stiffness. Walls 0,6 m long had 50% lower stiffness relative to the long
walls. Due to the low racking stiffness, the sheeting connections in these walls did not fail, which lead to the
extraordinary ductility (Salenikovich, 2000). The large drifts arise due to a greater effect of body rotation, the
uplift displacements of the end studs contribute to horizontal deflections in proportion to the aspect ratio
(Salenikovich & Dolan, 2003). In STEP 3 this effect is described is following. A wall panel with a small width to
height ratio will reach its maximum load at a rather large displacement. A wall panel with a large width to height
ratio will reach its maximum load at a lower displacement. Therefore the full plastic capacity of the wall with
small width to height ratio might never be reached. (Källsner & Lam, 1995)
Lower values for the stiffness of walls with a smaller width can be explained by comparing a slender wall with a
standard wall. Let the walls be loaded with the same shear load:
4:1 2:1
figure 13: Wall panels with height-to-width ratio 4:1 & 2:1 (Forces acting on the wall panel, shear forces on the sheeting, magnification
of δv.
As can be seen from figure 13, the walls are executed in the same way. The walls are loaded to the same extend;
an equal shear force is developing on the edges of the panel. δv is the total vertical deformation due to anchorage
slip, and lengthening / shortening due to tension and compression in the leading studs. Because of the small
width of the slender wall (4:1), the deformation δv is magnified more than for the wall with ratio 2:1.
page 12 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
The influence of the aspect ratio was also considered in an analytical calculation method (Källsner & Girhammar,
2009). Based on the conditions of full anchorage a plastic model was derived in which: h/b is the height-to-width
ratio of the wall, sr is the fastener spacing of the sheet-to-timber connections, b is the width of the wall panel, H is
the horizontal racking load, and k is the stiffness of the fastener sheet-to-timber connections. The stiffness of a
shear wall panel can be computed by:
! -
!%&'() =
, (1)
2*1 + . /&
-
When this relation is plotted for different height-to-width ratios, the decreasing stiffness for higher ratios is
evident.
kframe as function of h/b
0,40
0,35
0,30
0,25
kframe
0,20
0,15
0,10
0,05
0,00
0 1 2 3 4 5
ratio h/b
figure 14: kframe as function of h/b. (h/b = 2 )
From literature, and simple analysis can be concluded that for walls with slenderness ratio higher than or equal to
4:1, the stiffness properties of the standard wall (2:1) have to be reduced with 50%. Walls with aspect ratios ≤ 2:1
developed identical load-deformation patterns (Salenikovich & Dolan, 2003). On first hand, this 2:1 ‘limit’ might
be strange. An explanation, found in literature, will be given in the next paragraph.
figure 15: Rotation of the sheeting of a shear wall panel figure 16: Rotation of sheeting of a shear
as observed in experimental test. (Källsner, 1984) wall panel. (Ni et al., 2010)
page 13 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
For the described walls, the individual load-displacement curves can be superimposed when sufficient tie-down
capacity is provided by hold-down anchorage and / or vertical load. In this way, an equally distributed shearforce
will develop along the edges of the shear wall panel. (See also §2.1.2) Another requirement is that the different
material / fastener combinations that are used have to show enough deformation capacity until the level of
shear-wall diaphragm utilization.
Research performed by Wolfe in 1983 revealed that the law of superposition explained the contribution of
Gypsum to the ultimate shear capacity of OSB/Gypsum sheeted shear-walls. Wolfe tested 30 walls to study the
contribution of GKB to the racking resistance (Sinha & Gupta, 2009). A first comment to the conclusion of Wolfe
could be made after Karacabeyli and Ceccotti did a similar research in 1996. They verified that the law of
superposition was valid up to a drift of approximately 50 mm for monotonic tests (Ceccotti & Karacabeyli, 2002).
(experimental verification)
(superimposed)
When these findings are studied further, it appears that the principle of superposition also holds for the stiffness
of the walls. The deformation of both sheets will be the same because they are fastened to the same frame. The
system can be seen as a parallel set of springs:
k :3;<>?@A = k7 + k 8 (3)
page 14 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
The possibility of adding the capacity and load-displacement behaviour of gypsum sheeted panel side to the
capacity and load-displacement behaviour of the plywood side of the shear-wall panel was also demonstrated by
Johnson in 1997. He concluded that GKB will help to resist shear at moderate load level, but plywood resists most
of the shear at higher load levels (Sinha & Gupta, 2009).
Comparison of load-displacement curves for wall panels, consisting of normally used combinations of interior and
exterior sheeting materials in Sweden, showed that the maximum load is obtained at about the same
displacement. Considering the ultimate limit state, the following conclusions were drawn. If a wall panel is built
with sheets of different types or thickness on both sides, a reduction of the weaker side has to be calculated with.
Based on experimental data a reduction of the load carrying capacity of the weaker side should be in the range of
20%. Only if fastener sheet combinations with completely different slip properties were used, a reduction of 50%
is justified (Källsner & Lam, 1995). The same is written in the Eurocode 5, where a reduction of 25% is prescribed.
(See §4.2.) These findings can be explained by studying figure 17 more detailed. When ultimate racking load is
reached for the combined action, the gypsum part of the wall is already over its ultimate capacity, therefore it is
logical to reduce its attribution in the assembly of gypsum and OSB when considering ultimate strength limits.
Not only the load-bearing capacity of the weakest side needs to be reduced when considering combined action,
also the deformation capacity of the wall is reduced. This was already stated by Karacabeyli and Ceccotti in 1996,
and confirmed from research performed in 2003. Uang and Gatto observed a 12% increase in shear wall strength,
and 60% increase in initial stiffness, but also, a decrease in shear-wall deformation capacity of 31%.
Independently, Toothman found comparable results (Sinha & Gupta, 2009). Explanation of the effect is, that the
material, which originally showed the largest deformation capacity, is subjected to a higher load in the combined
situation, than in the situation of single performance. This can be seen from figure 17.
Sinha and Gupta performed an unusual study to get better insight in the combined action and effects of
combined action. Using digital optical imaging techniques, they were able to record the strains on the surface of
the shear-wall panel sheeting. 16 Full-scale timber-frame shear-walls were tested, 11 were sheeted on both sides,
with OSB on one side and GKB on the other. Five walls were tested without GKB. From the tests they derived the
following conclusions. Upon failure of the GKB sheeting, the GKB carries a load four times higher than the OSB
sheeting because of the higher initial stiffness of the gypsum sheeting. However, when GKB starts to fail, the
strain in OSB will increase on a higher rate. Hence, OSB is taking over the load from the gypsum sheeting. This
continues up to complete failure of the GWB sheeting. On first sight, the research of Sinha and Gupta showed
different results than the previous mentioned tests. The elastic shear stiffness is increased by 50%. However, the
contribution of GKB to the strength of the wall is very low, namely, 0,8%. See also figure 19.
Sinha and Gupta explained the difference between these results and the test results of Karacabeyli and Ceccotti,
and Toothman, by the variation in the size of walls and different fasteners used for attaching OSB and GKB to the
shear-wall panel framing (Sinha & Gupta, 2009). However, are the different fastener characteristics really the
explanation for the difference in test results?
page 15 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
It seems very logical to attribute the brittle behaviour of the gypsum sheeting material to the sheeting-to-timber
fastener behaviour. However, when a wall is sufficiently tied down, a shear force parallel to the framing members
will develop along the edge. From the experimental information (§3.2) can be concluded that a dry-wall screw
Ø2,31x41,3 will not show brittle behaviour. The shift from load taken by the gypsum panel to the OSB panel
should develop more gradually. The correct explanation for the low contribution of gypsum in the ultimate
strength is the vertical uplift of the stud. The hold-down capacity of the anchorage provisions was too low. This
results in a force on the fasteners perpendicular to the edge of the gypsum panel in the lower corner near the
hold-down anchor. Fasteners tearing through the gypsum board are the reason for the brittle behaviour. (See also
§2.1.2.)
Conclusion
As could be seen in the present discussion concerning load-sharing between gypsum and OSB in a shear-wall
assembly, three conclusions can be drawn.
· Load is shared by both OSB and GKB initially in a shear wall assembly. When the gypsum sheet is starting
to fail, the load will shift to the OSB panel.
· GKB will contribute to the overall strength of the shear wall, and it will increases the stiffness of the wall,
provided sufficient tie-down capacity or vertical load is applied.
· For OSB also Plywood or another similar wood-based panel can be read.
page 16 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
Reduction of stiffness
Doudak and Smith tested seven different configurations of shear-wall panels. Only geometry and boundary
conditions were changed. The fastener and sheeting configuration remained the same for all panels. Wall lay-out:
OSB t = 11,1 mm 1200 x 2400 mm, overall wall dimension: b x h = 2400 x2400 mm, studs spaced 400 mm center
to center, fastener: nail Ø??x60,fastener spacing s = 150 mm
2 4 6 7
figure 20: Shear-walls with opening: wall2, wall 4, wall 6 and wall 7. (Doudak & Smith, 2009)
Vertical load was applied on top of the walls respectively 4,16 kN/m on wall 2 and 2,08 kN/m on walls 4, 6 and 7.
No significant uplift was observed. A certain initial stiffness was calculated from the test-data. These stiffness
values are stated in table 1. From the tests can be seen that perforations can cause a reduction in the stiffness of
the wall-diaphragms. Despite the fact that tie-down anchorage is applied in the inside bottom corners and in the
door openings, adding a door (4) to the standard wall (2) is the reason for a reduction of 44 % in stiffness. The
door dimensions were 1938 x 838 mm which is 35% of the wall width. An explanation for the magnification of the
effect, could be the reduced panel width. The standard wall is sheeted with OSB. The width of these sheets, 1200
mm, will decrease to 781 mm because of the door. This is a reduction in width of the wall of 35%. In §2.1.4 was
explained that this will lead to a relatively higher reduction in stiffness (44%).
Initial Ultimate
Wall
stiffness racking load
test
(N/mm) (kN)
2 558 20,8
3 313 9,3
4 380 11,2
5 416 10,9
6 562 12,1
7 603 15,3
table 1: Calculated values for initial stiffness of
tested shear wall panels with perforations. figure 21: load-displacement graphs tested walls. (Doudak & Smith, 2009)
(Doudak & Smith, 2009) Secants are drawn at 10% and 40% of the ultimate load.
On first sight the table reveals a strange effect, when adding a window to the standard wall, the initial stiffness of
the wall increases. This effect could happen because of the method to calculate the initial stiffness. ‘Because the
response of the walls is nonlinear, the initial stiffness is taken as a secant stiffness defined using racking loads and
associated racking deformations at 0,1 and 0,4 times the ultimate racking load. This is intended to characterize
the response in the recoverable deformation range.’ (Doudak & Smith, 2009) Because the ultimate racking load
decrease, the curve length over which the initial stiffness is calculated is much smaller, this results coincidentally
in a higher initial stiffness. Another remark stated in the paper is the sensitivity of the wall behaviour for small
page 17 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
changes in boundary conditions. Take for instance the difference between wall 6 and 7. Because the tie-down
anchor in wall 7 was mounted to the outside edge of the tensile stud, instead of the inside bottom corner of the
wall, the stiffness increased with 7,3%. According to Doudak and Smith, the wall perforations have a
disproportionate influence on the stiffness of the wall panels when hold-down anchors are omitted. In such a
case, the wall stiffness of wall 2 was reduced with 56% by adding a door (wall 3).
1 H 9 IL>
and: r= E = H 9 IL + IJ (6)
1+ > >
G
Results of testing done by Dolan and Johnson in 1996 showed the applicability of the empirical relation
determined by Sugiyama and Yasumura. The results also indicated that the ‘panel area ratio’ method is slightly
conservative especially at smaller ratio of openings (Dujic et al., 2006). Sugiyama and Yasumura developed the
empirical equation provided hold-down anchorage is only applied on the end studs of the wall. No additional tie-
down anchorage at intermediate locations of individual shearwall segments was provided.
According to the results of another series of tests performed by the American Plywood Association in 1994, the
empirical equation was also proven to provide correct or slightly conservative values. The difference between the
equation and test results does not exceed 10% (Douglas & Sugiyama, 2001).
Douglas and Sugiyama stated that the method is applicable to use in practice. The statements below were
especially introduced to receive wider acceptation of the procedure in the traditional US design methodology:
page 18 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
· Shearwall segments are considered to be part of the total full-height length, if the length of the segment
is equal to, or larger than, one-half of the wall height.
· Shear capacities of the sheeting materials have been limited to a maximum ultimate shear capacity of
1500 plf. (Equal to 21,89 kN/m.)
· Hold-downs with the capacity to resist the maximum overturning in a wall segment are required at each
corner and at all discontinuities that occur in the wall line.
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0,0
0,0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0
From research of Dolan and Heine can be concluded that the amount of tie-down anchors influences the load-
displacement characteristics and failure mode. The magnitude of the influence of these anchors depends on the
amount of openings in the wall. If there is a higher amount of perforation, every additional tied-down anchor on a
stud near to an opening will be more effective than in a situation with lower amount of perforation. The study
also reveals an interesting issue with respect to the curve determined by Yasumura and Sugiyama (figure 23). The
amount of conservatism of this relation increases as the amount of opening in the wall increase. This can also be
stated as following. The lower the panel area ratio, the larger the underestimation by the Yasumura and Sugiyama
curve of the stiffness of the perforated element. (Dolan & Heine, 1997)
Conclusion
To conclude with, the most important remarks that can be made to the empirical equation are:
· only hold-down anchorage was applied on the edges of the wall diaphragm, no tie-down provisions on
studs next to openings was applied
· tests which were the basis for the equation, and tests confirming the applicability of the equation, did not
take in account the effects of vertical loading
An analysis will be made if the Sugiyama and Yasumura equations are applicable to the test-data as found in
literature. This analysis will be done in a later phase of the master’s project.
page 19 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
(A) (B)
Hence, the in-plane stiffness of the floor and roof diaphragms is influencing the distribution of forces over the
shear-walls. On the question how to determine if timber-frame floor diaphragms can be seen as either rigid or
flexible, information is found in literature.
Horizontal diaphragms can only be considered as rigid, when the configuration of the diaphragm satisfy a number
of requirements. One of the demands can be found in a publication of Kasal, Collins, Paevere, and Foliente from
2004. They state that the flexibility of the diaphragm has to be defined relative to the rest of the structure. The
magnitude of expected deflection of the horizontal diaphragm relative to the shear-wall deformation can be used
to characterize a diaphragm as rigid or flexible. A rule is stated in the International Building Code that a
diaphragm is rigid when the deformation of the diaphragm is less than two times the average racking deformation
of the shear-wall diaphragms. For most wood-frame buildings, the diaphragms can be considered to be rigid, due
to the significant larger shear wall deformations compared with the floor-diaphragm deflection. (Kasal et al.,
2004) Comments on the backgrounds of the IBC statements however are not present in the paper. More research
into this topic would be justified.
A qualitative requirement would be that the sheeting panels are fastened to the framing along the entire
perimeter. Therefore, the floor structure has to be provided with so-called blocking.
figure 25: Blocking timber applied between the main joists. (Falk &
Itani, 1989)
The effect of blocking was demonstrated in experimental testing performed by Bott in 2005, and numerical
modelling done by Falk and Itani in 1989. If blocking is left away, a force distribution will develop different from
what was already explained in §2.2.1 and drawn in figure 9 (page 10). Forces perpendicular to the sheeting edges
and the phenomenon of buckling will result in unfavourable force distribution and failure mechanisms. Falk and
Itani investigated the effect of blocking on the stiffness of the floor diaphragm by analyzing the diaphragm with
blocking, and without blocking. From their numerical work could be concluded that leaving blocking from the
floor structure could reduce the stiffness of the horizontal diaphragm with 35 to 49 % (Falk & Itani, 1989). The
effect of blocking was also shown by experimental testing. Research was done on the effectiveness of measures
page 20 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
to increase diaphragm stiffness by several structural choices. These were the application of blocking, the
application of foam adhesive, the effect of openings in the sheeting (staircases), the influence of walls along the
edge of the diaphragm, and the sheeting nail density. A limiting factor however, is the choice to study all issues
separate. No combination of effects was studied. In conclusion can be said that the most effective measure was
to provide the diaphragm with blocking. It provided the largest individual increase in diaphragm stiffness with an
average of 135% increase in shear stiffness. Only qualitative results were published. These include the following
conclusions.
Using a smaller fastener distance, applying sheeting connected to each other with glued tongue-and-groove
finished edge, or gluing the perimeter of the sheeting to the floor joists, can increase the stiffness of the
diaphragm enormous.
Perimeter walls can effectively stiffen a diaphragm if the bottom plate is continuous and adequately fastened-
down. Due to the resistance of the bottom plate to the tension forces developing in the diaphragm edge through
bending action, the primary effect of walls on diaphragms is increased flexural stiffness. (Bott, 2005)
A few years ago an extensive research program (NEESWood) was conducted in the United States. In this project,
full-scale buildings were tested to verify their behaviour when supposed to seismic loading. From these tests a lot
of knowledge was gained. In addition, information about the stiffness of the floor-diaphragms was acquired.
Christovasilis, Filiatrault and Wanitkorkul reported about the research on a full-scale two-storey timber-frame
building in 2007. The building is shown in figure 27.
Garage
Dining Living
Atrium
figure 27: View and lower-level plan of the two-storey timber-frame building. (Christovasilis et al., 2007)
Exposed to different magnitudes of seismic loads, the building became damaged. From observations and
interpretation of this damage and the measurements done during testing was concluded that the horizontal
diaphragms of the two main parts of the building acted as a rigid plane. However, because of the atrium and the
staircase, the in-plane stiffness of the floor and roof at this location was lower than the rest of the structure.
Although the application of gypsum sheeting to the ceiling increased significantly the in-plane stiffness of these
diaphragms. Damage was observed in the gypsum sheeting, in the atrium / staircase are, after testing. The
gypsum sheeting in the two main parts of the building had a minimal effect on the floor diaphragm since the
structural floor system alone provided enough in-plane stiffness to act as a rigid diaphragm. (Christovasilis et al.,
2007)
page 21 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
figure 28: The floor diaphragm was made of plywood panels and floor joists connected by
nails. On the right hand side, the gypsum ceiling is visible. (Christovasilis et al., 2007)
During the tests, the deformations were recorded with multiple sensors. The shapes of deformation could be
composed from these measurements. These shapes show the rigid behaviour of the diaphragm in the main parts
of the building, and the flexible part in the atrium / staircase area.
Based on the findings from literature as presented above the following conclusion can be drawn. For the
dimensional proportions of the diaphragms treated above, the assumption of rigid diaphragm behaviour can be
justified. The assumption should be critically treated for more slender floor plan proportions, and floor
diaphragms with perforation such as atrium and staircases. For rigid diaphragms, modelling can consist of rigid
bracing, or plate elements. Flexible floor diaphragms can be modelled as if shear-wall diaphragms would be
modelled.
page 22 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
2.2.1 Fasteners
As will be presented in chapter 3, test-data of fasteners are result of the literature review. In a later phase of the
masters’ project, these data will be used to determine stiffness values according to NEN-EN 26891. The
determined stiffness values will then be compared with stiffness values derived from Eurocode 5. This process will
result in more insight into the applicability of the Eurocode 5 rules for the fastener slip-modulus (Kser) to timber-
frame shear-wall analysis.
In Eurocode 5 gypsum-to-timber connections are not mentioned. About this type of connection, some
information was found in the German code DIN 1052 (2008-12, tabelle G.1). There it is stated that the fastener-
slip modulus Kser has to be reduced with 40% for connections of timber to gypsum paperboard panels. In the
German code, the characteristic timber density ρk needs to be used instead of ρm.
An example for the equations given can be the formula to calculate the slip-modulus for nail-to-timber
connections with nail fasteners:
U( 7VW 9 XYVZ
ST)& = (7)
C[
In which:
U( = \U(V7 9 U(V8 (8)
The applicability of the design rules on deriving Kser, to timber-frame shear-wall analysis, will be studied by
comparing the Eurocode derived stiffness values with the stiffness values determined using NEN-EN 26891 and
the test-data from literature.
page 23 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
Considering European spruce, the increase of the moisture content is about 12%, when changing the RH from
65% to 95% (Banga & Graaf, 2002). Assuming the plywood from Nakjima’s tests to behave the same, this will
result in 2,1% change in initial stiffness per 1% change in moisture content.
According to NEN-EN 26891, 20°C and 65%RH is the standard climate condition for testing when comparison of
joints under similar conditions is aimed at. In some of the test reports and papers, reference is made to these
circumstances as boundary condition for the shown load-displacement figures. From other sources of load-
displacement graphs no information about the relative humidity is known.
One might say that for shear-walls applied in Serviceclass 2 a reduction in stiffness has to be calculated with. And,
if the situation in timber-frame structures is analyzed, it becomes clear that the circumstances inside a cavity wall
(Serviceclass 2) are different from the atmosphere inside the building (Serviceclass 1). However, the differences
observed in testing at 90%RH and 65%RH influence the stiffness of the sheeting-to-timber connections much
more, than the smaller differences between the interior and cavity side of the shear-wall will do. The moisture
content of the timber on the inside of the building and inside the cavity wall will be always between 10% and
20%. Additionally the stiffness values of the timber based panel applied on the inner side of the building
(Serviceclass 1) would have to be increased compared with values determined from testing at 20°C and 65%RH
atmosphere.
Therefore the conclusion can be drawn that both effects could counterbalance each other. Hence, no effect of
moisture content will be considered in the next phases of the project.
Conclusion
In conclusion can be said that the factors influencing the fastener stiffness Kser, of the fastener are the following:
· Density of the timber (taken into account in Eurocode 5)
· Diameter of the fastener (taken into account in Eurocode 5)
· Type of sheeting material
· Moisture content of the wood (not taken into account by Eurocode 5, will not be considered)
· Thickness of the sheeting material
Although the thickness is important for the ultimate capacity (strength) of the connections, it is not taken into
account in Eurocode 5. Confirmation of this can also be seen in test-data. Compare curve 6.2 and 9.1 in figure
45, and curve 2.1 and 2.2 in figure 46.
· Yield strength of the fastener (Plastic moment capacity)
Although the yield-moment capacity of the fastener is influencing the ultimate capacity (strength) of the
connections, the influence on the stiffness of timber-to-framing connection is negligible. (Leichti et al., 2006)
figure 30: Experimental test figure 31: Idealized load-deformation curve and
set-up to derive fastener measurements.(NEN-EN 26891)
characteristics. (Christovasilis
et al., 2007)
The influencing factors stated above will determine the fastener-slip characteristics and failure mechanism, as
long as enough edge distance is applied. If the distance to the edge is too short, other effects will become
page 24 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
important. For example, the way in which the edge is finished can be of influence on the characteristics of the
fastener (manufacturing issue). For gypsum-based panels this can be seen from the test-data found from
literature. Differences between sawn edges and edges finished with a paper cover become visible in the test
results when not enough edge distance is applied. Compare test results 7.3 and 7.4 in figure 47. The shortest edge
of a standard gypsum paperboard is the sawn edge. No finishing is applied on this edge. The longest edge of a
standard gypsum paperboard can be finished in different ways. The reinforcing paper will make this edge a little
bit stronger than the short edge.
page 25 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
The design rules to derive Kser according to Eurocode 5 are already discussed above. The fastener-slip modulus will
again be used to derive a stiffness value for the hold-down anchorage.
When the designer is calculating the design strength for hold-down anchorage, the calculation starts with the
design strength for a single fastener (#%V]^ ). A number of _ fasteners are used. When calculating the combined
action of all fasteners, the number of fasteners has to be reduced. The effective number of fasteners can be
calculated as following:
_)% = _`ab (9)
In which !)% is a reduction factor bringing in account the fastener spacing and the option of predrilled holes. The
capacity of the hold-down can now be calculated to be:
The reduction of the number of fasteners is introduced because of the splitting behaviour visible near failure of a
parallel to grain positioned and loaded row of fasteners. The accumulation of perpendicular to the grain tensile
stresses, gives reason to reduce the capacity of the connection (Jorissen, 1998). However, considering the
serviceability limit state, this reduction is no issue because it is the stress-level in ultimate limit state causing the
splitting of the timber grains. Therefore, the stiffness of the individual fastener does not have to be reduced when
contributing to the total stiffness of the hold-down anchor.
This is only valid when the fasteners act as a set of parallel springs, which is the fact when the deformation of the
steel section can be neglected. A comparison can be made with the stiffness value determined on basis of the
test-data. For the standard anchorage solutions, manufactured by Rotho Blaas and Simpson, test-data were
provided, and found in literature. Stiffness values for custom made configurations of hold-down anchors can be
estimated when it is possible to derive the stiffness of hold-down anchorage solutions in the way as it is described
above.
page 26 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
3 Experimental results
As was mentioned in §1.2, the test-data of timber-frame shear-walls, shear-walls with opening, sheeting-to-
timber fasteners, and hold-down anchorage, will be presented. How the information will be used is already
discussed in §1.2 and 1.3. The information will be the experimental basis to determine stiffness values for the wall
assemblies and connections (§2.2 & 4.3). These stiffness values will be compared to the present code directives in
a later phase of the project. Validation of the modelling approach with the experimental information will be
another purpose of the test-data.
From a wide range of shear-wall configurations test results were found, this can be seen in table 2. References
displayed in the table can be found on page 31 in the reference list.
Wall dimensions (b x h): 600 x 2400 1200 x 2400 1800 x 2400 2400 x 2400 3600 x 2400 4800 x 2400
[mm]
Fastener spacing (s):
[mm] 50 75 150 50 75 100 150 200 100 200 75 100 150 200 75 100 150 200 150 200
Board material:
(3.3)
OSB (3.1) (3.2) (1.2) (7.2) (5.2) (5.1) (3.4)
(7.1)
(1.3)
Plywood (6.1) (14.21) (2.3) (4.1)
(8.1)
(10.1) (10.2) (1.1) (2.1) (14.3)
Gypsum paper board (GKB) (10.3) (10.4)
(14.1)
(8.2)
(14.27) (14.2)
(2.2)
(14.9)
(14.10)
(4.2)
(12.1) (12.2,3,4)
Gypsum fibre board (11.1)
(13.1)
(11.2) (11.3,5,7)
(13.2,3,4)
(11.4,6,8)
(14.15)
Particleboard (14.19)
Hardboard fibre board (9.1) (9.2)
MDF (14.17)
The information in the legend of the graphs can be read as following: Ply t = 9,5 nail Ø2,87 x 50, s = 100, b x h =
1820 x 2440, (1.3) means that the tested panel was made using plywood sheeting with thickness 12,0 mm. The
fastener type is stated, as well as the fastener spacing (s) in mm. Thereafter the dimensions of the shear-wall
panel are stated (b x h). For reference (1.3) is added, in which 1 refer to the source in literature: reference 1, and
3 means that this is the third test in the publication referred to. Reference to literature is made on page 31.
40
10
Gypsum Fiber Board, s = 75, both sides sheeted, t = 15,
nail Ø2,5 x 65, b x h = 625 x 2600, (13.1)
5
0
0 20 40 60 80 100 120 140 160
Displacement [mm]
figure 35: Load displacement characteristics for timber-frame shear-wall panels 600 x 2400 (b x h).
page 28 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
25
Gypsum Fiber board, s = 150, no hold-down,
t = 12,5, staple Ø1,53 x 50, h x b = 1250 x 2600, (11.6)
20
Displacement [mm]
figure 37: Load displacement characteristics for timber-frame shear-wall panels 1200 x 2400 (b x h).
page 29 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
40
OSB, s = 140, t = 11,11, nail Ø3,3 x 63,5,
b x h = 2440 x 2450, (5.1)
35
15
OSB, s = 75, t = 9,5, nail Ø2,5 x 50, (7.2)
10
Displacement [mm]
figure 40: Load displacement characteristics for timber-frame shear-wall panels 3600 x 2400 (b x h).
page 30 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
45
40
Plywood, s = 150, t = 9,5, nail Ø2,5 x 63,5,
b x h = 4880 x 2440, (4.1)
35
30
Load [kN]
25
20
15
GKB, s = 200, t = 12,7, nail Ø2,5 x 31,8,
b x h = 4880 x 2440, (4.2)
10
0
0 20 40 60 80 100 120 140 160
Displacement [mm]
figure 41: Load displacement characteristics for timber-frame shear-wall panels 4800 x 2400 (b x h).
References to literature
In the legend of the graphs, reference is made to the following numbers. These references can be found in the
back of the report on page 46.
page 31 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
Load-displacement characteristics for perforated timber-frame shear-walls) GKB, t = 13, screw Ø3,0 x 37,6 s = 200, 2400 x 2400,
gap = 1200 x 1200 (bxh), (14.4)
20
GKB, t = 13, screw Ø3,0 x 37,6 s = 200, 2400 x 2400,
18 gap = 1200 x 1200 (bxh), (14.5)
14
GKB, t = 13, screw Ø3,0 x 37,6 s = 200, 3600 x 2400,
gap = 2400 x 1200 (bxh), (14.7)
12
Load [kN]
figure 42: Load displacement characteristics for timber-frame shear-wall diaphragms with opening. (Källsner, 1984)
120
Plywood, t = 12, nail Ø3,3x63,5 s = 152,
+ GKB, t = 13, nail Ø2,41x38,1, s = 178,
12200x2440 (bxh), door: 1220x2032, door:
Load [kN]
100
2400x1220, window:3658x2032, (16.3)
Displacement [mm]
figure 43: Load displacement characteristics for timber-frame shear-wall diaphragms with opening. (Dolan & Heine, 1997), (Dolan &
Johnson, 1996)
page 32 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
20
OSB, t = 9,5, nail Ø3,3x63,5 s = 50, 2440 x 2440,
gap = 1200 x 2000 (bxh), (15.5)
Load [kN]
15
OSB, t = 9,5, nail Ø3,8x76 (with washer) s = 150, 2440x2440,
gap = 1200 x 2000 (bxh), (15.7)
10
0
0 20 40 60 80 100 120 140 160
Displacement [mm]
figure 44: Load displacement characteristics for timber-frame shear-wall diaphragms with opening. (Richard et al., 2002)
References to literature
(14) (Källsner, 1984)
(15) (Richard et al., 2002)
(16) (Dolan & Johnson, 1996) & (Dolan & Heine, 1997)
page 33 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
From table 3 can be concluded that from a wide range of fastener and sheeting combinations, test results were
found. Reference displayed in the table can be found on page 34 in the reference list.
Ø2,87 x 65 (63,5)
Ø1,34 / 1,62 x 47
Ø1,83 / 2,06 x 50
Ø2,5 x 65 (63,5)
Ø2,0 (2,1) x 50
Ø2,34 x 40
Ø2,87 x 50
Ø3,35 x 45
x 65 (63,5)
Ø1,8 x 65
Ø2,2 x 45
Ø2,9 x 48
Ø2,5 x 50
Ø3,0 x 51
Ø2,5 x 55
Ø2,8 x 75
Ø3,8 x 76
Ø3,1 x 80
Ø3,9 x 41
Ø4,2 x 35
Board
Board material
OSB 9,5 (11.1) (1.2) (6.1) (6.2) (6.3)
(5.1) (3.4)
11 (5.2)
(9) (3.6)
(3.5)
12 (2.2)
Hardboard 8 (10.1)
References to literature:
(1) (Yasumura & Kawai, 1997)
(2) (Komatsu et al., 1999)
(3) (Dujic & Zarnic, 2003)
(4) (Karacabeyli & Ceccotti, 1996)
(5) (Christovasilis et al., 2007)
(6) (Richard et al., 2002)
(7) (Bouw- en woningtoezicht Rotterdam, 1989)
(8) (Andreasson, 2000)
(9) (Salenikovich, 2000)
(10) (Vessby et al., 2008)
(11) (He et al., 2001)
(12) (VHT Versuchsanstalt fur holz- und trockenbau Darmstad, 29-05-2002)
(13) (VHT Versuchsanstalt fur holz- und trockenbau Darmstad, 10-06-2002)
(14) (Conte et al., 2011)
(15) (Källsner, 1984)
page 34 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
Displacement [mm]
figure 45: Load-displacement characteristics for fastener tests with OSB sheeting.
1600
1400
t = 9,5 mm nail Ø2,87x50 (1.3)
1200 t = 9,0 mm nail Ø2,9x48 (2.1)
400
200
0
0 5 10 15 20 25
Displacement [mm]
figure 46: Load-displacement characteristics for fastener tests with Plywood sheeting.
page 35 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
Load-displacement characteristics for sheeting-to-timber fastener test (Gypsum (fiber) board sheeting)
1800 t = 12,0 mm nail Ø2,34x40 (1.1)
1200
t = 12,5 mm screw Ø3,35x45 (sawn edge) (7.3)
1000
Load [N]
Load-displacement characteristics for sheeting-to-timber fastener test (different type of board materials)
1800
1600
1400
400
200
0
0 5 10 15 20 25
Displacement [mm]
figure 48: Load-displacement characteristics for fastener tests with different types of sheeting.
page 36 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
The meaning of the information on the hold-down stiffness aspect, can be explained as following. Often hold-
down anchorage is prescribed by engineers based on a ULS approach. These hold-downs can be bought from
stock, or can be designed individually for each single project as metal straps with certain dimensions, fastener,
and fastener spacing. The hold-down solutions can be very stiff, as can be seen from the curves. When the
deformations of the hold-down contribute to the deflections of the shear-wall panel as a whole, there can be
reason to include the hold-down stiffness in the modelling. In such a situation, Eurocode 5 can be used to
calculate a stiffness value for the hold-down anchor. (As explained in §2.2.2.) However, verification of this
approach is only possible by comparison with the stiffness values determined from the load-displacement graphs.
100
80
18 x nail Ø4,11 x 89, (smooth shank), (2)
60
Load [kN]
0
0 2 4 6 8 10 12 14 16 18
Displacement [mm]
figure 49: Hold-down test-data from testing, mean curves. figure 50: Impression of
situation after failure.
(NAHB Research Center,
2003)
100 100
30 x nail Ø4,0 x 40 (rillenagel), ρ = 419, (1.2) 25 x nail Ø4,0 x 75 (rillenagel), ρ = 401, (1.7)
80 35 x nail Ø4,0 x 40 (rillenagel), ρ = 407, (1.3) 80 25 x nail Ø4,0 x 75 (rillenagel), ρ = 452, (1.8)
40 x nail Ø4,0 x 40 (rillenagel), ρ = 418, (1.4) 25 x nail Ø4,0 x 75 (rillenagel), ρ = 431, (1.9)
60 60
Load [kN]
Load [kN]
40 x nail Ø4,0 x 40 (rillenagel), ρ = 438, (1.5) 22 x nail Ø4,0 x 75 (rillenagel), ρ = 421, (1.10)
40 40
18 x nail Ø4,11 x 89, (smooth shank), (2) 18 x nail Ø4,11 x 89, (smooth shank), (2)
figure 51: Hold-down test-data from testing, figure 52: Hold-down test-data from testing,
nail Ø4x40. nail Ø4x75.
page 37 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
40
Research Center, 2003)
18 x nail Ø4,11 x 89, (smooth shank), (2)
page 38 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
F ½F ½F
50
45 x 90 mm
40 (ungraded framing
members) (1.1)
Load [kN]
45 x 90 mm
(ungraded framing
30 members) (1.2)
45 x 120 mm (2.1)
20
45 x 90 mm (secant)
(1.3)
10
0
0 2 4 6 8
Displacement [mm]
figure 55: Load-displacement test results from several compression ┴ to grain tests. figure 56: Compression ┴ to grain
deformation. (NAHB Research Center, 2003)
References to literature:
(1) (Andreasson, 2000) (also information available concerning tension & shear in framing member connections)
(2) (Vessby et al., 2008) (also information available concerning tension & shear in framing member connections)
page 39 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
Source for the stiffness values, which will be used as input in the framework modelling, can be either, the
Eurocode 5 design rules, test-data, a combination of both, or could be derived using more detailed modelling. To
perform more detailed modelling, a software package will be used, more advanced than the common framework
structural analysis software. This will be a commercially available FEM structural analysis program with user-
friendly interface (Scia Engineer). No academic methods will be used because in these methods the possibilities
are too extensive (Ansys / Diana). This choice will limit the possibilities of the FE method to the most used
options. However, 3D analysis, plate and shell elements, and non-linear spring elements are among the
possibilities.
hd
figure 57: Example of intended thesis result: modelling a timber-frame structure using experimental input. Figure composed from
several sources: Rothofixing WHT hold-down device picture &graph (Rothoblaas GmbH), photo test set-up (NAHB Research Center Inc.,
2005), graph test result (Salenikovich, 2000).
page 40 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
Pang and Rosowsky developed a modelling approach to take part in a benchmark study concerning the
NEESWood project. (Some other findings from this project are discussed in §2.1.8) In the picture below the
physical existing shear-wall and floor diaphragms are drawn in grey colour. The representation of the shear-walls
in longitudinal direction (x-axis) is omitted for clarity. As can be seen, the diaphragms are represented by spring
elements, which are connected rigidly to, master and slave, nodes. The springs contain all the stiffness
information needed to get a sufficient accurate model. In fact, the model only consists of a set of equations and
programming, because it is a mathematical numerical model.
Pang and Rosowsky applied the principle of sub-modelling to get correct stiffness values as input for the spring
elements. Therefore, more detailed modelling was done on shear-wall level:
figure 59: Detailed FEM modelling of a timber-frame shear-wall. (Pang & Rosowsky, 2010)
The horizontal floor diaphragm in figure 58 was modelled using the so-called two-node-beam element. Therefore,
first an analysis was performed using a detailed FEM approach. The information on stiffness of the diaphragms
could thereafter be implemented in the two-node-beam element approach. See figure 60, and figure 61.
page 41 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
figure 60: Deformed shape of floor diaphragm, calculated using detailed FEM approach.
(Pang & Rosowsky, 2010)
figure 61: Two-node-beam element modelling approach, beam stiffness derived from more
detailed FEM modelling. (Pang & Rosowsky, 2010)
Using different methods of modelling for different levels of scale is a usual approach. Dujic and Zarnic followed
this modelling procedure as well. In a detailed FEM model, the fasteners and hold-down anchorage were
modelled using non-linear springs. The framing elements were represented by the normal dimensions, and were
connected with plastic hinges. The sheeting and glulam beams were modelled using linear elastic panel elements.
figure 62: From a complex and detailed FEM model (L) to the equivalent strut model (R). (Dujic
& Zarnic, 2002)
Using this type of modelling also perforated shear-walls can be analysed. The results of the detailed modelling can
thereafter be used in the less complex models using equivalent bracing.
page 42 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
figure 63: Details of the FEM model. (Dujic & Zarnic, 2002)
The simplified bracing approach can be used to construct a larger 3D model of the whole building.
How the modelling aspect of the master’s thesis will exactly be dealt with will be determined in a later phase of
the project. The information stated in this paragraph only presented the findings from the literature research.
page 43 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
#%V]^ -m qm
#mlV]^p (13)
/
In qm , the height-to-width ratio ,n- is included. The fastener strength may be increased with a factor 1,2 because
of system-action. A reduction of the weakest side has to be calculated with when different sheeting is applied on
both sides of the wall panel, this reduction is 50% or 75% (§2.1.6). Perforated panels with windows or door
openings do not contribute to the strength of the shear-wall assembly (§2.1.7). Additionally is stated that the
external tensile and compression forces on the edges of the panel need to be taken up by the supporting
structure. Sufficient hold-down capacity has to be provided using tie-down anchorage or vertical load. Vertical
load however is not considered in the Eurocode method. No rules or guidelines are given on stiffness aspects of
wall and floor diaphragms. In practice, the limit state approach will be limited to strength considerations only.
This is one of the reasons to perform this master’s study (See §1.1).
Experimental tests of timber-frame shear-wall panels are often assigned to research institutes by manufacturers
of sheeting materials such as: Oriented Strand Board, Plywood, Particleboard, Medium Density Fibreboard,
Gypsum Paper Board (GKB) or Gypsum Fibre Board. The manufacturers use the tests to gain European Technical
Approval (ETA) to sell their products for structural purposes on the European market. Strength values taken up in
the product information are often based on these ETA’s. Although the tests are done to acquire characteristic
strength values in most cases, the load-displacement graphs can also be used to derive stiffness values. This
information however, is almost never given in the product information. From literature and the archive of
Boorsma Consultants, load-displacement graphs were found for a number of shear-wall configurations. Using
NEN-EN 594, stiffness values can be determined from this test-data.
According to NEN-EN 594 the racking stiffness of the panel can be calculated from the following equation:
#t D #8
s= 6 (14)
vt D v8
page 44 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
Fmax is reached when either the panel collapses, or the panel attains a deformation v of 100 mm, whichever
occurs first.
page 45 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
5 References
Andreasson, S., 2000. ISSN 0349-4969 Three-dimensional interaction in stabilisation of multi-storey timber frame
building systems. Licentiate Thesis. Lund (Sweden): Lund University division of structural engineering. TVBK-1017.
Banga, J. & Graaf, P.d., 2002. Handboek Houtskeletbouw. 2nd ed. Rotterdam: SBR Stichting bouwresearch.
Bott, J.W., 2005. Horizontal stiffness of wood diaphragms. Virginia Polytechnic Institute and State University,
Masters thesis.
Ceccotti, A. & Karacabeyli, E., 2002. Validation of seismic design parameters for wood-frame shearwall systems.
Canadian journal of civil engineering, 29, pp.484-98.
Christovasilis, I.P., Filiatrault, A. & Wanitkorkul, A., 2007. Seismic testing of a full scale two-story light-frame wood
building. Buffalo: University at Buffalo.
Conte, A., Piazza, M., Sartori, T. & Tomasi, R., 2011. Influence of sheathing to framing connections on mechanical
properties of wood framed shear walls. ANIDIS Bari 2011.
Dolan, J.D. & Heine, C.P., 1997. Monotonic tests of wood-frame shear walls with various openings and base
restraint configurations. Virginia Polytechnic Institute and State University, Department of Wood Science and
Forest Products.
Dolan, J.D. & Johnson, A.C., 1996. Monotonic tests of long shear walls with openings. Virginia Polytechnic Institute
and State University - Department of Wood Science and Forests Products.
Doudak, G. & Smith, I., 2009. Capacities of OSB-sheated light-frame shear-wall panels with or without
perforations. Journal of structural engineering ASCE, 135(3), pp.326-29.
Douglas, B.K. & Sugiyama, H., 2001. Perforated shearwall design approach. American Forest & Paper Association.
Dujic, B., Aicher, S. & Zarnic, R., 2006. Testing of wooden wall panels applying realistic boundary conditions.
Portland (Oregon): World conferenc on timber engineering (WCTE 2006).
Dujic, B., Klobcar, S. & Zarnic, R., 2006. Influence of openings on shear capacity of masive cross-laminated wooden
walls. International workshop on "Earthquake engineering on timber structures", Coimbra(Portugal), pp.105-18.
Dujic, B. & Zarnic, R., 2002. Influence of vertical load on lateral resistane of timber-frames walls. International
council for research and innovation in building and construction - Working commission W18 Timber Structures,
pp.CIB-W18/35-15-4.
Dujic, B. & Zarnic, R., 2003. Comparison of hysteresis responses of different sheating to framing joints., 2003.
Falk, R.H. & Itani, R.Y., 1989. Finite element modeling of wood diaphragms. Journal of Structural Engineering,
115(3), pp.543-59.
Foschi, R.O., 1974. Load-slip characteristics of nails. Wood Science, 7(1), pp.69-76.
page 46 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
Girhammar, U.A., Bovim, N.I. & Källsner, B., 2004. Characteristics of sheathing-to-timber joints in wood shear
walls. World conference on timber engineering WCTE 2004 , 8, pp.165-70.
He, M., Lam, F. & Foschi, R.O., 2001. Modeling three-dimensional timber light-frame buildings. Journal of
structural engineering, 127(8), pp.901-13.
Jorissen, A., 1998. Double shear timber connections with dowel type fasteners. PhD-thesis Delft University of
Technology.
Källsner, B., 1984. Panels as wind-bracing elements in timber-framed walls - Wood Technology Report Nr. 56.
Stockholm: TräteknikCentrum.
Källsner, B. & Girhammar, U.A., 2009. Plastic models for analysis of fully anchored light-frame timber shear walls.
Engineering structures, 31(03), pp.2171-81.
Källsner, B. & Lam, F., 1995. Diphragms and shear walls. In H.J. Blaß, R. Görlacher & G. Steck, eds. STEP 3:
Holzbauwerke nach Eurocode 5: grundlagen, entwicklungen, ergänzungen. Düsseldorf: Fachverlag Holz. p.15/13.
Karacabeyli, E. & Ceccotti, A., 1996. Quasi-static reversed-cyclic testing of nailed joints. Bordeaux, 1996.
Kasal, B., Collins, M.S., Paevere, P. & Foliente, G.C., 2004. Design models of light frame wood buildings under
laterl loads. Journal of Structural Engineering ASCE, 130(8), pp.1263-71.
Kessel, M.H. & Kammer, T.z., 2005. Räumliches Tragverhalten mehrgeschossiger Gebäude in Holztafelbauart.
Bauingenieur, (may).
Kessel, M.H. & Sandauw-Wietfeldt, M., 2004. Wood panels with thin low buckling resistance sheeting. World
conference on timber engineering WCTE 2004, 8, pp.643-47.
Komatsu, K., Hwang, K.H. & Itou, Y., 1999. Static cyclic lateral loading tests on nailed plywood shear walls. Graz,
1999.
Leichti, R., Anderson, E., Sutt, E. & Rosowsky, D., 2006. Sheathing nail bending-yield strength - Role in shearwall
performance. World Conference on Timber Engineering WCTE.
LHT Labor für Holztechnik - Fachbereich Bauingenieurswesen Hildesheim, 29-08-2002. Bericht 01/P1002. 18180th
ed. Archive Boorsma projectnr. 05654 (Knauf): Industriegruppe Gipskartonplatten IGG im Bundesverband der
Gips- und Gipsbauplattenindustrie Darmstadt.
McCutcheon, W.J., 1985. Racking deformations in wood shear walls. Journal of structural engineering ASCE,
111(2), pp.257-69.
NAHB Research Center Inc., 2005. Full-scale tensile and shear wall performance testing of light-frame wall
assemblies sheathed with Windstorm OSB panels. Test report. Upper Marlboro: NAHB Research Center Inc.
Norbord Windstorm OSB.
NAHB Research Center, 2003. Light-frame wood shear walls with various overturning restraints. 2003rd ed. Upper
Marlboro: NAHB Research Center.
page 47 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
Nakajima, S., 2001. The effect of the moisture content on the performance of the shear walls. CIB-W18
International council for research and innovation in building and construction - working commission w18 - timber
structures, CIB-W18/34-15-2.
Nakajima, S. & Okabe, M., 2004. Effects of dry and humid cyclic climate on the performance of nail joints and
shear walls. WCTE 2004 World conference on timber engineering Lahti (Finland), pp.117-22.
Ni, C., Shim, K. & Karacabeyli, E., 2010. Performance of braced walls under various boundary conditions. Trentino
(Italy): World conference on timber engineering (WCTE 2010).
Ni, C., Shim, K. & Karacabeyli, E., 2010. Performance of braced walls under various boundary conditions. World
Conference on Timber Engineering WCTE 2010.
Pang, W.C. & Rosowsky, D.V., 2010. Beam-spring model for timber diaphragm and shear walls. Structures and
Buildings - Proceedings of the Institution of Civil Engineers, (163 (SB4)), pp.227-44.
Richard, N., Daudeville, L., Prion, H. & Lam, F., 2002. Timber shear walls with large openings - experimental and
numerical prediction of the structural behaviour. Canadian journal of civil engineering, 29, pp.713-24.
Rotho Blaas GmbH Rothofixing, 07-04-2010. Prüfbericht Nr. 106115 Versuche zur Untersuchung des trag- und
verformungsverhaltens von verbindungen mit GH hold-down-verbindern Rothofixing WHT 80/620. KIT Karlsruher
Institut für Technologie: Rotho Blaas GmbH.
Rothoblaas GmbH, n.d. Information on Rothoblaas WHT angle bracket hold-down device. Generously provided by
Ing. Fabio Verber from Rothoblaas GmbH.
Salenikovich, A.J., 2000. The racking performance of light-frame shear walls. Dissertation. Blacksburg: Faculty of
the Virginia Polytechnic Institute and State University.
Salenikovich, A.J. & Dolan, J.D., 2003. The racking performance of shear walls with various aspect ratios - part 1 -
monotonic tests of fully anchored walls. Forest products journal, 53(10), pp.65-73.
Sinha, A. & Gupta, R., 2009. Strain distribution in OSB and GWB in wood-frame shear walls. Journal of structural
engineering ASCE, 135(6), pp.666-75.
Songlai, C., Chengmou, F. & Jinglong, P., 2010. Experimental study on full-scale light frame wood house under
lateral load. Journal of structural engineering ASCE, 136(7), pp.805-12.
Vessby, J., Källsner, B. & Olsson, A., 2008. Influence on initial gap between timber members on stiffness and
capacity of shear walls. Miyazaki: World conference on timber engineering (WCTE 2008).
VHT Versuchsanstalt fur holz- und trockenbau Darmstad, 10-06-2002. Prüfung P-187/4-02/He. 150th ed. Archive
Boorsma Consultants projectnr. 05654: Firma Rigips GmbH.
VHT Versuchsanstalt fur holz- und trockenbau Darmstad, 29-05-2002. Prüfbericht P-187/3-02/He. 150th ed.
Archive Boorsma Consultants projectnr. 05654: Firma Rigips GmbH Düsseldorf.
VHT Versuchsanstalt fur holz- und trockenbau Darmstadt, 04-10-2001. Prüfbericht P-187/2-01/He. 150th ed.
Archive Boorsma Consultants projectnr. 05654: Firma Rigips GmbH Düsseldorf.
page 48 / 49
‘Multi-storey timber frame building’ – literature review 23-04-2012
VHT Versuchsanstalt fur holz- und trockenbau Darmstadt, 16-02-2000. Prüfbericht P-186/1-00/He. 125th ed.
Archive Boorsma Consultants projectnr. 05654: Firma Rigips GmbH Düsseldorf.
Yasumura, M., 1991. Seismic behavior of wood-framed shear walls CIB-W18/24-15-3. Oxford: CIB working
commission W18 - timber structures.
Yasumura, M. & Karacabeyli, E., 2007. International standard development for lateral load test method for shear
walls CIB-W18/40-15-5. Bled: CIB working commission w18 - timber structures.
Yasumura, M. & Kawai, N., 1997. Evaluation of wood framed shear walls subjected to lateral load. Vancouver,
1997.
page 49 / 49