Power System Faults
Power System Faults
Vandalism
K. Kaberere Birds shorting overhead lines
Ice storms
2
3 4
1
7 8
10
2
Introduction Assumptions commonly made in 3- fault studies
Most power system faults are unsymmetrical.
All sources are balanced and equal in magnitude & phase
They may be unsymmetrical short circuits or
Sources are represented by the Thevenin’s voltage prior to
open conductors.
fault at the fault point
They may be classified as: Large systems may be represented by an infinite bus-bar
1. Single line-to-ground (SLG or L-G) Transformers are on nominal tap position
2. Line-to-line (L-L or DL) Resistances are negligible compared to reactances
3. Double line-to-ground (DLG or L-L-G). Transmission lines are assumed to be fully transposed and
all 3 phases have same impedance
Unsymmetrical faults result in the flow of
Loads currents are negligible compared to fault currents
unbalanced currents in the system
Line charging currents can be completely neglected
Symmetrical components are used to determine
post fault system currents and voltages
13 14
1. Single line-to-ground fault on an unloaded generator (S-L-G) The symmetrical components of the currents are
I a 0 1 1 1 1 I a 1 1 1 1 I a
The fault I a1 1 a a 2 I b 1 a a 2 0
occurs on I a 2 3 1 a 2 a I c 3 1 a 2 a 0
phase 'a'.
The fault I a …………………………….(1)
conditions
I a 0 I a1 I a 2
3
are: From the generator sequence network drawn earlier
1. Ib = Ic = 0
2. Va = 0 Va 0 0 Z 0 0 0 I a 0
Va1 Ea 0 Z1 0 I a1
Va 2 0 0 0 Z 2 I a 2
Substitute Ia0 = Ia1 = Ia2 in the [Is] vector
15 16
17 18
3
If the neutral of the generator is ungrounded, the zero SLG faults on power systems
sequence network is open-circuited.
Then, Ia1 and hence Ia = 0. Prefault voltage is designated Vf and only appears
in the positive sequence network
After determining Ia1 The sequence networks for the system are first
Va1 = Ea – Ia1Z1 drawn
Va2 = – Ia1Z2 Then Thevenin equivalent for each network as
Va0 = – Ia1Z0 seen from the fault location is derived
The value of equivalent impedance is applied in
Vb Va 0 a 2Va1 aVa 2 the equations derived earlier for each type of
Phase voltage of the healthy phases fault.
Vc Va 0 aVa1 a 2Va 2
19 20
Example 1 Table E1
Consider the power system whose one-line diagram is shown Item MVA Voltage rating X1 X2 X0
below. rating (kV) (pu) (pu) (pu)
G1 100 25 0.2 0.2 0.05
G2 100 13.8 0.2 0.2 0.05
T1 100 25/230 0.05 0.05 0.05
Bus 5 is at the midpoint of transmission line TL2. T2 100 13.8/230 0.05 0.05 0.05
a) Draw the sequence networks and clearly mark the buses. TL1 100 230 0.1 0.1 0.3
b) Reduce the networks in (a) to their Thevenin equivalents TL2 100 230 0.2 0.2 0.6
as seen at Bus 5.
c) Determine the fault current and the phase voltages for a
SLG fault at bus 5.
System data are as given in Table E1. 21 22
23 24
4
Zero sequence network Single-line-to-ground fault at bus 5
10
I a 0 I a 2 I a1 j1.821
j 0.175 j 0.175 j 0.199
I a 1 1 1 j1.821 j 5.46
I b 1 a 2 a j1.821 0 pu I n j 5.46 pu
I c 1 a a j1.821 0
2
Va 1 1 1 0.362 0
Vb 1 a 2 a 0.681 1.022 238 pu
Vc 1 a a 2 0.319 1.022122
25 26
2
Example 2 kVbase 1382
Zbase(line) 190.44
MVAbase 100
Zline1 Zline2 j 0.105 pu and Zline0 j 0.315 pu
j0.15 j0.20
1.050 1.050
Positive sequence
a) Draw the sequence networks for the system Z1 j 0.20 // j 0.455 j 0.139
b)Reduce the sequence networks to their Thevenin equivalents as j0.139
seen from bus 2
c) Determine the fault current for a SLG fault at bus 2 V1
1.050
The pre-fault voltage Vf = 1.050 pu. Neglect the pre-fault load
current and the transformer phase shift. 27 Thevenin equivalent 28
5
2. Line-to-line fault on an unloaded generator (L-L or DL) The symmetrical components of the voltage are
31 32
1
Ia 2 Ic a a 2
3 From (1) and (2), it can be concluded that the positive and
negative sequence networks must be connected in parallel
Ia1 = -Ia2 …………………………………….…….(2) without the zero sequence network since Z0 does not
appear in (3).
Va 0 0 Z 0 0 0 I a 0
But Va1 Ea 0 Z1 0 I a1
Va 2 0 0 0 Z 2 I a 2
33 34
Vb Vc Va 0 a 2Va1 aVa 2
I b I a 0 a 2 I a1 aI a 2 I a1 a 2 a
I f a2 a
Ea
Z1 Z 2
…...…………………….…….(4)
Va1 Va 2 and Va 0 0
35 36
6
Example 3 Example 4
Repeat Example 1 for a L-L fault. Repeat Example 2 for a L-L fault.
10 1.050
I a1 I a 2 j 2.857 I a1 I a 2 j 3.684
j 0.175 j 0.175 j 0.139 j 0.146
Ia 0 0 Ia 0 0
I a 1 1 1 0 0 I a 1 1 1 0 0
I b 1 a 2 a j 2.857 4.95 pu In 0 I b 1 a 2 a j 3.684 6.382 pu
I c 1 a a 2 j 2.857 4.95
I c 1 a a j 3.684 6.382
2
3. Double line-to-ground fault on an unloaded generator (L-L-G or DLG) Va 0 1 1 1 1 Va 1 Va
Va1 1 a a 2 0 Va
Let the fault be Va 2 3 1 a 2 a 0 3 Va
on phase ‘b‘ V
and ‘c’. Va 0 Va1 Va 2 a ………….………………….(1)
Ib 3
The fault I a 0 I a 0 I a1 I a 2
conditions are: I a 0 I a1 I a 2 ………….………………….(2)
1. Ia = 0
Vb 0 Va 0 a 2Va1 aVa 2
2. Vb = Vc = 0 ………….………….(3)
Vc 0 Va 0 aVa1 a 2Va 2
If = Ib + Ic
But Va0 = – Ia0Z0
Substituting (2) for Ia0 gives
Ic Va0 = (Ia1 + Ia2)Z0
Va1 = Ea – Ia1Z1 ………….……………………….(4)
39
Va2 = – Ia2Z2 40
7
Case 4: Double-line-to-ground fault at bus 5
10
I a1 j 3.73 Va 1 1 1 0.348 1.044
j 0.175 j 0.199 Vb 1 a 2 a 0.348 0 pu
j 0.175
j 0.175 j 0.199 Vc 1 a a 0.348 0
2
j 0.199
Ia 2 j 3.73 j1.99
j 0.175 j 0.199
j 0.175
Ia 0 j 3.73 j1.75
j 0.175 j 0.199
I a 1 1 1 j1.75 0
I b 1 a 2 a j 3.73 5.60152.1 pu
I c 1 a a 2 j1.99 5.60 27.9
I n j 5.25 pu
43 44
3. DLG
If the fault occurs on phases ‘b’ and ‘c’ and
ground, the fault conditions are:
1. Ia = 0
2. Vb = Vc SYMMETRICAL FAULTS
3. Vb = ZF(Ib + Ic)
I a1
VF
VF SHORT CIRCUITS
Z1 Z 2 // Z 0 3 Z F Z2 Z0 3 Z F
Z1
Z2 Z0 3 Z F
Z0 3 Z F
I a 2 I a1
Z 2 Z 0 3 Z F
Z2
I a 0 I a1
Z 2 Z 0 3 Z F
47 48
8
Transients in RL series circuits The 1st term of (1) varies sinusoidally with time (ac
component) whereas the 2nd term is non-periodic and
decays exponentially with a time constant of L/R (dc
component)
e Vmax sin( t )
di Current i for - = 0 Current i for - = -/2
Vmax sin( t ) L Ri for t 0
dt
Vmax
i sin( t ) Rt / L sin .............(1)
Z
where Z R 2 ( L)2 and tan 1 L / R
49 50
9
Initial fault current after fault occurrence is high due to reduced EXAMPLE 1
armature reaction but reduces to a lower value as armature
reaction increases. If the pre-fault rms phase voltage at the Two generators are connected in parallel to the L.V. side
generator terminal (on no load) is |Eg|, of a - transformer. G1 is rated 50 MVA, 13.8 kV and
G2 25 MVA, 13.8 kV. Each generator has a subtransient
| Eg | reactance of 25%. The transformer is rated 75 MVA, 13.8
| I | rms steady state current / 69 kV with a reactance of 10%. Before the fault
Xd
| Eg | occurs, the H.V. side of the transformer is at 66 kV and
| I | rms transient current the transformer is unloaded with no circulating current
X d
between the generators. Find the subtransient fault
| Eg |
| I | rms subtransient current current in each generator when a short circuit occurs on
X d the H.V. side of the transformer.
The q-axis reactances do not significantly affect fault current
since armature resistance is small.
55 56
Solution 50 MVA
13.8 kV I1 2.734 pu
75 MVA
13.8 /69 kV
I2 1.367 pu
MVAbase 103
I base
3 kVbase
25 MVA 2091.85 A
Let kVbase = 69 kV and
MVAbase = 50 MVA
13.8 kV I1 5.72kA
X eq X 1 // X 2 X Tx I2 2.86kA
2
MVAbase ( new ) kVbase ( old )
X new X old
MVAbase ( old ) kVbase ( new )
0.233 pu
Vf
X 1 0.25 pu If 4.101 pu
X 2 0.50 pu Pre-fault voltage X eq
X Tx 0.067 pu = 66/69 = 0.957 pu
57 58
59 60
10
Solution
EXAMPLE 2
The synchronous motor in the power system shown below
is drawing 80 MW at 0.8 p.f. leading and a terminal
voltage of 13.4 kV, when a symmetrical 3 phase fault
occurs at Bus 2. Find the sub-transient current in the
generator, motor, and fault.
11
1. Generator reactor – between generator and busbar 4. Earthing resistor or reactor connected to
Not common in modern design –generators transformer neutral
have inherently high reactance windings • Increase ZPS impedance hence limit SLG and DLG
and they are protected by very fast relays fault current
Neutral grounding
2. Busbar reactor – between sections of busbars
A system whose neutral point is NOT connected to
Prevents total voltage collapse at the ground is said to have an isolated or free neutral
station in case of a fault on one bus bar.
The connection of the generator and transformer neutrals
Limits circulating current in case of
influences fault currents and voltages during unbalanced
imbalance e.g. fault on one section of the
busbar. faults that involve the ground (S-L-G and D-L-G)
Usually, grounding is done through the transformer or
3. Feeder reactor
generator neutral
Prevents voltage collapse in case of a fault Transformers are normally solidly grounded (no
near the generating station. impedance connected in the neutral path)
67 68
69 70
12