MTS200R: TER Time-Sync
MTS200R: TER Time-Sync
masTER Time-Sync
www,masibus.com [email protected]
TECHNICAL SPECIFICATIONS
GPS Receiver
Timing Accuracy < 15 ns with GPS Receiver (Receiver is locked on fixed position)
Positioning Accuracy < 10m
Input Frequency 1575.42 MHz L1 C/A code
Tracking 12 parallel channels
Hot Start < 5 sec
Acquisition time Warm Start < 38 sec
Cold Start < 45 sec
Antenna
Type Active L1. GPS, 28 dB gain
Antenna Cable type RG 6
Operating Temperature -40 to +85°C
Coverage 360 Degree
Ingress Protection IP67
Weight 150 g
Interface and Configuration
Display 2 x 20 Character backlit LCD Display
Local / UTC Time and Date
Day of the week
Displayed data Position latitude, longitude
Status of the GPS receiver
Configuration parameters.
Status LEDs Power, 1PPS, Watchdog, Error, GPS Locked
Front Keypad
Configuration Methods Front Console DB-9 Port (Serial RS232)
Web server(HTTP/HTTPS),SSH,SNMP, TELNET (Ethernet RJ45 Port)
Universal time zone correction, DST Settings
Hour settings for Display (12 or 24 format), UTC/LOCAL time display
Data format selection (NGTS/T-FORMAT/GPGGA/GPZDA)
Repetitive event generation output via Potential free Contact (Per Minute or Hour)
Keypad Configurable
Additional Event Configuration (Total & On time of Events)
Parameters
Manual Time setting
Propagation delay correction (compensation for antenna cable length)
IPv4 Network parameters [IP, Subnet, Gateway] , DHCP
Ethernet protocols (NTP, SNMP, Syslog, SSH, HTTP, HTTPS) service setting
IPv4, IPv6
TCP, UDP, DHCP, AUTOCONF(IPv6)
NTP v2[RFC 1119], v3[RFC 1305] and v4[RFC 5905] with Unicast, Broadcast / Multicast Modes
SNMP v1[RFC 1157], v2[RFC 1901-1908] and v3[RFC 3411-3418] with Enterprise MIB file
Network Protocols SNMP v1, v2 and v3 compatible Traps with two configurable SNMP Trap Managers
SYSLOG for internal and remote Alarm logging
SSH v1, v2, Telnet for remote configuration
PTPv2 Master - IEEE C37.238-2011, IEEE C37.238-2017, IEC 61850-9-3 (except SNMP)
Webserver through HTTP and HTTPS – Browser based Configuration & monitoring
Configurable MD5 based encrypted password user access to SSH, Telnet and Webserver access
NTP v3,v4 MD5 Authentication with Symmetric and Autokey Management
SNMP v3 - AES/DES Encryption and SHA/MD5 Authentication
Network Security Features
SNMP v3 with no-auth / auth / priv security feature
Configurable SSH v1, v2 with configurable 768 / 1024 / 2048 bits size security keys
Configurable HTTPS SSL certificate
Alarms and system Messages logging using SYSLOG
100Kbytes of internal log memory
Logging & Alarms
Remote logging feature two configurable SYSLOG servers
Remote Alarm Notification through SNMP Traps and SYSLOG
Platform Support: Windows 10/8.1/7 SP1/ Windows Server 2012 R2/ 2008 R2 SP1 Unix Linux,
NTP / SNTP Client Software
Solarisserver synchronization
1 x USB Port on front panel
USB Port Download/ Upload of configuration files
Install firmware upgrades
Firmware Upgrade Via Webserver, USB (All Binaries + Configuration)
TECHNICAL SPECIFICATIONS
CPU Card
Output Description Connector Accuracy (to UTC) Output per card
1 x 10/100 Mbps or
IPv4, IPv6, DHCP, NTP, SNMP, Webserver, SSH, Telnet
±1mSec 1 x 10/100 Mbps +
ETH x (LAN) Mode: Server RJ45
[NTP Server] 1 x 10/100/1000
Network Interface: RJ45, Auto-negotiation, 1st port 10/100 Mbps
Mbps (Optional)
NMEA frame – GPRMC
Plug in screw ±100nSec
NMEA Isolated output, RS232 /RS485** 1 no
terminals (PPS o/p)
Fix configuration: 9600-8-N-1
**RS232/RS485 in CPU Card is site selectable, default setting RS232
Time Signal Output
Output per card
Output Card Type Description Connector Accuracy (to UTC) Optional
Option-1 Option-2
1 Pulse per second
PPS Card TTL into 250 Ω BNC Female ±100nSec 2 nos 4 nos
200 ms Pulse Width
Format : IRIG-B(127),IEEE 1344/C37.118-2005
IRIG-B 1 KHz AM Signal
BNC Female ±10µSec 2 nos 4 nos
Modulated Card Modulation Ratio: 3:1
3 Vp-p, into 100Ω ±10%
Format: IRIG-B (007) or IEEE1344 (field set)
IRIG-B TTL Card BNC Female ±1.5µSec 2 nos 4 nos
TTL into 50Ω
Protocol Support: NTP V3, SNTP
NTP (LAN ±1mSec
Network Protocol: TCP, Telnet, UDP, IPv4 RJ45 2 nos 4 nos
Interface) [NTP Server]
Mode: Server
Configurable Serial Frames (NMEA / NGTS / T-format)
NMEA frames – GPRMC / GPZDA / GPGGA
Output Status LED
Serial Card Isolated outputs DB9 Female - 2 nos NA
RS232 or RS485 (Factory set to be selected from
ordering code)
Fix configuration: 9600-8-N-1
Configurable event period (1sec to 1 Day) with ON
Time from 50 milliseconds to 50% of total period Plug in screw
Event Card PMOS relay terminals AWG - 2 nos 4 nos
Rating: 350V DC/120mA max. 2.5 mm2
Output Status LED
GPS LOCK, Redundancy, Watchdog, Error relay Plug in screw
Relay Card Rating: 230V AC/ 30V DC @ 2A; 110V DC@ 0.3A; terminals AWG - - 4 nos
220V DC@ 0.12 A (max) max. 2.5 mm2
Protocol: IEEE 1588v2, NTP, SNTP
Power Profile-IEEE C37.238-2011, IEEE C37.238-2017
(except SNMP)
Power Utility Profile-IEC-61850-9-3 (except SNMP)
Multicast, Unicast - Layer2, Layer 3 Ethernet (L2) or
UDP IPv4, IPv6 (L3)
PTP Card RJ45 <200 nSec 1 no 2 nos
Delay Mechanism - E2E / P2P
Sync Messages - Upto 128 messages/second per client
PTP Modes 1 Step / 2 Step mode
Protocols IPv4, IPv6, DHCP, DHCP6 FTP, Telnet, SSH
Interface 1 x 10/100/1000 Mbps
Freq Output 1 x 1PPS
PRP Card PRP will support NTP, SNTP and PTP RJ45 x 2 - 1 no NA
Signal Type: IRIG-B TTL (007)/PPS/PPM/PPH/PPD –
configurable
Pulse o/p Card Transmission: Simplex Multimode
As per Signal type 2 nos 4 nos
(Fiber Optic) Fiber Size: 62.5/125 μm ST connector
Wavelength: 820 nm
Distance: 1750 meters
As defined As defined Max 2 nos IRIG-B AM or
Multi-port Output 2 nos IRIG-B AM /TTL / PPS (any one factory set) TTL or PPS (any one
2 nos Event o/p above above
Card (M1)# respectively respectively factory set), 2 nos Event &
2 nos Alarm (GPS lock and Watchdog) 2 nos Alarm in One Card
1 no IRIG-B AM /TTL / PPS (any one factory set) Max 1 no IRIG-B AM or TTL
As defined As defined or PPS (any one factory set,2
2 nos Event o/p
Multi-port Output nos FO over IRIG-B TTL/PPS
2 nos FO over IRIG-B TTL (007)/PPS/PPM/PPH/PPD – above above
Card (M2)# /PPM/PPH/PPD – factory
factory configurable respectively respectively set, 2 nos Event & 2 nos
2 nos Alarm (GPS lock and Watchdog) Alarm in One Card
TECHNICAL SPECIFICATIONS
Power Supply Environmental
Standard 90 - 264 V AC / 125- 370 V DC, 35W Operating temperature 0 to +55°C
Option-1 18 - 36 V DC, 30W Storage temperature -20 to +80°C
Option-2 36 - 75 V DC, 30W Humidity 20-95 % RH Non Condensing
Output Status Power LED status, Power Fail Relay output Type test
Isolation (Withstanding voltage) Electrostatic Discharge (ESD) IEC 61000-4-2
Between primary terminals* and secondary terminals**: At least 1500 V AC for 1 minute
Between primary terminals* and grounding terminal: At least 1500 V AC for 1 minute Radiated Susceptibility IEC 61000-4-3
Between grounding terminal and secondary terminals**: At least 1500 V AC for 1 minute EFT Test IEC 61000-4-4
Between secondary terminals**: At least 500 V AC for 1 minute
* Primary terminals indicate power terminals and relay output terminals.
Surge Test IEC 61000-4-5
** Secondary terminals indicate Output Ports Conducted Susceptibility (Conducted RF) IEC 61000-4-6
Insulation resistance: 50MΩ or more @ 500 V DC between power terminals and grounding
terminal. Power Frequency Magnetic Field IEC 61000-4-8
Note: No Isolation between IRIGB-TTL and PPS Output. High Frequency Disturbance IEC 61000-4-10
Physical Voltage interruption/voltage dips IEC 61000-4-11
Mounting 1U, 19” Rack Mount Ringwave Immunity test IEC 61000-4-12
Dimensions (mm) 45(H) x 483(W) x 251(D) Radiated Emission
As per CISPR 11
Ingress protection IP20 enclosure Conducted Emission
Weight 3 Kg Vibration IEC 68-2-6
Bump Test IS 9002 Part-7
Mounting Dimensions Dry Heat Test IEC 60068-2-2
Damp Heat Steady State test IEC 60068-2-30
Shock Test IEC 60255-21-2
Dielectric Test
Cold Test IEC 60068-2-1: 2007
Ordering Code
Output Card(select code for
Receiver Power supply CPU with card type from Table1.1) Antenna Cable
Model
Clock Module Ethernet o/p Length
PS-1 PS-2 Card-1 Card-2 Card-3 Card-4*
MTS200R X X X X X X X X X
1 1 x Clock 90 - 264 V AC/
1 125- 370 V DC N None C1 1 x 10/100 Mbps 0 None
Module 1 15 meters
2 x Clock 90 - 264 V AC/ 1 x 10/100 Mbps
2* Module 2 18-36 V DC 1 125- 370 V DC C2 + 1 x 1Gbps 2 30 meters
3 36-75 V DC 2 18-36 V DC 3 50 meters
3 36-75 V DC 4 100 meters
Output Card Table1.1
S Special
Code-X Card Type/ No of ports
N None
1B IRIG-AM (2 ports)
1C IRIG-AM (4 ports)
2B IRIG-TTL (2 ports)
2C IRIG-TTL (4 ports)
3B 1PPS (2 ports)
3C 1PPS (4 ports)
4B Serial (2 ports)
PB PRP
AB Pulse FO (2 ports)
AC Pulse FO (4 ports)
M1 Multiport Card#
M2 Multiport Card#
#Customer to specify the required o/p type in Multiport Card while ordering
*When Redundant Receiver Clock module is selected, only 3 Output Cards possible